NOTICE

1. Read this manual thoroughly before using the VT210S, and store in
a safe place for reference.
2. Make sure that this manual is delivered to the final user.






MEIDENSHA CORPORATION


MEIDEN
AC SPEED CONTROL EQUIPMENT
THYFREC-VT210S
400V System 37 to 315kW (C/T)
400V System 45 to 370kW (V/T)

QUICK START GUIDE
Feb 2000 QS210S Rev1
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 1

Warning




This Quick Start Instruction Guide is intended as a guide only.

Read the Instruction Manual thoroughly before using the VT210S.

Use extreme caution during installation.

Do not open the front cover while power is applied.

Always ground the Inverter heatsink.

If in doubt, refer to your supplier or

MEIDEN DRIVELINE Tel: 01908 276000

The information contained in this publication, including numerical data, has
been prepared as a general guide to the product. No responsibility is assumed
for errors herein. Meiden Europe Ltd reserve the right to make changes to this
document and Instruction Manual at any time.

E&OE
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 2
Installation

Install the Inverter vertically, so that the cable glands face downwards.
Allow for the correct spacing around the Inverter for ventilation
(X +>50mm, Y +>200mm). Fig. 1.

Always ensure that the Inverter is switched off before wiring.
Please note that TBA must be set in position shown (Fig. 2.)
for 380-400V operation, and in position 1-2 for 415-460V
operation.

Connect wiring as shown in Fig. 2. Make sure that correct
short circuit protection devices are fitted and best wiring
practises are observed (see page 2-3 in the supplied
manual).

A Ferrite is supplied with the filter, which must be fitted to
meet EMC compliance. The motor phase cables must be
inserted through the output ferrite as per EMC Filter Kits
Guide to Installation and Use.
Voltage Surge

For long motor cable lengths (>30m), a motor choke can be ordered which
must be fitted between the Inverter and the motor. Motor cables must be
screened at both ends.

Connect inputs as shown in Fig. 3. or to suit your application. If using a
potentiometer, connect the wiper to FSV terminal. Analogue signal
cables MUST be screened. Connect one end of the screen to COM.
The COM terminals are linked internally.
RY0 is isolated and must NOT be connected to COM.
Test Running the Drive

Please note that VT210S drives are supplied either as Constant Torque or Variable Torque and cannot be changed
by the user. Operating the drive type is identical in all other ways although maximum and minimum values of some
parameters may vary.

Default settings allow the basic running of the motor to prove the system, but first set:

B00-1 set 31 assuming 415V, 50Hz B00-5 set motor rated current (A)
supply, and max freq B00-4 Output Voltage may have
requirement of 50Hz. to be set for non-standard
motors.

On power up, the Inverter display will cycle through a self-diagnostics check, and then show confirming the
drive is in a ready state.

Press FWD on the keypad and the motor will ramp up to 10Hz in a forward direction. The display will change
from to ( local frequency setting A00-0).
Press REV and check that the motor changes direction. Now press STOP, the motor will stop.

Acceleration and Deceleration will be default values at this stage.

(R RUN)
(F JOG)
(R JOG)
N.B. Terminal/Busbar
arrangements differ on
larger drives.
(Refer to page 2-8 in the
supplied manual).
Fig.2.
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 3
Remote Running

The inverter is set to run in Local (keypad) mode.

With the drive display showing press STOP + LCL together to toggle between local and remote modes.

From default settings, the inverter is set up to accept the following signal inputs: (page 6-11).

FRUN Forward Run PSI1 Reverse Run
RST Reset PSI2 Forward Jog
EMS Emergency Stop ** PSI3 Reverse Jog
FSV 0-10V signal reference

** by default is a normally open contact, coast to stop. Refer to manual (page 6-10) for options.

Set B08-0 to 12 to power up in remote mode (page 6-16).

If necessary, set new Accel/Decel times in A01-0 and A01-1 (page 6-3).
Jog Accel/Decel can be set in B21-2 and B21-3 (page 6-21).

Braking is set on from default.

From default the signal reference is obtained from the 0-10V analogue input. This can be from a number of sources
including a potentiometer as shown in Fig. 3.
Configuration

The Inverter parameter menu system is grouped into Modes and Blocks
according to their functions and frequency of usage.

