Академический Документы
Профессиональный Документы
Культура Документы
A thesis submitted to The University of Manchester for the degree of MPhil in the Faculty of Engineering and Physical Sciences
Sitao Li
Contents
Contents..................................................................................................................................... 3 List of Figures ........................................................................................................................... 7 List of Tables........................................................................................................................... 11 Abstract ................................................................................................................................... 13 Declaration .............................................................................................................................. 15 Copyright Statement .............................................................................................................. 17 Acknowledgement .................................................................................................................. 19 Chapter 1 Introduction .......................................................................................................... 21 1.1 1.2 1.3 2.1 Background Study ............................................................................................. 21 Research Objectives .......................................................................................... 22 Outline of Thesis ................................................................................................ 22 Introduction of Transformer Liquid ............................................................... 25 2.1.1 2.1.2 2.1.3 2.2 2.2.1 2.2.2 2.2.3 2.3 2.3.1 2.3.2 2.3.3 2.3.4 2.3.5 2.4 2.4.1 2.4.2 Mineral Oil Nytro Gemini X .................................................................. 25 Natural Ester FR3 ................................................................................... 26 Sample Processing Methodology............................................................... 27 Partial Discharge Fault .............................................................................. 28 Electrical Sparking Fault........................................................................... 29 Thermal Fault ............................................................................................. 29 Gas Formation ............................................................................................ 31 Headspace Method ..................................................................................... 33 Gas Chromatograph................................................................................... 34 Duval Triangle Interpretation Method ..................................................... 34 Online DGA and Laboratory DGA Comparison ..................................... 35 Working Principle ...................................................................................... 36 Dual-Column GC Analysis ........................................................................ 37 3
PC Data Analysis ......................................................................................... 38 Electrical Sparking ..................................................................................... 39 Electrical PD Test ........................................................................................ 40 Thermal Test ................................................................................................ 43
Tests Comparison and Summary ..................................................................... 48 Introduction ........................................................................................................ 51 Experiment Setup .............................................................................................. 51 3.2.1 3.2.2 Test Circuit Design ...................................................................................... 51 Test Vessel Design ........................................................................................ 53 Drain Oil out of System .............................................................................. 57 Clean Test System and Fill Processed Oil into the System ...................... 58 Measuring Background DGA level............................................................ 59 Generating Sparking Faults ....................................................................... 59 GIG and GIT ............................................................................................... 60 Dissolved Gas Generation Calculation ..................................................... 61 Sparking Energy Calculation .................................................................... 63
3.3
3.4
3.5 3.6
Test Condition and Observation ....................................................................... 69 Test Result and Analysis .................................................................................... 70 3.6.1 3.6.2 3.6.3 3.6.4 3.6.5 3.6.6 3.6.7 Gas Generation of Sparking Faults ........................................................... 70 Energy of Sparking Faults ......................................................................... 71 Gas generation rate (per J) ........................................................................ 72 Absolute Gas generation rate (per J) ........................................................ 74 Gemini X and FR3 Comparison ................................................................ 74 Duval Triangle Analysis .............................................................................. 75 Laboratory DGA and Online Monitor Comparison ................................ 77
3.7
Summary............................................................................................................. 78
Introduction ....................................................................................................... 79 Experiment Setup .............................................................................................. 79 Test Procedure ................................................................................................... 80 4.3.1 4.3.2 4.3.3 Calibrate the PD Detector ......................................................................... 81 Measuring Background PD Noise ............................................................. 82 Generating PD Faults................................................................................. 82 Total Gas Generation Calculation ............................................................ 83 PD Energy Calculation .............................................................................. 84
4.4
4.5 4.6
Test Condition and Observation ...................................................................... 88 Test Result and Analysis ................................................................................... 89 4.6.1 4.6.2 4.6.3 4.6.4 4.6.5 4.6.6 PD Fault Gas Generation .......................................................................... 89 PD Fault Energy ......................................................................................... 91 Gas generation rate (per J) ........................................................................ 93 Absolute Gas generation rate (per J) ........................................................ 95 Duval Triangle Analysis ............................................................................. 96 Laboratory DGA and Online Monitor Comparison ............................... 98
Summary ............................................................................................................ 99 Introduction ..................................................................................................... 101 Experiment Setup ............................................................................................ 101 5.2.1 5.2.2 Test Circuit Design ................................................................................... 101 Test Vessel Design ..................................................................................... 102 Generate Thermal Faults ......................................................................... 104 Temperature Measurement Method ....................................................... 104 Heating & Cooling Method ..................................................................... 105
5.3 5.4
Test Procedure ................................................................................................. 103 5.3.1 5.4.1 5.4.2 Measurement Methods.................................................................................... 104
5.5 5.6
Test Conditions and Observations ................................................................. 107 Test Result and Analysis ................................................................................. 107 5.6.1 Thermal Fault Gas Generation ............................................................... 108 5
Gas Generation Rate Comparison under Different Temperatures ...... 109 Duval Triangle Analysis ............................................................................ 111 Laboratory DGA and Online Monitor Comparison .............................. 113
Summary........................................................................................................... 113 Conclusions ....................................................................................................... 115 6.1.1 6.1.2 Research Areas .......................................................................................... 115 Main Findings ........................................................................................... 116
6.2
Reference ............................................................................................................................... 119 Appendix I. Matlab Code Used In the Thesis .................................................................... 123 I.1 Sparking Energy Calculation ..................................................................................... 123 I.1.1 High Frequency Energy Calculation .......................................................... 123 I.1.2 Low Frequency Energy Calculation ........................................................... 125 I.2 PD Energy Calculation ............................................................................................... 128 Appendix II. The Results Used in the Thesis...................................................................... 131 Words count: 34975
List of Figures
Figure 2.1 Basic Hydrocarbon Structures in Mineral Oil [20] ................................. 25 Figure 2. 2 Molecular Structure of FR3 [23] .............................................................. 27 Figure 2. 3 Diagram of Indicator Gases and Faulty Type and Severity in Transformers Filled By Mineral Oil [38] ............................................................ 32 Figure 2. 4 Headspace Sampling Method [39] ............................................................ 33 Figure 2. 5 Gas Chromatograph Concept Diagram [41] ........................................... 34 Figure 2. 6 Duval Triangle Diagrams .......................................................................... 35 Figure 2. 7 TM8 Online Transformer Monitor .......................................................... 36 Figure 2. 8 The Working Principle Diagram of TM8 ................................................ 37 Figure 2. 9 Dual- Column GC Analysis Diagram ....................................................... 38 Figure 2. 10 Example of Analysis Diagram of TM8 Viewer [17] .............................. 38 Figure 2. 11 Photo of Lighting Impulse Sparking Test Vessel [12] .......................... 39 Figure 2. 12 Comparision of Fault Gas-in-Oil Generation between Lyra X and FR3 [12] .......................................................................................................................... 40 Figure 2. 13 Electrical PD Test Diagram [10] ............................................................ 40 Figure 2. 14 Test Vessel Diagram of PD Test [10] ...................................................... 41 Figure 2. 15 Thermal Test 1(Heating Element) [11] .................................................. 44 Figure 2. 16 Thermal Test 2 (Heating Element) [12] ................................................. 45 Figure 2. 17 Thermal Test 3 ......................................................................................... 47 Figure 2. 18 Gas-in-Oil Generations in Different Oils under Various Temperatures ......................................................................................................... 48
Figure 3.1 Schematic View of Electrical Sparking Test Circuit ............................... 52 Figure 3.2 Test Vessel Design Diagram ....................................................................... 54 Figure 3.3 Photo of Sealing Test 1 ............................................................................... 55 Figure 3.4 Pressure Versus. Time of Sealing Test 1 ................................................... 56 Figure 3.5 Partial Coefficients for FR3 and Gemini X .............................................. 61 Figure 3.6 Example of High Frequency Component of Sparking Current ............. 65 Figure 3.7 Example of Power Frequency Component of Sparking Current ........... 66 7
Figure 3.8 Example Filtered Waveform of Power Frequency Sparking Current ... 66 Figure 3.9 Different Types of Sparking ....................................................................... 67 Figure 3.10 Total Gas Generation in Gemini X /FR3 Tests ....................................... 70 Figure 3.11 GIT Generation rate (per) J in Gemini X and FR3 Sparking Tests ..... 73 Figure 3.12 GIT Generation rate (per J) Comparison between Gemini X and FR3 ................................................................................................................................. 75 Figure 3.13 Duval Triangle Evaluation (GIO) of Sparking Fault in Gemini X and FR3 .......................................................................................................................... 77
Figure 4.1 Schematic Diagram of Electrical PD Test Circuit .................................... 80 Figure 4.2 PD Calibration Panel of PD Measuring System Software ....................... 81 Figure 4.3 PD Noise in FR3 under 60 kV .................................................................... 82 Figure 4.4 Example of PD Test DGA Peak Value ....................................................... 84 Figure 4.5 PD Noise Filter ............................................................................................. 85 Figure 4.6 Gas Generation in Gemini X and FR3 PD Test ........................................ 90 Figure 4.7 PD Patterns of Gemini X (60 Minutes PD signals from the 3000 pC Test) and FR3 (1 Minute PD signals from 3000 pC Test 1) ......................................... 91 Figure 4.8 GIT Generation rate (per J) Comparison between 2000 pC Tests of Gemini X and FR3 ................................................................................................. 93 Figure 4.9 GIT Generation rate (per J) Comparison between 3000 pC Tests of Gemini X and FR3 ................................................................................................. 94 Figure 4.10 GIT gas Generation rate (per J) Comparison between 4000 pC Tests of Gemini X and FR3 ................................................................................................. 95 Figure 4.11 Duval Triangle Evaluations for Gemini X and FR3 PD Tests .............. 98 Figure 5.1 CIrcuit Diagram of Hot-Spot Thermal Test Circuit .................... 102 Figure 5.2 Test Vessel Design...................................................................................... 103 Figure 5.3 Thermocouples and Heating Element Configuration ............................ 105 Figure 5.4 Heating and Cooling Procedure ............................................................... 106 Figure 5.5 GIT Generation Rate of Fault Gases in Gemini X and FR3 ................. 109 Figure 5.6 GIT Generation Rate Comparisons between Gemini X and FR3 ........ 110 8
Figure 5.7 Duval Triangle Evaluation of Gemini X and FR3 Thermal Fault ....... 112
10
List of Tables
Table 2.1 Key Properties of Nytro Gemini X [18] ...................................................... 26 Table 2.2 Key Properties of FR3 [24] .......................................................................... 27 Table 2.3 Water Content and Relative Humidity of Processed Liquid Samples at Room Temperature [25] ....................................................................................... 28 Table 2.4 Bond Dissociation Energy [33] .................................................................... 31 Table 2.5 GIO DGA Results under PD Fault of Various Amplitudes [10] .............. 42 Table 2.6 GIO DGA Results under PD Fault of Various Energy [10] ..................... 43 Table 2.7 GIO DGA Result of Thermal Test 1 (Heating Element)........................... 45 Table 2.8 GIO DGA Results in both Liquids .............................................................. 46 Table 2.9 Tests Features Comparison ......................................................................... 49
Table 3.1 Example GIO Concentration in Gemini X ................................................. 62 Table 3.3 Sparking Types ............................................................................................. 67 Table 3.4 Example of Group Sparking Energy Calculation ..................................... 68 Table 3.6 Sparking Energy for Each Test Group inside Gemini X/ FR3 ................ 71 Table 3.7 Absolute GIT Generation Rate (t/J) of Sparking Tests .......................... 74 Table 3.8 GIO Generation Rate (ppm/J) .................................................................... 76 Table 3.9 Comparison of GIO Results between TM8 and Laboratory Analysis .... 78
Table 4.1 Example of PD Test Energy Calculation .................................................... 88 Table 4.2 List of PD Tests ............................................................................................. 89 Table 4.3 PD Energy and Distribution for each Test inside Gemini X/ FR3 ........... 92 Table 4.4 Absolute GIT Generation Rate (a/J) ........................................................ 96 Table 4.5 GIO Generation Rate (ppm/J) .................................................................... 97 Table 4.6 Comparison of GIO DGA Results between TM8 and Laboratory .......... 98
Table 5.1 Thermal Test Conditions and Observations ............................................ 107 Table 5.2 GIO Generation Rate (ppm/J) .................................................................. 111
11
Table 5.3 Comparison of GIO DGA Results between TM8 and Laboratory Analysis ................................................................................................................. 113
12
Abstract
Mineral oil has been traditionally used as an insulating liquid in power transformers for over a century, and Dissolved Gas Analysis (DGA) technique has been used for decades as one of the most useful diagnosis tools to assess the conditions of mineral oil filled transformers. However, due to increasing awareness of environmental protection and fire safety, there is a trend of replacing mineral oil with environmentally friendly natural esters; DGA data interpretation method should then be studied, if necessary revised, in order to be applicable for natural ester filled transformers. This thesis covers experimental studies on performances of a mineral oil (Gemini X) and a natural ester (FR3) in terms of fault gas generation. Laboratory simulated faults include electrical sparks, electrical partial discharges (PD) and high temperature thermal hotspot types. The electrical sparking fault was generated by using a sharp needle electrode with a tip radius of curvature of 5 micrometers, a 2.57 L sealed test vessel was designed and built with the TM8 online DGA monitoring system, and two CTs were used to measure the high frequency and power frequency components of the sparking current, respectively. The electrical PD fault was simulated using the same test system but under lower voltages, and a traditional PD detector was used to record the characteristics of PD signals, including the repetition rate and amplitude. The hotspot thermal fault was generated by heating up a copper element locally in a 2.73 L sealed test vessel, and three thermocouples were used to measure the temperatures of the heating element. Furthermore, the dissolved fault gases in oil were measured by both the online DGA monitoring system and the oil analysis laboratory, and the DGA results were also compared. The main findings of this thesis are outlined below: FR3 generates similar amounts of fault gases to Gemini X under sparking faults. Under the same sparking energy (per J), FR3 generates fault gases 25% higher than Gemini X. FR3 generates higher amounts of fault gases than Gemini X under PD faults. Under the same PD amplitude, the gas generation in FR3 is much higher than that in Gemini X due to a higher PD repetition rate in FR3. FR3 generates less amount of fault gases than Gemini X under high temperature thermal faults (>300 C). This indicates that FR3 is more thermally stable than Gemini X. DGA results obtained by the TM8 online monitor are comparable to those from laboratory analysis, within a deviation of 30% under all the faults.
