Serial interface for Genset applications: - CANOpen - J1939 Functional Description E532246/00E
Printed in Germany 2007 Copyright MTU Friedrichshafen GmbH This Publication is protected by copyright and may not be used in any way whether in whole or in part without the prior written permission of MTU Friedrichshafen GmbH. This restriction also applies to copyright, distribution, translation, microfilming and storage or processing on electronic systems including data bases and online services. This handbook is provided for use by maintenance and operating personnel in order to avoid malfunctions or damage during operation. Subject to alterations and amendments.
Table of Contents
01
CANOpen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 1.2 1.3 1.4 1.5 1.6 Transmission values CANOpen Genset ...................................... ................. ................. ........ .......... ..........
03 03 10 13 52 59 62 67 67 69 71 72 80 83
Binary values Sending (ECU/SAM to external Device/System) Analog values Sending (ECU/SAM to external device/system)
Diagnosis messages Sending (ECU/SAM to an external device/system) Binary settings/values Receive (External Device/System to ECU/SAM) Analog settings/values Receive (external device/system to ECU/SAM)
J1939 Standard Sending (MTU to External Device) . . . . . . . . . . . . . . . . . . . . . . . . . . . J1939 Standard Receive (External Device to MTU) ........................... ..................... .......................
Proprietary objects Sending (MTU to an external device) Proprietary objects Received (external device to MTU) Index
..................................................................
E532246/00E
07/2007
MTU
02
Table of Contents
E532246/00E
07/2007
MTU
CANOpen
03
1
1.1
CANOpen
Transmission values CANOpen Genset
Interface - General
Use MTU provides an interface for genset applications in accordance with the CANOpen protocol. This document sets out the Process Data Objects (abbreviated in the following as PDOs), which are transmitted in accordance with this protocol. The PDOs, which are up to 8 bytes in length, with a total of 64 bits, can transmit the following values: Binary values Analog values Diagnostic messages Binary settings/values Analog settings/values Physical information CAN specification: ISO11898, CAN 2.0A/B, electrically isolated, 3-wire The following values are set for nodes and baud rates: Node no.: 6 Baud rate: 125kb 11 bit identifier Start/Stop CANOpen devices CANOpen NMT and communication CANOpen specification: DS301 V 4.01 The MTU system operates as a slave and waits to be started by a master. Static mapping and dynamic mapping are not supported. SDOs are not supported No written access to the object directory via SDOs Support of the standard PDOs Transmitted data format: Intel format The NMT monitoring takes place exclusively by means of a heartbeat, Heartbeat Producer Time: 500 ms Transmission Type 255 Inhibit Time: 250 ms Event Time 20 s Analog values are transmitted in the format Unsigned32 Boolean values are transmitted in the Boolean format IMPORTANT: MTU inserts data packets with less than 8 data bytes. The statement is held in the DCF/EDS file compiled by MTU (provided) ( see also PDO tables). Detection of data failure, Missing Data (MD)/Sensor Defect (SD) The following values are transmitted in the event of failure: Analog values: MD-value: 0x7FFFFFFF SD-value: 0x80000001 Boolean values The standard requires, that the binary values are transmitted for PDOs, bytes 0-3 contain the user data and bytes 4-7 the status values: PDO structure for Boolean values Byte 1 MSW Byte 2 MSW Byte 3 MSW Byte 4 MSW Byte 5 MD/SD Status Byte 6 MD/SD Status Byte 7 MD/SD Status Byte 8 MD/SD Status
E532246/00E
07/2007
MTU
04
CANOpen
Example: Measured value in Byte 1 is e.g. 0 The associated status is given in Byte 5: e.g. 0 for measured value is OK e.g. 1 for measured value is MD/SD
Notes
Notes on the tables In the headlines of the tables * appear at various positions. These have the following significance: * One of the following error codes: 134, 136, 142, 144, 145, 147, 149, 151, 363, 364 ** Takes the value ZERO or 1 additionally, with Sensor Defect (SD) ZERO in the case of Missing Data (MD) 1 *** Prerequisite for this COB-Id is: NODE-ID = 11. For other Node-ID ( see calculation of the COB-Ids) **** ERR_MD is indicated if PV110010 MD is ERR_MD = 1. Combination ERR_MD = 1 and PV510037 bit 0 = 1 Communication error Calculation of the COB-Ids The calculation of the CAN_IDs must be carried out as follows: TXPDO(n): tx_Base_identifier/s + Offset + Node_ID RXPDO(n): rx_Base_identifier/s + Offset + Node_ID for n= 1.. 4: tx_Base_identifier(1..4) = 0x180,0x280,0x380,0x480 rx_Base_identifier(1..4) = 0x200,0x300,0x400,0x500 Transmit PDOs Table columns PDO Binary values Sending The table heading for the binary messages (Send) has the following structure: PV No. Byte BitNo. PD BitNo. Obj. BitNo. PDO-Bin. Status message: NODE-ID + 0, Transmit PDO 1; COB-Id 186*** PV Sys. No. Index Remarks
Name
Byte
The columns have the following meaning: Name Name of the process variables PV No. Number of the process variables Byte Number of the Byte Byte Bit No. Number of the bit within the corresponding byte PD Bit No. Number of the bit, referenced to the complete PDO Object Bit No. Number of the bit, referenced to the object PDO type and COB-ID e.g.: PDO binary status signal: describing the type of process data object NODE-ID + 0, Transmit PDO 1; : Statement of the value COB-Id 186***: Statement of the value and *** further information The PV is described in detail in the field below PV, this number comprises: System number (MTU internal number in the governor) System Index (MTU internal number in the governor)
E532246/00E
07/2007
MTU
CANOpen
05
Remarks If required, further information can be given here Table Columns PDO analog values Sending The table heading for analog values (Send) has the following structure: PV No. Byte BitNo. PD BitNo. Obj. BitNo. PDO Analog Measured values: NODE-ID + 0, Transmit PDO 2; COB-Id 286***
