Water Pressure Drop Adjustment Calculations - ref: 550/590 appendix G Evaporator Piping

Upstream Pipe, Water Temperature (F) Flow Tube Inside Diameter at Static Pressure Measurement Location (inches) Contraction or Enlargement Section (if included - allowed for unit connections > 4") Elbow Section (if included - allowed for unit connections > 4") Downstream Pipe, Water Temperature (F) Inside Diameter at Static Pressure Measurement Location (inches) Contraction or Enlargement Section (if included - allowed for unit connections > 4") Elbow Section (if included - allowed for unit connections > 4") 54 13.25 included included 44 13.25 included included Flow Rate (gpm) Length (of straight pipe) Upstream Dia (in) ID (inch) => 5000 14 13.25 13.25 (inches) Dwnstrm Dia (in) 15.25 r/d or mitre=> 2 x 45 mitre Press Drop Correction (ft) 0.031 0.074 0.886

Length (of straight pipe) Upstream Dia (in) ID (inch) =>

14 15.25 13.25

(inches) Dwnstrm Dia (in) 13.25 r/d or mitre=> 2 x 45 mitre

0.032 0.093 0.897 2.013

* Maximum Pressure Drop correction for the Evaporator (ft H2O) =

Condenser Piping
Upstream Pipe, Water Temperature (F) Inside Diameter at Static Pressure Measurement Location (inches) Contraction or Enlargement Section (if included - allowed for unit connections > 4") Elbow Section (if included - allowed for unit connections > 4") Downstream Pipe, Water Temperature (F) Inside Diameter at Static Pressure Measurement Location (inches) Contraction or Enlargement Section (if included - allowed for unit connections > 4") Elbow Section (if included - allowed for unit connections > 4") 85 13.25 included included 95 13.25 included included Flow Rate (gpm) Length (of straight pipe) Upstream Dia (in) ID (inch) => 6000 14 13.25 13.25 (inches) Dwnstrm Dia (in) 15.25 r/d or mitre=> 2 x 45 mitre

Press Drop Correction (ft) 0.043 0.107 1.229

Length (of straight pipe) Upstream Dia (in) ID (inch) =>

14 15.25 13.25

(inches) Dwnstrm Dia (in) 13.25 r/d or mitre=> 2 x 45 mitre

0.043 0.134 1.222 2.778

* Maximum Pressure Drop correction for the Condenser (ft H2O) =

* Note: The pressure drop adjustment is limited to 10% of the pressure drop reading Notes: 1) Length (of straight pipe) - the straight pipe length of the flow tube section between the static pressure taps and the unit connection. Do not include any lengths associated with an elbow or expansion/contraction section. 2) r/d or mitre - The worksheet calculates an adjustment for various 90 degree elbow fittings. r/d = is the turn radius of the elbow divided by the inside diameter. Mitre type elbows are allowed for mitres <= 45 degrees.

Water Pressure Drop Adjustment Calculations - ref: 551/591 appendix G Evaporator Piping
Upstream Pipe, Water Temperature (C) Flow Tube Inside Diameter at Static Pressure Measurement Location (mm) Contraction or Enlargement Section (if included - allowed for unit connections > 100mm) Elbow Section (if included - allowed for unit connections > 100mm) Downstream Pipe, Water Temperature (C) Inside Diameter at Static Pressure Measurement Location (mm) Contraction or Enlargement Section (if included - allowed for unit connections > 100mm) Elbow Section (if included - allowed for unit connections > 100mm) 12 200 included included 7 200 included included Flow Rate (l/s) Length (of straight pipe) Upstream Dia (mm) ID (mm) => 60 800 200 200 (mm) Dwnstrm Dia (mm) 250 r/d or mitre=> 2 x 45 mitre Press Drop Correction (kPa) 0.120 0.202 0.901

Length (of straight pipe) Upstream Dia (mm) ID (mm) =>

800 250 200

(mm) Dwnstrm Dia (mm) 200 r/d or mitre=> 2 x 45 mitre

0.122 0.173 0.916 2.433

* Maximum Pressure Drop correction for the Evaporator (kPa) =

Condenser Piping
Upstream Pipe, Water Temperature (C) Inside Diameter at Static Pressure Measurement Location (mm) Contraction or Enlargement Section (if included - allowed for unit connections > 100mm) Elbow Section (if included - allowed for unit connections > 100mm) Downstream Pipe, Water Temperature (F) Inside Diameter at Static Pressure Measurement Location (mm) Contraction or Enlargement Section (if included - allowed for unit connections > 100mm) Elbow Section (if included - allowed for unit connections > 100mm) 30 200 included included 35 200 included included Flow Rate (l/s) Length (of straight pipe) Upstream Dia (mm) ID (mm) => 70 800 200 200 (mm) Dwnstrm Dia (mm) 250 r/d or mitre=> 2 x 45 mitre

Press Drop Correction (ft) 0.155 0.275 1.162

Length (of straight pipe) Upstream Dia (mm) ID (mm) =>

800 250 200

(mm) Dwnstrm Dia (mm) 200 r/d or mitre=> 2 x 45 mitre

0.154 0.235 1.153 3.133

* Maximum Pressure Drop correction for the Condenser (kPa) =

* Note: The pressure drop adjustment is limited to 10% of the pressure drop reading Notes: 1) Length (of straight pipe) - the straight pipe length of the flow tube section between the static pressure taps and the unit connection. Do not include any lengths associated with an elbow or expansion/contraction section. 2) r/d or mitre - The worksheet calculates an adjustment for various 90 degree elbow fittings. r/d = is the turn radius of the elbow divided by the inside diameter. Mitre type elbows are allowed for mitres <= 45 degrees.