13
14
Declaration
I declare that no part of the work referred to in the thesis has been submitted in support of an application for another degree or qualification of this or any other university or other institutes of learning.
15
16
Copyright Statement
I. The author of this thesis (including any appendices and/or schedules to this thesis) owns certain copyright or related rights in it (the Copyright) and he has given The University of Manchester certain rights to use such Copyright, including for administrative purposes. II. Copies of this thesis, either in full or in extracts and whether in hard or electronic copy, may be made only in accordance with the Copyright, Designs and Patents Act 1988 (as amended) and regulations issued under it or, where appropriate, in accordance with licensing agreements which the University has from time to time. This page must form part of any such copies made. III. The ownership of certain Copyright, patents, designs, trade marks and other intellectual property (the Intellectual Property) and any reproductions of copyright works in the thesis, for example graphs and tables (Reproductions), which may be described in this thesis, may not be owned by the author and may be owned by third parties. Such Intellectual Property and Reproductions cannot and must not be made available for use without the prior written permission of the owner(s) of the relevant Intellectual Property and/or Reproductions. IV. Further information on the conditions under which disclosure, publication and
commercialisation of this thesis, the Copyright and any Intellectual Property and/or Reproductions described in it may take place is available in the University IP Policy (see http://www.campus.manchester.ac.uk/medialibrary/policies/intellectual-property.pdf), in any relevant Thesis restriction declarations deposited in the University Library, The University Librarys regulations (see http://www.manchester.ac.uk/library/aboutus/regulations) and in The Universitys policy on Presentation of Theses.
17
18
Acknowledgement
Firstly I would like to express my sincerely gratitude to my supervisor Professor Zhondong Wang for her support and guidance during my MPhil research study at the University of Manchester. My MPhil research project would not succeed without her hard work and patient guidance. I am also truly grateful to all the sponsoring companies, i,e. Serveron and TJH2B who provided continuous support to this project at the University of Manchester. In particular, John Hinshaw from Severon and John Noakhes from TJ2HB are extremity helpful. I would also like to thank Cooper Power System for providing natural ester over the years. To all my colleagues in the transformer research group , I appreciate for your company and thank you for offering me an enjoyable working environment. Special thanks to Dr. Xin Wang who taught me so much on test cell design, experimental setup and thesis writing through all the project and Dr. Xiao Yi who offered many patient and wise suggestions. Last but not least, I would like to take this opportunity to thank my parents for their continuous support and understanding, to my girlfriend Miss Jinping Huang for her support and selfless love. They encouraged me to go through all the hard work all the time.
19
20
Chapter 1 Introduction
1.1 Background Study
Mineral oil has been used as a traditional insulating liquid for power transformers for over a century. However, in face of the increasing awareness of environmental protection recently, applying environmental friendly transformer liquids such as natural esters or synthetic esters in transformers of distribution or transmission level is getting more and more popular [1, 2, 3]. Up to now, ester based transformer liquids have been widely used in distribution transformers and there are more and more development work in the aim of used by esters in power transformers [4, 5]. DGA, short for dissolved gas analysis, is one of the most useful diagnosis tools for incipient fault indication of oil-filled transformers [6]. When either thermal or electrical faults are occurred, transformer oil will decompose and recombine into many kinds of fault gases. In the past several decades, experience of DGA based fault interpretation of mineral oil-filled transformers has been accumulated after a wide range of lab research and on-site operation practices. Many standards were established for assessing conditions of mineral oil-filled transformers, such as IEC 60599 and IEEE C57.104 [7, 8]. Among all kinds of DGA interpretation methods listed in the above guide, the most comprehensive one is Duval triangle which was established by Michal Duval offering graphical interpretation [9]. Due to the increased use of environmental friendly transformer liquids, mineral oil based diagnosis methods need to be revised for the use of fault indication for nature ester-filled transformers. Researchers have already carried out some experiments on studying the gas generation characteristics of nature ester FR3 under thermal or electrical transformer faults [10-15]. Based on the results of large amount of experiments, the Duval triangle interpretation method was revised for FR3 in 2008 [16]. Traditionally, laboratory DGA technique, which required taking oil samples from transformers periodically and then sending them to the analytical laboratory, becomes mature for fault indication. Recently, affordable online transformer monitoring products, which are able to provide results based on up to hourly oil sampling, are installed at power level transformers for predicting faults and avoiding failures [17]. However, due to the lack of experience, there are 21
still many concerns about the measurement accuracies of online transformer monitoring equipment. In this aspect, this thesis will compare DGA results from the analytical laboratory and the online transformer monitor TM8 to verify if the monitors results are reliable or not.
Chapter 1 Introduction This chapter includes a brief description of the research background, the objectives of the project and the outline of the thesis.
Chapter 2 Literature Review of Dissolved Gas Analysis on Natural Ester This chapter gives a brief description of transformer liquids used in the experiments, Gemini X as a mineral oil and FR3 as a natural ester, the dissolved gas analysis (DGA) technique, the
22
development of TM8 online DGA monitor, the three main types of transformer fault and a recent experimental study of natural ester DGA.
Chapter 3 Experimental Study on DGA under Sparking Fault This chapter shows the method to generate the sparking fault and also the method to measure the sparking current. By using a needle to plate electrode configuration, a test cell is designed. It has achieved a good sealing state and complete oil circulation. The sealing state of the electrical test cell is verified by a pressure gauge based sealing test. A proper test procedure is carefully followed to use the test cell TM8 close loop measuring system in order to obtain reliable test results. The experiment in this chapter shows the gas generation characteristics of Gemini X and FR3 under the sparking faults. The simulated faults for both liquids are also evaluated by using the original and revised Duval triangle. Furthermore, oil samples are collected after the electrical sparking test and sent out for laboratory DGA analysis.
Chapter 4 Experimental Study on DGA under PD Fault This chapter describes the method to generate the PD fault using similar configuration to previous sparking test under lower voltage/ electrical fields and also the method to calculate the PD energy. The same electrical test cell as Chapter 3 is used and the proper test procedure is carefully followed to reduce gas leakage. The experiments in this chapter study the gas generation of Gemini X and FR3 under the controlled PD faults up to 2 days.
Chapter 5 Experimental Study on DGA under Thermal Fault This chapter shows the method used to simulate the thermal fault inside the transformer via the W shaped copper heating element, the method to measure the temperature of the heating element is also given. A thermal test cell is designed to achieve a good sealing state, complete oil circulation and oil expansion protection. A proper test procedure is made for using the test cell TM8 measureming system. The experiments in this chapter study the gas generations of Gemini X and FR3 under the simulated thermal faults. The simulated faults inside both liquids are evaluated by using the original and revised Duval triangle. Oil samples are collected after the thermal tests and sent out for laboratory DGA analysis.
23
Chapter 6 Conclusions and Further Work This chapter summarizes the main conclusions of the thesis and also gives some suggestions for future studies.
24
The main advantages of Gemini X are good heat transfer, excellent oxidation stability, good low temperature properties and high dielectrically strength [18]. Gemini X is chemically stable 25
with a high anti-oxidation ability. The dielectric strength of Gemini X is higher than 70 kV (measurement based on IEC 60156 with a 2.5 mm gap distance) when the liquid is preserved. However, once it has been contaminated by water or particles, the dielectric strength will reduce accordingly [19]. The major drawbacks of Gemini X are fire hazards and less biodegradability. The water saturation level of Gemini X is 55 Parts per Million (ppm) at room temperature. Table 2.1 shows the key properties of Gemini X.
Property Density,20 C Viscosity,40 C Flash point Pour point Acidity Aromatic content Water content Breakdown voltage before treatment after treatment
Unit Test Method Physical kg/dm3 ISO12185 2 mm /s ISO3104 C ISO2719 C ISO3016 Chemical mg KOH/g IEC62021 % IEC60590 mg/Kg IEC60814 Electrical kV IEC60156
40-60 >70
26
FR3 is highly biodegradable but can also oxidize easily due to the structure of triglycerides. The dielectric strength of FR3 is above 56 kV (measured by ASTM D1816 using a 2 mm gap distance). FR3 is now mainly applied in distribution transformers in North and South America [22]. The water saturation level of FR3 is 1100 ppm at room temperature which is 20 times higher than that of Gemini X. Table 2.2 shows the key properties of FR3.
Table 2.2 Key Properties of FR3 [24]
Property Density,20 C Viscosity,40 C Flash point Pour point Acidity Water content Breakdown voltage
Unit
Test Method
Physical kg/dm3 ASTM D1298 2 mm /s ASTM D445 C ASTM D92 C ASTM D97 Chemical mg KOH/g ASTM D974 mg/Kg ASTM D1533 Electrical kV ASTM D1816
under 5 mbar inner pressure and 85 C, a further 24 hours cooling down is also required afterwards. The qualities of both Gemini X and FR3 are trusted to be the same. The water content was measured according to the Karl Fisher titration analysis, using Metrohm 684 coulometer and 832 Termoprep ovens [25]. The dissolved gas is measured by the TM8 online transformer monitor. The result of relative humidity (water content versus saturation level) and dissolved gas for the processed liquid sample are below 5% and very close to 0 ppm respectively [10]. Table 2.3 shows the water content and relative humidity of processed samples.
Table 2.3 Water Content and Relative Humidity of Processed Liquid Samples at Room Temperature [25]
28
while the others such as the one which occurs in a transformer liquid is commonly named as streamer [7, 8].
Partial discharges, known as one of the most influencing reasons for insulator degradation, could lead to electric breakdown when they accumulate and propagate fully between two conductors. To avoid costly transformer failures, it is critically important to monitor the PD activities for early detection of the incipient of transformer fault. Dissolved gas analysis (DGA) is now the most widely used method to determine the condition of transformer insulation liquid as it is a non-destructive technique [26-30].
29
Dissolved gas analysis (DGA) is known as one of the most widely used diagnosis tools of oilfilled transformers, it is noted as the non-interrupt test method which has already functioned for decades. Furthermore, DGA is also famous for the reliable fault forecast tool that is developed based on a vast amount of faulty oil-filled equipment in service and laboratory experiment results worldwide [7, 8].
In general, DGA can be divided into 4 steps: collect oil sample, extract dissolved gas, gas chromatograph measurement and data interpretation. The oil sample collection is based on the international standard IEC 60567 which gives the recommended procedure for taking an oil sample from oil filled equipment. The oil sample collection is considered to be the first primary factor of a good DGA result; therefore, the recommended procedure needs to be followed carefully.
The extraction of dissolved gas from the oil sample is the second step. The traditional vacuum method or the alternative vacuum pump method such as headspace and stripper methods are also available in IEC60567 [31]. The headspace method is used in the TM8 and will be explained in Section 2.3.2.
The third step is the gas chromatograph (GC) which could separate and analyze different gas components. Detail of the GC will be described in Section 2.3.3.
The last step will use the DGA results to interpret the transformer conditions. The international standards IEC 60599 and IEEE C57.104 provide many diagnosis tools for DGA results, such as the key gas method, the Roger ratio method and the Duval triangle method. Among all the diagnosis methods, the Duval triangle method seems to be the most popular one in fault prediction [32]. However, because the interpretation methods are all developed based on the known transformer fault data, it may not be correct for some other cases, such as application of new ester liquids. The range and typical values of those interpretation methods might need to be changed as the database is updated. The Duval triangle is used as the interpretation method in this thesis of which the detail will be shown in Section 2.3.4.
30
CC (HCCH) 837
Arcing, low energy sparking, PD and overheating are some of the common faults that could happen in the oil-filled transformers. Once any of these faults occurs, the insulation liquid will be decomposed and then a certain amount of combustible and non-combustible faulty gases will be formed. Generally speaking, there are 7 types of fault gases that could be generated after the transformer faults; they are hydrogen (H2), methane (CH4), ethane (C2H6), ethylene (C2H4), acetylene (C2H2), carbon dioxide (CO2) and carbon monoxide (CO) [7, 8, 34].
Due to the different amounts of energy required to break different kinds of molecular bonds, the type and amount of fault gas generation vary and depend upon the magnitude of the fault energy. As a result, there exists a relationship between the fault type and fault gas generation which can be used to interpret the DGA results.
Figure 2.3 shows the diagram of the indicator gases related to each fault type.