Name
Byte
Remarks
The columns have the following meaning: Name Name of the process variables PV No. Number of the process variables Byte Number of the Byte Byte Bit No. Number of the bit within the corresponding byte PD Bit No. Number of the bit, referenced to the complete PDO Object Bit No. Number of the bit, referenced to the object PDO type and COB-ID e.g.: PDO Analog Measured values: describing the type of process data object NODE-ID + 0, Transmit PDO 2; : Statement of the value COB-Id 286***: Statement of the value and further information on *** The PV is described in detail in the field below Remarks If required, further information can be given here Diagnostic Messages Sending The table heading for binary diagnostic messages (Send) has the following structure: PV No. Byte BitNo. PD BitNo. Obj. BitNo. PDO-Bin. Diagnostic message: NODE-ID + 5, Transmit PDO 1; COB-Id 18B*** PV Sys. Index PV Index Remarks
Name
Byte
The columns have the following meaning: Name Name of the process variables PV No. Number of the process variables Byte Number of the Byte Byte Bit No. Number of the bit within the corresponding byte PD Bit No. Number of the bit, referenced to the complete PDO Object Bit No. Number of the bit, referenced to the object PDO type and COB-ID e.g.: PDO-Bin. Diagnostic message: describing the type of process data object
E532246/00E
07/2007
MTU
06
CANOpen
NODE-ID + 5, Transmit PDO 1; COB-Id 18B*** statement of the values and further information on *** The PV is described in detail in the field below PV, this number comprises: System number (MTU internal number in the governor) System Index (MTU internal number in the governor) Remarks If required, further information can be given here Binary settings/values Receive The table heading for binary data (Received) has the following structure: PV No. Byte BitNo. PD BitNo. Obj. BitNo. PDO-Bin. Input: NODE-ID + 0, Receive PDO 1; COB-Id 206*** PV Sys. Index PV Index Remarks
Name
Byte
The columns have the following meaning: Name Name of the process variables PV No. Number of the process variables Byte Number of the Byte Byte Bit No. Number of the bit within the corresponding byte PD Bit No. Number of the bit, referenced to the complete PDO Object Bit No. Number of the bit, referenced to the object PDO type and COB-ID e.g.: PDO-Bin. Input: describing the type of process data object NODE-ID + 0, Receive PDO 1; COB-Id 206***: Statement of the values and further information on *** The PV is described in detail in the field below PV, this number comprises: System number (MTU internal number in the governor) System Index (MTU internal number in the governor) Remarks If required, further information can be given here Analog settings/values Receive The table heading for analog values (Received) has the following structure: PV No. Byte BitNo. PD BitNo. Obj. BitNo. PDO analog settings: NODE-ID + 0, Receive PDO 2; COB-Id 306***
Name
Byte
Remarks
The columns have the following meaning: Name Name of the process variables PV No. Number of the process variables Byte Number of the Byte Byte Bit No. Number of the bit within the corresponding byte PD Bit No.
E532246/00E
07/2007
MTU
CANOpen
07
Number of the bit, referenced to the complete PDO Object Bit No. Number of the bit, referenced to the object PDO type and COB-ID e.g.: PDO analog settings: describing the type of process data object NODE-ID + 0, Receive PDO 2; : Statement of the value COB-Id 306***: Statement of the value and further information on *** The PV is described in detail in the field below Remarks If required, further information can be given here
Overview
The following tables provide an overview of all send and receive PDOs. Each PDO can transmitted up to two process variables (PVs). Send PDOs (Transmit) Node-ID Offset 0 Node-ID Offset 0 0 0 0 TransmitPDO 1 2 3 4 COB-ID 186 286 386 486 PV-Name PV500030 Binary Signal 3 PV001140 T-Lube Oil PV001002 Engine Speed PV001115 ECU Operating Hours PV-Name PV500031Binary Status3 PV001126 T-Coolant PV001006 Nominal Speed PV001005 Idle Speed
Node-ID Offset 1 Node-ID Offset 1 1 1 1 TransmitPDO 1 2 3 4 COB-ID 187 287 387 487 PV-Name PV001026 P-Lube Oil PV001131 T-Charge Air PV001046 P-Fuel PV001137 T-Coolant Intercooler PV-Name PV001049 P-Charge Air PV001152 T-Fuel PV001205 Actual Droop PV001169 T-ECU
E532246/00E
07/2007
MTU
08
CANOpen
Node-ID Offset 2 Node-ID Offset 2 2 2 2 TransmitPDO 1 2 3 4 COB-ID 188 288 388 488 PV-Name PV001012 Speed Demand Source PV001219 Nominal Power PV001195 Feedback Speed Demand ana.CAN PV001063 ECU Operating hours (sec) PV-Name PV001075 Actual Failure Codes PV001409 Requested Torque PV001196 Feedback Speed Demand analog PV001104 ECU Power Supply Voltage
Node-ID Offset 3 Node-ID Offset 3 3 3 3 TransmitPDO 1 2 3 4 COB-ID 189 289 389 489 PV-Name PV005352 Level Day-Tank % PV006035 Pressure 1 PV006010 AIN T-Exhaust A PV006070 AIN T-Winding PV-Name PV005362 Level Holding Tank % PV006055 Pressure 2 PV006020 AIN T-Exhaust B PV006080 AIN T-Winding 2
Node-ID Offset 4 Node-ID Offset 4 4 4 4 TransmitPDO 1 2 3 4 COB-ID 18A 28A 38A 48A PV-Name PV006090 AIN T-Winding 3 PV001016 Selected Speed Demand PV001017 Effective Engine Speed Demand dummy 2 PV-Name PV006100 AIN T-Ambient dummy 1 PV001176 Engine Optimized dummy 3
Node-ID Offset 5 Node-ID Offset 5 5 5 TransmitPDO 1 2 3 COB-ID 18B 28B 38B PV-Name PV500010 CANopen Binary Signal 1 PV500020 CANopen Binary Signal 2 dummy 4 PV-Name PV500011 CANopen Binary Status 1 PV500021 CANopen Binary Status 2 dummy 5
E532246/00E
07/2007
MTU
CANOpen
09
Receive-PDOs (Receive) Node-ID ReceiveCOB-ID Offset PDO 0 0 0 1 2 3 206 306 406 PV-Name PV500110 CANopen Binary In Signal 4 PV009201 CANopen Speed Demand Analog PV009244 CANopen Speed Demand Sw. PV-Name PV500111 CANopen Binary In Status 4 PV009274 CANopen Load Signal dummy 8
E532246/00E
07/2007
MTU
10
CANOpen
1.2
The binary messages, which are transmitted, are represented on the following pages.