To manoeuvre around the menu system, pressing the MOD key will change
between the Monitor, A and B block parameters. Pressing the key will
change through the parameters in that block. See Fig. 4.

The display will alternate between the parameter number and its current value.
Press SET to change the parameter value. Increase/decrease the value by
using the and keys, and move to next digit by pressing the key.
When you have set the parameter to the value you want, press SET.

It is possible to reset to default values when the drive is not running, by setting
parameter B06-3 to 9 (page 6-12).

The parameter default values are such that the inverter can be quickly, and
safely, checked after power on. However, some of the default values may
need to be changed to suit specific applications.

From default, only the Basic Function parameters can be accessed.

Set parameter A05-0 from 2221 to 1111 to release further parameters blocks.
Fig.4.
Torque Boost

A02-0 Increase this value for loads with high Starting Inertia.
(Refer to pages 6-3/6-6).
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 4
Other Useful Features

LCD Operator Panel - Upload/Download parameters, save 10 programs
Contact you Supplier or Meiden Europe Ltd for more information.
Parameter (password) protection - B06-0 Pages 6-11/6-19
Programmable outputs - B05-0/2 Pages 6-11/6-18
Dynamic Braking - B80-1 Pages 7-3/7-4
Pattern Run - B5x-x Pages 6-38/6-39
PID Control - B43-x Pages 6-37/6-43
4-20mA input - B04-1 Page 6-11
Auxiliary Input - B24-0 Pages 6-22/6-29
Arbitary Scale - B05-2 Pages 6-11/6-18
Setting Pre-set Speeds

As well as running from 0-10V analogue reference, it is possible to set up to 8 pre-set speeds (plus Jog). Digital
inputs PSI1-PSI5 can be programmed in a number of ways to suit the application.

A worked example of using 10Hz, 13.20Hz, 25Hz, 40.32Hz and 50Hz pre-set speeds is shown below:

Set B03-1 to 0 turns off F Jog Set B04-6 to 5 uses PSI5 as S2
Set B03-2 to 0 turns off R Jog Set B20-0 to 10.00 Prog Freq 0 - 10Hz
Set B04-2 to 2 uses PSI2 as PROG Set B20-1 to 13.00 Prog Freq 1 - 13.20Hz
to enable pre-set speeds Set B20-2 to 25.00 Prog Freq 2 - 25Hz
Set B04-4 to 3 uses PSI3 as S0 Set B20-3 to 40.32 Prog Freq 3 - 40.32Hz
Set B04-5 to 4 uses PSI4 as S1 Set B20-4 to 50 Prog Freq 4 - 50Hz

Using inputs PSI3-PSI5 as binary inputs (see Fig. 5) it is possible to set any of the speeds. Please note that it is also
possible to set independent accel/decel ramps to each pre-set speed. (Refer to B40-0, B41-x and B42-x on pages
6-37/6-40).
Sequence Command Selected Frequency
Prog S2 S1 S0

ON OFF OFF OFF Prog Freq 0 - 10Hz
ON OFF OFF ON Prog Freq 1 - 13.2Hz
ON OFF ON OFF Prog Freq 2 - 25Hz
ON OFF ON ON Prog Freq 3 - 40.32Hz
ON ON OFF OFF Prog Freq 4 - 50Hz
ON ON OFF ON Prog Freq 5 - Unset
ON ON ON OFF Prog Freq 6 - Unset
ON ON ON ON Prog Freq 7 - Unset
OFF ANY ANY ANY Analogue I/P
Fig.5.
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 5
Param Description

Monitor/(Display) Parameters
Output frequency
D00-0 O/P frequency (Hz)
D00-1 O/P frequency (%)
D00-2 O/P frequency (AS)
Frequency Setting
D01-0 Set frequency (Hz)
D01-1 Set frequency (%)
D01-2 Set frequency (AS)
Output (O/P) current
D02-0 O/P current (A)
D02-1 O/P current (%)
D02-2 OLT monitor (%)
D02-3 Heatsink temperature (C)
Voltage
D03-0 DC voltage (V)
D03-1 O/P voltage command (V)
Sequence status
D04-0 I/P
D04-1 O/P
Extended monitor
D05-0 Fault history
D05-1 Trace data entry
D05-2 Non-default parameter list
D05-3 Cumulative cond time (Hrs)
D05-4 Cumulative run time (Hrs)
D05-5 CPU version
D05-6 ROM version
Pattern run monitor
D06-0 Step No.
D06-1 Remaining time (s)
Speed detection monitor (ASR)
D07-0 Detection speed (Hz)
D07-1 Detection speed (%)
D07-2 Detection speed (AS)

