Texecom Series

WebWay Alarm Panel Integration


WebWayOne Alarm System Alarm Mon-itorin t integration improves security and reduces costs
WebWayOne and Texecom have integrated the WebWay IP/GPRS and WebWay GPRS/PSTN to provide Insurance Class Alarm signalling including the six essential elements of a fully managed Alarm System. Automatic Commissioning ATS Monitoring and Fault Reporting Alarm and Fault reporting Remote Support Upload/Download Remote Maintenance

Serial Panel Connection


Connect the 05-0246 connector cable to the Texecom onto Com Port 1. Com port 2 usually has a local PC or other peripheral equipment connected. Note Com port 2 on a Premier 88 uses a different Molex connector. See premier 88 install for more details.

Texecom Alarm Systems


The following panels have been integrated to the WebWay signalling solution Texecom Premier 60, 88, 168, 816, 412, 832 Premier Elite 48

For 60, 88,168, 816 (wwo) integrations are via a TTL link to com port 1 on the Texecom panel WebWayOne cable 05-0246 is required for installation 412,816 (Std),832 are via a webway modem capture module (22-5059) For Wintex programming via a PC a USB Com cable (Texecom part no JAA-0001 or JAC-0001). Texecom TTL Cable 05-0246 (5 Pin)

Simple installation and commissioning


The WebWay solution is quick and easy to install and commission with your chosen ARC. A cable to the Alarm System, a two-wire connection for power, an Ethernet cable to the Router and locate the aerial. Our Auto Take On process completes the WebWay installation. The WebWay servers automatically programme the WebWay to work seamlessly with the Texecom to enable SIA alarms, Upload Download and secure remote access using the Texecom Wintex software.

(Non WWO Version)

Texecom Compatibility List Panel Variant Connection Type Install Guide Premier 24 Modem Capture Pg 5 Premier 48 Serial TTL Pg 6/7 Premier 60 Serial TTL Pg 2/3 Premier 88 Serial TTL Pg 2/3 Premier 168 Serial TTL Pg 2/3 Premier 412 Modem Capture Pg 5 Premier 816 Serial TTL Pg 4 (WWO Version) Premier 816 Modem Capture Pg 5 Modem Capture Serial TTL Serial TTL Pg 5 Pg 6/7 Pg 6/7 Texecom
Pin 2 from right

Premier 832 Premier Elite 24 Premier Elite 48 WebWay SPT T - Red R - Green RTN - Blue
Automatic SIA 3 with text enriched messages
All alarms generated by the Alarm System are automatically sent to the AMS using SIA. SIA messages provide a full audit trail of an event which detector, location, time and date, and a permanent record of every alarm. Messages for set and unset include who, where, time, and date, all recorded. No need to check that each PIN is correctly wired; the Texecom and the WebWay take care of everything automatically.

Com Port 1

Pin 1 for right Pin 3 from right

The wiring above refers to the WebWay part 05-0246 Other cables can be used, please note the pin details above. Connect the WebWay PWR + and - to any relevant Power (+12V/+24V) and Ground (0V) terminals.

1
www.webwayone.co.uk sales@webwayone.co.uk 01635 231500

Texecom Series
Texecom Premier 88/168/60 Series
The Texecom panel configuration is uploaded via the Wintex software and downloaded to the panel on com port 2 from a local PC. The following requires configuring in the panel, Communications Menu In Options 1. Enable communicator must be ticked 2. UDL passcode (set in the panel) must match. 3. Dial attempts 1, ring before answer 3 In ARCs 1. Account number (site ID) 2. SIA Level 2/3 3. Connect Via IP - ticked 4. Send SIA text ticked In Radio-Pad and Com Port options 1. Com Port 1 WebWayOne module 2. Local IP address 127.0.0.1 3. Local IP port 50561 4. Gateway 127.0.0.1 5. Subnet Mask 255.255.255.0 6. Name/SMG port 50561

Important: The WebWay should be connected to Com port 1. If you wish to use Com port 2 on a Premier 88 panel then please contact Texecom for a 5 to 7 pin Molex converter.

