Вы находитесь на странице: 1из 26

Product Flier

PF51.1:E August 2005

easy-er Valves

easy-er Control Valves

W7957

S Valves for general, erosive, cavitating, or noisy applications S DN 25 to 300 x 200 and 0.5 to 24 x 20-inch sizes S Choice of balanced or unbalanced trim and metal or soft seats S Temperatures to 538_C S Pressures to DIN PN 160 and ANSI Class 900 S ENVIRO-SEALr and HIGH-SEALt packing systems are available to assist in compliance with environmental emissions requirements S FIELDVUEr digital valve controllers offer digital control and remote diagnostics. The traditional proven line of Fisherr positioners, controllers, transmitters and switches also is available. Note Neither Emersonr, Emerson Process Management, Fisher, nor any of their affiliated entities assumes responsibility for the selection, use and maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end-user.

www.Fisher.com

D102414X412

Product Flier

easy-er Valves

PF51.1:E August 2005

The easy-er Valve Family


easy-er valves are rugged, single-port globe, angle, and reverse-acting (push-down-to-open) valves designed for many varied applications. Although there are many variations available, internal trim parts are interchangeable for many different trims, and maintenance procedures are similar. These features reduce spare parts inventory and simplify maintenance training. Interchangeable Trim Sizes... Many e-bodies feature interchangeable, restricted-capacity and full-size trims to meet variable flow demands.

W0451-3

Figure 1. Typical easy-er Globe Valve

Select from Several Flow Characteristics...In most types, J quick-opening, J linear, and J equal percentage flow characteristics are available.

Noise-Attenuating Trim...To help reduce aerodynamic noise in gaseous service, Whisper Trimr cages are available. To minimize liquid cavitation damage, Cavitrolr III cages are available.

W0958

W0957

W0959

W0961

Quick Opening Cage

Equal Percentage Cage

Linear Cage

Whisper Trimr Cage for Noise Attenuation

Figure 2. Typical Cages

Product Flier
PF51.1:E August 2005

easy-er Valves

The easy-er Valve Family (Continued)


Materials for Sour Environments...Materials and manufacturing procedures for compatibility with NACE MR0175-2002 are available. Protection Against Process Fluid Emissions...Optional ENVIRO-SEAL and HIGH-SEAL packing systems provide an improved stem seal to help prevent the loss of valuable or hazardous process fluids. These live-loaded systems provide longer packing life and reliability.

W6962

Cavitrolr III Trim for Control of Liquid Cavitation (Typical FL Coefficients for Two- or Three-Stage Trim is 0.98)

W5803-1*

PTFE ENVIRO-SEALr Packing System

W2629/IL

Whisper Trimr III Cage for Reduction of Noise in Gas and Vapor Applications

Figure 3. Typical Trims

W85331

HIGH-SEALt Graphite ULF Packing System

Figure 4. ENVIRO-SEALr and HIGH-SEALt Packing

Product Flier

easy-er Valves

PF51.1:E August 2005

Actuators
Type 657 and 667 Pneumatic Diaphragm Actuators...Rugged, heavy-duty spring-return actuators. These actuators are available with a variety of instrument accessories, handwheels, and adjustable travel stops. They can be used for on-off or throttling operation with or without a valve positioner. feature high thrust and long travels for very large valves. J Type 350 electrohydraulic actuators permit valve operation in locations where compressed air is difficult to supply.

Accessories
Type 3025 Diaphragm Actuators...Spring-opposed diaphragm actuators. Suitable for travels up to 200 mm (8 inches). Specified as either direct or reverse acting, actuator action can be easily changed on site without need of additional parts. They can be used for on-off or throttling operation of automatic control valves. FIELDVUE Digital Valve Controller...The controller is available mounted on actuators.

Positioners and Transducers...Pneumatic positioners and electro-pneumatic positioners and transducers can be provided with these valves.

Special Service Actuators... J Type 585C size 25 through 130 actuators for high thrust requirements. J Type 585CLS (long stroke) piston actuators

Position Transducers, Solenoid Valves, and Limit Switches...Also available.

W1916-2

W9088 W6296

Type 657 or 667 Actuator

Type 3025 Actuator

Type 585C Actuator

Figure 5. Typical Actuators

Product Flier
PF51.1:E August 2005

easy-er Valves

Selecting easy-er Products


Only a few of the more commonly selected product materials, sizes, options, and accessories are covered in this flier. Contact your nearest sales office or sales representative (refer to the back cover) for assistance in selecting and sizing these products. More detailed specifications are available on request.

Selecting Valve Components


Valve Trim and Body Style . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 End Connections and Valve Body Materials . . . . . . . . . . . . . . . . . . . 8 Valve Plug, Seat, Ring, and Cage (Trim) Materials . . . . . . . . . . . . . 9 Bonnets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Other Valve Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Selecting an Actuator
Type 657 and 667 Pneumatic Diaphragm Actuators . . . . . . . . . . . 11 Type 3025 Diaphragm Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Selecting Accessories
FIELDVUE Digital Valve Controller . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Valve Positioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Other Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Reference Information
Trim Material Pressure/Temperature Capabilities . . . . . . . . . . . . . Flow Coefficients . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Conversion of Sizing Coefficients . . . . . . . . . . . . . . . . . . . . . . . . . . . Actuator Size Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Typical Valve and Actuator Weight . . . . . . . . . . . . . . . . . . . . . . . . . . Typical Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sales Offices and Sales Representatives . . . . . . . . . . . . . . . . . . . . 16 18 19 21 23 24 25 26

Product Flier

easy-er Valves
Valve Trim and Body Style
Letter Designations Used in this Table % Application Trim Type E: Valve design series T, D, S, and Z: Trim type Fisher Trim Designation Body Style Globe Reverse acting (push-down-to-open) Balanced, cage-guided cage guided with elastomer cage-plug seal and soft or metal l seats Angle T Globe with expanded end connections Globe with expanded end connections and long travel for noise-attenuating trim Large globe with long travel Globe Reverse acting (push-down-to-open) Angle U: Large size W. Expanded ends N: Long travel Fisher Valve Body ET ETR EAT

PF51.1:E August 2005

Size DN 25 200 1 8 inches DN 25 100 1 4 inches DN 25 150 1 6 inches

A: Angle valve style R: Reverse acting (push down to open) Standard Ratings Shutoff Class PN 10 100 Class 125 600 PN 10 100 Class 150 600 PN 25 160 Class 300 900 PN 25 160 Class 300 900 Class 150 600 PN 10 100 Class 125 600 PN 10 100 Class 150 600 PN 25 160 Class 300 900 PN 25 160 Class 300 900 Class 150 600 PN 10 100 Class 125 600 PN 10 100 Class 150 600 PN 25 160 Class 300 900 Through 12 x 8: II Larger sizes: III Soft seat: Air test(2) or V Metal seat: IV

Stringent shutoff with process temperatures to 204_C

EWT

EWNT (metal seats only) EUT ED EDR EAD

DN 100 x 50(1) (4 x 2) through 24 x 20 inches DN 200 x 150 and DN 300 x 200 8 x 6 and 12 x 8 inches 12, 16, 20 inches DN 25 200 1 8 inches DN 25 100 1 4 inches DN 25 150 1 6 inches DN 100 x 50 (4 x 2 inches) through 24 x 20 inches DN 200 x 150 through DN 300 x 200 8 x 6 through 12 x 8 inches 12, 16, 20 inches DN 25 200 1/2 8 inches DN 25 150 1 6 inches DN 100 x 50 through DN 300 x 200 4 x 2 through 12 x 8 inches

IV Soft seat: V Metal seat: IV

II

General applications for process temperatures to 427_C

Balanced, cage-guided cage guided with graphite cage-plug seal and metal seats

Globe with expanded end connections Globe with expanded end connections and long travel for noise-attenuating trim Large globe with long travel Globe

EWD

EWND

III

EUD ES

III

General applications for process temperatures to 538_C

Unbalanced Unbalanced, cage-guided without cage-plug seal and with metal or soft seats

Angle S Globe with expanded end connections

EAS

Metal Seat: IV Soft Seat: VI

EWS

Viscous, non-lubricating, or other hard-to-handle fluids with process temperatures to 427_C

Unbalanced cageless, post-guided with metal or soft seals

Globe

EZ

DN 25 100 1/2 4 inches

PN 10 100 Class 125 600

Metal Seat: IV Soft Seat: VI

1. End connection size x nominal trim size. 2. Standard Fisher air test (maximum leakage is 0.05 mL/min/psid/inch of port diameter).

