Multilin 850
Innovative Feeder Protection System for Industrial & Distribution Utility Feeder Applications
The Multilin 850 relay is a member of the Multilin 8 Series protective relay platform and has been designed for the management, protection and control of distribution feeder applications. The Multilin 850 is used to provide primary or backup protection for underground and overhead medium voltage feeders from distribution and industrial power networks. Designed with advanced communications options and detailed asset monitoring capabilities, the Multilin 850 provides advanced functionality, including high-performance protection, extensive programmable logic and flexible configuration capabilities. Built from a rich history and legacy in providing advanced protection and control solutions and utilizing advanced design practices, superior technology, and state-of-the art test and manufacturing facilities, GE is raising the bar on system performance, quality and reliability.
10 YEAR
WORLDWIDE
WARRANTY
Key Benefits
Increase uptime with industry-leading quality, reliability and design processes ensuring long operational life Reduce downtime with relay environmental diagnostic information Simplify testing and increase process uptime withlow-insertion force, draw-out construction Designed with no electrolytic capacitors and manufactured to IPC-A 610 Class 3 industry standard Minimize system configuration time with optional point-to-point Wi-Fi connectivity, allowing secure, local relay programming and diagnostic retrieval
Key Applications
Oil & Gas / Petrochemical / Refineries
Protection and control for feeders and incomers Reliable motor-bus auto transfer and high-speed interlocking schemes Distribution load-shedding schemes
Distribution Utility
Protection and control for radial or looped distribution circuits Auto-reclosing control schemes Distribution generation interconnect protection
imagination at work
GEDigitalEnergy.com
GEDigitalEnergy.com
1 2 3
4
4 5 6
No Electrolytic Capacitors
Increasing quality and reliability for continuous plant operations by removing high failure components
Draw-Out
Providing simplified device fleet management
GEDigitalEnergy.com
Front View
Menu path display indicating location within menu structure Graphic Control Panel (GCP) Soft navigation menu Soft menu navigation keys LED status indicators Navigation keys
User-programmable pushbuttons
Rear View
Grounding screw Power supply Analog I/O Advanced communications module (fiber optic port) Standard communications module (Ethernet port)
GEDigitalEnergy.com
Environmental Monitoring
The 850 Feeder Protection System implements a patented Environmental Monitoring system that measures and provides operating condition information. The 850 continuously monitors the
GEDigitalEnergy.com
Detailed Diagnostics
EnerVista Launchpad
The setup tools within Launchpad allow for the configuration of devices in real-time, by communicating via serial, Ethernet or modem connections, or offline, by creating device setting files to be sent to devices at a later time.
GEDigitalEnergy.com
D400
D400
0 300 CH ML SWIT
A
000 ML3 ITCH SW 000 ML3 ITCH SW
B
000 ML3 ITCH SW 000 ML3 ITCH SW
Solution:
Being able to dynamically balance and maintain loads in this type of separation scenario requires an intelligent device that has advanced automation and control logic capabilities. The Multilin 850 provides distribution networks and industrial facilities with the system stability and cost saving options required to maintain power system availability and process continuity. With high resolution sampling (128 samples per cycle Oscillography), comprehensive monitoring & metering (measuring up to the 25th harmonic), and advanced protection features including sensitive reverse power, distribution utilities and industrial facilities rely on GE to deliver power system reliability, efficiency and security required.
Solution:
The Multilin 8 Series offers the ideal solution for protecting, monitoring and controlling electrical cables and overhead lines from disturbances or faults. With a fast protection pass, running every 2 msec, the 8 Series provides unmatched overcurrent , overvoltage, undervoltage, and frequency protection. Supporting the latest in industry standard communication protocols, including IEC 62439/PRP and IEC 61850, the Multilin 8 Series easily integrates into new or existing networks.
GEDigitalEnergy.com
FIBER/COPPER CB1
850 850
CB2
850
Solution
The Multilin 850 offers seamless automated bus transfer scheme solutions, maximizing system availability and process uptime. Using a minimal amount of programming, the 850 eliminates the need for any discrete devices and device inter-wiring by integrating all the functions directly into the intelligent device. With advanced communications including embedded support for IEC 61850 peer-to-peer communications, inter-relay wiring and physical I/O can be eliminated. The 850 provides a fast, automatic bus transfer solution that is easy to design, configure, and maintain.
TCB1 CB3 CB4 CB5 CB6
Technical Application Example 2: Arc Flash Mitigation & Zone Selective Interlocking
Challenge
An arc flash event in an industrial or utility distribution system is a catastrophic event that causes severe damage to equipment and often results in extended system and process downtime. These events require a solution that can quickly and reliably detect and issue a coordinated trip command to clear the fault as fast as possible, reducing total incident energy, equipment damage and system downtime.