A Parameters
Frequency setting
A00-0 Set local frequency (Hz)
A00-1 Set jog frequency (Hz)
Acceleration/Deceleration times
A01-0 Acceleration time - 1 (s)
A01-1 Deceleration time - 1 (s)
Torque boost
A02-0 Torque boost voltage (%)
A02-1 Reduced volt squ law trq (%)
A02-2 Auto torque boost gain
A02-3 Slip compensation gain (%)
DC brake
A03-0 DC braking voltage (%)
A03-1 DC braking time (s)
Custom parameters
A04-0 Custom - 0 (Ref B07-0)
A04-1 Custom - 1 (Ref B07-1)
A04-2 Custom - 2 (Ref B07-2)
A04-3 Custom - 3 (Ref B07-3)
A04-4 Custom - 4 (Ref B07-4)
A04-5 Custom - 5 (Ref B07-5)
A04-6 Custom - 6 (Ref B07-6)
A04-7 Custom - 7 (Ref B07-7)
Block B skip parameters
A05-0 Skip selector (1111-2221)

B Parameters - Basic Functions
Output ratings
B00-1 Preset V/F pattern
B00-2 Max O/P freq (Fmax) (Hz)
B00-3 Base freq (Hz)
B00-4 O/P voltage (V)
B00-5 Motor rated current (A)
B00-6 Carrier frequency (kHz)
Control methods
B01-0 Run/stop
B01-1 Inhibit (EMS)
B01-2 Control source
Start/stop frequency
B02-0 Start freq (Hz)
B02-1 Stop freq (DC brake start) (Hz)
Min - Max







































0.10 - Fmax
0.10 - Fmax

0.1 - 6000
0.1 - 6000

0.0 - 10.0
0.0 - 25.0
0.00 - 10.00
0.0 - 5.0

0.1 - 10.0
0.0 - 20.0










1111 - 2221



10 - 59
3.0 - 440.0
0.0 - 440.0
0 - 460
Icrx0.3 - Irc
3 - 8

1111 - 3223
11 - 32
11 - 22

0.1 - 60.0
0.1 - 60.0
Param Description

B Parameters - Basic Functions
Prog I/P config 1 - operating commands
B03-0 R RUN
B03-1 F JOG
B03-2 R JOG
B03-3 HOLD
B03-4 BRAKE
B03-5 PICK
B03-6 COP
B03-7 CSEL
B03-8 IPASS
Prog I/P config 2 - select commands
B04-0 VFS
B04-1 IFS
B04-2 PROG
B04-3 CFS
B04-4 S0
B04-5 S1
B04-6 S2
B04-7 FUP
B04-8 FDW
B04-9 FUP/FDW step (Hz)
Meter O/P gain/scale multiplier
B05-0 O/P gain (FM)
B05-1 O/P gain (AM)
B05-2 AS display coeff (AS)
Protection/operation (PP/O) locks
B06-0 PP/O locks
B06-1 Reverse lock
B06-2 Fault history buffer clear
B06-3 Default value load
Custom parameter register
B07-0 Custom - 0 (Ref A04-0)
B07-1 Custom - 1 (Ref A04-1)
B07-2 Custom - 2 (Ref A04-2)
B07-3 Custom - 3 (Ref A04-3)
B07-4 Custom - 4 (Ref A04-4)
B07-5 Custom - 5 (Ref A04-5)
B07-6 Custom - 6 (Ref A04-6)
B07-7 Custom - 7 (Ref A04-7)
Operation panel initial mode
B08-0 Initial mode
B08-1 Operation monitor
B08-2 LCD OPU monitor
B08-3 LCD OPU bar graph

