STEP No.

Capacitor Induced Voltage Calculation


NC = UN = f= Irms = Us = UF = L= P= H1 = H3 = H5 = H7 = H9 = H11 = H13 = U1 = Q1 = 50 440 50 65.61 433 440 ?? 7 7 0.00 0.00 0.00 0.00 0.00 0.00 kVar Volts Hz Amp Volts Volts mH % % % % % % % % Rated Voltage

Rated kVar (Reactive Power of Cap) Rated Frequency Rated Current System Voltage Detuned Filter Voltage Detuned Filter Inductance Detuned Filter % 1st Harmonic % 3rd Harmonic % 5th Harmonic % 7th Harmonic % 9th Harmonic % 11th Harmonic % 13th Harmonic % Voltage Across Capacitor Reactive Power of Capacitor

U S /(1-P%) N C /(1-P%)

466 53.76

Volts kvar

STEP No.2

Harmonic Current flowing through Capacitor Calaculation


Use detuned reactor 7% XC = U 1 2 /(Q 1 *1000) XL = X C *P% XC = XC3 = XC5 = XC7 = XC9 = XC11 = XC13 = 4.032 XL= 1.344 XL3= 0.806 XL5= 0.576 XL7= 0.448 XL9= 0.367 XL11= 0.310 XL13= 4.03 Ohms 0.282 Ohms 0.282 Fundamental Frq. 0.847 increase 3 times of 50 Hz 1.411 increase 5 times of 50 Hz 1.976 increase 7 times of 50 Hz 2.540 increase 9 times of 50 Hz 3.105 increase 11 times of 50 Hz 3.669 increase 13 times of 50 Hz

So, Harmonic Order 1st : F=50Hz Harmonic Order 3rd : F=150Hz Harmonic Order 5th : F=250Hz Harmonic Order 7th : F=350Hz Harmonic Order 9th : F=450Hz Harmonic Order 11th : F=550Hz Harmonic Order 13th : F=650Hz Harmonic Current of order h Harmonic Current of order 1stI1=1.06*Ic Harmonic Current of order 3rd Harmonic Current of order 5th Harmonic Current of order 7th Harmonic Current of order 9th Harmonic Current of order 11th Harmonic Current of order 13th So, Irms of total Harmonic

Ih = U h /(1.732* |X Lh -X ch | I1 = 70.20 Amp I3 = I5 = I7 = I9 = I11 = I13 = IS = 0.00 Amp 0.00 Amp 0.00 Amp 0.00 Amp 0.00 Amp

0.00 Amp IS = SQRT (I1 2 +I3 2 +I5 2 +I7 2 )

70.20

Amp 1.3 times of Irms

So, Capacitor is desined to withstand maximum current about ???*Irms =

85.29 Amp

STEP No.3

Maximum Voltage acorss Capacitor Calaculation


XC=U12/(Q1*1000)

XC =

Harmonic Voltage of order h Harmonic Voltage of order 1st Harmonic Voltage of order 3rd Harmonic Voltage of order 5th Harmonic Voltage of order 7th Harmonic Voltage of order 9th Harmonic Voltage of order 11th Harmonic Voltage of order 13th Maximum voltage acorss Capacitor = If capacitor is designed for
And the reactive power is =Q 2 =Q 1 *(V 2 2 /V 1 2 )

4.03 Ohms Uh = 1.732* Ih*Xc/h Where h is Harmonic order number U1 = 490.3 Volts U3 = U5 = U7 = U9 = 0.0 Volts 0.0 Volts 0.0 Volts 0.0 Volts 0.0 Volts 0.0 Volts

U11 = U13 = 525 Q2 = Volts

490 68.36

Volts
Note: nearest to above Max. voltage