Product Flier
PF51.1:E August 2005

easy-er Valves

Valve Trim and Body Style (Continued)

W0972-3

W2002-3

W3318

Typical Angle Valve

Typical Reverse-Acting Valve

Valve with Long Travel and Expanded End Connections

W0451-1

W3421-1

Design ED Trim

Design ES Trim

W2966B-1

W3162-1

Design EZ Trim

Design ET Trim

Product Flier

easy-er Valves
End Connections and Valve Body Materials
END CONNECTIONS EN --ANSI NPT female (Class 250 (cast iron) or 600 (steel) body rating Class 125 flat-face and 250 raised-face flanged Class 150, 300, and 600 raised-face or ring-type joint flanged Class 300, 600, or 900 raised-face or ring-type joint flanged Class 150, 300, and 600 raised-face or ring-type joint flanged Socket weld ends (Class 600 body rating) EN --SIZES ANSI 0.5 2 Inches MATERIALS Cast iron, WCC steel, CF8M (316 stainless steel), and other steel alloys Cast iron WCC steel, CF8M (316 stainless steel), and other steel alloys WCC steel, CF8M (316 stainless steel), and other steel alloys WCC steel, CF8M (316 stainless steel), and other steel alloys WCC steel, CF8M (316 stainless steel), and other steel alloys WCC steel, CF8M (316 stainless steel), and other steel alloys WCC steel, CF8M (316 stainless steel), and other steel alloys WCC steel, CF8M (316 stainless steel), and other steel alloys

PF51.1:E August 2005

NOTES Not available in angle valves Not available in 1.25 inch Not available in 1.25 inch ---

PN 10, 16, and 25 raised-face flanged PN 16, 25, 40, 63, and 100 raised-face flanged PN 16, 25, 40, 63, 100, and 160 raised-face flanged ---

DN 25 200

1 8 Inches

DN 25 200 DN 100 x 50 through 300 x 200 ---

1 8 Inches 4 x 2(1) through 12 x 8 Inches 12 24 and 16 x 12 through 24 x 20 Inches 0.5 2 Inches

---

---

---

Not available in angle valves Not available in 1.25 inch Available in Class 600 Class 300, 600, or 900

---

1 8 Inches 4x2 through 12 x 8 Inches 12 through 24 and 16 x 12 through 24 x 20 Inches

----Buttwelding ends

---

Class 600

1. End connection size x nominal trim size.

W0668-2 W6733

W0667-2 W5800-2

Plain Bonnet with Single PTFE V-Ring Packing

Style 1 Extension Bonnet

Style 2 Extension Bonnet

ENVIRO-SEALr Bellows Seal Bonnet

Product Flier
PF51.1:E August 2005

easy-er Valves
MATERIALS Valve Plug S41600 (416 stainless steel) hardened to 38 HRC S31600 (316 stainless steel) S41600 (416 stainless steel) hardened to 38 HRC Seat Ring Depending on size, S41600 or CA15 (410 stainless steel) both hardened to 38 HRC Cage S17400 (17-4PH stainless steel) hardened to 40 HRC S31600 with electroless nickel coating (ENC) S17400 (17-4PH stainless steel) hardened to 40 HRC S31600 or CF8M with electroless nickel coating (ENC) FISHER TRIM NUMBER(2)

Valve Plug, Seat Ring, and Cage (Trim) Materials


VALVE TYPE BODY MATERIAL Standard for all body materials except CF8M (316 stainless steel) SEAT TYPE NOTES Trims with alloy 6 hardfacing also are available. For optional ES, ES EWS soft seat, use trim 29 or 57

ED, ES, EWD, EWS through DN 300 x 200(1) 12 x 8 inch sizes

Metal

CF8M

Metal

S31600

29

ET, EWT through DN 300 x 200 12 x 8 inch sizes

Standard for all body materials except CF8M (316 stainless steel)

Soft

S31600

57

CF8M

Soft

S31600

S31600

29

Trims with alloy 6 hardfacing also are available For available. optional metal seats, use trim1 or 29 Trims with alloy 6 hardfacing also are available. ---

Cast iron and steel EZ CF8M

Metal

S41600 hardened

Metal

S31600

S41600 hardened seat ring with CB7Cu-1 (17-4PH stainless steel) seat ring retainer S31600 with CF8M seat ring retainer

---

101

---

129

1. End connection size x nominal trim size. 2. Refer to the following pages for pressure and temperature limits of the trim.

Bonnets
Bonnet Style Valve Type or Size Packing Material PTFE V-Ring Plain All types and sizes PTFE/composition Graphite ribbon/filament Globe and angle g only; not available for Design EUD, EUD EUT or 16 x 12 or larger Design EW Globe and angle g only; not a ailable for Design EUD, available EUD EUT, EWN, or 16 x 12 or larger Design EW Available only on globe and angle valves through DN 100 and DN 200 x 100 (4-inch and 8 x 4 inch sizes) PTFE V-ring PTFE/Composition Graphite ribbon/filament PTFE V-ring PTFE/Composition Graphite ribbon/filament For exceptional stem sealing capabilities with PTFE or graphite standard packing or with ENVIRO-SEAL packing system Contact your nearest sales office or sales representative 101 to 18 and above 232 46 to 18 and above 232 In-Body Process Temperature Range, _C 18 to 232 18 to 232 18 to maximum limit shown in other tables These in-body process temperatures assume an ambient temperature of 21_C. When using g any y packing ki at t low l process temperatures, an extension bonnet might be needed to prevent valve stem frost. Frost can damage the packing. Notes

Style y 1 extension

Style y 2 extension

ENVIRO-SEAL bellows seal bonnet

Product Flier

easy-er Valves
Other Valve Parts
PART VALVE TYPE OR SIZE Use for Body Material: Cast iron WCC, C5, and WC9 steel Body-to-bonnet y b lti bolting All sizes and types except as listed below CF8M MATERIALS Cap Screws, Stud, or Nut Material Steel SAE GR 5 cap screws SA-193-B7 steel studs SA-194-2H steel nuts SA-193-B7 steel studs SA-194-2H steel nuts SA-193-B8M stainless steel studs (strain hardened) SA-194-2H steel nuts SA-193B8M stainless steel studs (annealed) SA-194-2H steel nuts PTFE V-ring PTFE/composition Graphite ribbon/filament in oxidizing service Graphite ribbon/filament in non-oxidizing service ENVIRO-SEAL and HIGH-SEAL packing systems with PTFE, duplex, Kalrez, or graphite packing FGM in oxidizing service Design EZ Flat gaskets All sizes and types except Design EZ FGM in non-oxidizing service PTFE-coated monel S31600/graphite in oxidizing service S31600/graphite in non-oxidizing service S31603 (316L stainless steel)/composition N06600 (Inconel)/graphite PTFE Carbon-filled PTFE Piston ring for ED type trim Design ED and EWD Graphite in oxidizing service Graphite in non-oxidizing service Carbon-filled PTFE seal ring with fluoroelastomer backup ring TEMPERATURE RANGE, _C --29 to 232 29 to 427 46 to 427 198 to 427 The lower limit is 198; other valve parts determine the upper limit 40 to 232 73 to 232 198 to 371 198 to 538

PF51.1:E August 2005

NOTES

---

Specify lubricated nuts for temperatures greater than 232_C

---

---

Packing (also refer to the bonnet selection table)

All types (see notes for exceptions)