B Parameters - Extended Functions
Program frequency setting
B20-0 Program frequency - 0 (Hz)
B20-1 Program frequency - 1 (Hz)
B20-2 Program frequency - 2 (Hz)
B20-3 Program frequency - 3 (Hz)
B20-4 Program frequency - 4 (Hz)
B20-5 Program frequency - 5 (Hz)
B20-6 Program frequency - 6 (Hz)
B20-7 Program frequency - 7 (Hz)
Acceleration/deceleration times
B21-0 Acceleration time 2 (s)
B21-1 Deceleration time 2 (s)
B21-2 Jog acceleration (s)
B21-3 Jog deceleration (s)
B21-4 S curve characteristics (s)
B21-5 Time unit multiplier
Frequency skip
B22-0 Skip frequency 1 (Hz)
B22-1 Skip band 1 (Hz)
B22-2 Skip frequency 2 (Hz)
B22-3 Skip band 2 (Hz)
B22-4 Skip frequency 3 (Hz)
B22-5 Skip band 3 (Hz)
Ratio Interlock setting
B23-0 Polarity setting (A&B)
B23-1 Coefficient A value
B23-2 Bias B value (Hz)
B23-3 Upper limit (Hz)
B23-4 Lower limit (Hz)
I/P terminal function
B24-0 I/P terminal mode
B24-1 AUX I/P gain setting
O/P terminal function
B25-0 FM/AM O/P parameters
B25-1 RUN terminal parameters
B25-2 ATN terminal parameter
Min - Max



0 - 16
0 - 16
0 - 16
0 - 16
0 - 16
0 - 16
0 - 16
0 - 16
0 - 16

0 - 16
0 - 16
0 - 16
0 - 16
0 - 16
0 - 16
0 - 16
0 - 16
0 - 16
0.01 - 2.00

0.20 - 2.00
0.20 - 2.00
0.01 - 100.0

1111 - 1239
11 - 22
0 - 9999
0 - 9999

0.00 - 99.9
0.00 - 99.9
0.00 - 99.9
0.00 - 99.9
0.00 - 99.9
0.00 - 99.9
0.00 - 99.9
0.00 - 99.9

11 - 32
0.0 - 9.9
0.0 - 9.9
0.0 - 9.9



0.10 - Fmax
0.10 - Fmax
0.10 - Fmax
0.10 - Fmax
0.10 - Fmax
0.10 - Fmax
0.10 - Fmax
0.10 - Fmax

0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0
0.0 - 5.0
1 - 3

0.10 - 440.00
0.0 - 10.0
0.10 - 440.00
0.0 - 10.0
0.10 - 440.00
0.0 - 10.0

11 - 22
0.000 - 10.000
0.00 - 440.00
0.10 - 440.00
0.10 - 440.00

1111 - 1232
0.000 - 5.000

00 - 88
0 - 15
0 - 15
Parameter Listing
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 6
Param Description

B Parameters - Extended Functions
Detect levelssequence O/P
B26-0 ATN detect band (%)
B26-1 Current det level (IDET) (%)
B26-2 Speed det level 1 (SPD1) (%)
B26-3 Speed det level 2 (SPD2) (%)
Retry/Pick up
B28-0 No. of retries
B28-1 Retry wait time (s)
B28-2 Pick-up wait time (s)
B28-3 Pick-up voltage time (s)
Overcurrent limit
B29-0 Drive current limit (%)
B29-1 Regen torque limit (%)
Overload
B30-0 Overload setting (%)
B30-1 0Hz overload (%)
B30-2 0.7 Ftrq overload (%)
V/F middle point
B31-0 Frequency 2 (GF2) (Hz)
B31-1 Voltage 2 (GV2) (%)
B31-2 Frequency 1 (GF1) (Hz)
B31-3 Voltage 1 (GV1) (%)
Start interlock
B32-0 Start/stop frequency (Hz)
B32-1 Start/stop freq hysterises (Hz)
B32-2 Interlock frequency (Hz)
B32-3 RUN delay timer (s)
High-efficiency operation
B33-0 High-efficiency time constant (s)
B33-1 Voltage lower limit (%)
S/W option configuration
B40-0 S/W operation select
Program ramp - acceleration
B41-0 Acceleration time - 0 (s)
B41-1 Acceleration time - 1 (s)
B41-2 Acceleration time - 2 (s)
B41-3 Acceleration time - 3 (s)
B41-4 Acceleration time - 4 (s)
B41-5 Acceleration time - 5 (s)
B41-6 Acceleration time - 6 (s)
B41-7 Acceleration time - 7 (s)
Program ramp - deceleration
B42-0 Deceleration time - 0 (s)
B42-1 Deceleration time - 1 (s)
B42-2 Deceleration time - 2 (s)
B42-3 Deceleration time - 3 (s)
B42-4 Deceleration time - 4 (s)
B42-5 Deceleration time - 5 (s)
B42-6 Deceleration time - 6 (s)
B42-7 Deceleration time - 7 (s)