Fiber LAN, single or redundant, for added security
Solution
With embedded support for IEC 61850, the 850 provides high-speed data exchange between relays without the use of a communications hub or ancillary equipment. As a coordinated system, interlocked protection can be enabled, to provide the necessary bus protection. Fast clearance can be achieved for a fault that occurs during maintenance while still maintaining coordination should a fault occur on a different feeder under normal operation.
CB2
CB3 Fault 2
GEDigitalEnergy.com
Solution
For customers wanting a customized auto-reclose scheme, a device with integrated logic capabilities is necessary. The 850 offers comprehensive protection and integrated auto-reclose functions. Up to four auto-reclose operations are possible, each with a programmable dead time. For each reclose shot, the relay can be programmed to block IOC elements, and to adjust the curve characteristics of any TOC element. The number of shots can be reduced by high currents.
S
52 52
52
52
52
Solution:
The Multilin 850 offers effective, reliable management of distribution feeders. With dynamic, sensitive settings, the 850 provides secure and dependable protection. With six setting groups the 850 provides the sensitive settings range and groups required to ensure no compromise is made to meet changing system conditions. These setting groups can be enabled automatically or manually to address system needs, ensuring greater system reliability and efficiency.
52
10
GEDigitalEnergy.com
ANSI Device 25 (2) 27P (2) 32 (2) 32N 27X 49 50BF 50G
27P V_2 3 CTs 50BF CLP 51P 2 51G CT 50G/ 50G 51G 67G 50P 2 67P 51_2 50_2 67_2 32 2 49 32N 51N 2 50N 2 67N RGF V_0 2 59P 2 59N 59_2 VTFF 81U 4 81O 2 81R
Description Synchrocheck Phase Undervoltage Directional Power Wattmetric Ground Fault (Wattmetric zero sequence directional) Auxiliary Undervoltage Cable Thermal Model Breaker Failure Ground Ground Instantaneous Overcurrent Sensitive Ground Instantaneous Overcurrent Neutral Instantaneous Overcurrent Phase Instantaneous Overcurrent Negative Sequence Instantaneous Overcurrent Ground Time Overcurrent Sensitive Ground Time Overcurrent Neutral Time Overcurrent Phase Time Overcurrent Negative Sequence Time Overcurrent AC Circuit Breaker Neutral Overvoltage Phase Overvoltage Auxiliary Overvoltage Negative Sequence Overvoltage Ground Directional Element Sensitive Ground Directional Element Neutral Directional Element Phase Directional Element Negative Sequence Directional Element Automatic Recloser Overfrequency Underfrequency Frequency Rate of Change Restricted Ground Fault Broken Conductor Voltage Transformer Fuse Failure
50SG 50N (2) 50P (2) 50_2 51G 51SG 51N (2) 51P (2) 51_2 52 59N
BREAKER
52 79 TRIP CLOSE
MONITORING
67N
2
27X 2 LOAD
59X
67P 67_2
892770A1.CDR
9.90
8.84
7.5
8.42
1.5
GEDigitalEnergy.com
11
52
WYE VT CONNECTION
SEE VT WIRING IN INSTRUCTION MANUAL
L O A D
SEE GROUND INPUT WIRING IN INSTRUCTION MANUAL J1 J2 J3 J4 J5 J6 J7 J8 K7 K8 J9 J10 J11 J12 J13 J14 J15 J16 VA VA VB VB VC VC VX VX A1 A2 A3
CONTROL POWER
SLOT A
CURRENT INPUTS
GROUND
VOLTAGE INPUTS
SLOTS J&K
TRIP
NEUTRAL
GROUND
BUS
IA IA N
IC N IG N Isg N
LINE
DIGITAL INPUTS
DIGITAL INPUT 2 DIGITAL INPUT 3 DIGITAL INPUT 4 DIGITAL INPUT 5 DIGITAL INPUT 6 DIGITAL INPUT 7 COMMON
V CLOSE
52a
TRIP COIL
TRIP CIRCUIT
OUTPUT RELAYS
52b
CLOSE COIL
AUXILIARY
CONTACT INPUT 1 CONTACT INPUT 2 CONTACT INPUT 3 CONTACT INPUT 4 CONTACT INPUT 5 CONTACT INPUT 6 CONTACT INPUT 8 CONTACT INPUT 9 CONTACT INPUT 10 CONTACT INPUT 11 CONTACT INPUT 12 CONTACT INPUT 13 CONTACT INPUT 14 CONTACT INPUT 15 CONTACT INPUT 16 RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED
CONTACT INPUT 7
AUXILIARY
H1 H2 H3 H4 H5 H6 H7 H8 H9 H10
AUXILIARY
AUXILIARY
AUXILIARY
H11 H12 H13 H14 H15 H16 H17 R18 H19 H20 H21 H22 H23 H24
AUXILIARY
ETHERNET
[BACK PANEL ETHERNET PORT RJ45 OR ST]
AUXILIARY
USB
[FRONT PANEL LOCAL PROGRAMMING PORT]
ETHERNET
SLOT E: COMMUNICATIONS
AUXILIARY
FIBER2
ST
ST
AUXILIARY
PERSONAL COMPUTER
Front Panel
USB TYPE B
COMMUNICATIONS RESERVED
CAN
IRIG-B
RS485
COM
WIFI
E E E E E E E E E E 1 2 3 4 5 6 7 8 9 10
12
GEDigitalEnergy.com
Power Supply
High Voltage: Low Voltage: Redundant Feature: No Electrolytic Capacitor: Ride-through: INPUTS
Pulsed output is energized for one second and then de-energized for one second after the programed energy increment.