31
Figure 2.3 Diagram of Indicator Gases and Faulty Type and Severity in Transformers Filled By Mineral Oil [38]
For example, C2H2 and C2H4 which have CC bond and C=C bond require a higher energy to be formed than CH4 and C2H6. In other words, the generation of C2H2 and C2H4 stands for the significant faults for oil-filled transformers like an electrical arcing and some hotspot of very high temperatures. As a result, these two types of fault gases have higher weighing factors in the industry scoring system of transformer operation condition assessment [35-37]. Even a small amount of C2H2 would raise concerns of utility companies who own and operate the transformers. 32
Some of the dissolved gas will spread to the headspace from the oil until the equilibrium condition of a certain temperature, agitation and pressure is reached. Afterwards, the headspace gas will be passed to the gas chromatograph (GC) columns. Then the obtained gas concentration in headspace, GIG, will be used to calculate gas-in-oil (GIO) or gas-in-total (GIT) according to Henrys law. GIT = GIG (K (T, gas) + ) P/P0 T0/T
(2.1)
Equation (2.1) shows the calculation method to convert GIG value into gas-in-total [34]. The parameters in the Equation are described below:
GIT, represented as GIT is the concentration of total gas generation including the gas in both oil and headspace. GIG, represented as GIG is the concentration of gas that acquired from GC system directly, which stands for the gas concentration in headspace.
33
K, partition coefficient, is a ratio of concentrations of gas compound between the two solutions, such as transformer liquid and air. , phase ratio, is a ratio of gas volume over liquid volume. P and T are the atmospheric pressure and temperature when the oil sample was measured. Po and To are the standard pressure and temperature. (Po is the 14.7 psi while To is 273.2 K)
mineral oil filled transformers, load tap changers (LTCs) of the oil type and the low temperature fault. The triangle coordinates value can be computed by the DGA results in ppm as below:
= = =
100 * C2H2 / (C2H2 + C2H4 + CH4); 100 * C2H4 / (C2H2 + C2H4 + CH4); 100 * CH4 / (C2H2 + C2H4 + CH4);
In this thesis, the original mineral oil Duval triangle and the revised FR3 Duval triangle will be used to interpret the simulated transformer faults [16].
35
fault. With the help of software, those monitors will be able to calculate and display some of the interpretation results like the Duval triangle [42].
36
Transformer oil
Oil flow
Gas flow
Helium flow
Data flow
In the closed loop system, transformer oil keeps circulating between the test vessel/ transformer and the oil chamber of the TM8 extractor. The gases dissolved inside the transformer oil will go through the liquid blockage membrane into the gas chamber of the TM8 extractor. The carrier gas helium flow (red arrows) will carry the dissolved gases into the extractor gas chamber and will go to the selective columns. These will separate all 8 kinds of gases and let them reach the GC analysis part at different times. Lastly, in the GC analysis part, the fault gases are analyzed by the sequence as shown in next Section.
37
38
A 4-stage impulse generator is used as the voltage supply. The test configuration is with a 4 mm gap distance and a 134 kV impulse voltage which results in a 4096 J fault energy. Most of the fault energy is converted into heat and less than 1% of it is consumed to generate fault gases. The test result after 90 lighting impulse sparking is shown in Figure 2.12. It can be seen from this figure that, C2H2 and H2 are the key indicator for the impulse sparking fault inside both oils, as much as 50.0% and 41.8% in Lyra X and 46.7% and 29.7% in FR3. The total gas generation of Lyra X is twice that of FR3. The CO is only significant in FR3 which makes up to 7.6% of total gas generation.
39
L/L
H2 1775 605
CH4 155 99
CO 0 155
Figure 2.12 Comparision of Fault GIO Generation between Lyra X and FR3 [12]
40
The test vessel diagram is shown in Figure 2.14. It can be seen from the diagram that the 100 ml glass vial sealed by an aluminum crimp cap is fully filled with test oil. The needle electrode is penetrated into the rubber sealing whose tip radius of curvature is 6-7 m from front view and 2-3 m from lateral view.
The assemble of the test vessel and the needle electrode is immersed inside an insulating oil filled container. A copper base of 100 mm diameter is placed under the bottom of the test vessel as a plate electrode. The gap distance between the needle and plate electrode is kept as 50 mm for all tests. A new needle electrode will be replaced after each test. The oil sample is immediately sealed by the Acrylic-based sealing compound from RS Ltd [43] and is then sent to the TJH2B analytical laboratory for DGA measurement. The test results of FR3 and Gemini X are compared by the PD amplitude and PD energy. As can be seen from Table 2.5, FR3 generates around twice the amounts of total combustible gases (TCG) of Gemini X under large PD amplitudes (when the PD amplitudes is over 500 pC). The fault gas generation increases as the PD amplitude rises.
41
Table 2.5 GIO DGA Results under PD Fault of Various Amplitudes [10]
Oil
Test G.Test1
PD amplitude (pC) 200 300 500 1000 200 300 500 1000 0.2 0.2 0.2 1.5 0.2 2.7 5.5 9.1 0.2 0.1 0.3 3.5 0 5 11.5 22.4
H2
12.4 7 62.4 163 29.9 63.7 69.1 140
CH4 CO TCG
0.9 0.5 0.4 2.9 1.2 3.9 5.8 11.4 21.7 12.4 13.9 13.6 20.1 36.2 30 49.9 35.8 20.4 77.5 185.4 96.1 194.9 167.9 296.2
Gemini X
FR3
Note: Those unexpected results listed in bold and italic style may be caused by leakage.
The difference is mainly contributed by C2H6 which makes up to 46.5% (200 pC), 42.8% (300 pC), 80.5% (500 pC), and 21.4% (1000 pC) of the total gas generation for FR3. H2 is the most significant hydrocarbon gases except C2H6. H2 is making up to 34.6% (200 pC), 34.3% (300 pC), 27.4% (500 pC), and 87.9% (1000 pC) of the total gas generation in Gemini X tests while that is only 31.1% (200 pC), 32.7% (300 pC), 41.2% (500 pC), and 47.3% (1000 pC) in FR3. The concentration of CO in FR3 is around twice of that in Gemini X. C2H2 starts to generate under the 1000 pC PD fault inside Gemini X while the trace of it could be found inside FR3 under 300 pC PD fault.
Another 8 groups of tests of both the FR3 and Gemini X under the 500 pC PD fault and different time durations are carried out; the test results are calculated into l/J for comparison as shown in Table 2.6.
42
Table 2.6 GIO DGA Results under PD Fault of Various Energy [10]
Oil
Test
1 2 3 4 1 2 3 4
Times (mins)
15 30 45 60 15 30 45 60
Gemi ni X
DGA(ppm) C2H4
0.5 0.2 0.3 0.6 0.4 1.5 3.3 6.0
C2H2
0.4 0.3 0.5 0.7 0.6 3.1 7.0 13.6
C2H6
0.2 0.3 0.2 0.3 12.7 18.2 28.0 63.5
H2
31.3 62.4 70.9 110.0 46.7 88.4 74.7 138.0
CH4
1.7 0.4 0.9 1.8 0.7 1.9 3.9 6.6
CO
10.9 13.9 12.5 40.5 10.1 17.9 29.7 39.6
TCG
45.0 77.5 85.3 153.9 71.2 131.0 146.6 267.3
l/J
584.4 956.7 927.2 980.3
FR3
1020
Note: The unexpected result in bold and italic style may be caused by leakage.
It can be seen from Table 2.6 that the PD fault in Gemini X generates around half of total fault gases than FR3 under the same test conditions. However, when the PD energy is taken into consideration, the amount of gas generation rate (per J) in Gemini X is 10 times higher than that in FR3. The reason is that PD repetition rate in FR3 is much higher than that Gemini X. For the same type of liquid, the gas generation is increased as the voltage applying time becomes longer. However, the amount of gas generation rate (per J) in FR3 test is not linear for different voltage applying times because the needle electrode changed as the test carried on.
The energy calculation method used in this test is also applied in this thesis. The energy is calculated by using the sum of PD discharge magnitude times the instantaneous voltage when each PD discharge occurs. As stated before, there is some leakage during sample transportation; the new design therefore uses a sealed online DGA system to avoid such an influence. The oil volume is also increased from 100 ml to 2.57 L in this thesis in order to obtain a more stable result even when accident occurred.
In this design, the copper heating element which is made of 7 strands of copper wires (each strand is 7cm long and 0.5mm in diameter) is used to simulate the hotspot thermal fault. A single phase, 50 Hz loading transformer with 240/3.5V and 45-90/3000A rating is chosen as the current supply of the heating element. The thermocouple sensor was twisted into the copper strands for temperature measurement. The Perspex test vessel was kept open during the tests for safety reasons; as a result, the generated gas will partially leak out. The transformer liquid is heated up to 700 C and the total heating duration is up to 50 minutes. Huge bubbles are generated in the mineral oil during the test while fewer fumes are formed in the FR3 test [11].
Table 2.7 shows the DGA result of heating element thermal test. It could be noticed that all GIO fault gas concentration in FR3 is much higher than that of the mineral oil. However, the dissolved gas cannot represent the total generated gas because the test vessel was kept open
44
during the test. The test is then redesigned so that it can be carried out inside a sealed closed loop system in this thesis.
Times (mins)
35 50
C2H4
0.1 20.9
C2H2
0.0 0.0
CO
13.8 14.4
TCG
20.1 60.7
2.5.3.2 Thermal Test 2 Mark designed a localized heating element test using a special material which linearly changed the resistor in a wide range of temperatures up to 550 C [12]. Figure 2.16 shows Marks test design. As shown in the figure below, the special material Resistherm is used as the heating element and put inside the oil-filled sealed test vessel. A funnel is set upside down to collect the generated fault gases; the fault gases will finally go into the top syringe and held there. Another syringe is used to release the pressure that is caused by the oil expansion during the test. The voltage across the heating element and the current that passes through it are recorded for temperature calculation.
45
The heating element is maintained at 300 C to 600 C for 1 to 6 hours. Higher temperatures cannot be achieved due to the melting of the Resistherm. The DGA results for all tests in both liquids are shown below in Table 2.8.
Table 2.8 GIO DGA Results in both Liquids (a) GIO DGA Results in FR3
CO2
1353 2973 3698 3923
C2H4
27 209 631 1061
C2H2
0 0 0 0
DGA(l/J) C2H6 H2
489 934 1005 1307 92 278 472 382
CH4
33 214 351 453
CO
932 4219 3095 5148
TCG
1573 5854 5554 8351
CO2
57 169
C2H4
8 198
C2H2
0 38
DGA(l/J) C2H6 H2
2 7 11 70
CH4
20 149
CO
510 687
TCG
551 1149
It can be seen from the table that the total generated fault gases in Lyra X is around 5 times higher than that in FR3 under 400 C thermal stress. CO and CO2 are the main generated fault gases under the thermal fault for both oils. C2H4, CH4 and C2H6 are also significant in FR3 tests while the C2H4 and CH4 are significant in Lyra X. C2H2 was already generated in Lyra X 400 C thermal test which indicates that the fault temperature in some areas is already much higher than the calculated average temperature. The temperature distribution of the heating element is therefore not even.
2.5.3.3 Thermal Test 3 Dave designed the following experiment to heat up different transformer liquids under various temperatures. The test equipment shown in the Figure 2.17 includes:
46
1. An expansion chamber which is maintained at atmospheric pressure. An insolation valve is installed between the connection of equipment 1 and 3. 2. A pressure gauge. 3. A gas chamber that can be sealed by the isolation valve. 4. A liquid reservoir. 5. A pump that circulates liquid between 4 and 6. . 6. An oven.
The natural ester (the soybean oil, the high oleic sunflower oil) and the mineral oil are all heated for 8 hours. The test results are shown below in Figure 2.18. It can be seen from Figure 2.18 there is a 50 C temperature difference for main fault gases yielding between the soybean oil and the high oleic sunflower oil; a 50 C difference between the high oleic sunflower oil and the mineral oil and a 100 C difference between the soybean oil and the mineral oil.
47
(c) Gas Generation in Mineral Oil under Various Temperatures Figure 2.18 GIO Generations in Different Oils under Various Temperatures [14]
48
On-line or Lab DGA Lab DGA Lab DGA Lab DGA Lab DGA Lab DGA
Features Long Energy term calculation test No Yes No No No N/A No N/A N/A N/A
Heating element or oven N/A N/A Heating element Heating element Oven
Therm al test
Resisthermal
N/A
In comparison, On-line DGA which can ensure a fully sealed system and provide hourly DGA sample for more reliable fault indication is getting more and more popular all around the world. On the other hand, GIT fault gas concentration reflects real fault gas generation which is better than GIO, since the GIG compound is also taken into consideration in GIT calculation. To achieve better test result, the GIO calculation and on-line DGA method are used in this thesis.
Thermal test 1 is an open test in case the oil expansion will damage the test vessel. However, the generated gas leaked out during the test, making the result unreliable. The test system in this thesis is designed as fully sealed for reliable result.
Resisthermal is used in thermal test 2 for temperature measurement. This measurement method obtained the average temperature by using voltage and current going through the heating element. The thermal couple which could be used to measure the hot spot temperature is used to get the hot spot temperature in this thesis. Thermal oven which can offer relatively balanced heating up process for whole oil is used in thermal test 3. Thermal fault in real transformers occurs more like a hot spot instead of oven; therefore, the heating element are chosen as the heating method in this thesis.
49
50
51
The cage
Over Current Protection relay 5A Variac 0-240 V Output CT V/A = 1/10 High frequency CT
CT
240V/80kV
500 pF
R2
Oil inlet
TM8
Oil outlet
PC based TM8 control software 100 MHz oscilloscope 1 100 MHz oscilloscope 2
Due to the limitation of the voltage divider, the maximum voltage used in the test was 70 kV. The over current protection relay was set to 5 A to trigger the sparking faults. A 600 k water resistor was connected between the HV output and the test vessel to reduce the sparking current in case any damage is made to the gas tight system. The cylinder shaped gas tight test vessel, which was made of transparent Perspex contains a needle - plate electrode system. The needle electrode was connected to the high voltage output and the bottom plate electrode was connected to earth. A TM8 on-line DGA monitor was connected to the test vessel to measure the fault gases generated in the sparking tests.