Temperature limits vary with pressure and fugitive emissions standards; contact your nearest sales office or sales representative for information 198 to 427 198 to 593 73 to 149 198 to 427 198 to 593 73 to 232 198 to 593 73 to 204 73 to 232 46 to 427 46 to 538 18 to 204 --------Do not use fluoroelastomer with ammonia, steam, or hot water Do not use ethylene-propylene with petroleum-based fluids or other hydrocarbons -------------

Spiral-wound Spiral wound gasket Soft seat disc

All Design ES, ET, EUT, EWS, EWT, EZ

---

Seal ring for ET type trim

Design ET, EWT (up to DN 300 x 200 or 12 x 8 inch sizes)

Carbon-filled PTFE seal ring with ethylene-propylene backup ring

40 to 232

Spring-loaded PTFE seal ring with Hastelloy C spring and stainless steel backup ring and retaining ring

73 to 232

10

Product Flier
PF51.1:E August 2005

easy-er Valves

Type 657 and 667 Pneumatic Diaphragm Actuators


These heavy-duty actuators feature spring-return action and a variety of operation options and actuator-mounted accessories. The actuator can be used for on-off or throttling service, with or without a positioner. With a push-down-to-close valve, the Type 657 is air to close, and the Type 667 is air to open. Options...J Adjustable travel stop, J top-mounted handwheel, and J side-mounted manual actuator. Specifications...Refer to the following table and the actuator-valve selection tables. Accessories...Refer to the following pages for J pneumatic and electro-pneumatic valve positioners, J FIELDVUE digital valve controllers, and other accessories

W0363-1

Figure 6. Type 657 and 667 Actuator

Type 657 and 667 Actuator Specifications


ACTUATOR SIZE 30 34 40 45 46 50 60 70 80 100 0.2 to 1.0 or 0.4 to 2.0 3 to 15 or 6 to 30 NOMINAL OPERATING PRESSURE RANGES Bar Psig MAXIMUM CASING PRESSURE, BAR Type 657 9.6 5.2 5.2 4.1 3.4 4.1 3.4 4.5 4.1 7.9 Type 667 7.6 6.2 6.2 5.2 4.5 5.2 4.5 4.1 4.1 7.9 10 321 12 010 25 132 33 584 25 131 30 246 39 142 63 392 200 160 Nitrile: 40 40 to 82 Silicone: 50 to 149 Y k C ti Yoke: Cast iron Diaphragm Plate: Aluminum Other Major Metal Parts: steel or cast iron with bronze seal bushing MAXIMUM THRUST, N AMBIENT TEMPERATURES, _C MATERIALS Diaphragm: Nitrile (standard) or APPROXIMATE WEIGHT, kg Type 657 16 22 23 37 49 42 53 107 234 346 Type 667 15 22 23 41 55 43 55 115 284 544

11

Product Flier

easy-er Valves
Type 3025 Diaphragm Actuators
These heavy-duty spring-opposed actuators can be specified as either direct (air-to-close) or reverse (air-to-open). Actuator action can be easily changed on site without need of additional parts. The actuator can be used for on-off or throttling operation of automatic control valves. Options...J Side-mounted gear handwheel, J Oversize signal connections. Specifications...Refer to the following table. Accessories...Refer to the following table.
Type 3025 Actuator Specifications
Features Long travel, up to 200 mm (8 inches) Style Spring-opposed pneumatic diaphragm Typical Maximum Thrust, Newtons (Varies with Operating Pressure, Spring, and Construction) Air to Close, Size P900: 70935 Air to Open, Size P900: 61200 Accessories Handwheels, transducers, position transmitters, air relays, volume boosters, switching valves, lockable valves, limit switches, and solenoid valves are available for actuator mounting. AIR TO CLOSE

PF51.1:E August 2005

AIR TO OPEN

Figure 7. Type 3025 Actuator

12

Product Flier
PF51.1:E August 2005

easy-er Valves
Options (contact your sales office for details on product specific options)... J HARTr, J FOUNDATIONt fieldbus, J remote mounting, J stainless steel housing, J SIS applications, J Performance Diagnostics, J extreme temperatures, and J low bleed relay. Approvals (contact your sales office for details on product specific approvals) Explosion proof, Division 2, Dust-Ignition proof, Intrinsically Safe Explosion proof, Non-incendive, Dust-Ignition proof, Intrinsically Safe

FIELDVUEr Digital Valve Controller


FIELDVUE digital valve controllers are communicating, microprocessor-based controllers that convert a current signal to a pressure signal to operate the actuator. Through digital communications, the controller gives easy access to actuator-valve information that is critical to process operation. AMS ValveLinkr Software...AMS ValveLink Software allows easy access to the information available from FIELDVUE digital valve controllers. The software provides diagnostic information such as dynamic error band and step response on easy-to-interpret screens. Tests can be run while the valve is operating, without disrupting the process. Access to diagnostics is through a Model 375 Field Communicator or a personal computer using AMS ValveLink Software.

APPROVED

ATEX Flameproof, Type n, Intrinsically Safe IECEx Flameproof, Type n, Intrinsically Safe

W7957 W8755

Figure 8. FIELDVUEr DVC2000 Digital Valve Controller

Figure 9. FIELDVUEr DVC6000 Digital Valve Controller on a Type 657 or 667 Actuator

Digital Valve Controller Electrical Specifications (HARTr instruments only)


ELECTRICAL INPUT Point-to-Point Connection Analog Input Signal 4 to 20 mA dc nominal Minimum Control Current Minimum Current without Microprocessor Restart 3.5 mA Maximum Voltage Overcurrent Protection Input circuit limits current to prevent internal damage MultiDrop Connection Instrument Power 11 to 30 Vdc at approximately 8 mA REVERSE POLARITY PROTECTION

4.0 mA

30 Vdc

No damage occurs from reversal of loop current

Digital Valve Controller Electrical Specifications (FOUNDATIONt fieldbus Communication only)


POWER REQUIREMENTS COMMUNICATION PROTOCOL Voltage Level Maximum Current Reverse Polarity Protection Device is not polarity sensitive Termination Bus must be properly terminated per ISA SP50 guidelines

FOUNDATION fieldbus registered device Physical Layer Type(s): 121Lowpower signaling, buspowered, Entity Model I.S. 511Lowpower signaling, buspowered, FISCO I.S.

9 to 32 volts

18 mA

13

Product Flier

easy-er Valves
Valve Positioners
Type 3582 and 3582i Valve Positioners (for Type 657 and 667 Actuators) The Type 3582 pneumatic and 3582i electro-pneumatic valve positioners are accurate, efficient positioners for use with Type 657 and 667 actuators. The field-proven design is fast to respond to input signal changes and is able to withstand the vibrations of most plants. Options... J Gauges and J bypass valve for direct-acting positioners using full input signal range. Approvals (contact your sales office for details on product specific approvals) Explosion proof, Division 2, Dust-Ignition proof, Intrinsically Safe
APPROVED

PF51.1:E August 2005

Explosion proof, Non-incendive, Dust-Ignition proof, Intrinsically Safe Intrinsically Safe, Flameproof, Type n
Supply Pressure
0.3 bar above the actuator requirement up to 3.4 bar maximum 0.3 bar above the actuator requirement up to 3.4 bar maximum

W5500

Figure 10. Type 3582 and 3582i Valve Positioners

ATEX Flameproof, Type n, Intrinsically Safe SAA


Type 3582 and 3582i Positioner Specifications
Type Input Signal Input Bellows Rating Operative Temperature Weight Connections

3582

0.2 to 1.0 or 0.4 to 2.0 bar

3 to 15 or 6 to 30 psig

2.4 bar

40 to 71_C

2.5 kg Pressure and Vent Connections: 1/4-inch NPT type 3582i Conduit: 1/2 NPT

3582i

4 to 20 mA constant current with 30 Vdc maximum compliance voltage; equivalent circuit is 120 ohms shunted by three 5.6 V zener diodes

---

40 to 71_C

3.6 kg

Type 3582 and 3582i Capacities and Housing


SUPPLY PRESSURE PRESSURE, BAR
1.4 2.0 2.4

SUPPLY AIR DEMAND, Nm3/h


4.7 7.0 8.1

AIR CONSUMPTION, Nm3/h Type 3582


0.38 0.48 0.54

Type 3582i
0.42 0.53 0.59

HOUSING
IP 54 per IEC 529 classification (weatherproof); vent should be on the side or bottom for weatherproof applications

14

Product Flier
PF51.1:E August 2005

easy-er Valves

Other Accessories
Type 67CFR FilterRegulator...The Type 67CFR provides constantly controlled supply pressure to actuator accessories system. This regulator features an internal filter and limited-capacity internal relief,
Type 67CFR Filter-Regulator Specifications
OUTLET PRESSURE SETTINGS Bar
0 to 1.4 0 to 2.4 0 to 4.1 0 to 8.6

allowing partial reduction of downstream pressure. Also featured is an integral check valve option that allows the actuated valve to fail to a desired safe position when inlet pressure is lost.