AC Currents
CT Rated Primary: CT Rated Secondary: Nominal Frequency: Burden: Conversion Range: 1 to 12000 A 1 A or 5 A based on relay ordering 50 and 60 Hz < 0.2 VA at rated secondary Standard CT: 0.02 to 46 x CT rating RMS symmetrical Sensitive Ground CT: 0.002 to 4.6 x CT rating RMS symmetrical CT Accuracy: 0.1 to 2.0 x CT 0.25% of reading or 0.1% of rating (whichever is greater) > 2.0 x CT 1.0% Short Term CT Withstand: 1 second at 100 x rated current 2 seconds at 40 x rated current continuous at 3 x rated current 10 to 260 V 0.5% of reading from 10 to 240 V 50 or 60 Hz <0.25 VA at 120 V 1 to 275 V continuous at 260 V to neutral 1 min/hr at 420 V to neutral
Curve Shape:
AC Voltage
VT Range:. VT Accuracy: Nominal Frequency: Burden: Conversion Range: Voltage Withstand:
Overfrequency (81o)
Pickup Level: Dropout Level: Pickup Time Delay: Dropout Time Delay:
Contact Inputs
Number of Inputs: Wet Contacts: Selectable Thresholds: Tolerance: Recognition Time: Debounce Time: Continuous Current Draw: OUTPUTS Based on relay ordering 300 VDC maximum 17, 33, 84, 166 VDC 10% <1/8 cycle 0.0 to 16.0 ms in steps of 0.5 ms 2 mA
Operate Time:
Form-C Relays
Configuration: Contact Material: Operate Time: Continuous Current: Make and carry for 0.2s: Break (DC Inductive, L/R=40 ms): electromechanical silver-alloy <8 ms 10 A 30 A per ANSI C37.90 24 V / 1 A 48 V / 0.5 A 125 V / 0.3 A 250 V / 0.2 A Break (DC Resistive): 24 V / 10 A 48 V / 6 A 125 V / 0.5 A 250 V / 0.3 A Break (AC Inductive): Break (AC Resistive): 720 VA @ 250 VAC Pilot duty A300 277 VAC / 10 A 3-phase positive and negative active energy measurement, 3-phase positive and negative reactive energy measurements Polarizing Voltage Threshold: Current Sensitivity Threshold: Characteristic Angle: Angle Accuracy: Operation Time (FlexLogic Operands): Relay Connection: Quadrature Voltage:
Underfrequency (81U)
Pickup level: Dropout level: Pickup time delay: Dropout time delay: Minimum operating voltage: Minimum operating current: Level accuracy: Timer accuracy:
Operate time:
Pulsed Outputs
Mode:
GEDigitalEnergy.com
13
Synchrocheck(25)
Maximum Frequency Difference: Maximum Angle Difference: Hysteresis for Maximum Frequency Difference Difference: Breaker Closing Time: Dead Source Function: Dead/Live Levels for Bus and Line:
Transient Recorder
Default AC Channels: Configurable Channels:
0.01 to 0.10 Hz in steps of 0.01 Hz 0.000 to 6000.00 s in steps of 0.001 s None, LB & DL, DB & LL, DB & DL, DB OR DL, DB XOR DL 0.00 to 1.25 x VT in steps of 0.01 x VT
non-volatile memory
1024 relay name, order code, firmware revision any element pickup, any element operate, digital input change of state, digital output change of state, selftest events non-volatile memory to one microsecond 16 1 cycle, 1 sec., 30 sec., 1 min., 15 min., 30 minutes, 1 hour any analog parameter from the list of available analog parameters continuous, trigger any digital flag from the list of digital flags 0 to 100% in steps of 1% 16 preset, compare reset, up/down, set to pre-set, freeze/ reset, freeze/count
Event Recorder
Number of events Header: Content:
Autoreclose (79)
Number of Breakers: Number of Poles: Reclose attempts: Blocking:
Adjustability:
Data Logger
Data Logger Channels: Data Logger Rate: Inputs: Data Collection Mode: Trigger Source: Trigger Position:
Timer Accuracy:
Demand