During the test, the HV voltage was measured by the 10 k: 1 voltage divider which was connected in parallel with the test vessel. Two current transformers were used to measure the sparking current, in which a power frequency current transformer (CHAUVIN ARNOUX MN 52
60 current clamp, bandwidth from 40 Hz to 40 kHz) with a 1/100 output ratio was used to measure the power frequency component of the sparking current, and another high frequency current transformer (Stangenes pulse current transformer, model No. 0.5-0.1, Square Pulse Rise Time = 20 ns) with a 1/10 ratio was used to measure the high frequency component of the sparking current. The results of the two current transformers were combined together to get the total result of current.
53
(b) Photo of Electrical Test Cell Figure 3.2 Test Vessel Design Diagram
In order to obtain a complete oil circulation, several methods were applied as follows. Firstly, the headspace was completely removed before test. Secondly, the 20 degree slope at the vessel top is designed to remove the headspace and collect the fault gases. Thirdly, the oil inlet pipe 54
and outlet pipe are installed at the top/bottom of the test vessel to make sure that all oil is in the circulation loop. Finally, the tube between the inlet pipe of TM8 and the syringe adaptor was as short as possible to reduce the dead volume, since oil in this area is barely circulated and it represents dead volume.
The syringe of 50 ml connecting to the top of the test cell is also used to remove the gas bubbles during test setup and also balance the inner system pressure with outside atmosphere pressure during test operation.
3.2.2.2 Sealing Tests Two sealing tests are carried out to check whether the sealing state is qualified for both the electrical sparking and electrical partial discharge (PD) tests.
Sealing test 1 is designed to check how much pressure difference between the inner and outside of the test vessel is reduced in a period of 23 hours. The setup of sealing test 1 is shown in Figure 3.3.
The empty test vessel is sealed and connected to the pressure gauge with a maximum 100 mbar measurement range. A syringe pressurized the test vessel until the pressure difference between the inside and the outside of the test vessel reached 100 mbar. Then, the syringe was removed
55
and the test vessel was kept for a further 23 hours. Figure 3.4 plots the pressure difference with time (the pressure data is not recorded at night).
Pressure(mbar)
100 80 60 40 20 0 0 5 10
Sealing test
Pressure(mbar)
15
20
25
Time(h)
Sealing test 1 showed that the test vessel was in a good sealing state, and the pressure difference between the inside and the outside of the test vessel fell from 98 mbar to 89 mbar after 23 hours. This means only 10% gas leaked out within 23 hours and equivalent 0.4% in the first hour.
Sealing test 2 aimed at finding out the relationship between pressure, gas volume and sparking numbers. A test circuit was built up according to Figure 3.1 (the TM8 was not connected in the circuit) with the same electrode configuration. The test vessel was fully filled with FR3. After 50 sparking tests, a 51.5 mbar pressure difference was detected by the pressure gauge and the pressure difference is maintained the same half hour after the test.
Sealing test 1 and 2 indicate the test vessel can be used for the sparking test which only has 15 sparking tests for each case, and for the PD test which could last for 2 days. Only 20% will leak during the test maximally.
56
Process transformer oil as described in Section 2.1.3. Drain oil out of the system. Clean test system, fill processed oil into the system (eliminate the headspace). Measure background gases. Generate sparking faults. Use syringe to push fault gases to be dissolved back into the oil circulation, and measure the amount of fault gases. Process and analyze test data.
First of all, the oil inlet pipe of TM8 needs to be disconnected and put into a waste oil barrel. Secondly, the xtr suspend command needs to be used to suspend the extractor of TM8. The extractor of TM8 needs to be suspended before the pump starts to rotate backwards because the TM8 does not allow oil pump to rotate backwards when the extractor is in operation otherwise the TM8 extractor would be damaged. Thirdly, the pump f oil rev 35 command will be used to pump the oil backwards at the maximum speed (875 rpm) for 5 minutes. The reason that the oil inlet pipe of TM8 needs to be disconnected instead of the oil outlet pipe is because the oil outlet pipe is at the bottom of the test vessel. This kind of setup allows all the oil inside test vessel to be drained out.
Afterwards, the oil pump must be pumped forwards in order to get rid of some oil residue. Firstly, the pump oil off command needs to be used to stop the oil pump; then the oil outlet 57
pipe of TM8 needs to be disconnected and put into the waste oil barrel while the oil inlet pipe needs to be taken out from the waste oil barrel and then put on to an empty oil beaker. Next, the pump oil 35 command needs to be used, making the oil pump rotate forwards at the maximum pumping speed. Wait around 10 minutes and repeat the pump oil backward and forward procedures again to make sure most of the oil is drained out from TM8. According to the test experiment, the previous dissolved gas residue can be reduced to less than 10% after this procedure.
Sometimes the needle electrode needs to be changed before the processed oil is filled into the system. In the sparking test, the needle electrode needs to be changed only when the oil is changed from Gemini X to FR3. To change the needle electrode, the top brass cap nut needs to be screwed out first and then the needle fixer has to be released to remove the medical needle. A new medical needle is put into the needle fixer. The needle is carefully measured by ruler, making sure the gap distance is 35 mm.
3.3.2 Clean Test System and Fill Processed Oil into the System
Processed oil can be filled into the system after the previous oil residue was cleaned. The oil outlet pipe of TM8 needs to be connected back to the bottom of the test vessel while the inlet pipe of TM8 needs to be put into the processed oil test vessel. The oil outlet valve of the test vessel needs to be set in a closed state, the oil inlet valve should be kept in an open state and the syringe valve of the test vessel needs to be set as open, letting the air go out. The pump oil 35 command needs to be used to make TM8 pump the oil from the oil beaker to the test vessel, oil will then go through the TM8 extractor and be filled into the test vessel from bottom to top. The pump oil off command is used to stop the oil pump when the oil is close to the top of the test vessel. The oil inlet pipe of TM8 needs to be connected with the oil outlet valve of test vessel; the valve should be set to the open state afterwards. The oil filled 50 ml syringe needs to be connected with the syringe valve to replace the headspace gas with processed oil.
Lastly, the syringe will be used to apply some negative pressure to the sealed system, checking whether the sealing state of the system is reliable or not. If any gas bubbles come into the 58
system when the pressure is applied, the leakage place of the vessel or the connection must be checked and sealed.
Normally the GIO concentration of previous test will reduce to nil after procedure 3.3.1, therefore the test system didnt require a formal clean procedure. However, the test system needs to be washed and cleaned by processed oil under two certain circumstances: (1) the GIO concentration is too high, i.e. several thousand ppm, (2) the next test oil type is different with previous one.
In this two cases, the Procedure 3.3.1 and 3.3.2 needs to be repeated for a totally clean background.
59
During the sparking test, the output voltage was increased at a rate of 2 kV/s until a sparking (an interrupted breakdown) occurred. The reason 5 kV/s is applied is to avoid any sparking will be formed due to the fast increasing voltage. The sparking voltage and current (high frequency and power frequency) were recorded for further analysis. This procedure was repeated 15 times for each liquid sample.
The K under different temperatures and pressures can be derived from TM8 monitor. Figure 3.5 plots the partition coefficient K for FR3 and Gemini X at different temperatures.
60
10 H2 N2 1 0 40 80 120
10
H2 N2
C
160
CO O2 CH4 1 0 40 80 120
C
160
CO O2 CH4
0.1
0.1
0.01
0.01
C2H6
FR3
Gemini X
In Equation (2.1), is the ratio of gas volume and oil volume inside the oil circulation system. In the sparking test and PD test, =Vgas/Voil= 77 ml/ 2570 ml = 0.02996. P0 is the equilibrium pressure given by the unit of psi and P is the pressure of one atmosphere that is equal to 14.67 psi. T0 is the oil temperature and T is the standard temperature that is equal to 25 C which is 298.2 K.
When the test data were plotted in Duval triangle, the GIG value should be converted into GIO value first. The way to calculate GIO is shown in Equation (3.1) [39].
GIO = GIG K (T, gas) P/P0 T0/T The parameter used in Equation (3.1) is the same as that in Equation (2.1).
(3.1)
hour after the sparking test, and then it started to fluctuate and fell due to leakage, consumption and temperature change. On the other hand, the GIG values of C2H4, C2H2, CH4 and CO reached their peaks at the 3rd hour after the sparking test. Since all the GIG values will reach their peaks within 3 hours, the average values around 3rd hour (result from 2nd 3rd and 4th hours) after the test were reported as the final results in order to minimize the error. The GIT amount can be obtained as the difference between the background and the final results using the equation below: GIT = GIT average - GIT0.
Taking H2 value as an example, the background GIT value can be calculated as GIT = GIG (K + ) P/P0 T0/T = 48.4 ppm (K+0.02996) 14.3 psi/14.7 psi 298.2 K / 295.5 K. According to Figure 3.5, K = 0.044 when T is 22.3 C. Substitute K = 0.044 into the above Equation, we have GIT = 3.5 ppm.
Following the same calculation step, the GIT1, GIT2 and GIT3 can be obtained as 135.3 ppm, 152.1 ppm, 151.0 ppm. The average GIT is GIT
average
ppm + 152.1 ppm + 151.0 ppm) / 3 = 146.1 ppm. Therefore, the total amount of H2 generated during the test is GIT = GIT average - GIT0 = 146.1 ppm 3.5 ppm = 142.6 ppm.
P O2
138031.8 136751.1
H2
48.4 1835
CH4 CO
0 28.8 36.4 36.8 42.9 14.3 22.3 39.7 14.5 22.6 40.7 14.6 22.6 51.4 14.6 22.7
Table 3.2 shows the calculation results of all gases in the example. The Total Dissolved Combustible Gas (TDCG) is also listed as the sum of hydrocarbons, hydrogen and carbon monoxide. For gases with a generation amount less than 0, such as C2H6 -0.7, the GIT is regarded as 0. 62
GIT (ppm)
No. C2H4 C2H2 C2H6 GIT0 0 3 -0.7 GIT1 11.9 76 0 GIT2 15.2 93.7 0 GIT3 16.4 94.5 0 14.5 88.1 0 Average GIT 0 Generation GIT 14.5 85.1 TDCG
CH4 CO 0 6.2 11.3 5.8 14.4 6 14.5 7.5 13.4 6.4 9.8 0.3
(3.2)
It should be noted that the time scale set by the oscilloscopes for the high frequency and low frequency currents are different. For the high frequency current, the time scale is usually 160 ns (one high frequency current pulse) and for low frequency current, the time scale is usually 40 ms. Consequently, Equation (3.2) can be written into Equation (3.3), in which n is the number of sample points and t is the time step between sample points. W = 0 (() () )
(3.3) 63
In Section 3.5, it could be found that the oscilloscopes were set to compensate the CT output ratio and as a result, thus the CT ratios have been taken in account in the recorded readings and therefore will not affect the calculation equation. On the other hand, as stated in section 3.1, the voltage divider is used to reduce the voltage to 1/10 k and the probe of the oscilloscope is also set to 10:1 in compensation, Equation (3.3) needs to be rewritten into Equation (3.4). W = 0 (() () ) 10000/10 W = 0 (() () ) 1000 (3.4)
3.4.3.1 High Frequency Component of Sparking Signal For the calculation of high frequency energy, the V (n) and I (n) were converted into absolute value since sparking in both the negative and positive direction will produce fault gases. Consequently, Equation (3.4) can be rewritten into Equation (3.5). W h = 0 (|()| |()| ) 1000
(3.5)
Figure 3.6 shows an example of a high frequency component. Channel 1 records the sparking voltage while channel 3 records the high frequency sparking current. Figure 3.6(a) shows a full time scale of high frequency sparking signals which includes 2 pulses in a 200 s time range. Figure 3.6(b) is the zoom-in view of Figure 3.6(a), focusing on the first pulse in a 2 s time range. It should be noted that noises exist in the recordings and should be filtered. In this example, the noise is about 5 A while the maximum pulse signal is 250 A (channel 3 voltage to current ratio is 1: 1, therefore 250 V noise signal from oscilloscope stands for 250 A). Matlab was used to calculate the energy for the high frequency component. 200 k points are recorded for each test and therefore n in Equation (3.5) is 200,000. V[n] and I[n] are stored in two arrays and time step t is set to 1 ns.
64
3.4.3.2 Power Frequency Component of Sparking Signal For the calculation of power frequency energy, the power frequency current was measured in the primary winding side of the voltage supply transformer because the current is too small to be measured in the secondary winding side. Therefore, the measured current should be converted to the value at the secondary winding side by a factor of 240/ 80k. Equation (3.4) can be rewritten into Equation (3.6) to compute power frequency power. W p = n 0 (V(n) I(n) t) 1000 240/ 80000 W p = n 3 / 1000 0 (V(n) I(n) t) 1000 W p = n 0 (V(n) I(n) t) 3 (3.6)
Figure 3.7 shows an example of power frequency energy calculation for the same sparking test shown in Figure 3.6. Channel 1 (yellow) shows the sparking voltage and channel 2 (pink) shwos the power frequency current. Theoretically the background relative power before sparking should be 0, however, there is a slight phase difference between the current from the primary and the secondary winding, making the reactive power not equal to zero. Therefore, the background energy should be eliminated in the energy calculation. Since the background energy within any period before the sparking faults is a constant W0, the actual sparking energy 65
can be obtained by using the sparking energy W1 (as shown in Figure 3.7) minus the corresponding background energy W0.
It should be noted that the power frequency current transformer (made by Chauvin Arnoux) has a frequency range from 40 to 10 kHz. Therefore, the high frequency noises should be filtered. A Matlab ellipse filter is applied to filter the current signals for two times. As shown in Figure 3.8, the high frequency noises contained in the original power frequency current (blue curve) were removed, leaving only the filtered power frequency current (red curve).