Psig
0 to 20 0 to 35 0 to 60 0 to 125

MAXIMUM INLET PRESSURE (BODY RATING) BAR

MAXIMUM DIAPHRAGM PRESSURE PRESSURE, BAR

TEMPERATURE CAPABILITIES
Nitrile diaphragm and plug: 29 to 82_C Fluoroelastomer diaphragm and plug: 18 to 149_C

CONNECTIONS

MAXIMUM FLOW COEFFICIENT COEFFICIENT, CV

WEIGHT, kg

17.2

3.4 over outlet setting

Inlet and Outlet: 1/4-inch NPT female Vent: 6.4 mm hole or 1/4-inch NPT female

0.36

0.5

Type 546, 646, 846, or i2P-100 ElectroPneumatic Transducers...These transducers convert a standard 4 to 20 mA dc signal to a proportional pneumatic signal. Type 846 and i2P100 transducers incorporate an explosive fluid process seal to meet safety regulations for use with natural gas as the pneumatic supply. Approvals (contact your sales office for details on product specific approvals) Explosion proof, Division 2, Dust-Ignition proof, Intrinsically Safe
APPROVED

Type 2625 Volume Booster...The volume booster can be used in conjunction with a positioner to increase actuator stroking speed. Others...J Highpressure supply pressure regulators, J proximity switches, J microswitches, J solenoid valves, and J signal volume boosters. Contact your nearest sales office or sales representative for more information.

Explosion proof, Intrinsically Safe, Non-incendive, Dust-Ignition proof

ATEX Intrinsically Safe, Flameproof, and Type n IECEx Intrinsically Safe, Flameproof, and Type n

15

Product Flier

easy-er Valves
Trim Material Pressure/Temperature Capabilities for Sizes through DN 300 x 200 (12 x 8 Inches) for ED, ES, and ET Trim

PF51.1:E August 2005

16

Product Flier
PF51.1:E August 2005

easy-er Valves

Trim Material Pressure/Temperature Capabilities for Design EZ Trim


Design EZ Trim Temperature Capabilities (Also Refer to the Following Table)
BODY MATERIAL Cast iron FISHER TRIM NUMBER 101 129 101 WCC Steel 129 VALVE SIZE DIN All All All to DN 50 DN 80 DN 100 to DN 40 DN 50 DN 80 DN 100 to DN 40 DN 80 DN 100 ANSI All All All to 2 inches 3 inches 4 inches to 1.5 inches 2 inches 3 inches 4 inches to 2 inches 3 inches 4 inches TEMPERATURE, _C 29 to 232 73 to 232 29 to 427 29 to 260 29 to 371 29 to 338 29 to 354 29 to 288 29 to 216 12 to 177 198 to 260 198 to 377 198 to 371 NOTES --With non-lubricating fluids, limit to 149_C --With non-lubricating fluids, limit to 149_C

101 CF8M (316 stainless steel) 129

---

With non-lubricating fluids, limit to 149_C

17

Product Flier

easy-er Valves
Design ED, ES, and ET Flow Coefficients
MAXIMUM TRAVEL mm
19 19 19 19 29 38 38 51 51 76 19 19 19 19 29 38 38 51 51 76 19 19 29 38 38 51 51 76 19 19 29 38 38 51 51 76 19 19 29 38 38 51 51 76 19 19 29 38 38 51 51 76

PF51.1:E August 2005

FLOW CHARACCHARAC TERISTIC

VALVE SIZE

PORT DIA. 10 mm
33.3 33.3 33.3 47.6 58.7 73.0 87.3 111.1 177.8 203.2 33.3 33.3 33.3 47.6 58.7 73.0 87.3 111.1 177.8 203.2 33.3 47.6 58.7 70.3 87.3 111.1 177.8 203.2 33.3 47.6 58.7 70.3 87.3 111.1 177.8 203.2 33.3 47.6 58.7 73.0 87.3 111.1 177.8 203.2 33.3 47.6 58.7 73.0 87.3 111.1 177.8 203.2 ----4.86 7.79 13.4 20.9 27.2 37.7 73.6 135 ----.556 .494 .605 .601 .626 .623 .664 .643 3.21 4.23 7.87 9.34 14.5 23.3 46.3 91.4 .340 .656 .641 .680 .671 .691 .656 .651 .783 1.52 1.66 3.43 4.32 5.85 12.9 27.0 .766 .780 .827 .778 .774 .731 .688 .644

DESIGNS ED AND ET DESIGN ES (FLOW UP) (FLOW DOWN) Valve Opening, Percent of Total Travel 30 CV
----13.4 20.5 39.9 58.8 77.9 125 232 434 ----21.1 39.4 73.7 103 149 238 416 759 ----22.1 44.0 77.6 109 161 251 460 863 ----.556 .597 .623 .652 .577 .694 .710 .827 20.6 39.2 72.9 108 148 236 433 846 .636 .656 .638 .641 .620 .688 .740 .807 17.2 35.8 59.7 99.4 136 224 394 818 .667 .679 .687 .660 .675 .716 .778 .807

70

100

100 FL
----.81 .79 .77 .81 .77 .79 .82 .85
---

10

30 CV

70

100

100 FL

EN
----DN 25 DN 40 DN 50 DN 65 DN 80 DN 100 DN 150 DN 200 Q i k Quick Opening ----DN 25 DN 40 DN 50 DN 65 DN 80 DN 100 DN 150 DN 200 DN 25 DN 40 DN 50 DN 65 DN 80 DN 100 DN 150 DN 200 DN 25 DN 40 DN 50 DN 65 DN 80 DN 100 DN 150 DN 200 DN 25 DN 40 DN 50 DN 65 DN 80 DN 100 DN 150 DN 200 DN 25 DN 40 DN 50 DN 65 DN 80 DN 100 DN 150 DN 200

ANSI (Inch)
0.5 0.75 1, 1.25 1.5 2 2.5 3 4 6 8 0.5 0.75 1, 1.25 1.5 2 2.5 3 4 6 8 1, 1.25 1.5 2 2.5 3 4 6 8 1, 1.25 1.5 2 2.5 3 4 6 8 1, 1.25 1.5 2 2.5 3 4 6 8 1, 1.25 1.5 2 2.5 3 4 6 8

4.00 4.94 5.24 7.60 14.3 21.8 23.3 39.0 89.9 156 .681 .576 .540 .577 .633 .659 .585 .642 .572 .520 2.27 3.56 8.49 10.4 15.3 23.7 55.0 100 .691 .628 .618 .672 .607 .553 .597 .616 .783 1.54 1.74 4.05 4.05 6.56 13.2 25.9 .754 .674 .863 .747 .768 .722 .723 .825

6.22 11.8 15.0 22.3 48.6 66.6 78.3 132 255 490

6.52 14.2 21.1 38.0 67.2 93.1 136 225 418 796

6.53 14.2 21.4 38.0 67.2 93.1 150 235 469 875 .622 .534 .650 .789 .810 .868 .720 .780 .700 .774 20.1 34.9 65.3 86.5 135 212 417 836 .690 .764 .762 .866 .751 .791 .745 .799 17.4 33.4 56.2 82.7 121 203 357 808 .721 .793 .848 .878 .757 .822 .816 .827