E532246/00E
07/2007
MTU
CANOpen
11
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Obj. BitNo. 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
Binary Status 3
PV 500 031
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Load generator ON Preheat. Temp. Not Reached. Automatic Shutdown Feedback Alarm Reset Feedback CAN Mode Sw. Priming Pump On
External Stop Activated Speed Demand Fail Mode Feedback Increase Speed Feedback Decrease Speed Override Feedback for ECU Engine Running Cylinder Cutout
1 13 18 19 66 68 74
E532246/00E
07/2007
MTU
12
CANOpen
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Obj. BitNo. 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
Binary Signal 3
PV 500 030
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Load generator ON Preheat Temp. Not Reached Automatic Shutdown Feedback Alarm Reset Feedback CAN Mode Sw. Priming Pump On
External Stop Activated Speed Demand Fail Mode Feedback Increase Speed Feedback Decrease Speed Override Feedback for ECU Engine Running Cylinder Cutout
1 13 18 19 66 68 74
E532246/00E
07/2007
MTU
CANOpen
13
1.3
The following pages show the analog values that are transmitted.
E532246/00E
07/2007
MTU
14
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
T-Coolant
PV 001 126
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.01 C (signed) Range -40 C to +150 C For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: 90 C = 9000 digit = 0x2328
23
28
E532246/00E
07/2007
MTU
CANOpen
15
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
FF
Byte 3
3 4 5 6
FF
T-Lube Oil
PV 001 140
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 0.01 C (signed) Range -40 C to +150 C For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: -20 C = -2000 digit = FFFFF830
F8
30
E532246/00E
07/2007
MTU
16
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
Nominal speed
PV 001 006
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.1 rpm Range 0 - 3000 rpm (signed) For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: 600 rpm = 6000 digit = 0x1770
17
70
E532246/00E
07/2007
MTU
CANOpen
17
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
Engine Speed
PV 001 002
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 0.1 rpm Range 0 - 3000 rpm (signed) For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 600 rpm = 6000 digit = 0x1770
17
70
E532246/00E
07/2007
MTU
18
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
Idle Speed
PV 001 005
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.1 rpm Range 0 - 3000 rpm (signed) For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: 2050 rpm = 20500 digit = 0x5014
50
14
E532246/00E
07/2007
MTU
CANOpen
19
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
PV 001 115
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 1 h Range 0 - 200 000 h (signed) For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 10000h = 10000 digit = 0x2710
27
10
E532246/00E
07/2007
MTU
20
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
P-Charge Air
PV 001 049
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.01 mbar (signed) Range -4.5 to +4.5 bar For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: 1.6 bar = 160000 digit = 0x21700
17
00
E532246/00E
07/2007
MTU
CANOpen
21
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
P-Lube Oil
PV 001 026
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 0.01 mbar (signed) Range -10 bar to +10 bar For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 4.0 bar = 400000 digit = 0x61A80
1A
80
E532246/00E
07/2007
MTU
22
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
FF
Byte 7
3 4 5 6
FF
T-Fuel
PV 001 152
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.01 C (signed) Range -40 C to +150 C For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: -5 C = -500 digit = 0xFFFFFE0C
FE
0C
E532246/00E
07/2007
MTU
CANOpen
23
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
T-Charge Air
PV 001 131
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 0.01 C (signed) Range -40 C to +150 C For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 60 C = 6000 digit = 0x1770
17
70
E532246/00E
07/2007
MTU
24
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
Actual Droop
PV 001 205
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.001 % Range: 0-15 % For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: 2.5 % = 2500 digit = 0x9C4
C4
E532246/00E
07/2007
MTU
CANOpen
25
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
P-Fuel
PV 001 046
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 0.01 mbar (signed) Range -15 bar to +15 bar For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 2.5 bar = 250000 digit = 0x3D090
D0
90
E532246/00E
07/2007
MTU
26
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
FF
Byte 7
3 4 5 6
FF
T-ECU
PV 001 169
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.01 C (signed) Range -40 C to +150 C For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: -5 C = -500 digit = 0xFFFFFE0C
FE
0C
E532246/00E
07/2007
MTU
CANOpen
27
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
T-Coolant Intercooler
PV 001 137
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 0.01 C (signed) Range -40 C to +150 C For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 60 C = 6000 digit = 0x1770
17
70
E532246/00E
07/2007
MTU
28
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
00
Byte 7
3 4 5 6
00
PV 001 075
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Unit: digits Range: 0-1000 For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: 60 digit = 0x3C
00
3C
E532246/00E
07/2007
MTU
CANOpen
29
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
00
Byte 3
3 4 5 6
00
PV 001 012
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Unit: digits Range: 0-7 For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 7 digit = 0x7
00
07
E532246/00E
07/2007
MTU
30
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
0 Unit: Nm Resolution: 0.1 Nm (signed) Range: -10,000 Nm to +10,000 Nm For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: 2050 Nm = 20500 digit = 0x5014 50
Requested Torque
PV 001 409
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
14
E532246/00E
07/2007
MTU
CANOpen
31
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
3 Unit: KW Resolution: 0.01 KW (signed) Range: -10,000 KW to +10,000 KW For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 250 KW = 250000 digit = 0x3D090 D0
Nominal Power
PV 001 219
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
90
E532246/00E
07/2007
MTU
32
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