66
Similar to the high frequency energy, Matlab is used to calculate the power frequency energy. 500 k points are recorded for each sparking test and therefore n in Equation (3.6) is 500,000. The V[n] and I[n] are stored in two arrays and time step t = 1 ns.
3.4.3.3 Sparking Types Since sparking (interrupted breakdown) is of the random nature, three different types of sparking were observed during the tests even under the similar test conditions. The sparking could be classified as normal sparking, slight sparking and continuous sparking as shown in Table 3.3.
Table 3.3 Sparking Types
A normal sparking is followed by the interruption of the current relay, after which the applied voltage is cut off. A slight sparking is not followed by the interruption of the current relay, and the voltage is continuously applied on the sample liquid after having a slight voltage dip. Therefore, the energy of the slight sparking was not calculated since the amount of fault gases is small and the sparking energy is also small. A continuous sparking contains two or more sparking faults before the current relay cuts off the voltage. Therefore, the energy of all sparking faults contained in a continuous sparking was calculated. The waveforms of different types of spankings are shown in Figure 3.9.
67
3.4.3.4 Example of Sparking Energy Calculation To calculate the energy for each sparking test, firstly, the number of sparking faults should be determined. Secondly, the average high frequency power and power frequency power need to be used for group sparking energy estimation.
For example, Table 3.4 shows the energy of Gemini X sparking test group 2. This group contains 13 normal sparking and 1 continuous sparking (including two consecutive sparking) which in total form 15 sparking in this group. When the double sparking occurred, the power frequency signal is completely recorded as shown in Figure 3.9 (c) while the high frequency pulse of the second consecutive sparking (Sparking 10 b) is missed for the sampling period of the oscilloscope is too short (200 s) to catch the second pulse.
Test 2 Sparking 1 Sparking 2 Sparking 3 Sparking 4 Sparking 5 Sparking 6 Sparking 7 Sparking 8 Sparking 9
PF Energy(J ) 1.77 1.37 1.64 1.63 1.51 4.01 1.77 1.92 1.3
HF Energy(J ) 2.02 1.07 1.42 1.79 1.42 2.24 1.64 2.25 1.04
Test 2 Sparking 10 a Sparking 10 b Sparking 11 Sparking 12 Sparking 13 Sparking 14 average total Group energy (J)
55.57
As shown in Table 3.4, the power frequency energy of sparking 10 (4.93 J), the double sparking, is roughly the double of the power frequency energy of other sparking in this group (average 1.96 J). In this case the average power frequency energy is equal to 1/15 of the sum of all sparking which is (1.77 J + 1.37 J + 4.93 J+ 1.75 J+ 1.92 J)/ 15 = 1.96 J, the total power frequency energy is then 15 1.96 J = 29.37 J.
68
On the other hand, the high frequency energy of sparking 10 only stands for the first consecutive sparking (Sparking 10 a) whose energy (1.55 J) is close to the average value (1.75 J). The sum of high frequency power is 15 average energy of high frequency energy (1.75 J) and such the total energy is 1.75 J 15 = 26.20 J. Group energy is the summary of total power frequency energy and high frequency energy which is 29.37 J +26.20 J = 55.57 J.
Oscilloscope Setting Power frequency current Channel 1 Voltage div probe Voltage divider ratio Channel 2 Current div probe CT ratio Trigger Coupling Time Delay Point number div 50 V 10/1 1/10 k 1V 10/1 1/10 HF reject 0 500 k 10 ms High frequency current Channel 1 Voltage div probe Voltage divider ratio Channel 3 Current div probe CT ratio Trigger Coupling Time Delay Point number div 50 V 10/1 1/10 k 100 V 100/1 1/100 DC -80 s 200 k 20 s
The average sparking voltage for FR3 is 51 kV with a 3 kV fluctuation and is 54 kV for Gemini X with a 3 kV fluctuation. Compared with FR3, under the same test conditions,
69
Gemini X requires higher energy for the incipient of sparking and will also generate a higher amount of gas bubbles after each sparking.
ppm
(a) GIT of Gemini X Tests 250.0 200.0 150.0 100.0 50.0 0.0 Test group 1 Test group 2 Test group 3 Test group 4 Test group 5 Test group 6 C2H4 14.5 11.6 13.0 13.8 13.0 11.4 C2H2 92.5 84.5 84.6 100.7 86.0 92.5 C2H6 0.6 0.1 0.0 0.6 1.1 0.0 H2 194.1 194.3 170.4 212.2 179.3 218.6 CH4 6.2 6.2 7.5 6.7 5.9 6.1 CO 42.0 38.2 31.2 49.9 45.0 47.9
ppm
70
It can be seen that the total amount of fault gases of Gemini X and FR3 are similar at about 200 ppm. However, the fault gases generation of FR3 is relatively stable compared with Gemini X, and the fault gas amount varies in each group probably due to different energies even when the test condition was well controlled. Therefore, the sparking energy should be taken into account to compare the gas performance of different oils. Generally speaking, fault gas generation is relatively similar when the same numbers of sparking faults are applied. However, when the sparking energy is taken into consideration, the conclusion is varied slightly.
Table 3.6 Sparking Energy for Each Test Group inside Gemini X/ FR3
Gemini X test group Average(J) Total(J) PF average(J) HF average(J) 1 2.96 44.47 1.71 1.25 2 3.7 55.57 1.96 1.75 3 3.52 52.74 1.77 1.75 4 3.65 54.79 1.76 1.89 5 3.6 54.05 1.73 1.87 Average of Gemini X 3.49 52.32 1.79 1.70 FR3 test group Average(J) Total(J) PF average(J) HF average(J) 1 3.20 48.04 1.97 1.23 2 2.89 43.32 1.63 1.26 3 2.78 41.76 1.53 1.25* 4 2.77 41.51 1.63 1.14 5 2.89 43.28 1.65 1.24 6 2.19 32.82 1.38 0.81 Average of FR3 2.79 41.79 1.63 1.15 Note: * The original test data are damaged, 1.25 J is estimated data
71
The sparking energy for each test group is different with the maximum deviation of 20%. FR3 has a 20% lower energy compared with Gemini X. The difference of the energy is mainly attributed to the high frequency component of the sparking faults, since the difference of high frequency component energy for Gemini X and FR3 is 48% while that of power frequency component energy is only 9%.
72
8.0 6.0 4.0 2.0 0.0 Test group 1 Test group 2 Test group 3 Test group 4 Test group 5 Average of groups
ppm/ J
(a) Gas generation rate (per J) in Gemini X tests 12.00 10.00 8.00 6.00 4.00 2.00 0.00 Test group 1 Test group 2 Test group 3 Test group 4 Test group 5 Test group 6 Average of groups
ppm/ J
(b) Gas generation rate (per J) in FR3 tests Figure 3.11 GIT Generation rate (per) J in Gemini X and FR3 Sparking Tests
73
It can also be seen from Figure 3.11 that the gas generation rate (per J) is repeatable for all groups. For both liquids, H2 is the main fault indicator which takes up to 60% of the total fault gases, followed by C2H2 which takes up to 25% of the total fault gases. However, CO is only significant in FR3 which always takes up to 12% of total fault gases, which probably due to the ester part in the FR3 molecular structure.
Oil
Gemini X
FR3
J/BD
ppm/BD
ul/BD
ppm/J
ul/J
ml/test
3.0 3.5 3.4 3.5 3.4 3.4 2.69 3.00 2.86 3.24 2.88 2.19 2.8
16.8 22.8 23.4 24.2 18.5 21.1 23.32 22.33 20.44 25.59 22.02 25.10 23.1
43.2 58.6 60.1 62.2 47.5 54.3 59.94 57.40 52.52 65.77 56.58 64.49 59.5
5.59 6.46 6.96 6.94 5.37 6.3 8.66 7.45 7.15 7.90 7.65 11.45 8.4
14.4 16.6 17.9 17.8 13.8 16.1 22.25 19.15 18.38 20.30 19.67 29.41 21.5
0.65 0.88 0.90 0.93 0.71 0.8 0.90 0.86 0.79 0.99 0.85 0.97 0.9
9.0 8.0 7.0 6.0 5.0 4.0 3.0 2.0 1.0 0.0 Gemini X FR3
ppm/ J
H2 3.7 4.7
CO 0.0 1.0
Figure 3.12 GIT Generation rate (per J) Comparison between Gemini X and FR3
It can be seen that the sparking faults in FR3 generates 33% higher amount of total fault gases than that in Gemini X. The amount of H2 in FR3 is 27% higher than that in Gemini X, while the amount of C2H2 in FR3 is 16% higher. Furthermore, CO takes up to 12% in FR3 while it is almost 0 for Gemini X.
75
GIO DGA(ppm) Mineral oil C 2H 4 Test group 1 Duval ratio Test group 2 Duval ratio Test group 3 Duval ratio Test group 4 Duval ratio Test group 5 Duval ratio FR3 C 2H 4 Test group 1 Duval ratio Test group 2 Duval ratio Test group 3 Duval ratio Test group 4 Duval ratio Test group 5 Duval ratio Test group 6 Duval ratio 14.2 12.80% 11.4 11.40% 12.8 12.40% 13.5 11.30% 12.8 12.40% 11.2 10.30% C2H2 91.3 82.10% 83.5 83.00% 83.5 81.00% 99.5 83.50% 84.9 82.30% 91.4 84.50% 0 136.4 1 114.9 0.6 134.5 0 108.2 0.1 123.4 C2H6 0.6 H2 123.1 CH4 5.8 5.20% 5.7 5.70% 6.9 6.70% 6.2 5.20% 5.5 5.30% 5.6 5.20% 37.7 282.3 35.6 254.7 39.4 293.7 24.6 236 30.2 254.3 CO 33.2 TDCG 268.1 14.2 13.40% 17.4 13.50% 17.6 13.40% 17.8 13.30% 15.2 13.20% C2H2 82.7 78.10% 97.8 76.10% 100.4 76.50% 101.3 75.60% 87.9 76.40% 0.5 93.7 0 228.3 1.8 125.9 1.4 123.4 C2H6 0 H2 84.9 CH4 9 8.50% 13.3 10.40% 13.2 10.10% 14.9 11.10% 1191.20% 10.40% GIO DGA(ppm) 1 210.1 0.7 363.1 1.6 260.6 0.7 254.1 CO 0.2 TDCG 191.1
The Duval triangle method can then be applied as shown in Figure 3.13. The FR3 Duval Triangle used here is obtained from the latest publications by M. Duval [16]. It should be noted 76
that the Duval triangle plots for different tests of the same oil are quite close to one another, indicating that the test repeatability is good. It can be seen that the sparking faults in Gemini X and FR3 were all plotted in D1 area (low energy discharge), indicating that the energy of sparking faults was not very high because the sparking current was interrupted by the current protection relay immediately after the fault occurred. Therefore, a continuous arcing path could not be formed in the oil.
Figure 3.13 Duval Triangle Evaluation (GIO) of Sparking Fault in Gemini X and FR3
77
Table 3.9 Comparison of GIO Results between TM8 and Laboratory Analysis
Oil type FR3 TM8 sample Laboratory sample Laboratory / TM8 C2H4 24 19
79.08%
C2H6 3 3
99.84%
H2 80.4 59
73.43%
O2 14190.4 59060
416.20%
CH4 12.1 8
65.91%
CO 53.5 34
63.60%
3.7 Summary
In this chapter, the amount of total fault gases in FR3 and Gemini X are measured using a sealed online DGA test system. The main summaries are listed as follows:
1. FR3 generates a similar amount of fault gases to Gemini X under sparking faults. 2. Considering the sparking energy, FR3 generates fault gases (per J) 25% higher than Gemini X. 3. The fault gas generation (per J) might be a more reasonable parameter to evaluate the gas performances of different liquids. 4. The Duval triangle method can recognize these sparking faults as low energy discharges for both liquids. 5. TM8 online monitor result is comparable with laboratory DGA analysis method with a deviation of 30%.
78
79
The cage
Over Current Protection relay 6.5 A 600 k Water resistor Voltage divider Test vessel Ratio R1 10000:1 500 pF
R2
Zm
Oil inlet
TM8
Oil outlet
Measuring impedence
Process transformer oil (Chapter 2). Drain oil out of the system.
Clean test system, fill processed oil into the system (eliminate the headspace). (Chapter 3.3) Calibrate PD detector. Measure the background gases. Generate PD faults. Measure the amounts of fault gases. Data processing and analysis.
To calibrate the LEMKE LDS-6 PC based PD detector, both the PD amplitude and voltage readings need to be calibrated. The PD calibrator was connected in parallel to the test vessel in order to apply a 50 pC PD signal to the test vessel. The PD detector will then be used to check and calibrate the measured signal to see if it is 50 pC. The PD calibrator needs to be removed and a 30 kV voltage will be applied to the test vessel. The measured voltage from the PD detector was checked and adjusted until the voltage reading matches that of the oscilloscope. Figure 4.2 shows the screen shot of the software.
81
As we can see from Figure 4.3, the maximum PD noise in FR3 under 60 kV is only 30 pC which is extremely low in comparison with 4000 pC PD amplitude when the needle electrode is installed. For this case, the background PD noise could be ignored since the noise is much lower than the noise cutoff level when the needle electrode is in use. The noise cutoff level was used to remove the background noise in the PD test, and the detail is described in Section 4.4.2.1.
is of vital importance for a reliable test result. For this reason, anything could reduce the dissolved gas concentration such as (1) leakage caused by oil flow or (2) gas consumption caused by TM8 sampling must be prevented.