.88 .83 .89 .94 .93 .91 .87 .89 .82 .85
---

XT
----.724 .682 .737 .738 .745 .733 .667 .757 ----.566 .649 .641 .669 .619 .689 .728 .857

XT
.653 .605 .656 .639 .619 .720 .602 .714 .601 .654 .624 .534 .663 .743 .797 .848 .737 .769 .681 .818

---------------------

---------------------

CV
8.18 11.8 24.9 35.5 52.1 78.1 171 325 16.9 30.3 62.0 83.6 118 181 367 711

FL
.71 .68 .59 .66 .68 .67 .71 .75
---

CV
6.23 11.1 25.9 34.9 52.8 72.9 180 330 15.8 26.7 59.2 73.7 112 165 341 719

FL
.89 .92 .91 .93 .89 .89 .81 .85
---

Linear

XT
.494 .758 .728 .644 .697 .720 .744 .677 .610 .708 .683 .716 .707 .748 .784 .823

XT
.690 .604 .689 .739 .663 .644 .701 .669 .709 .715 .742 .858 .762 .743 .787 .762

-----------------

-----------------

CV
2.20 3.87 4.66 10.8 10.9 18.3 43.3 105 7.83 17.4 25.4 49.2 66.0 125 239 605

FL
.88 .84 .85 .84 .82 .82 .85 .96
---

CV
1.86 3.57 4.72 10.6 10.0 17.3 41.1 97.8 9.54 17.2 25.0 45.5 59.0 103 223 618

FL
.95 .94 .92 .93 .89 .91 .86 .85
---

Equal Percentage g

XT
.587 .716 .774 .678 .682 .643 .682 .636 .743 .690 .702 .661 .663 .672 .736 .725

XT
.763 .694 .849 .745 .761 .739 .767 .681 .630 .698 .792 .783 .754 .718 .808 .735

-----------------

-----------------

18

Product Flier
PF51.1:E August 2005

easy-er Valves
QUICK OPENING --100 FL 4.44 9.72 16.8 33.4 58.4 126 219 XT .894 .769 .500 .861 .831 .783 .809 4.44 9.72 16.9 34.2 58.6 129 223 .894 .769 .494 .848 .834 .774 .835 .83 .88 .94 .96 .94 .91 .88
---

Design EZ Flow Coefficients (Flow Up)


LINEAR 10 30 CV ----2.21 3.99 6.08 15.4 21.3 ----.638 .633 ----5.29 11.1 18.0 43.4 57.5 XT ----.638 .657 ----.636 .696 ----.834 .818 ----11.1 25.8 42.8 93.8 157 ----13.6 31.9 52.4 110 209 70 100 100 FL ----.96 .96 .95 .92 .89
---

VALVE SIZE ANSI (Inch) 0.5 0.75 1 1.5 2 3 4 0.5 0.75 1 1.5 2 3 4

MAXIMUM TRAVEL mm 19 19 19 19 29 38 51 19 19 19 19 29 38 51

PORT DIA. mm 33.3 33.3 33.3 47.6 58.7 87.3 111.1 33.3 33.3 33.3 47.6 58.7 87.3 111.1

Valve Opening, Percent of Total Travel 10 30 CV 1.76 3.85 4.39 5.64 13.0 30.8 50.8 .364 .314 .400 .623 .548 .672 .733 4.29 9.40 14.0 20.6 44.3 92.4 159 .764 .654 .523 .726 .765 .713 .724 70 100 -----

EN ----DN 25 DN 40 DN 50 DN 80 DN 100 ----DN 25 DN 40 DN 50 DN 80 DN 100

-----------------

---------------

---------

---------

EQUAL PERCENTAGE CV DN 25 DN 40 DN 50 DN 80 DN 100 1 1.5 2 3 4 19 19 29 38 51 33.3 47.6 58.7 87.3 111.1 .79 .80 1.65 3.11 4.90 1.80 1.91 4.30 9.12 13.5 XT DN 25 DN 40 DN 50 DN 80 DN 100 1 1.5 2 3 4 19 19 29 38 51 33.3 47.6 58.7 84.3 111.1 .641 .726 .655 .619 .594 .598 .733 .520 .598 .560 .646 .597 .653 .586 .532 .886 .840 .899 .781 .834 7.59 9.84 32.8 60.4 96.7 13.2 28.1 53.8 114 190 FL .96 .97 .95 .92 .90
---

--.560 .655 .779 .924 ----.622 .692 .758 .888 ----.554 .684 .677 .866 --DN 25 (1-INCH) VALVE WITH MICRO-FORM AND MICRO-FLUTEt VALVE PLUG 19 mm TRAVEL EQUAL PERCENTAGE CHARACTERISTIC
PORT DIA. 6.4(1) 9.5(1) 12.7(1) 19.1(1) 6.4(2) 6.4(3)

CV .075 .099 .133 .276 .0385 .0562 .804 .795 .787 .723 .778 .692 .175 .308 .492 .965 .0560 .101 XT .658 .641 .628 .588 .690 .639 .641 1.29 2.12 4.57 .162 .433 .596 .560 .600 .603 .637 .597 1.52 3.07 4.91 8.84 .354 1.07 .647 .662 .803 .919 .656 .624

FL .88 .89 .93 .97 .87 .90


---

-----------

6.4(1) 9.5(1) 12.7(1) 19.1(1) 6.4(2) 6.4(3)

-------------

1. Micro-Formt valve plug. 2. Micro-Flute valve plug1 flute. 3. Micro-Flute valve plug3 flutes.

Conversion of Sizing Coefficients


Following are conversions for use with other common sizing equations. Kv = (0.865)Cv C1= 39.76(pXT) Cg = CvC1 Km = FL2 Cs = 1/20(Cg). Cs is only applicable for inlet pressures up to 70 bar(a)

19

Product Flier

easy-er Valves
Design EWD, EWS, and EWT Flow Coefficients
FLOW CHARACCHARAC TERISTIC VALVE SIZE MAXIPORT MUM DIA. TRAVEL mm
29 51 51 51 51 76 76 152 29 51 51 51 51 76 76 152 29 51 51 51 51 76 76 152 29 51 51 51 51 76 76 152 29 51 51 51 51 76 76 152 29 51 51 51 51 76 76 152

PF51.1:E August 2005

DESIGNS EWD AND EWT DESIGN EWS (FLOW UP) (FLOW DOWN) Valve Opening, Percent of Total Travel 10 30 CV
13.8 40.8 43.2 79.0 80.1 138 149 234 .571 .577 .629 .544 .515 .665 .687 .872 6.80 21.4 23.2 44.0 51.7 95.9 104 307 .625 .686 .694 .796 .716 .683 .700 .676 2.53 7.34 8.01 13.2 23.6 32.3 28.4 126 .626 .996 .684 .837 .628 .725 .666 .655 42.7 140 147 247 250 468 481 1220 105 306 328 531 621 903 1000 2080 124 340 379 637 817 1040 1260 2230 .693 .818 .817 .705 .782 .787 .636 .614 107 320 340 617 729 975 1160 2020 .654 .725 .753 .656 .633 .843 .696 .671 82.2 271 286 508 565 924 1090 2090 .587 .712 .675 .684 .627 .802 .663 .546

70

100

100 FL
.82 .88 .89 .89 .82 .88 .79 .79
---

10

30 CV

70

100

100 FL

EN
100 x 50 150 x 100 200 x 100 200 x 150 300 x 150 250 x 200 300 x 200 400 x 250 Q i k Quick Opening 100 x 50 150 x 100 200 x 100 200 x 150 300 x 150 250 x 200 300 x 200 400 x 250 100 x 50 150 x 100 200 x 100 200 x 150 300 x 150 250 x 200 300 x 200 400 x 250 100 x 50 150 x 100 200 x 100 200 x 150 300 x 150 250 x 200 300 x 200 400 x 250 100 x 50 150 x 100 200 x 100 200 x 150 300 x 150 250 x 200 300 x 200 400 x 250 100 x 50 150 x 100 200 x 100 200 x 150 100 x 50 150 x 100 200 x 100 200 x 150