PV 001 196
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.1 rpm Range 0 - 3000 rpm For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: 600 rpm = 6000 digit = 0x1770
17
70
E532246/00E
07/2007
MTU
CANOpen
33
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
PV 001 195
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 0.1 rpm Range 0 - 3000 rpm For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 600 rpm = 6000 digit = 0x1770
17
70
E532246/00E
07/2007
MTU
34
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
PV 001 104
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.001 V Range: 0 - 35 V For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: 20.5 V = 20500 digit = 0x5014
50
14
E532246/00E
07/2007
MTU
CANOpen
35
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
PV 001 063
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 1 s Range 0 - 10000000000 s For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 10000 s = 10000 digit = 0x2710
27
10
E532246/00E
07/2007
MTU
36
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
FF
Byte 7
3 4 5 6
FE
Level HoldingTank %
PV 005 362
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.001 % (signed) Range: -150 to +150% For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: -75% = -75000 digit = FFFEDB08
DB
E532246/00E
07/2007
MTU
CANOpen
37
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
Level Day-Tank %
PV 005 352
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 0.001 % (signed) Range: -150 % to +150% For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 2.5 % = 2500 digit = 0x9C4
C4
E532246/00E
07/2007
MTU
38
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
FF
Byte 7
3 4 5 6
FC
Pressure 2
PV 006 055
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.01 mbar (signed) Range -10 bar to +10 bar For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: -2.5 bar = -250000 digit = FFFC2F70
2F
70
E532246/00E
07/2007
MTU
CANOpen
39
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
0B
Pressure 1
PV 006 035
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 0.01 mbar (signed) Range -10 bar to +10 bar For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 7.5 bar = 750000 digit = 0xB71B0
71
B0
E532246/00E
07/2007
MTU
40
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
FF
Byte 7
3 4 5 6
FF
AIN T-Exhaust B
PV 006 020
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.01 C (signed) Range -40 C to +800 C For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: -20 C = -2000 digit = FFFFB1E0
B1
E0
E532246/00E
07/2007
MTU
CANOpen
41
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
AIN T-Exhaust A
PV 006 010
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 0.01 C (signed) Range -40 C to +800 C For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 90 C = 9000 digit = 0x2328
23
28
E532246/00E
07/2007
MTU
42
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
AIN T-Winding 2
PV 006 080
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.01 C (signed) Range -40 C to +150 C For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: 90 C = 9000 digit = 0x2328
23
28
E532246/00E
07/2007
MTU
CANOpen
43
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
FF
Byte 3
3 4 5 6
FF
AIN T-Winding 1
PV 006 070
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 0.01 C (signed) Range -40 C to +150 C For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: -40 C = -4000 digit = FFFFF060
F0
60
E532246/00E
07/2007
MTU
44
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
AIN T-Ambient
PV 006 100
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Resolution: 0.01 C (signed) Range -40 C to +150 C For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: 90 C = 9000 digit = 0x2328
23
28
E532246/00E
07/2007
MTU
CANOpen
45
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
FF
Byte 3
3 4 5 6
FF
AIN T-Winding 3
PV 006 090
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Resolution: 0.01 C (signed) Range -40 C to +150 C For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: -5 C = -500 digit = 0xFFFFFE0C
FE
0C
E532246/00E
07/2007
MTU
46
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
dummy 1
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
E532246/00E
07/2007
MTU
CANOpen
47
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
PV 001 016
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Unit: rpm Resolution: 0.1 rpm range: 0 - 3000 rpm For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 600 rpm = 6000 digit = 0x1770
17
70
E532246/00E
07/2007
MTU
48
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
Engine Optimized
PV 001 176
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Unit: digits Range: 0 - 7 For computing values, the byte sequence must be as follows: Bytes: 8 7 6 5 Example: 6 digit = 0x6
E532246/00E
07/2007
MTU
CANOpen
49
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
0 Unit: rpm Resolution: 0.1 rpm Range 0 - 3000 rpm For computing values, the byte sequence must be as follows: Bytes: 4 3 2 1 Example: 600 rpm = 6000 digit = 0x1770 17
PV 001 017
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
70
E532246/00E
07/2007
MTU
50
CANOpen
Name
PV No.
Byte
PD Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
dummy 3
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
E532246/00E
07/2007
MTU
CANOpen
51
Name
PV No.
Byte
PD Bit No. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
dummy 2
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
E532246/00E
07/2007
MTU
52
CANOpen
1.4
E532246/00E
07/2007
MTU
CANOpen
53
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Obj. BitNo. 24 25 26 27 28 29 30 31 16 17 18 19 20 21 22 23 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
PDO-Bin. Diagnosis mess.: NODE-ID + 5, Transmit PDO 1; COB-Id 18B*** HI T-Coolant HI T-Charge-Air HI T-Coolant Intercooler HI T-Lube Oil HI T-ECU SS Engine Speed Low AL Priming Fault AL Start Spd. Not Reach. AL Combined Alarm Yellow LO P-Lube Oil LO Coolant Level LO Intercooler Cool. Lev. AL ECU Defect AL Speed Demand Defect LO Power Supply HI Power Supply
PV Sys. Index 001 001 001 001 001 001 001 001 001 001 001 001 001 001 001 001 PV Index 129 133 139 143 170 177 237 239 10 29 55 99 116 118 122 123 Status = "0" if value is valid Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
Binary Status 1
PV 500 011
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
AL Combined Alarm Red SS Overspeed LOLO P-Lube Oil HIHI T-Coolant HIHI T-Lube Oil HIHI T-Charge Air HIHI ECU Pow. Sup. Volt.