To generate a PD fault, the applied voltage is raised at the rate of 2 kV/s until the target voltage is reached. The voltage is then kept for a certain period of time according to the fault gas generation rate of each liquid. In FR3 test, because the PD repetition rate is high, the PD signal was recorded for 1 minute in every 15 minutes; On the other hand, the PD signal in Gemini X test was recorded from the beginning to the end due to a much lower repetition rate. The test voltage was reduced to zero after the test is finished. Then the oil valves were re-opened and the oil circulation was resumed before the measurement of fault gases by TM8.
83
The H2 is the most significant and easy-leaking gas among all generated fault gases. The H2 peak is therefore chosen as the sign for peak value to obtain a maximum H2 reading. As we can see from Figure 4.4, the H2 (dark blue curve) reaches a peak in 4 hours after the test. Therefore, the readings of fault gases at the 4th hour after the test should be used as the results.
84
noted that the noise of the PD signal should be filtered out via LDS-6 PD measurement software before the calculation.
4.4.2.1 Instrument Noise Filtering During the PD recording, the PD detector was able to remove the small PD noises. This was achieved by applying a cut-off level manually provided by the operator, and any PDs or noises with magnitude less than the threshold level was removed. The cut-off level was determined as a level slightly higher than the PD noise, i.e. a cut-off level of 50 pC based on the noise result in Figure 4.3. Figure 4.5 shows the effect of noise filtering of a 44 kV test of FR3. As shown in Figure 4.5, the filtered PD signal (Figure 4.5 (b)) was obtained by removing the noises less than 130 pC in the recording of all signals (Figure 4.5 (a)).
4.4.2.2 PD Energy Calculation Method As it stated before that several PD files were used to record a PD test, as a result, the energy for each test PD test can be linearly extrapolated The PC-based PD detector recorded 4 parameters of each PD signal: the PD sequence number, the PD occurrence phase when a PD was detected, the PD apparent charge (Q in the unit of pC) and the instantaneous voltage (in the unit of kV). The PD charge and PD voltage can be used to calculate the PD energy using Equation (4.1). 85
W=
(4.1)
where the unit of Q is pC and the unit of V is kV. If we convert the pC to C, kV to V, Equation (4.1) can be rewritten into Equation (4.2) to get the energy in J.
W=
(4.2)
In order to judge the PD energy distribution to each band of PD amplitude, the PD energy is calculated according to 6 PD amplitude bands: 0-1000 pC, 1000-2000 pC, 2000-3000 pC, 3000-4000 pC, 4000-5000 pC, and 5000-6000 pC (barely used). The Find function of Matlab will be used here to pick out these PD that are within the proper amplitude band. Equation (4.2) is still capable for PD energy computation after the qualified PDs are picked out by the Find function.
In order to calculate the overall PD energy, the PD power should be obtained by following Equation (4.3) and linearly extrapolated to the overall period.
(4.3)
P=
(4.4)
Equation (4.4) could be used to calculate energy for each PD record file. In Equation (4.4), t is the sampling period of the PD record file. The unit of P is W, in order to convert the unit of power into standard unit mW, Equation (4.4) then needs to be rewritten into Equation (4.5):
P=
P=
(4.5)
86
As stated at the beginning of Chapter 4.4, the PD signal is recorded into several individual PD files, after the power of each individual file is calculated by Equation (4.5); the average power needs to be acquired by Equation (4.6):
(4.6)
(4.7) Where ttotal is the full time duration for each PD test. Equation (4.7) is used to compute the total PD faults energy by Excel, example shown in next Section.
4.4.2.3 Example of PD Energy Calculation Table 4.1 presents the detail of PD files of the 2000 pC Gemini X PD test which lasts for 1380 minutes. This continuous PD test is separated into 5 PD files. The PD detector recorded 5 PD files for this continuous PD test with a 60 minutes interval. In this case, according to Equation (4.6), the average power Paverage of all PD files is equal to (0.02mW*60minutes + 0.08mW*60minutes +0.12mW*60minutes +0.12mW*120minutes +0.06mW*1020 minutes)/ (60 minutes +60 minutes +60 minutes +120 minutes +1020 minutes) = 0.07mW. Because there are 60 minutes of the PD tests was not recorded by the PD detector due to operation during the test; the recorded total test duration is then 1320 minutes instead of the full test period of 1380 minutes. The total PD energy of the PD test needs to be linearly extended, the result could be achieved based on Equation (4.7): 0.07mW * 1380 minutes = 5.61 J.
87
88
Oil
Test
Test Voltage(kV) 50 50 58 58 34 34 44 44 57 57 57 61
Test duration (minutes) 2880 2580 1380 1290 390 360 180 235 70 150 70 62
PD amplitude (pC) 1500 3000 2000 4000 1000 1000 2000 2000 3000 3000 3000 4000 New After test 1 New After test 3 New New New After test1 After test 3 After test 5 New After test 7 Needle
1 Gemini X 2 3 4 1 2 3 FR3 4 5 6 7 8
All headspace is eliminated from the test vessel before the test started. The oil and headspace volume of the whole TM8-test vessel system are 2.57 L oil and 77 ml which is the same as the sparking test.
Compared with Gemini X, under the same test condition, FR3 generated much higher amounts of fault gases.
89
Figure 4.6 shows the gas generation rate per hour for Gemini X (Figure 4.6 (a)) and FR3 (Figure 4.6 (b)). The result of FR3 shows in Figure 4.6(b) is the average of two tests with the same PD magnitude.
6.0 5.0 4.0 3.0 2.0 1.0 0.0 1500pC 2000pC 3000pC 4000pC
ppm/h
300.0 250.0 200.0 150.0 100.0 50.0 0.0 1000 pC 2000 pC 3000 pC 4000 pC
ppm/h
(b) Gas generation per hour in FR3 Figure 4.6 Gas Generation in Gemini X and FR3 PD Test
It can be seen that the generation rate increases as the PD amplitude increases for both liquids. An exception is that, in Gemini X, the gas generation rate under 2000 pC PD fault is slightly higher than that under a 3000 pC PD fault. This might be caused by different needle states, 90
since the repetition rate of 2000 pC test is higher than that of 3000 pC test. Among all PD tests of Gemini X, the amount of H2 takes up to 50% of the total gas generation while C2H2 takes up to around 25% of total gas generation. Similarly, H2 and C2H2 are also the key indicators for the PD test in the FR3 test whose contributions to the total gas generation are 60% and 15% respectively.
However, the CO generation is only significant in FR3, which might be attributed to the ester part in the FR3 structure. It is also observed that the gas generation rate of FR3 is much higher (5 -150 times higher) than that of Gemini X for the same magnitude. Considering the difference between the PD characteristics of Gemini X and FR3 [10], a larger fault gases concentration in FR3 does not necessarily indicate a higher PD magnitude in FR3. Therefore, the gas generation rate per hour may not be a good parameter to compare the gas performance between different oils, and the PD energy should be taken into consideration.
Figure 4.7 PD Patterns of Gemini X (60 Minutes PD signals from the 3000 pC Test) and FR3 (1 Minute PD signals from 3000 pC Test 1)
91
The difference of PD patterns between both oils leads to the different energy distribution as shown in Table 4.3.
Table 4.3 PD Energy and Distribution for each Test inside Gemini X/ FR3
Oil
Test 1500 pC
Power(mW)
Duration (mins) 2880 1380 2580 1290 390 360 180 235 70 150 70 62
0.02 0.07 0.03 0.13 0.32 0.16 0.65 0.83 6.13 3.35 5.82 7.34
Gemin ix
1000 pC1 1000 pC2 2000 pC1 2000 pC2 FR3 3000 pC1 3000 pC2 3000 pC3 4000 pC
below Energy(J) 1000 pC 77.95 3.21 % 26.69 5.61 % 10.85 5.05 % 12.41 10.44 % 85.54 7.41 % 88.59 3.53 % 46.93 7.04 % 51.58 11.76 % 70.31 25.74 % 74.88 30.14 % 65.89 24.43 % 64.74 27.29 %
10002000 pC 22.05 % 73.22 % 86.09 % 46.99 % 14.46 % 11.41 % 52.65 % 48.03 % 19.00 % 14.57 % 25.70 % 21.35 %
0.42% 0.39% 10.34 0.35% % 9.83% 0.71% 8.11% 0.30% 9.21% 4.57% 0.11% 0.02%
Table 4.3 shows that the PD power is not only related to the PD amplitude but also linked to the PD repetition rate. For example, the Gemini X 2000 pC test had a 0.07mW power while the Gemini X 3000 pC only had a 0.03mW power for the reason that the PD repetition rate in Gemini X 2000 pC test was much higher than that of the Gemini X 3000 pC test. It can also be seen that PD energy distribution in Gemini X is mainly concentrated in the middle range of the PD activities while that of the FR3 is mainly contributed by the low energy PDs located in the negative half cycle. The different energy distributions for both liquids require PD power to be the characteristic parameter to be corresponding to the total gas generation rather than PD amplitude or the PD number. 92
Figure 4.8 shows the gas generation rate (per J) plot under 2000 pC PD tests. It can be seen that the total gas generation rate (per J) of FR3 test is 7.7 ppm/J and is only 10% higher than that of Gemini X, which is 6.6 ppm/J. H2 (4 ppm/J) and CO (1 ppm/J) in FR3 are 30% higher than that of Gemini X which are 3.1 ppm/J and 0.7 ppm/J respectively. The gas generation rates of C2H2 in both liquids are almost the same which is 1.9 ppm/ J. Other hydrocarbons in both liquids are all below 10% of the total gas generation which are not significant. Consequently, the H2 and C2H2 are the key indicators for the 2000 pC PD test of both Gemini X and FR3.
ppm/ J
H2 3.1 4.0
CO 0.7 1.0
Figure 4.8 GIT Generation rate (per J) Comparison between 2000 pC Tests of Gemini X and FR3
Figure 4.9 shows the gas generation rate (per J) plot under 3000 pC PD tests. It can be seen that total gas generation rate (per J) of the FR3 test is 9 ppm/J and is about 10% lower than that of Gemini X which is 10.5 ppm/J. As in the 2000 pC PD tests, H2 (5.9 ppm/J) and CO (1 93
ppm/J) in FR3 are slightly higher than that of Gemini X which are 5 ppm/J and 0.7 ppm/J respectively. The gas generation rate of C2H2 in Gemini X is 2.5 ppm/J and is twice that in FR3 which is 1.3ppm/J. Other hydrocarbons in both liquids are still all below 10% of total gas generation. Consequently, the H2 and C2H2 are the key indicators for the 3000 pC PD test of both Gemini X and FR3.
12.0 10.0 8.0 6.0 4.0 2.0 0.0 Mineral oil FR3
ppm/ J
H2 5.0 5.9
CO 0.7 1.0
Figure 4.9 GIT Generation rate (per J) Comparison between 3000 pC Tests of Gemini X and FR3
Figure 4.10 shows the amount of gas generation rate (per J) for both Gemini X and FR3 under 4000 pC PD tests. It can be seen that the total gas generation rate (per J) of the FR3 test is 10.8 ppm/J and is about 7% lower than that of Gemini X which is 11.6 ppm/J. Similar as that in the 2000 pC PD tests and the 3000 pC PD tests, H2 (7 ppm/J) in FR3 are 8% higher than that of Gemini X (6.6 ppm/J). GIT of CO in FR3 (1.3 ppm/J) is 3 times as that in Gemini X (0.4 ppm/J). respectively. The gas generation rate of C2H2 in Gemini X is 2.5 ppm/J and is about twice as that of FR3 which is 1.4 ppm/J. Other hydrocarbons in both liquids are all below 10% of total gas generation.
94
Figure 4.10 GIT gas Generation rate (per J) Comparison between 4000 pC Tests of Gemini X and FR3
Accordingly, for all PD tests under different PD amplitudes, the amounts of gas generation rate (per J) of both oils are comparable. The gas generation rates increase slightly from around 7 ppm/J to around 11 ppm/J as the PD amplitude increases from 2000 pC to 4000 pC. This phenomenon shows that those PD with large amplitudes actually contribute more to the total gas generation. The gas generation rates of H2 and CO in FR3 are always slightly higher than that in Gemini X. On the other hand, the gas generation rates of C2H2 in Gemini X tests are always higher than those in FR3. H2 and C2H2 are the key indicators for PD fault in both Gemini X and FR3. H2 is significant in FR3 when PD amplitude is high enough (4000 pC).
95
Test FR3 1000 pC 2000 pC 3000 pC 4000 pC Test Mineral oil 1500 pC 2000 pC 3000 pC 4000 pC
C2H4 0.00 0.74 0.98 1.30 C2H4 0.00 0.00 1.26 1.63
C2H2 0.00 4.93 3.39 3.55 C2H2 5.08 4.79 6.53 6.31
GIT (l/J) C2H6 H2 0.38 4.10 0.65 10.22 0.25 15.15 0.59 18.04 GIT(l/J) C2H6 H2 1.33 4.06 0.00 7.88 1.76 12.93 1.16 16.85
CH4 0.00 0.66 0.86 0.95 CH4 0.00 1.18 2.93 3.00
TDCG 6.17 19.89 23.24 27.73 TDCG 13.59 15.69 27.24 29.84
96
Test Mineral oil 1500 pC Duval ratio 2000 pC Duval ratio 3000 pC Duval ratio 4000 pC Duval ratio Test FR3 1000 pC Duval ratio 2000 pC Duval ratio 3000 pC Duval ratio 4000 pC Duval ratio C2H4 C2H2 C2H6
C2H6
0.1 0.3 0.1 0.2
H2
1.6 4 5.9 7
CO
0.7 1 1 1.3
TDCG
2.4 7.7 9 10.8
The Duval triangle method can then be applied as shown in Figure 4.11. It can be seen that PD faults in Gemini X and FR3 all move from D1 towards D2 area as PD amplitudes increase from 2000 pC to 4000 pC which indicate the fault severity increases as the PD amplitude grows. Meanwhile, the FR3 plots are all located in the revised D1 area (low energy discharge area), which conform to the Duvals new triangle quite well. It should be noted that the 1000 pC FR3 test results is not plotted due to low gases levels.