Wintex Settings

Important: The WebWay SPT should be connected to Com port 1. All settings are configured with the Wintex Communications menu (7th option down on the left side of the Wintex program labeled Comms). This can be configured on a local PC plugged on to Com Port 2 with the WebWay unit running on Com Port 1. (In keypad settings leave Com Port 2 as unassigned, when the PC cable is connected it will automatically detect and allow you to configure settings).

www.webwayone.co.uk sales@webwayone.co.uk 01635 231500

Texecom Series
Texecom Premier 88/168/60 Series

Account No: should match the ARC Site/Chip ID and tick the relevant trigger event boxes relevant to the premises.

If the SMS call centre is utilised the engineer should enter the appropriate number and it should be configured under: UDL/Digi Options Radio/SMS Option SMS Centre Pri. The SMS centre telephone number is used to send SMS text messages to mobile phones. (Default = 07860980480). Note if the Texecom is being programmed with a laptop on com port 2 and the WebWay is connected to com port 1 the SPT will be lost from the panel until the Wintex session is closed.

3
www.webwayone.co.uk sales@webwayone.co.uk 01635 231500

Texecom Series
Texecom Premier 816 (WWO Version)
A special version of the 816 known as the Premier 816 WWO is shipped with special software which allows it to communicate with the 2424 SPT, however it does not have a dialer which means that it can only be used with the 2424 system. Note that a cable assembly is required , which WebWayOne can supply although any 5-Way Molex type connecter can be modified. The Texecom main board assembly has only 1 Com port on the PCB with a 5-pin connection interface. This connects to the TTL R, T and gnd terminals of the WebWayOne 2424 panel interface. This means that a local PC and the 2424 SPT cannot be connected to the panel at the same time. When connecting the local PC, leave the SPT disconnected for about 30 seconds before connecting to the PC. This should ensure that the panel recognizes that the SPT has been disconnected. If there are problems establishing communications with the local PC, try entering user code + menu + 7 on the panel keypad (abort all communications). The connection details are as follows:

Menu 76: Download Menu


1: Com1 equipment type 003 - ComIP Module 2: Com IP-address & port 12700000000150561 Enter full octet (***.***.***.***) with no periods. Port should always be 50561 Example, IP 192.168.0.101 Port 50561: Enter as 19216800010150561 Note that 127.0.0.1 is interpreted by the SPT as use DHCP. 3: LAN gateway IP (the local router) 127000000001 Enter full octet (***.***.***.***) with no periods. Example, IP 192.168.0.1: enter as 192168000001 Note that 127.0.0.1 is interpreted by the SPT as use DHCP. 4: Netmask 8 (255.255.255.0) This is selected from a list (see the Premier manual for full details). DHCP settings for IP & LAN gateway will override this setting. 5: IP & port for main MCT Enter full octet (***.***.***.***) with no periods. Port should always be 50561. Example, IP 85.200.242.12 Port 50561: Enter as 08520024201250561

WebWay SPT T - Red R - Green RTN - Blue

Texecom
Pin 2 from right

Com Port 1

Pin 1 for right Pin 3 from right

The wiring above refers to the WebWay part 05-0246 Other cables can be used, please note the pin details above.

Panel configuration Enter Programming Options Menu 70: Communicator Options


1: Enable Communicator 2: Enable DTMF Dialing 3: Pulse after 3rd attempt 4: European Pulse Dialing ENABLED DISABLED DISABLED DISABLED

Configuration can also be done via the Wintex program

5: Enable Test Transmission OPTIONAL 6: Enable Cancel Call Waiting DISABLED 7: Enable Backup to ARC 8: Enable Blind Dialing DISABLED DISABLED

Menu 71: ARC 1 Menu


0: Phone number Leave blank 1: Account number Site Chip Number 2: Protocol SIA Level 2/3 3: Dial Attempts 9 4: Partition Options 1234 (optional) 5: Reporting Options 12345678 (optional)

6: Protocol Options * * * * * * * 8 Connect Via IP

www.webwayone.co.uk sales@webwayone.co.uk 01635 231500

Texecom Series
Texecom Premier 24 (Modem Capture Only), 412,816 (Standard Edition),832
The following models are integrated via a modem capture module, provided by WebWay. This type of integration does not support Upload/Download functionality.

Panel configuration can also be completed with Texecoms wintex program.


In the comms menu set the following in Options;

The modem capture board needs wiring as follows to the Texecom panel.