E532246/00E
07/2007
MTU
54
CANOpen
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Obj. BitNo. 24 25 26 27 28 29 30 31 16 17 18 19 20 21 22 23 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
PDO-Bin. Diagnosis mess.: NODE-ID + 5, Transmit PDO 1; COB-Id 18B*** HI T-Coolant HI T-Charge-Air HI T-Coolant Intercooler HI T-Lube Oil HI T-ECU SS Engine Speed Low AL Priming Fault AL Start Spd. Not Reach. AL Combined Alarm Yellow LO P-Lube Oil LO Coolant Level LO Intercooler Cool.t Lev. AL ECU Defect AL Speed Demand Defect LO Power Supply HI Power Supply
PV Sys. Index 001 001 001 001 001 001 001 001 001 001 001 001 001 001 001 001 PV Index 129 133 139 143 170 177 237 239 10 29 55 99 116 118 122 123 Value Range Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
Binary Signal 1
PV 500 010
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
AL Combined Alarm Red SS Overspeed LOLO P-Lube Oil HIHI T-Coolant HIHI T-Lube Oil HIHI T-Charge Air HIHI ECU Pow. Sup. Volt.
E532246/00E
07/2007
MTU
CANOpen
55
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Obj. BitNo. 24 25 26 27 28 29 30 31 16 17 18 19 20 21 22 23 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
Byte 8
3 4 5 6 7 0 1 2
HI Level Holding-Tank LO Level Holding-Tank HI T-Winding 1 HI T-Winding 2 HI T-Winding 3 HI T-Ambient AL Water In Fuel Prefilter 1 AL Water In Fuel Prefilter 2 LOLO ECU Pow. Sup. Volt. HI T-Fuel HI T-Exhaust A HI T-Exhaust B HI Pressure 1 HI Pressure 2 HI Level Day-Tank LO Level Day-Tank AL Runup Spd. Not Reach. AL Idle Speed Not Reached
005 005 009 009 009 009 009 009 001 001 009 009 009 009 005 005 001 001
363 364 540 550 560 580 590 600 270 299 500 510 520 530 353 354 240 241 Status = "0" if value is valid
Byte 7
3 4 5 6
Binary Status 2
PV 500 021
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
T-Generator Warning
005
241 MTU
E532246/00E
07/2007
56
CANOpen
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Obj. BitNo. 24 25 26 27 28 29 30 31 16 17 18 19 20 21 22 23 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
Byte 4
3 4 5 6 7 0 1 2
HI Level Holding-Tank LO Level Holding-Tank HI T-Winding 1 HI T-Winding 2 HI T-Winding 3 HI T-Ambient AL Water In Fuel Prefilter 1 AL Water In Fuel Prefilter 2 LOLO ECU Pow. Sup. Volt. HI T-Fuel HI T-Exhaust A HI T-Exhaust B HI Pressure 1 HI Pressure 2 HI Level Day-Tank LO Level Day-Tank AL Runup Spd. Not Reach. AL Idle Speed Not Reached
005 005 009 009 009 009 009 009 001 001 009 009 009 009 005 005 001 001
363 364 540 550 560 580 590 600 270 299 500 510 520 530 353 354 240 241 Value range
Byte 3
3 4 5 6
Binary Signal 2
PV 500 020
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
T-Generator Warning
005
241 MTU
E532246/00E
07/2007
CANOpen
57
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Obj. BitNo. 24 25 26 27 28 29 30 31 16 17 18 19 20 21 22 23 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
dummy 5
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
E532246/00E
07/2007
MTU
58
CANOpen
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Obj. BitNo. 24 25 26 27 28 29 30 31 16 17 18 19 20 21 22 23 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
dummy 4
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
E532246/00E
07/2007
MTU
CANOpen
59
1.5
The following pages display the binary receive data PDOs (Bin_Receive)
E532246/00E
07/2007
MTU
60
CANOpen
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Obj. BitNo. 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
Binary In Status 4
PV 500 111
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
Mode Switch Gov.ParameterSetSelect. Droop 2 Intermittent Oil Priming Engine Start 50/60Hz Rating Switch 1 Rating Switch 2 Disable Cylinder Cut Out 2 Override Speed Increase Speed Decrease Request Test Overspeed Engine Stop Alarm reset Speed Setting Limit Active
009 009 009 009 009 009 009 009 009 009 009 009 009 009 009 009
242 248 267 278 280 304 305 306 205 207 208 209 211 214 216 221
E532246/00E
07/2007
MTU
CANOpen
61
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Obj. BitNo. 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
Binary In Signal 4
PV 500 110
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Mode Switch Gov.ParameterSetSelect. Droop 2 Intermittent Oil Priming Engine Start 50/60Hz Rating Switch 1 Rating Switch 2 Disable Cylinder Cut Out 2 Override Speed Increase Speed Decrease Request Test Overspeed Engine Stop Alarm Reset Speed Setting Limit Active
009 009 009 009 009 009 009 009 009 009 009 009 009 009 009 009
242 248 267 278 280 304 305 306 205 207 208 209 211 214 216 221
Value range
E532246/00E
07/2007
MTU
62
CANOpen
1.6
The following pages display the analog receive data PDOs (Ana_Receive)
E532246/00E
07/2007
MTU
CANOpen
63
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Obj. BitNo. 24 25 26 27 28 29 30 31 16 17 18 19 20 21 22 23 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
0 Unit: % Resolution: 0.001 % (signed) Range: -100%- +100% To calculate, the byte order must be as follows: Byte: 8 7 6 5 Example: 2.5 % = 2500 digit = 0x9C4 9
Load Signal
PV 009 274
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
C4
E532246/00E
07/2007
MTU
64
CANOpen
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Obj. BitNo. 24 25 26 27 28 29 30 31 16 17 18 19 20 21 22 23 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
0 Unit: rpm Resolution: 0.1 rpm Range 0 - 3000 rpm To calculate, the byte order must be as follows: Byte: 4 3 2 1 Example: 600 rpm = 6000 digit = 0x1770 17
PV009 201
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
70
E532246/00E
07/2007
MTU
CANOpen
65
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Obj. BitNo. 24 25 26 27 28 29 30 31 16 17 18 19 20 21 22 23 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
Remarks
Byte 8
3 4 5 6 7 0 1 2
Byte 7
3 4 5 6
dummy 8
7 0 1 2 Byte 6 3 4 5 6 7 0 1 2 Byte 5 3 4 5 6 7
E532246/00E
07/2007
MTU
66
CANOpen
Name
PV No.