97
(a) Gemini X tests (b) FR3 tests Figure 4.11 Duval Triangle Evaluations for Gemini X and FR3 PD Tests
It could be seen from Table 4.5 that C2H4 and CH4 are 0 ppm/J in 1000 pC PD test inside FR3 and 1500 pC PD test inside Gemini X. The low GIO concentration does not allow the application of Duval triangle.
Table 4.6 Comparison of GIO DGA Results between TM8 and Laboratory
GIO(ppm)
C2H4
12
C2H2
41
C2H6
12 10 7 9
H2
46 58 57 58
O2
18118 20819 20206 20513
CH4
23 24 19 22
91.55%
CO
9 10 9 10
105.69%
Laboratory 17 44 sample 1 Laboratory 13 27 sample2 Laboratory 15 36 average Laboratory / TM8 125.35% 86.98%
98
The Gemini X oil sample was taken after 23 hours 2000 pC PD fault and 21.5 hours 4000 pC PD fault. The oil sample is analyzed by TM8 with the headspace method before the sample collection. The laboratory result was obtained 7 days later. Table 4.6 indicates that for most fault gases, the laboratory results and monitor results agree with each other within a deviation of 30%.
4.7 Summary
In this chapter, the amount of fault gases in FR3 and Gemini X tests were measured using a sealed test system with an online DGA monitor. The main summaries are drawn as follows:
1. At the same PD amplitude, the higher PD repetition rate in FR3 than that in Gemini X leads to a much higher PD energy in FR3 for a given period of time. 2. The gas generation rate (per J) in FR3 is slightly higher than that in Gemini X. 3. For each liquid, the gas generation rates (per J) are similar to each other, and increase slightly for increased PD amplitudes. This indicates that: The total gas generations under PD faults are determined by energy instead of PD amplitude or PD numbers only; a PD with higher energy contributes more to the total gas generation. 4. The PD faults in FR3 can be recognized correctly as low energy discharge from the adjusted Duval triangle method. 5. The TM8 online monitor result using the headspace method is comparable with the laboratory DGA analysis result by the Toepler pump method with a maximum of 30% deviation.
99
100
101
102
(b) Photo
Compared with the previous studies [11], such a design provides several advantages. Firstly, by carefully using rubber gaskets in each joint, the vessel has an excellent sealing capability. Secondly, by using the 20-degree-slope cavity at the top, the test vessel provides a complete oil circulation and ensures the collection of all the fault gases generated in the tests. Finally, by using the syringe assists the removal of headspace before the tests and the collection of large gas bubbles during the tests and push-back fault gases into oil circulation after the tests. Furthermore, the pressure inside and outside the test vessel could also be balanced by the syringe.
Process transformer oil, as described in Chapter 2. Drain oil out of the system. 103
Clean test system, fill processed oil into the system (eliminate the headspace). (Chapter 3.3) Measure the background gases. Generate thermal faults. Push fault gases back into the oil circulation, and measure the amounts of fault gases. Data processing and analysis.
The heating element was bent into a W shape, and 3 holes were drilled at each corner of the heating element, with 10 mm in depth and 0.5 mm in diameter. The thermocouples with 0.5 mm in diameter were inserted into these holes.
Such a design ensures that the thermocouples are in good contact with the heating element, thus the measurement result is close to the actual hot spot temperature. This is evidenced by a verification test in air, that the measured temperature reached 900 C when the heating element melted (1100 C), which indicated a measurement error of only 22%. In this chapter, the average of the three thermocouple recordings is reported as the final measured temperature.
105
However for a thermal fault with temperature less than 300 C, the gas generation rate is so slow that it may take several hours to generate a measurable amount of fault gases. During this period, the temperature of the bulk oil will be gradually increased. Since the oil temperature limitation of the TM8 monitor is 50 C, the maximum temperature of the bulk oil should be controlled. Therefore, a special heating and cooling procedure was applied as shown in Figure 5.4.
The procedure includes the following three steps: the temperature raising period, the heating period and the cooling period. In the temperature raising period, the current gradually increases until the fault temperature reaches the aimed temperature. During the heating period, the current is kept the same until the bulk oil temperature reaches 50 C or the oil expands by a volume of 50 ml. In the cooling period, the current is quickly reduced to zero and the temperature gradually cools down to the environmental temperature. The three steps are repeated until enough fault gases are produced.
Taking 300 C thermal fault for FR3 as an example, the fault temperature increased from room temperature to 300 C in about 30 seconds in the temperature raising period. Afterwards in the heating period, the current was kept stable and lasted for 30 minutes, during which time the fault temperature stayed 300 C and the oil temperature increased to 50 C. Finally, the current supply was stopped and the oil was cooled down for 20 minutes until the temperature was 106
reduced to room temperature. The procedure was repeated six times until enough gases were detected.
Total Free Input temperature heating Voltage Current gas power Test ( C) time evolved (min) (ml) (V) (A) (W) 1 300 60 0.4 261 104 5.5 2 400 5 1.3 600 780 10 Gemini apparent 3 16(s) 2 510 1020 0 X 400 A apparent 4 50(s) 1.3 600 780 30 400 B 1 300 270 0.4 260 104 0 2 400 270 0.6 310 186 2 FR3 3 500 50 1.7 424 721 27 4 600 3 2.9 554 1607 17
Diameter of Heating heating element element melted? (mm) 1.9 N 1.9 N 1.5 1.9 1.9 1.9 1.5 1.5 Y N N N N N
* Apparent 400 A and 400 B: during the test, the displayed temperature is 400 C; however the real temperature should be higher than 400 C, due to a melting element (A) or a high generation rate of fault gases (B).
107
In Figure 5.5 (a), it can be seen that the fault gas generation rate is increased with the increase of the fault temperature for Gemini X. It also shows that the CH4 and C2H4 take up the most part of the total fault gases. Under 300 C thermal faults, CH4 takes up 43% of the total fault gases. Under 400 C thermal fault, CH4 and C2H4 take up 66% of the total fault gases. When the temperature is further increased, the percentage of CH4 and C2H4 increased to 77% for both 400 C A and apparent 400 C B tests. This indicates that CH4 and C2H4 are the key gases of high-temperature thermal faults in Gemini X.
Similar conclusions can be drawn from Figure 5.5 (b) for FR3, that the fault gas generation rate is increased with the increase of the fault temperature. However, different with the result in Gemini X, CO and C2H6 play the most important role in FR3, taking up to 29.3% and 28.0% of total gas generation separately, followed by CH4 and C2H4, which only contribute less important part in total gas generation which varies from 40.5% to 45.6%. It should be noted that CO and C2H6 always takes up more than 25% of total fault gases for all temperatures in FR3, which indicates that the key gases of high-temperature thermal faults in FR3 are CO and C2H6 followed by CH4 and C2H4. The reason that carbon monoxide produced in FR3 in such a larger amount than that in Gemini X might be attributed to the oxygen atoms contained in the ester part of FR3 molecules.
108
100000.0 10000.0 1000.0 100.0 10.0 1.0 300C-104W 400C-780W apparent 400C A apparent 400C B
ppm/ min
ppm/h
(b) Fault gases generation rate in FR3 Figure 5.5 GIT Generation Rate of Fault Gases in Gemini X and FR3
(a) GIT generation rate comparisons between Gemini X and FR3 under 300 C thermal fault
(b) GIT generation rate comparisons between Gemini X and FR3 under 400 C thermal fault
(c) Comparison of GIT generation rate between Gemini X under 400 C faults and FR3 under 500 C thermal faults Figure 5.6 GIT Generation Rate Comparisons between Gemini X and FR3
110
Mineral oil C2H4 300 C Duval ratio 400 C Duval ratio 400 CA Duval ratio 400 CB Duval ratio FR3 300 C Duval ratio 400 C Duval ratio 500 C Duval ratio 600 C Duval ratio C2H2
0
0.40%
0
1.40%
0 113.6 7 1085.3
0 210.4 8 1292.8
0.6
98.20%
532.7
50.50%
1.7
0.20%
521.5
49.40%
47
55.80%
3.7
4.40%
33.6
39.80%
6716.6
59.30% C2H4
71.6
0.60%
4539.5
40.10%
2.4
8.80%
0.4
1.40%
24.1
89.70%
23.8
26.20%
0.8
0.90%
66.4
73.00%
5
52.00%
0
0.00%
4.6
48.00%
107
64.10%
0.5
0.30%
59.5
35.60%
The test results of Gemini X and FR3 could then be plotted in the Duval triangles as shown in Figure 5.7 (a) and (b).
111
(b) Duval triangle evaluation of FR3 tests Figure 5.7 Duval Triangle Evaluation of Gemini X and FR3 Thermal Fault
For Gemini X, the thermal faults at different temperatures are recognized correctly by the Duval triangle method in Figure 5.7 (a). The results also verify the assumption that the actual temperature of the apparent 400 C A and apparent 400 C B tests are higher than the 400 C test. For FR3, most thermal faults (300 C, 500 C and 600 C) are recognized correctly by the revised Duval Triangle method. However, the 400 C thermal fault is recognized as a thermal fault below 300 C. This might be caused by the excellent sealing state of the oil circulation system, which leads to a higher CH4 percentage among the three indicated gases.
112
Table 5.3 Comparison of GIO DGA Results between TM8 and Laboratory Analysis
C2H2 58.56 67 55 61
104.17%
C2H6 H2 O2 CH4 CO 1060.74 945.86 14751.58 2956.23 186.84 961 836 898.5
84.70%
99 77 88
129.34% 47.10%
5.7 Summary
In this chapter, the total gas generation in FR3 and mineral oil are measured with a proper sealed with an online DGA monitor test system. The main summaries that can be drawn are: 1. The generation rates of fault gases are mainly determined by the hotspot temperature rather than the average temperature.
113
2. FR3 generates less amount of fault gases than Gemini X at higher temperatures (>300 C). This indicates that FR3 is more thermally stable than Gemini X. 3. The key indicator gases for thermal faults in Gemini X are CH4 and C2H4; while those for FR3 also include CO and C2H6. 4. The Duval triangle method can recognize all thermals fault in Gemini X while a little revision should be made for the Duval triangle method in order to recognize the thermal faults in FR3 (most of the FR3 results fit the revised Duval triangle method). 5. TM8 online monitor result is comparable with laboratory analysis by the Toepler pump method.
114
In this thesis, the main areas of research covered are: DGA under sparking faults Test cell design for electrical tests Test procedure for DGA measurements under the sparking fault Sparking energy measurement and calculation method Differences of gas performance between the mineral oil and the natural ester under the sparking fault DGA under PD faults Test procedure for DGA measurement under the PD fault Differences of gas performance between the mineral oil and the natural ester under the PD fault DGA under thermal faults Test cell design for thermal tests Test procedure for DGA measurement under the hotspot thermal fault Fault temperature measurement method Differences of gas performance between the mineral oil and the natural ester under the thermal fault
115
Under electrical sparking faults: FR3 generates the amount of fault gases similar to Gemini X. Considering the sparking energy, FR3 generates fault gases (per J) 25% higher than Gemini X. The fault gas generation rate (per J) might be a more reasonable parameter to evaluate the gas performances of different liquids. The Duval triangle method can recognize these sparking faults as low energy discharges for both liquids.
Under electrical PD faults: At the same amplitude, the higher PD repetition rate of FR3 leads to a much higher PD energy in FR3 than that in Gemini X for a given period of time. The gas generation rate (per J) in FR3 is slightly higher than that in Gemini X. For each liquid, the gas generation rate (per J) increases for PDs with higher amplitudes. The PD faults in FR3 can be recognized correctly as low energy discharge from the adjusted Duval triangle method. Total gas generation under PD faults is determined by the overall PD energy instead of either PD amplitude or PD number, and PDs with higher energy contribute more to the total gas generation.
Under hotspot thermal faults: The generation rates of fault gases are mainly determined by the hotspot temperature. FR3 generates less fault gases than Gemini X at higher temperatures (>300 C). This indicates that FR3 is more thermally stable than Gemini X.
116
The key gases for thermal faults in Gemini X are CH4 and C2H4; while those for FR3 also include CO and C2H6. The Duval triangle method can recognize correctly all thermals fault in Gemini X, while slight revision should be made for the Duval triangle method in order to recognize the thermal faults in FR3.
The DGA result obtained using TM8 online monitor is comparable with the laboratory analysis within a deviation of 30% under the electrical sparking faults, the PD faults and the thermal faults.
A thermal camera could be used to film and measure the thermal distribution along the heating element. However, the way to deal with the blockage of test vessel need to be further studied. Some insulation paper could be wrapped on the heating element to simulate the paper wrapped windings in power transformers.