WebWay Modem Capture A B


Panel configuration Enter Programming Options Menu 70: Communicator Options
1: Enable Communicator 2: Enable DTMF Dialing 3: Pulse after 3rd attempt 4: European Pulse Dialing ENABLED ENABLED DISABLED DISABLED

Texecom T R

In the comms menu set the following in ARCs;

5: Enable Test Transmission OPTIONAL 6: Enable Cancel Call Waiting DISABLED 7: Enable Backup to ARC 8: Enable Blind Dialing DISABLED ENABLED

Menu 71: ARC 1 Menu


0: Phone number 01234 567890 1: Account number Partiton 1Site Chip Number (Ensure reporting for partition(s) is enabled) 2: Protocol SIA Level 2/3 3: Dial Attempts 9 4: Partition Options 1234 (optional) 5: Reporting Options 12345678 (optional) 8: Protocol Options All blank

www.webwayone.co.uk sales@webwayone.co.uk 01635 231500

Texecom Series

If Upload/Download is needed ensure the settings below are configured

Texecom Premier Elite 24/48 & Premier 48


Requirements for the Texecom Premier Elite 24/48 Premier 48 For Wintex access via a PC or remote manager version 6 Build 2 For Wintex programming via a PC a USB Com cable (Texecom part no JAA-0001 or JAC-0001) Texecom TTL Cable 05-0246 Premier Elite 24/48 Version 1.0 or 2.0 firmware Premier 48 Version 8.0 firmware

Connect to the Texecom WebWay SPT Panel is as follows,

Texecom
Pin 2 from right Pin 1 for right Pin 3 from right

T - Red R - Green RTN - Blue

Com Port 1

In ARCs ensure that,


Account no matches the Chip ID for the site Protocol in SIA Level 2/3 is selected User Area accounts is ticked Connect Via IP is ticked Send SIA text is ticked

Wintex Programming
Simple Configuration can be achieved with Texecoms Wintex program and a suitable comms cable. To allow communications simply connect the cables to com port two on the device and then Config a account as usual with the following settings in comms. (In keypad settings leave Com Port 2 as unassigned, when the PC cable is connected it will automatically detect and allow you to configure settings).

In options
Enable Communicator must be ticked

Ensure any reporting settings are set as required

www.webwayone.co.uk sales@webwayone.co.uk 01635 231500

Texecom Series
Texecom Premier Elite 24/48 & Premier 48
Radio Pad and Com port settings
Ensure Com Port 1 is set to WebWayOne/Emizon Module

Also set the following; Local IP Address 127.0.0.1 Local IP Port 50561 Gateway 127.0.0.1 Subnet Mask 255.255.255.0 Name/SMG Port 50561 Finally send the update back to the panel.

To set up via keypad


Enter Engineer password > Press Menu Scroll to UDL/Digi Options (7) Select Digi Options Ensure the first option is set to E***** (Enable Communicator) Select UDL Options Scroll to UDL password is Set this to match the Texecom Wintex Application UDL Password (Default 1234) In Area Accounts set the Area ids to match the site Chip Number Select Program Digi Set Arc 1 Protocol to SIA level II Primary and Secondary Number are blank Set Account Number as the Chip number Dialling Attempts as 2 Reporting Areas as required Reports as required Set config as A*****IT A Use Area Accounts I Connect via IP T- Send SIA Text In Com port Options Select Com Port 1, set this to WebWayOne Local IP Address 127.0.0.1 Local IP Port 50561 Gateway 127.0.0.1 Subnet Mask 255.255.255.0 Name/SMG Port 50561

Texecom Premier48 Elite

General troubleshooting tips for Texecom panels We recommended that all Texecom installs are completed with Wintex software. Once you have completed programming the Texecom then restart the panel and WebWay the Texecom bus requires this reboot to see the WebWay as a communications module. Alternatively change the com port settings and move the WebWay to com Port 2. If you receive the following message on the keypad; ATS path fail com 1 this refers to a actual communication path. Please check your Ethernet/GPRS/PSTN connectivity. This does not refer to the com bus between the panel and the WebWay unit. To stop this alarm being sent to the keypad, select Areas > Options > ATS Path Faults and make sure that no areas are selected. Testing alarms, you can send a PA from the keypad by pressing 1 & 3 at the same time. If you wish to use com port 2 on a premier 88, please contact Texecom for a 5 to 7 pin converter or see the pin out on page 2