Byte
Byte BitNo. 0 1 2
PD BitNo. 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Obj. BitNo. 24 25 26 27 28 29 30 31 16 17 18 19 20 21 22 23 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
Remarks
Byte 4
3 4 5 6 7 0 1 2
Byte 3
3 4 5 6
PV 009 244
7 0 1 2 Byte 2 3 4 5 6 7 0 1 2 Byte 1 3 4 5 6 7
Unit: digits Range: 0-7 To calculate, the Byte order must be as follows: Byte: 4 3 2 1 Example: 6 digit = 0x6
E532246/00E
07/2007
MTU
J1939
67
2
2.1
J1939
Transmission values J1939
Abbreviations: Res: Reserved DP: Data Page DA: Destination Address GE: Group Extension Message Structure PDU The data field is a maximum 8 bytes long. MTU also uses shorter data fields, in order to reduce the volume of data to be transmitted. Therefore the Dlc (Data length code) must be evaluated.
E532246/00E
07/2007
MTU
68
J1939
A request message then has, for example, the following structure (see also SAE J1939-21 Section 5.2.7.1 Data from 0 to 8 Bytes): 29-Bit-Identifier 28...26 Priority 25 24 23...16 15...8 7...0 Source address requested PGN Dlc 3 PDU data field d0 d1 d2
Nodes and Baud Rate The following values are set for nodes and baud rates: SAM: Node No.: 128 External devices: Node No.: 1 Baud rate: 250kb Deterministic Note on the Process Variables PV The System Index can vary for the two applications MDEC and ADEC. The system number varies depending on the application engineering. The PV Number of the process variables comprises a System Index and a System Number. These PV Numbers vary on the basis of the information given above. Their purpose is exclusively to provide a rough orientation. The designations (e.g. engine rpm, Stop or Start) are uniquely assigned.
E532246/00E
07/2007
MTU
J1939
69
2.2
SPN SPN 100 SPN 102 SPN 110 SPN 1124 SPN 1125 SPN 1126 SPN 1136 SPN 1239 SPN 1240 SPN 1387 SPN 1388 SPN 158 SPN 166 SPN 171 SPN 174 SPN 175 SPN 188 SPN 189 SPN 190 SPN 2433 SPN 2434 SPN 247
PGN PGN 65263 PGN 65270 PGN 65262 PGN 65191 PGN 65191 PGN 65191 PGN 65188 PGN 65169 PGN 65169 PGN 65164 PGN 65164 PGN 65271 PGN 65214 PGN 65269 PGN 65262 PGN 65262 PGN 65251 PGN 65214 PGN 61444 PGN 65031 PGN 65031 PGN 65253
P-Lube Oil P charge-air T-Coolant T-Winding 1 T-Winding 2 T-Winding 3 T-ECU AL Water Fuel Filter 1 AL Water Fuel Filter 2 Pressure Measurement 1 Pressure Measurement 2 ECU Supply Voltage Rated Power T-Ambient T-Fuel T-Lube Oil Idle Speed Rated speed Engine Speed AIN T-Exhaust_B AIN T-Exhaust A ECU Operating Hours Counter
Analog measurement value in bar Analog measurement value in bar Analog measurement value in deg C Analog measurement value in deg C Analog measurement value in deg C Analog measurement value in deg C Analog measurement value in deg C Yellow alarm Yellow alarm Analog measurement value in bar Analog measurement value in bar Analog measurement value in V Analog measurement value in kW Analog measurement value in deg C Analog measurement value in deg C Analog measurement value in deg C Analog measurement value in rpm Analog measurement value in rpm Analog measurement value in rpm Analog measurement value in deg C Analog measurement value in deg C Analog measurement value in h (hours)
E532246/00E
07/2007
MTU
70
J1939
MTU PV System No. 1 1 1 1 1 1 1 System Ind. 131 226 137 14 10 46 213 Designation Description
SPN 2629 SPN 2815 SPN 52 SPN 623 SPN 624 SPN 94 SPN1110
PGN 64979 PGN 65252 PGN 65262 PGN 65226 PGN 65226 PGN 65263 PGN 65252
T-Charge-Air Feedback Alarm Reset T-Coolant Charge-Air AL Combined Alarm Red AL Combined Alarm Yellow P Fuel Automatic Shutoff
Analog measurement value in deg C Binary Value Analog measurement value in deg C Red Alarm Yellow Alarm Analog measurement value in bar Binary Value
E532246/00E
07/2007
MTU
J1939
71
2.3
SPN
PGN
SPN 1237 SPN 2881 SPN 2882 See Rating 1 SPN 898 SPN 970
PGN 65265 PGN 64971 PGN 64971 PGN 64971 PGN 0 PGN 61441
Override P-Deg 2 Rating Mode Bit 1 Rating Mode Bit 2 Set speed demand Motor Stop
Binary Value Binary Value Binary Value Binary Value Analog measurement value in rpm Analog measurement value in rpm
E532246/00E
07/2007
MTU
72
J1939
2.4
PGN 65280 Transmit repetition: 1000 ms Data length: 2 Data pages: 0 PDU format: 255 PDU-specific: 0 Preset priority: 6 Parameter group number: 65280 (0xFF00) J1939 proprietary BitLength Pos. 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 5 7 1 3 5 7 1 3 5 7 1 3 1 3 5 5 7 5 7 BytePGN Pos. 1 1 3 4 4 4 5 5 5 5 6 6 7 7 7 8 8 6 6 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 PGN 65280 MTU PV System No. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 9 9 System Ind. 29 30 55 116 118 122 123 129 130 133 143 144 168 170 177 270 271 500 510 Designation Description
