Project : Big Band - Incubation Building , ASF, Gwal Pahadi, Gurgaon LEED Compliance: Minimum IAQ performance and

Enhanced ventilation calculations (Table 6.3 of ASHRAE 62.1)

Zonal description People outdoor air rate

Standard case : ASHRAE Std 62.1-2004 , Verification rate procedure Outdoor air intake flow (CALCULATED @30% extra) IF APPLICABLE Breathing zone outdoor air flow (Vbz ) OR Vou Outdoor air intake flow (Vot ) System ventilation efficiency (Ev)

Design Case with enhanced ventilation (If Applicable) % increase over standard (NOT TO BE BELOW THE STANDARD CASE)
(%)

Zone primary Air flow fraction (Vpz )

Primary Outdoor air fraction (Zp=Voz/Vpz)

Outdoor air intake flow (ROUNDED OFF)

Zone outdoor air flow (Voz )

Occupancy category

Area outdoor air rate

Zone air distribution effectiveness (Ez)

Occupancy density

This zone This zone qualifies for qualifies for EQ LEED_CS IEQ Cr- PR-1 (Minimum 2 IAQ performance)

SqFt

CFM/ person

CFM/Sft

Occupancy
#

Zone

Area

#/1000

(CFM)

(CFM)

(CFM)

(CFM)

(CFM)

(CFM)

Basement-1
258 5.0 0.06 4 16 35.48 1 35.48 1 35 46
50 600

1.1 Lift lobby


Basement-2 2.1 Lift lobby Basement-3 3.1 Lift lobby 4 GROUND FLOOR 3 2

0.06

40.92%

TRUE

TRUE

258

5.0

0.06

16

35.48

35.48

35

46

50

600

0.06

40.92%

TRUE

TRUE

258

5.0

0.06

16

35.48

35.48

35

46

50

600

0.06

40.92%

TRUE

TRUE

4.1 Office 4.2 Entrance


5 First floor

7510 4690

5.0 5.0

0.06 0.06

115 50

15 11

1025.60 531.40

1 1

1025.60 531.40

1 1

1026 531

1333 691

1350 700

18000 12000

0.06 0.04

31.63% 31.73%

TRUE TRUE

TRUE TRUE

5.1 Office
6 Second floor

12718

5.0

0.06

195

15

1738.08

1738.08

1738

2260

2300

30000

0.06

32.33%

TRUE

TRUE

6.1 Office
7 Third floor

12590

5.0

0.06

195

15

1730.40

1730.40

1730

2250

2300

30000

0.06

32.92%

TRUE

TRUE

7.1 Office
8 Fourth floor

12320

5.0

0.06

190

15

1689.20

1689.20

1689

2196

2200

30000

0.06

30.24%

TRUE

TRUE

8.1 Office

12050

5.0

0.06

185

15

1648.00

1648.00

1648

2142

2200

30000

0.05

33.50%

TRUE

TRUE

MVAC Consulting Engineers : Dew Point Consultants Pvt Ltd. An ISO 9001 : 2008 certified company Page No.38

Version-1-02.05.12

Project : Big Band - Incubation Building , ASF, Gwal Pahadi, Gurgaon LEED Compliance: Minimum IAQ performance and Enhanced ventilation calculations (Table 6.3 of ASHRAE 62.1)

Zonal description People outdoor air rate

Standard case : ASHRAE Std 62.1-2004 , Verification rate procedure Outdoor air intake flow (CALCULATED @30% extra) IF APPLICABLE Breathing zone outdoor air flow (Vbz ) OR Vou Outdoor air intake flow (Vot ) System ventilation efficiency (Ev)

Design Case with enhanced ventilation (If Applicable) % increase over standard (NOT TO BE BELOW THE STANDARD CASE) 34.84% Zone primary Air flow fraction (Vpz ) Primary Outdoor air fraction (Zp=Voz/Vpz) Outdoor air intake flow (ROUNDED OFF)

Zone outdoor air flow (Voz )

Occupancy category

Area outdoor air rate

Zone air distribution effectiveness (Ez)

Occupancy density

This zone This zone qualifies for qualifies for EQ LEED_CS IEQ Cr- PR-1 (Minimum 2 IAQ performance)

Fifth floor 9.1 Office 10 Sixth floor 10.1 Office


Total

Occupancy

Zone

Area

11943

5.0

0.06

183 0 0

15

1631.58

1631.58

1632

2121

2200

30000

0.05

TRUE

TRUE

7695
82,290

5.0

0.06

118
1243

15

1051.70

1051.70

1052

1367 14,498

1400

20000

0.05

33.12%

TRUE

TRUE

14800

Note : For general offices space air distribution is overhead, hence Ez=1 Out door air fraction, Zp is less than 0.15, hence system ventilation efficiency is 1.0 For cells highlighted in blue above (zones having Zp equal to or less than 0.25) the Ev has been modified to 0.9 ; And increase in ventilation load accounted for in the final selections.

MVAC Consulting Engineers : Dew Point Consultants Pvt Ltd. An ISO 9001 : 2008 certified company Page No.39

Version-1-02.05.12

Project : Big Band - Incubation Building , ASF, Gwal Pahadi, Gurgaon LEED Compliance: Minimum IAQ performance and Enhanced ventilation calculations (Table 6.3 of ASHRAE 62.1)

Zonal description People outdoor air rate

Standard case : ASHRAE Std 62.1-2004 , Verification rate procedure Outdoor air intake flow (CALCULATED @30% extra) IF APPLICABLE Breathing zone outdoor air flow (Vbz ) OR Vou Outdoor air intake flow (Vot ) System ventilation efficiency (Ev)

Design Case with enhanced ventilation (If Applicable) % increase over standard (NOT TO BE BELOW THE STANDARD CASE) 1.0 0.9 0.8 0.7 0.6 Appendix A Zone primary Air flow fraction (Vpz ) Primary Outdoor air fraction (Zp=Voz/Vpz) Outdoor air intake flow (ROUNDED OFF)

Zone outdoor air flow (Voz )

Occupancy category

Area outdoor air rate

Zone air distribution effectiveness (Ez)

Occupancy density

This zone This zone qualifies for qualifies for EQ LEED_CS IEQ Cr- PR-1 (Minimum 2 IAQ performance)

vbz vp va rp ra pz az ez ev vot voz vou zp vpz

ventilation of a breathing zone ventilation for a person space / area ventilation rate of ventilation for a person rate of ventilation for a area population of the zone (occupancy) area of the zone zone air distribution effectiveness system ventilation efficiency design outdoor intake air (applicable for multiple zone AHU supplysing recirculated mixed air to many zones) zone outdoor air flow un-corrected out door air primary out door air fraction zone primary air flow

Occupancy

Zone

Area

.=vp+va Max Zp (Zone primary out door air fraction)

Table 6-3 (ASHRAE 62.1-2004) Ev (system ventilation efficiency)

less than or equal to 0.15 less than or equal to 0.25 less than or equal to 0.35 less than or equal to 0.45 less than or equal to 0.55 more than 0.15 determined as per appendix-A OR table 6.3 .=vou/ev .=vbz/ez .=(rp*pz+ra*az) .=voz/vpz for a single zone system vot=voz

this is primary air flow to zone from ahu including outdoor air and recirculated return air

MVAC Consulting Engineers : Dew Point Consultants Pvt Ltd. An ISO 9001 : 2008 certified company Page No.40