B Parameters - Software Functions
PID control
B43-0 Proportional gain
B43-1 Integral time constant (s)
B43-2 Differential time constant (s)
B43-3 Upper limit (%)
B43-4 Lower limit (%)
Traverse option
B44-0 Centre freq (FH) (Hz)
B44-1 Amplitude - A (%)
B44-2 Drop - D (%)
B44-3 Acceleration time - B (s)
B44-4 Acceleration time - C (s)
B44-5 Deviated traverse - X (%)
B44-6 Deviated traverse - Y (%)
Pattern run step - 0
B50-0 Mode
B50-1 Frequency (Hz)
B50-2 Time (s)
Pattern run step - 1
B51-0 Mode
B51-1 Frequency (Hz)
B51-2 Time (s)
Pattern run step - 2
B52-0 Mode
B52-1 Frequency (Hz)
B52-2 Time (s)
Pattern run step - 3
B53-0 Mode
B53-1 Frequency (Hz)
B53-2 Time (s)
Min - Max



0.0 - 20.0
5 - 300.0
1.0 - 105.0
1.0 - 105.0

0 - 10
1 - 30
1 - 10
1 - 300

50 - 300
5 - 300

50 - 105
20 - 105
50 - 105

0.0 - Fmax
0.0 - 100.0
0.0 - Fmax
0.0 - 100.0

0.0 - 20.0
0.0 - 20.0
0.0 - 20.0
0.00 - 10.00

10 - 301
55 - 100

11 - 24

0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0

0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.0



0.01 - 10.0
0.0 - 30.0
0.000 - 1.000
50 - 100
50 - 0

0.1 - Fmax
0.1 - 20.0
0.0 - 50.0
0.5 - 60.0
0.5 - 60.0
0.0 - 20.0
0.0 - 20.0

0 - 2
0.10 - Fmax
0.1 - 6000.0

0 - 2
0.10 - Fmax
0.1 - 6000.0

0 - 13
0.10 - Fmax
0.1 - 6000.0

0 - 23
0.10 - Fmax
0.1 - 6000.0


Param Description

B Parameters - Software Functions
Pattern run step - 4
B54-0 Mode
B54-1 Frequency (Hz)
B54-2 Time (s)
Pattern run step - 5
B55-0 Mode
B55-1 Frequency (Hz)
B55-2 Time (s)
Pattern run step - 6
B56-0 Mode
B56-1 Frequency (Hz)
B56-2 Time (s)
Pattern run step - 7
B57-0 Mode
B57-1 Frequency (Hz)
B57-2 Time (s)
Pattern run step - 8
B58-0 Mode
B58-1 Frequency (Hz)
B58-2 Time (s)
Pattern run step - 9
B59-0 Mode
B59-1 Frequency (Hz)
B59-2 Time (s)
Min - Max



0 - 33
0.10 - Fmax
0.1 - 6000.0

0 - 43
0.10 - Fmax
0.1 - 6000.0

0 - 53
0.10 - Fmax
0.1 - 6000.0

0 - 63
0.10 - Fmax
0.1 - 6000.0

0 - 73
0.10 - Fmax
0.1 - 6000.0

0 - 83
0.10 - Fmax
0.1 - 6000.0
Parameter Listing
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 7
Non-default Parameters
Inverter.. Job No..

Reference..
Parameter Set To.. Notes Parameter Set To.. Notes