LO P Lube Oil LOLO P Lube Oil LO coolant level AL ECU faulty AL Speed Demand Failure RCS LO voltage supply HI voltage supply HI T coolant HIHI T coolant HI T charge-air HI T Lube Oil HIHI T Lube Oil HIHI T charge-air HI T ECU SS engine speed too low LOLO ECU supply voltage HIHI ECU supply voltage HI T exhaust A HI T exhaust B
Yellow alarm Red alarm Yellow alarm Yellow alarm Yellow alarm Yellow alarm Yellow alarm Yellow alarm Red alarm Yellow alarm Yellow alarm Red alarm Red alarm Yellow alarm Yellow alarm Yellow alarm Red alarm Yellow alarm Yellow alarm
PGN 65281 Transmit repetition: 1000 ms Data length: 2 Data pages: 0 PDU format: 255 PDU-specific: 1 Preset priority: 6
E532246/00E
07/2007
MTU
J1939
73
Parameter group number: 65281 (0xFF01) J1939 proprietary BitLength Pos. 2 2 2 5 7 7 BytePGN Pos. 7 6 1 PGN 65281 PGN 65281 PGN 65281 MTU PV System No. 1 1 1 System Ind. 3 66 299 Designation Description
PGN 65284 Transmit repetition: 1000 ms Data length: 16 Data pages: 0 PDU format: 255 PDU-specific 4 Preset priority: 6 Parameter group number: 65284 (0xFF04) J1939 proprietary BitLength Pos. BytePGN Pos. MTU PV System No. System Ind. Designation Description
16
PGN 65284
75
Analog measurement value in digits Resolution: 1 digit/bit Range: 0 to 64,255 digits Cycle: 1000ms or after value changes
PGN 65296 Transmit repetition: 1000 ms Data length: 2 Data pages: 0 PDU format: 255 PDU-specific 14 Preset priority: 6
E532246/00E
07/2007
MTU
74
J1939
Parameter group number: 65296 (0xFF0E) J1939 proprietary BitLength Pos. BytePGN Pos. MTU PV System No. 1 System Ind. 1 Designation Description
PGN 65296
Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes
PGN 65296
13
PGN 65296
18
PGN 65296
19
PGN 65296
68
Engine is running
PGN 65296
74
Cylinder cutout
PGN 65296
78
Alternator switch ON
PGN 65296
89
PGN 65296
256
PGN 65296
301
Priming pump ON
PGN 65297 Transmit repetition: 1000 ms Data length: 2 Data pages: 0 PDU format: 255 PDU-specific: 17 Preset priority: 6
E532246/00E
07/2007
MTU
J1939
75
Parameter group number: 65297 (0xFF11) J1939 proprietary BitLength Pos. BytePGN Pos. MTU PV System No. 1 System Ind. 99 Designation Description
PGN 65297
Yellow alarm Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes Message Cycle: 1000ms or after value changes Message Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes
PGN 65297
139
HI T Coolant Intercooler
PGN 65297
237
AL Priming Fault
PGN 65297
239
PGN 65297
240
PGN 65297
241
PGN 65297
241
T-Alternator Warning
PGN 65297
353
PGN 65297
354
PGN 65297
363
PGN 65297
364
PGN 65297
520
HI Pressure Input 1
PGN 65297
530
E532246/00E
07/2007
MTU
76
J1939
PGN 65297
HI T-Coil 1
Yellow alarm Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes Yellow alarm Cycle: 1000ms or after value changes
PGN 65297
550
HI T-Coil 2
PGN 65297
560
HI T-Coil 3
PGN 65297
580
HI T-Ambient
PGN 65310 Transmit repetition: 1000 ms Data length: 16 Data pages: 0 PDU format: 255 PDU-specific: 30 Preset priority: 6 Parameter group number: 65310 (0xFF1E) J1939 proprietary BitLength Pos. BytePGN Pos. MTU PV System No. System Ind. Designation Description
16
PGN 65310
16
Analog measurement value in rpm Resolution: 0.125 rpm/bit Range: 0 to 8,031.875 Cycle: 1000ms or after value changes Analog measurement value in rpm Resolution: 0.125 rpm/bit Range: 0 to 8,031.875 Cycle: 1000ms or after value changes
16
PGN 65310
17
PGN 65316 Transmit repetition: 1000 ms Data length: 16 Data pages: 0 PDU format: 255 PDU-specific: 36 Preset priority: 6
E532246/00E
07/2007
MTU
J1939
77
Parameter group number: 65316 (0xFF24) J1939 proprietary BitLength Pos. BytePGN Pos. MTU PV System No. System Ind. Designation Description
16
PGN 65316
195
Analog measurement value in rpm Resolution: 0.125 rpm/bit Range: 0 to 8,031.875 Cycle: 1000ms or after value changes Analog measurement value in rpm Range: 0 to 8,031.875 Cycle: 1000ms or after value changes
16
PGN 65316
196
PGN 65317 Transmit repetition: 1000 ms Data length: 4 Data pages: 0 PDU format: 255 PDU-specific: 37 Preset priority: 6 Parameter group number: 65317 (0xFF25) J1939 proprietary BitLength Pos. BytePGN Pos. MTU PV System No. System Ind. Designation Description
PGN 65317
12
Analog measurement value in digits Resolution: 1 digit/bit Range: 0 to 7 Cycle: 1000ms or after value changes Analog measurement value in sec. Resolution: 1s/bit Cycle: 1000ms or after value changes