ANSI (Inch)
4x2 6x4 8x4 8x6 12 x 6 10 x 8 12 x 8 16 x 10 4x2 6x4 8x4 8x6 12 x 6 10 x 8 12 x 8 16 x 10 4x2 6x4 8x4 8x6 12 x 6 10 x 8 12 x 8 16 x 10 4x2 6x4 8x4 8x6 12 x 6 10 x 8 12 x 8 16 x 10 4x2 6x4 8x4 8x6 12 x 6 10 x 8 12 x 8 16 x 10 4x2 6x4 8x4 8x6 4x2 6x4 8x4 8x6

mm
58.7 111.1 111.1 177.8 177.8 203.2 203.2 257.2 58.7 111.1 111.1 177.8 177.8 203.2 203.2 257.2 58.7 111.1 111.1 177.8 177.8 203.2 203.2 257.2 58.7 111.1 111.1 177.8 177.8 203.2 203.2 257.2 58.7 111.1 111.1 177.8 177.8 203.2 203.2 257.2 58.7 111.1 111.1 177.8 177.8 203.2 203.2 257.2

13.7 39.4 42.1 79.3 86.1 151 157 221 .639 .619 .578 .682 .614 .632 .718 .689 6.88 26.2 25.1 52.5 57.4 106 119 343 .599 .713 .610 .655 .523 .666 .678 .786 2.40 7.18 8.37 12.0 18.6 33.9 28.8 63.2 .751 .794 .761 .733 .661 .836 .769 .565

42.1 147 149 249 261 471 480 1190

101 355 365 606 641 918 957 2100

123 382 450 714 874 1000 1110 2210 .793 .781 .704 .671 .736 .842 .836 .638 96.2 320 328 607 675 958 1050 2080 .794 .725 .729 .679 .719 .820 .836 .660 67.5 271 269 478 476 932 1020 1780 .777 .694 .704 .727 .788 .760 .766 .652

.89 .88 .85 .86 .79 .93 .89 .87


---

XT
.662 .612 .631 .578 .613 .651 .727 .682 .714 .793 .809 .759 .715 .741 .744 .652

XT
.652 .591 .560 .634 .571 .625 .712 .682 .843 .726 .733 .688 .677 .798 .855 .644

-----------------

-----------------

CV
23.0 78.7 80.6 170 176 336 348 834 70.8 201 211 405 458 798 907 1680

FL
.79 .86 .82 .88 .81 .91 .80 .82
---

CV
21.5 78.4 78.1 182 186 315 336 865 60.0 197 192 435 441 766 795 1680

FL
.89 .89 .89 .88 .84 .92 .89 .87
---

Linear

XT
.691 .651 .691 .758 .691 .610 .647 .670 .582 .672 .676 .801 .661 .715 .711 .702

XT
.728 .661 .682 .688 .612 .708 .811 .627 .744 .666 .716 .723 .704 .731 .809 .670

-----------------

-----------------

CV
6.66 19.8 21.1 45.4 52.8 111 112 238 29.4 108 118 256 248 635 687 959

FL
.82 .87 .85 .91 .79 .89 .81 .77
---

CV
5.97 18.2 20.0 36.9 43.8 97.7 102 189 26.3 100 102 226 231 568 654 837

FL
.90 .88 .90 .92 .88 .90 .88 .83
---

Equal Percentage g

XT
.664 .711 .643 .719 .694 .687 .667 .640 .646 .630 .566 .626 .695 .595 .664 .503

XT
.781 .775 .716 .874 .824 .894 .928 .501 .732 .718 .701 .773 .764 .699 .651 .497

-----------------

-----------------

20

Product Flier
PF51.1:E August 2005

easy-er Valves
D The selections are valid to 232_C only (204_C for soft-seat constructions). For higher temperatures, your sales office or sales representative can provide actuator selections for graphite ribbon/filament packing or extension bonnets. D Actuator force does not exceed maximum allowable stem load of standard 316 stainless steel stem material at 232_C. D Do not exceed the maximum inlet pressure of the valve (valve body rating) nor the pressure drop limits on pages 16 and 17.

Actuator Selection for Plain Bonnets and Standard Spring-Loaded PTFE Packing
The following tables allow you to select an actuator that will operate the valve at standard actuator pressures. It is not implied that the selections shown are best for your application. In many cases, a smaller actuator might be satisfactory for lower pressure drops, and higher pressure drops might be possible by using higher actuator pressures. Your sales office or sales representative can help you with more detailed actuator selection. D The actuator selections have been made at maximum valve travel using plain bonnets and standard valve stem diameter.

Design ED, ET, and EZ Valves: Flow Down for Design ED and ET; Flow Up for Design EZ
Maximum Inlet Pressure: Through EN PN 100 and ANSI Class 600 Maximum Shutoff Pressure Drop: As shown below unless limited by body pressure-temperature rating or trim capabilities at high temperatures Process Fluid Temperature: With plain bonnet, 18 to 204_C for soft seats and to 232_C for metal seats Ambient Temperature: 40 to 80_C with standard actuator materials; also refer to temperature limits of accessories. Valve Size EN DN 25 and 40 DN 25 and 40 ANSI (Inch) 1, 1.25, and 1.5 1, 1.25, and 1.5 Port Diameter, mm 33.3 47.6 33.3 47.6 6.4 9.5 12.7 19.1 25.4 38.1 Actuator Size Valve Bonnet: Cast iron, steel, or stainless steel Trim: any listed in this flier Gaskets: Any listed in this flier Packing: Single PTFE V-ring Other Valve Parts: Steel or stainless steel Pressure Drop, Bar 2.8 Bar Supply ----------4.1 Bar Supply 5.5 Bar Supply

Pressure Drop, Bar

2.8 Bar 4.1 Bar 5.5 Bar Supply Supply Supply Design ED Valve Class II Shutoff 70.9 40.5 35.4 3.6 99.3 95.4 86.7 38.5 21.7 2.3 99.3 85.9 97.8 49.0 99.3 99.3 99.3 46.5 23.4 7.9 99.3 99.3 99.3 94.5 99.3 99.3 99.3 69.1 36.1 13.6

Actuator Size

20 20 20 20 20 20 20 20 20 20

Design ET Valve Metal Seat Class IV Shutoff

Design ET Valve Soft Seat Class V Shutoff 20 20 20 20 20 20 20 20 39.6 16.2 99.3 99.3 86.7 38.5 21.7 4.0 86.8 50.2 99.3 99.3 99.3 46.5 23.4 9.5 99.3 84.2 99.3 99.3 99.3 69.1 36.1 15.0

Design EZ Valve Metal Seat Class IV Shutoff DN 25 and 40 DN 40 0.5, 0.75, 1, and 1.5 1.5

Design EZ Valve Soft Seat Class VI Shutoff

21

Product Flier

easy-er Valves

PF51.1:E August 2005

Actuator Selection for Plain Bonnets and Standard Spring-Loaded PTFE Packing (Continued)
Type 657 and 667 Actuators
Design ED and EWD Valve: Metal Seat with Class II Shutoff and Flow Down
Maximum Inlet Pressure: Through EN PN 100 and ANSI Class 600 Maximum Shutoff Pressure Drop: As shown below unless limited by body pressure-temperature rating or trim capabilities at high temperatures Process Fluid Temperature: With plain bonnet, 18 to 232_C for metal seats Ambient Temperature: 40 to 82_C with standard actuator materials; also refer to temperature limits of accessories Valve Size or Nominal Trim Size Valve and Bonnet: Cast iron, steel, or stainless steel Trim: Any listed in this flier Gaskets: Any listed in this flier Packing: Single PTFE V-ring Other Valve Parts: Steel or stainless steel Air to Open (Type 667 Actuator) 0 to 1.2 bar (0 to 18 psig) Air to Diaphragm Except Where Indicated Actuator Size
30 30 34 40 40 40 45 45 45 45 45 70 70 - - -(1)