Measured values: Phase A/B/C present and maximum current, three-phase present and maximum real/reactive/apparent power Thermal Exponential, 90% response time (programmed): 5, 10, 15, 20, 30, or 60 min Block Interval / Rolling Demand, time interval (programmed): 5, 10, 15, 20, 30, or 60 min
Measurement type:
Digital Counters
Number of Counters: Counting: Programmability:
RMS Parameters
Currents Parameters: Phase A, B, C, Neutral, Ground and Sensitive Ground 0.2% of reading or 0.2% of rated (whichever is greater) from 0.1 to 2.0 x CT 0.25% of reading > 2.0 x CT Voltages Parameters: Wye VTs: A-n, B-n, C-n, A-B, B-C, C-A, Average Phase, Neutral and Residual Delta VTs: A-B, B-C, C-A, Neutral and Residual Accuracy: Real Power (Watts) Range: Parameters: Accuracy: -214748364.7 kW to 214748364.7 kW 3-phase; per phase if VT is Wye 1.0% of reading or 0.1 kW (whichever is greater) at -0.8 < PF -1.0 and 0.8 < PF < 1.0 0.5% of reading from 10 to 208 V
Phasors
Currents Current pickup level: Real power pickup level: Reactive power pickup level: Apparent power pickup level: Apparent power pickup level: Level accuracy: 10 to 10000 A in steps of 1 A 0.1 to 300000.0 kW in steps of 0.1 kW 0.1 to 300000.0 kVar in steps of 0.1 kVar 0.1 to 300000.0 kVA in steps of 0.1 kVA 96-98% of Pickup level 2% 0.01 Lead to 1 to 0.01 Lag in steps of 0.01 0.01 Lead to 1 to 0.01 Lag in steps of 0.01 0.000 to 6000.000 s in steps of 0.001 s Magnitude Accuracy: Angle Accuracy: Angle Accuracy: Voltages Parameters: Wye VTs: A-n, B-n, C-n, A-B, B-C, C-A, Average Phase, Neutral and Residual; Delta VTs: A-B, B-C, C-A, Neutral and Residual 5% of reading from 10 to 208 V 0.5 (10 V<V< 208 V) Positive, Negative and Zero Sequence Current Magnitude Accuracy: 0.5% of reading or 0.2% of rated (whichever is greater) from 0.1 to 2.0 x CT 4.0% of reading > 2.0 x CT Parameters: Magnitude Accuracy: Phase A, B, C, Neutral and Ground 0.5% of reading or 2.0% of rated (whichever is greater) from 0.1 to 2.0 x CT 0.4% of reading > 2.0 x CT 2
Accuracy:
14
GEDigitalEnergy.com
Accuracy:
Range: Parameters: Update Rate: Accuracy:
2.0% of reading
-2147483.647 MVarh to 214748364.7 MWh 3-phase only 50 ms 2.0% of reading
USB
Standard specification: Data transfer rate: Compliant with USB 2.0 115 kbps Opto-coupled up to 115 kbps 1 ms typical None, Odd, Even Modbus RTU, DNP 3.0, IEC 608705-103 1200 m (4000 feet) 2 kV
Serial
RS485 port: Baud rates: Response time: Parity: Protocol: Maximum distance: Isolation:
Apparent Power (VA) Range: Parameters: Accuracy: Power Factor Parameters: Range: Accuracy:
Protocol:
Modes: Two Ports:
Watt-hours (positive and negative) Range: Parameters: Update Rate: -2147483.647 MWh to 214748364.7 MWh 3-phase only 50 ms
Protocols:
Reference Standard
EN60255-5 IEC61000-4-18IEC60255-22-1 EN61000-4-2/IEC60255-22-2 EN61000-4-3/IEC60255-22-3 EN61000-4-4/IEC60255-22-4 EN61000-4-5/IEC60255-22-5 EN61000-4-6/IEC60255-22-6 EN61000-4-7/IEC60255-22-7 IEC60255-11 CISPR11 /CISPR22/ IEC60255-25 IEC60255-21-1 IEC60255-21-2 IEC60255-21-3 IEC61000-4-8 IEC61000-4-9 IEC61000-4-10 IEC61000-4-11 IEC61000-4-16 IEC60529 IEC60068-2-1 IEC60068-2-2 IEC60068-2-30 IEEE/ANSI C37.90.1 IEEE/ANSI C37.90.1 IEEE/ANSIC37.90.2 IEEE/ANSIC37.90.3 UL508 UL C22.2-14 UL1053
Test Level