32
PGN 65317
63
PGN 65318 Transmit repetition: 1000 ms Data length: 16 Data pages: 0 PDU format: 255 PDU-specific: 38 Preset priority: 6
E532246/00E
07/2007
MTU
78
J1939
Parameter group number: 65318 (0xFF26) J1939 proprietary BitLength Pos. BytePGN Pos. MTU PV System No. System Ind. Designation Description
16
PGN 65318
409
Specified torque
Analog measurement value in Nm Resolution: 1 Nm/bit Range: 0 to 64,255 Nm Cycle: 1000ms or after value changes
PGN 65320 Transmit repetition: 1000 ms Data length: 16 Data pages: 0 PDU format: 255 PDU-specific: 40 Preset priority: 6 Parameter group number: 65320 (0xFF28) J1939 proprietary BitLength Pos. BytePGN Pos. MTU PV System No. System Ind. Designation Description
16
PGN 65320
176
Engine optimized
Analog measurement value in digit/bit Resolution: 1 digit/bit Range: 0 to 64,255 digits Cycle: 1000ms or after value changes
PGN 65321 Transmit repetition: 1000 ms Data length: 16 Data pages: 0 PDU format: 255 PDU-specific: 41 Preset priority: 6
E532246/00E
07/2007
MTU
J1939
79
Parameter group number: 65321 (0xFF29) J1939 proprietary BitLength Pos. BytePGN Pos. MTU PV System No. System Ind. Designation Description
16
PGN 65321
205
Current P degree
Analog measurement value in % Resolution: 0.0025 %/bit Range: 0 to 160.6375 % Cycle: 1000ms or after value changes Analog measurement value in % Resolution: 0.4 %/bit Range: 0 to 100 % Cycle: 1000ms or after value changes Analog measurement value in % Resolution: 0.4 %/bit Range: 0 to 100 % Cycle: 1000ms or after value changes
PGN 65321
352
PGN 65321
362
E532246/00E
07/2007
MTU
80
J1939
2.5
PGN 65325 Transmit repetition: 1000 ms Data length: 2 Data pages: 0 PDU format: 255 PDU-specific: 45 Preset priority: 6
E532246/00E
07/2007
MTU
J1939
81
Parameter group number: 65325 (0xFF2D) J1939 proprietary BitLength Pos. BytePGN Pos. MTU PV System No. 1 System Ind. Designation Description
PGN 65325
5* Request full engine 2 805** 8* Speed increase 808** 9* Speed decrease 809** 11* Request test overspeed 811** 16* Alarm reset 816** 21* Request speed limiter 821** 42* Mode switch 842** 48* Switchover governor 848** parameters 78* Intermittent oil priming 878** 80* Engine start 880** 104* 50/60Hz 904**
Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes Binary value Cycle: 1000ms or after value changes
PGN 65325
PGN 65325
PGN 65325
PGN 65325
PGN 65325
PGN 65325
PGN 65325
PGN 65325
PGN 65325
PGN 65325
*MDEC (ECU 4), ** ADEC (ECU 7) PGN 65326 Transmit repetition: 1000 ms Data length: 16 Data pages: 0 PDU format: 255 PDU-specific: 46 Preset priority: 6
E532246/00E
07/2007
MTU
82
J1939
Parameter group number: 65326 (0xFF2E) J1939 proprietary BitLength Pos. BytePGN Pos. MTU PV System No. System Ind. * Description
16
PGN 65326
Analog measurement value in % Resolution: 0.0025 %/bit Range: 0 to 160.6375 % Cycle: 1000ms or after value changes
*MDEC (ECU 4), ** ADEC (ECU 7) PGN 65327 Transmit repetition: 1000 ms Data length: 16 Data pages: 0 PDU format: 255 PDU-specific: 47 Preset priority: 6 Parameter group number: 65327 (0xFF2F) J1939 proprietary BitLength Pos. BytePGN Pos. MTU PV System No. System Ind. Designation Description
16
PGN 65327
Analog measurement value in digits Resolution: 1 digit/bit Range 0 to 7 digits Cycle: 1000ms or after value changes
E532246/00E
07/2007
MTU
J1939
83
2.6
Index
A J
62 13 J1939 Standard Receive (External Device to MTU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . J1939 Standard Sending (MTU to External Device) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 69
Analog settings/values Receive (external device/system to ECU/SAM) . . . . . . . . . . . . . . Analog values Sending (ECU/SAM to external device/system) . . . . . . . . . . . . . . . . . . . . . . . .
B
Binary settings/values Receive (External Device/System to ECU/SAM) . . . . . . . . . . . . . Binary values Sending (ECU/SAM to external Device/System) . . . . . . . . . . . . . . . . . . . . . . . . 59 10
P
Proprietary objects Received (external device to MTU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Proprietary objects Sending (MTU to an external device) . . . . . . . . . . . . . . . . . . . . . . . 80 72
D
Diagnosis messages Sending (ECU/SAM to an external device/system) . . . . . . . . . . . . . . . 52
T
Transmission values CANOpen Genset . . . . . Transmission values J1939 . . . . . . . . . . . . . . . 03 67
I
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83