Port Diameter, mm
33.3 33.3 47.6 33.3 58.7 47.6 73.0 58.7 87.3 73.0 111.1 111.1 177.8 203.2

Air to Close (Type 657 Actuator) 0 to 1.2 Bar (0 to 18 psig) Air to Diaphragm Except Where Indicated Actuator Size
30 30 34 40 40 40 45 45 45 45 45 50 70 - - -(1)

EN
DN 25 DN 40 DN 50 DN 65 DN 80 DN 100 DN 150 DN 200

ANSI (Inch)
1 or 1.25 1.5 2 2.5 3 4 6 8

Pressure Drop, Bar


99.3 99.3 99.3 99.3 91.0 99.3 99.3 99.3 98.9 99.3 83.8 80.5 99.3 99.3(1)

Pressure Drop, Bar


99.3 99.3 99.3 99.3 91.1 99.3 99.3 99.3 98.9 99.3 41.2 99.3 99.3 99.3(1)

1. Use a size 70 actuator with 0 to 2.4 bar air to diaphragm.

Design ET and EWT Valve: Flow Down


Maximum Inlet Pressure: Through EN PN 100 and ANSI Class 600 Valve and Bonnet: Cast iron, steel, or stainless steel Maximum Shutoff Pressure Drop: As shown below unless limited by body Trim: Any listed in this flier pressure-temperature rating or trim capabilities at high temperatures Gaskets: Any listed in this flier Process Fluid Temperature: With plain bonnet, 18 to 204_C for soft seats and Packing: Single PTFE V-ring to 232_C for metal seats Other Valve Parts: Steel or stainless steel Ambient Temperature: 40 to 82_C with standard actuator materials; also refer to temperature limits of accessories. Air to Close (Type 657 ACtuator) Air to Open (Type 667 Actuator) 0 to 1.2 Bar (0 to 18 psig) 0 to 1.2 Bar (0 to 18 psig) Valve Size or Air to Diaphragm Except Where Indicated Air to Diaphragm Except Where Indicated Port Nominal Trim Size Metal Seat Soft Seat Soft Seat Diameter, Class IV Shutoff Class IV Shutoff Class V Shutoff Class V Shutoff mm ANSI Actuator Pressure Actuator Pressure Actuator Pressure Actuator Pressure EN (Inch) Size Drop, Bar Size Drop, Bar Size Drop, Bar Size Drop, Bar
DN 25 DN 40 DN 50 DN 65 DN 80 DN 100 DN 150 DN 200 1 or 1.25 1.5 2 2.5 3 4 6 8 33.3 33.3 47.6 33.3 58.7 47.6 73.0 58.7 87.3 73.0 111.1 177.8 203.2 34 34 34 40 45 40 45 45 45 45 45 60 - - -(1) - - -(1) 99.3 99.3 99.3 99.3 99.3 99.3 86.9 99.3 61.7 86.9 46.7 99.3 49.8(1) 9.2(1) 34 34 34 40 45 40 45 45 45 45 45 60 70 - - -(1) 99.3 99.3 95.0 99.3 99.3 92.2 78.7 99.3 59.8 78.7 48.6 92.5 65.0 81.8(1) 34 34 34 40 45 40 45 45 45 45 70 - - -(1) - - -(1) 99.3 99.3 99.3 99.3 99.3 99.3 86.9 99.3 61.7 99.3 60.9(2) 99.3 99.3(1) 79.8(1) 34 34 34 40 45 40 45 45 45 45 - - -(2) 70 70 - - -(1) 99.3 99.3 94.9 99.3 99.3 92.2 99.3 99.3 59.8 99.3 59.2(2) 99.3 65.0 99.3(1)

1. Use a size 70 actuator with 0 to 2.4 bar (0 to 33 psig) air to diaphragm. 2. Use a size 45 actuator with 0 to 2.4 bar (0 to 33 psig) air to diaphragm.

22

Product Flier
PF51.1:E August 2005

easy-er Valves

Actuator Selection for Plain Bonnets and Standard Spring-Loaded PTFE Packing (Continued)
Type 657 and 667 Actuators (Continued)
Design EZ Valve: Metal Seat (Class IV Shutoff) or PTFE Seat (Class VI Shutoff, and Flow Up)
Maximum Inlet Pressure: Through EN PN 100 and ANSI Class 600 Valve and Bonnet: Cast iron, steel, or stainless steel Maximum Shutoff Pressure Drop: As shown below unless limited by body Trim: Any listed in this flier pressure-temperature rating or trim capabilities at high temperatures Gaskets: Any listed in this flier Process Fluid Temperature: With plain bonnet, 18 to 232_C for soft seats and Packing: Single PTFE V-ring 232_C for metal seats Other Valve Parts: Steel or stainless steel Ambient Temperature: 40 to 82_C with standard actuator materials; also refer to temperature limits of accessories Air to Close (Type 657 Actuator) Air to Open (Type 667 Actuator) 0 to 1.2 Bar (0 to 18 psig) 0 to 1.2 bar (0 to 18 psig) Valve Size Port Air to Diaphragm Except Air to Diaphragm Except Diameter, Where Indicated Where Indicated mm Pressure Drop, Pressure Drop, EN ANSI (Inch) Actuator Size Actuator Size Bar Bar
6.4 9.5 12.7 19.1 25.4 38.1 6.4 9.5 12.7 19.1 25.4 38.1 50.8 50.8 76.2 50.8 101.6 30 30 30 34 34 34 40 40 40 45 45 45 45 45 - - -(1) 45 - - -(1) 99.3 99.3 99.3 76.5 34.1 15.4 99.3 99.3 99.3 99.3 58.3 23.4 11.8 3.2 7.1(1) 11.8 3.2(1) 30 30 30 34 34 34 40 40 40 45 45 45 45 45 - - -(1) 45 - - -(1) 99.3 99.3 99.3 76.5 40.2 15.4 99.3 99.3 99.3 99.3 58.3 23.4 11.8 11.8 10.1(1) 11.8 2.7(1)

DN 25 and 40

0.5, 0.75, 1 and 1.5

DN 40

1.5

DN 50

DN 80 DN 100

3 4

1. Use a size 45 actuator with 0 to 2.4 bar (0 to 33 psig) air to diaphragm.

Typical Valve and Actuator Weight


VALVE SIZE EN
--DN 25 DN 40 DN 50 DN 65 DN 80 DN 100 DN 150 DN 200 DN 100 x 50 DN 150 x 100 DN 200 x 100 200 x 150 300 x 150 250 x 200 300 x 200

ANSI (Inch)
0.5 and 0.75 1 1.5 2 2.5 3 4 6 8 4x2 6x4 8x4 8x6 12x6 10x8 12x8

TYPICAL ACTUATOR SIZE


30 30 30 40 40 45 45 50 70 40 45 45 50 50 70 70

APPROXIMATE WEIGHT OF VALVE AND ACTUATOR, kg


25 27 34 59 68 95 116 202 523 123 236 316 351 764 859 971

23

Product Flier

easy-er Valves
Typical Dimensions (Plain Bonnet and Standard Stem Diameter)
Face-to-Face Dimensions, A (mm)
VALVE SIZE EN DN 25 DN 40 DN 50 DN 65 DN 80 DN 100 DN 150 DN 200 ANSI (Inch) 1 1.5 2 2.5 3 4 6 8 DIN PN 16-40 160 200 230 290 310 350 480 600 PN 63-100 230 260 300 340 380 430 550 650 Class 150 Raised Face 184 222 254 276 298 353 451 543

PF51.1:E August 2005

ANSI Class 300 Raised Face 197 235 267 292 317 368 473 568 Class 600 Raised Face 210 251 286 311 337 394 508 610