2.3 kV 5KV 2.5 kV CM, 1 kV DM Level 4 Level 3 Class A and B Level 3 & 4 Level 3 Class A & B 15% ripple, 200msinterrupts Class A Class 1 Class 1 Class 2 Class 5 Class 4 Class 4 0, 40, 70, 80% dips, 250/300 cycle interrupts Level 4 IP40 front, IP10 Back -40C 16 hrs 85C 16hrs 6day variant 2 4KV, 2.5 khz 2.5KV, 1 Mhz 20V/m, 80 MhZ to 1Ghz 8KV CD/ 15 kV AD e83849 NKCR e83849 NKCR7 e83849 NKCR
Approvals
Applicable Council Directive
CE compliance Low voltage directive EMC Directive cULus North America ISO Manufactured under a registered quality program
Environmental
According to
EN60255-5 / EN60255-27 EN60255-26 / EN50263 EN61000-6-2 / EN61000-6-4 UL508 UL1053 C22.2.No 14 ISO9001 Ambient temperatures: Storage/Shipping: Operating: Humidity: Altitude: Pollution Degree: Overvoltage Category: Ingress Protection: - 40C to 85C -40C to 60C Operating up to 95% (non condensing) @ 55C (As per IEC60068-2-30 Variant 2, 6days) 2000m (max) II III IP54 Front, IP10 back
GEDigitalEnergy.com
15
Ordering
850
Base Unit Language Phase Currents Bank 1/2 Ground Currents 850 E P1 P5 G1 G5 S1 S5 H A N A Faceplate Current Protection G S M A Voltage Monitoring & Protection Control S P B F C Monitoring Communications B C S 1 1 2 Fiber Optic Connector Wireless Communication Security E E P E N S N W B A
**
NN **
Description
English Language; High Voltage PS, Graphical Control Panel English 1A three phase current inputs 5A three phase current inputs 1A ground input 5A ground input 1A ground + 1A sensitive ground input 5A ground + 5A sensitive ground input 110 - 250 V dc/110 - 230 Vac 2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low / High voltage, Int/Ext supply) None 2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low / High voltage, Int/Ext supply) Color Graphical Display Basic = 50P, 50N, 50G, 51P, 51N, 51G Standard = Basic + 50SG, 50_2, 51SG, 51_2, RGF Advanced = Standard + 49,67P, 67N, 67G, 67SG, 67_2, Load Encroachment, Broken Conductor Standard = 27P, 27X, 59P, 59N, 59X, 81O, 81U Advanced = Standard + 25, 32, 32N, 55, 59_2, 81R Basic Standard = Basic + Flexlogic, CLP, 50BF, Trip Bus Advanced = Standard + Autorelcose, Bus Transfer (Requires voltage option P) Basic Basic + Advanced Breaker Health Standard = Front USB, 1 x Rear RS485 : Modbus RTU, DNP3.0, IEC60870-5-103 + 1 x Ethernet (Modbus TCP) Advanced = Front USB, 1 x Rear RS485 + 2 x Ethernet Fiber, MODBUS RTU / TCP, DNP3.0, IEC 60870-5-103/104, 1588, SNTP Advanced + PRP Advanced + PRP + IEC 61850 None ST, Multi-mode 850nm None WiFi 802.11 Basic Advanced - CyberSentry
Digital Energy 650 Markland St. Markham, ON Canada L6C 0M1 Toll Free (NA Only): 1-800-547-8629 Tel: 905-927-7070 Fax: 905-927-5098 gedigitalenergy@ge.com
GEDigitalEnergy.com
IEC is a registered trademark of Commission Electrotechnique Internationale. ISO is a registered trademark of the International Organization for Standardization. NERC is a registered trademark of North American Electric Reliability Council. ANSI is a registered trademark of American National Standards Institute, Incorporated. Modbus is a registered trademark of Schneider Automation.
GE, the GE monogram, Multilin, FlexLogic, EnerVista, MDS and PowerOn are trademarks of the General Electric Company. GE reserves the right to make changes to specifications of products described at any time without notice and without obligation to notify any person of such changes. Copyright 2013, General Electric Company. All Rights Reserved.
GEA-12715A(E) English 130930