Dimensions (mm) with Type 585C Actuators


VALVE SIZE EN DN 25 DN 40 DN 50 DN 65 DN 80 DN 100 DN 150 ANSI (Inch) 1 and 1.25 1.5 2 2.5 3 4 6 ACTUA ACTUA TOR SIZE 25 25 25 50 25 50 25 50 25 50 50 C 192 192 192 251 192 251 192 251 192 251 251 E 480 477 518 668 540 690 544 694 574 724 754

Dimensions (mm) with Type 657 and 667 Actuators


VALVE SIZE EN DN 25 DN 40 DN 50 DN 65 DN 80 DN 100 DN 150 DN 200 ANSI (Inch) 1 and 1.25 1.5 2 2.5 3 4 6 8 ACTUA ACTUA TOR SIZE 30 34 30 34 40 45 40 45 45 45 50 60 70 70 E C 289 333 289 333 333 406 333 406 406 406 406 473 536 536 Type 657 567 625 564 622 713 824 735 846 850 880 973 973 1091 1215 Type 667 605 700 602 697 759 933 781 955 959 989 1035 1035 1184 1308

24

Product Flier
PF51.1:E August 2005

easy-er Valves

Ordering Information
When ordering, please specify ...
Application Throttling or on-off Type of Application Reducing or relief Include chemical analysis of fluid if possible Specific gravity Fluid Temperature Minimum Inlet Pressures Normal Maximum Minimum flowing Normal flowing Pressure Drops Maximum flowing Maximum at shutoff Minimum controlled Flow Normal Maximum Maximum Permissible Noise Level, if Critical Shutoff Classification Required Line Size, Schedule, and End Connection Type Valve, Actuator, and Accessories

Controlled Fluid

F thi or other th product d t flier, fli select l t your choice h i wherever h From this a choice is offered. If you cannot find the selection you need, contact your nearest sales office or sales representative representative.

Note Neither Emerson, Emerson Process Management, Fisher, nor any of their affiliated entities assumes responsibility for the selection, use and maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end-user.

25

Product Flier

easy-er Valves
AUSTRIA Emerson Process Management AG Industrie Zentrum No Sud Strae 2a, obj M29 A 2351 Wr. Neudorf Tel. +43.2236.607 Fax +43.2236.60744 BELGIUM EPM NVSA De Kleetlaan 4 B 1831 Diegem Tel. +32.2.716.77.11 Fax +32.2.725.83.00 BULGARIA Emerson Process Management AG 22 Zlaten Rog Str. BG 1407 Sofia Tel. +359.2.962.94.20 Fax +359.2.962.94.30 CIS Emerson Process Management Malaya Trubetskaya Street 8 11th Floor CIS 119881 Moscow Tel. +7.095.232.69.68 Fax +7.095.232.69.70 CROATIA Emerson Process Management Tratinska 19 10000 Zagreb Tel. +385.1.309.42.20. Fax +385.1.309.44.69. CZECH Rep Emerson Process Management s.r.o. Hajkova 22 Cz 130 00 Praha 3 Tel. +420.2.710.35.600 Fax +420.2.710.35.655 DENMARK Emerson Process Management Hejrevang 11 DK 3450 Allerd Tel. +45.70.25.30.51 Fax +45.70.25.30.52 FINLAND EPM Oy Pakkalankuya 6 FIN 01510 VANTAA Tel. +358.0.201.11.200 Fax +358.0.201.11.250 FRANCE Emerson Process Management Europarc du chne 14 rue Edison BP 21 F 69671 BRON Cedex Tel. +33.4.72.15.98.00 Fax +33.4.72.15.98.99 GERMANY Emerson Process Management Gmbh & Co OHG Rheinische Str. 2 D 42781 HAAN Tel. +49.8153.939.0 Fax +49.8153.939.172 GREECE Kaminco Process Management SA 53 55, Akli Migouli po box 80115 GR 18510 PIRAEUS Tel. +30.210.4528.256/257 Fax +30.210.4528.273 HUNGARY Emerson Process Management Kft. Ersbet Kirlyn tja 1/c Hu 1146 Budapest Tel. +36.1.462.4000 Fax +36.1.462.0505 ITALY EPM/FisherRosemount Via Pavia 21 I 20053 Muggi (Mi) Tel. +39.39.2.702.1 Fax +39.39.2.780.750 NETHERLANDS Emerson Process Management Patrijsweg 140 Postbus 212 NL2289 EZ Rijswijk Tel. +31.70.413.66.66 Fax +31.70.390.68.15 NORWAY BJORGE A/S Postboks 6500 Etterstad Grenseveien 95 N 0606 OSLO Tel. +47.55.39.15.00 Fax +47.55.39.15.99 POLAND Emerson Process Management s.p.z.o.o. Ul. Konstruktorska 11 A PL 02673 Warszawa Tel. +48.22.54.85.240 Fax +48.22.54.85.231 PORTUGAL EPM /FisherRosemount Rua Alfredo da Silva 8 Bloco C Piso 0 Norte P2724508 Amadora Tel. +351.01.471.28.850 Fax +351.01.472.88.55 ROMANIA Emerson Process Management Str. Maior Gheorge Sontu 8 Sector 1 RO71264 Bucharest Tel. +40.21.260.03.86 Fax +40.21.260.03.85 SLOVAK Rep Emerson Process Management s.r.o. Hanulova 5/b SR 84101 Bratislava Tel. +421.2.643.62.182. Fax +421.2.642.87.245. SLOVENIA Intenta d.o.o. Tovarniska 15 Sl 8270 Krsko Tel. +386.74.90.22.40 Fax +386.74.90.22.41. SPAIN Emerson Process Management Ctra FuencarralAlcobendas Km 12.2; Edificio Auge 1 E 28049 Madrid Tel. +34.1.358.91.41 Fax +34.1.358.91.45

PF51.1:E August 2005


SWEDEN PEAB Process ABHammar Nokgardsvagen 11 S 66341 Hammaro Tel. +46.54.57.92.00 Fax +46.54.53.18.51 SWITZERLAND Emerson Process Management AG. Blegistr. 21 CH 6341 Baar Tel. +41.41.768.61.11 Fax +41.41.761.87.40 TURKEY Emerson Process Management Kisikli Cad Basaran Is N 81130 Altunizade TR skdar Istanbul Tel. +90.216.651.0909 Fax +90.216.651.0916 UKRAINE FisherRosemount Tereschenkovskaya St. 13, Rm. 58 252004 Kiev Tel. +380.44.246.46.56 Fax +380.44.246.46.58 UNITEDKINGDOM and MIDDLE EAST Emerson Process Management Horsfield Way Bredbury UK Stockport SK6 2SU Tel. +44.161.406.8826 Fax +44.161.406.8827 UZBEKISTAN Emerson Electric Beruniy Street Building N_83 of NBU, r 208 700 002 Tashkent Tel. +998.71.249.44.88 Fax +998.71.249.44.89

WEB site: www.fisher.com

easy-e, Cavitrol, ENVIRO-SEAL, FIELDVUE, HIGH-SEAL, Micro-Flute, Micro-Form, ValveLink, Whisper Trim, and Fisher are marks owned by Fisher Controls International LLC, a member of the Emerson Process Management business division of Emerson Electric Co. Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners. HART is a mark owned by the HART Communications Foundation. FOUNDATION fieldbus is a mark owned by the Fieldbus Foundation. This product may be covered by one or more of the following patents: 5,129,625; 5,131,666; 5,056,757; 5,230,498; and 5,299,812 or under pending patents. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Neither Emerson, Emerson Process Management, Fisher, nor any of their affiliated entities assumes responsibility for the selection, use and maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end-user.

Emerson Process Management Fisher Marshalltown, Iowa 50158 USA Cernay 68700 France Sao Paulo 05424 Brazil Singapore 128461 www.Fisher.com
26 E Fisher Controls International LLC 1997, 2005; All Rights Reserved
Printed in USA

Вам также может понравиться