118
Reference
[1] I. U. Khan, Z.D. Wang, I. Cotton, and S. Northcote, "Dissolved gas analysis of alternative fluids for power transformers, Electrical Insulation Magazine, IEEE, vol. 23, pp. 5-14, 2007. [2] C. Perrier and A. Beroual, Experimental investigations on insulating liquids for power transformers: mineral, ester, and silicone oils, Electrical Insulation Magazine, IEEE, Vol. 25, 2009. [3] EPRI, EPRI Report 1000438: Environmentally acceptable transformer fluids; Phase 1 state of the art review; Phase 2 Laboratory testing of fluids, Palo Alto, CA, Nov. 2000. [4] K. Rapp, and P. Stenborg, Cooper Power Systems field analysis of Envirotemp FR3 fluid in sealed versus free-breathing transformers, CP0414, Cooper Power Systems, Waukesha, WI, 2004. [5] D. Martin, I. U. Khan, J. Dai, and Z.D. Wang, An overview of the suitability of vegetable oil dielectrics for use in large power transformers, in Proc. 5th Annual Euro TechCon, Chester, United Kingdom, November 2830, 2006. [6] M. Duval, "A review of faults detectable by gas-in-oil analysis in transformers, Electrical Insulation Magazine, IEEE, vol. 18, pp. 8-17, 2002. [7] IEC, "IEC60599: Mineral oil-impregnated electrical equipment in service-guide to the interpretation of dissolved and free gases analysis, 1999. [8] IEEE, "IEEE Std C57.104-IEEE guide for the interpretation of gases generated in oilimmersed transformers, 2008. [9] M. Duval and A. de Pablo, Interpretation of gas-in-oil analysis using new IEC Publication 60599 and IEC TC10 databases, IEEE Electr. Insul. Mag., vol. 17, no. 2, pp. 3141, 2001. [10] X. Wang, Partial discharge behaviors and breakdown mechanisms of ester transformer liquids under AC stress, in Department of Electrical and Electronic Engineering, University of Manchester, 2011. [11] U. K. Imad, Assessment of the performance of ester based oils in transformers under the application of thermal and electrical stress, in Department of Electrical and Electronic Engineering, University of Manchester, 2009.
119
[12] M. Jovalekic, D. Vukovic and S. Tenbohlen, Dissolved gas analysis of alternative dielectric fluids under thermal and electrical stress, in 2011 IEEE International Conference on Dielectric Liquids, 2011. [13] D. Hanson, J. Luksich, K. Li, A. Lemm and J. Plascencia, Understanding dissolved gas analysis of ester fluids Part 1: stray gas production under normal operating conditions, Siemens Transformer Conference, 2010. [14] C.C. Claiborne, D. Hanson, D.B. Cherry and G.K. Frimpong, Understanding dissolved gas analysis Part 2: Thermal decomposition of ester fluids, in 2011 Euro TechCon, Warwick, UK, 2011. [15] M. Jovalekic, D. Vukovic and S. Tenbohlen, Dissolved gas analysis of natural ester fluids under electrical and thermal stress, in 2011 IEEE International Conference on Dielectric Liquids, 2011. [16] M. Duval, The Duval Triangle for load tap changers, non-Mineral oils and low temperature faults in transformers, IEEE Electrical Insulation Magazine, vol. 24, pp. 2229, 2008. [17] Severon, Serveron TM8 online transformer monitor, Retrieved 1st July 2011, from http://www.bplglobal.net/eng/knowledge-center/download.aspx?id=398. [18] www.nynas.com, Product data sheet Nytro Gemini X, 2008. [19] X. Wang and Z.D. Wang, Particle Effect on Breakdown Voltage of Mineral and Ester Based Transformer Oils, in 2008 Conference on Electrical Insulation and Dielectric Phenomena, Quebec, Canada, 2008, pp. 598-602. [20] www.nynas.com, Base oil handbook, Sweden, 2001, [21] Cooper power system, Envirotemp FR3 dielectric fluid, retrieved 1st July 2011, from http://www.cargill.com/products/industrial/dielectric-fluid/index.jsp. [22] Cooper Power Systems, "Medium and large power transformer users list Envirotemp FR3 fluid", Retrieved 17th August 2011, from
http://www.cooperindustries.com/content/public/en/power_systems/products/dielectric_f luid/envirotemp_fr3_fluid.resources.html, 2011. [23] D. Martin, "Evaluation of the dielectric capability of ester based oils for power transformers", in Department of Electrical Engineering and Electronics, University of Manchester, 2007, p. 225. 120
[24] Cooper power system, "Envirotemp FR3 Fluid - Testing Guide, Retrieved 1st July 2011, from:http://www.spxtransformersolutions.com/assets/documents/R900-20-12 FR3testingGuideApril2008 .pdf. [25] Q. Liu, Electrical performance of ester liquids under impulse voltage for application in power transformer, in Department of Electrical and Electronic Engineering, University of Manchester, 2011. [26] G.P. Cleary and M.D. Judd, "UHF and current pulse measurements of partial discharge activity in mineral oil, Science, Measurement and Technology, IEE Proceedings -, vol. 153, pp. 47-54, 2006. [27] R. Patsch, J. Menzel, and D. Benzerouk, "The use of the pulse sequence analysis to monitor the condition of oil, in IEEE Conference on electrical insulation and dielectric phenomena, 2006, 2006, pp. 660 - 663. [28] M. Elborki, N. Jenkins, P. A.Crossley, and Z.D. Wang, "Power transformer PD sources determination using current signals waveshape and pattern distributions, in The 15th International Symposium on Electrical Insulation (ISEI 2004) Indianapolis, Indiana, USA, September, 2004, pp. 178-181. [29] Z.D. Wang, S.N. Hettiwatte, and P.A. Crossley, "A measurements-based discharge location algorithm for plain disc winding power transformers, IEEE Transactions on Dielectrics and Electrical Insulation, vol. 12, pp. 416-422, June, 2005. [30] Y. P. Nerkar, R. N. Narayanachar, and R. S. Nema, "Characterisation of partial discharges in oil impregnated pressboard insulation systems, in 11th International Symposium on High Voltage Engineering, 1999. vol. 3, 1999, pp. 364 - 367. [31] ASTM D3612, Standard test method for analysis of gases dissolved in electrical insulating oil by gas chromatography, ASTM standard, 2009. [32] N.A. Muhamad, B.T. Phung, T.R. Blackburn, and K.X. Lai, "Comparative study and analysis of DGA methods for transformer mineral oil, in Power Tech, 2007 IEEE Lausanne, 2007, pp. 45-50. [33] S.J. Blanksby, G.B. Ellison, Bond Dissociation Energies of Organic Molecules , Acc. Chem. Res. vol. 36, no. 4, pp. 255-263, 2003. [34] IEC, IEC 60567: Oil-filled electrical equipment Sampling of gases and of oil for analysis of free and dissolved gases Guidance, IEC standard, 2005. 121
[35] J. Lapworth, "A novel approach (scoring system) for integrating dissolved gas analysis results into a life management system, in Electrical Insulation, 2002. Conference Record of the 2002 IEEE International Symposium on, 2002, pp. 137-144. [36] A. Naderian, S. Cress, R. Piercy, F. Wang, and J. Service, "An Approach to Determine the Health Index of Power Transformers, in Electrical Insulation, 2008. ISEI 2008. Conference Record of the 2008 IEEE International Symposium on, 2008, pp. 192-196. [37] A. Jahromi, R. Piercy, S. Cress, J. Service, and W. Fan, "An approach to power transformer asset management using health index, Electrical Insulation Magazine, IEEE, vol. 25, pp. 20-34, 2009. [38] S. Singh and M. N. Bandyopadhyay, "Dissolved gas analysis technique for incipient fault diagnosis in power transformers: A bibliographic survey", Electrical Insulation Magazine, IEEE, vol. 26, pp. 41-46, 2010. [39] Severon, Theory of headspace sampling (for internal use). [40] Linde AG, Gas chromatograph, retrieved 1st July 2011, from http://hiq.lindegas.com/international/web/lg/spg/like35lgspg.nsf/docbyalias/anal_gaschrom. [41] Severon, TMX training tutorial for users (for internal use). [42] Severon, Serveron White Paper: DGA Diagnostic Methods, retrieved 1st July 2011, from http://www.bplglobal.net/eng/knowledge-center/download.aspx?id=217. [43] RS Components, RS Arcrylic Based Sealing Compound retrieved 1st July 2011, from www.rswww.co.uk.
122
%fcutoff=15000; % [B,A]=ellip(4,0.5,20,fcutoff*2*timedelta); %[H,w] = freqz(B,A,512); %f = w/(2*pi)/timedelta; %lfcurrent = filter(B,A,current); %subplot(3,1,1); %plot(f,abs(H));hold on;
123
%%%%%%%%%%%%%%%%%%%%%% %add you energy calculation segment here, give the final energy value %to the variable 'energy'% if currentdiv==500 noise = 25; end if currentdiv==200 noise =15; end if currentdiv==100 noise =5; end M=current; N=voltage; SIZE=size(M); SIZ=SIZE(1); for i=1:SIZ if abs (M(i,1)) <noise M(i,1)=0; end end k=k+1; SIZ=SIZ*1; g=fix(0.1*SIZ); f=fix(0.2*SIZ); HIGH = 0; for i=g:SIZ HIGH = HIGH + M(i,1) *N(i,1)*timedelta*1000; end energy=HIGH b=[char(66),num2str(k)]; c=[char(65),num2str(k)]; title(strcat(header,num2str(seq),'fig')); % add title to the figure, and display the title in the figure saveas(gcf, strcat(header,num2str(seq))); % save the figure with a new name close all; % close this figure, especially when you are using the 'for' loop xlswrite('energy_cal.xls',{'BD number','energy'},'HF'); %xlswrite(strcat(header,num2str(seq),'.xls'),lfcurrent,strcat('A2:A',nu %m2str(tt+1))); %xlswrite(strcat(energy_cal,'.xls'),energy,'LF',a); xlswrite('energy_cal.xls',energy,'HF',b); xlswrite('energy_cal.xls',cellstr(strcat('XIAO0',num2str(seq))),'HF',c); %xlswrite(strcat(header,num2str(seq),'.xls'),energy,'LF');
end
124
125
LOW = 0; BASE= 0; BASE2 = 0; for i=g:ffff LOW = LOW + M(i,1) *N(i,1)*timedelta*3; end for i=gb:ffffb BASE=BASE+ M(i,1) *N(i,1)*timedelta*3; end for i=300000:400000 BASE2=BASE2+ M(i,1) *N(i,1)*timedelta*3; end energy=LOW-BASE b=[char(66),num2str(k)]; c=[char(65),num2str(k)]; title(strcat(header,num2str(seq),'fig')); % add title to the figure, and display the title in the figure saveas(gcf, strcat(header,num2str(seq))); % save the figure with a new name close all; % close this figure, especially when you are using the 'for' loop xlswrite('energy_cal.xls',{'after_lowpass_filter','energy'},'LF'); %xlswrite(strcat(header,num2str(seq),'.xls'),lfcurrent,strcat('A2:A',nu %m2str(tt+1))); %xlswrite(strcat(energy_cal,'.xls'),energy,'LF',a); xlswrite('energy_cal.xls',energy,'LF',b); xlswrite('energy_cal.xls',cellstr(strcat('WASCO0',num2str(seq))),'LF',c); %xlswrite(strcat(header,num2str(seq),'.xls'),energy,'LF');
end
126
% FID=fopen(strcat(header,num2str(startnumber),'_',num2str(endnumber))); % xlswrite(strcat(header,num2str(startnumber),'_',num2str(endnumber)),{'filen ame','energy'}); for seq=startnumber:endnumber timedelta=csvread(strcat(header,num2str(seq),'.csv'),5,1,[5 1 5 1]); voltagediv=csvread(strcat(header,num2str(seq),'.csv'),12,1,[12 1 12 1]); currentdiv=csvread(strcat(header,num2str(seq),'.csv'),13,1,[13 1 13 1]); alllecroy=csvread(strcat(header,num2str(seq),'.csv'),30,0); delay=csvread(strcat(header,num2str(seq),'.csv'),4,1,[4 1 4 1]); voltage=alllecroy(:,1); current=alllecroy(:,2); tt=size(current,1); time=(1:tt)*timedelta;
fcutoff=15000; [B,A]=ellip(4,0.5,20,fcutoff*2*timedelta); [H,w] = freqz(B,A,512); f = w/(2*pi)/timedelta; lfcurrent = filter(B,A,current); llfcurrent = filter(B,A,lfcurrent); subplot(2,1,1); plot(f,abs(H));hold on;
plot(time,current,'b');hold on;plot(time,llfcurrent,'r'); subplot(2,1,2); % bar(abs(fft(current))); %ff=fftshift(fft(current)); %ww=linspace(-0.5/timedelta,0.5/timedelta,tt); % plot(ww,abs(ff)); % subplot(3,1,3); plot(time,current,'b');hold on;plot(time,lfcurrent,'r'); %%%%%%%%%%%%%%%%%%%%%% %add you energy calculation segment here, give the final energy value %to the variable 'energy'% M=lfcurrent; N=voltage; SIZE=size(M); SIZ=SIZE(1); k=k+1; SIZ=SIZ;
127
LOW = 0; BASE= 0; for i=g:ffff LOW = LOW + M(i,1) *N(i,1)*timedelta*3; end for i=gb:ffffb BASE=BASE+ M(i,1) *N(i,1)*timedelta*3; end for i=170000:370000 BASE2=BASE+ M(i,1) *N(i,1)*timedelta*3; end energy= LOW-2*BASE b=[char(66),num2str(k)]; c=[char(65),num2str(k)]; title(strcat(header,num2str(seq),'fig')); % add title to the figure, and display the title in the figure saveas(gcf, strcat(header,num2str(seq))); % save the figure with a new name close all; % close this figure, especially when you are using the 'for' loop xlswrite('energy_cal.xls',{'after_lowpass_filter','energy'},'LF'); %xlswrite(strcat(header,num2str(seq),'.xls'),lfcurrent,strcat('A2:A',nu %m2str(tt+1))); %xlswrite(strcat(energy_cal,'.xls'),energy,'LF',a); xlswrite('energy_cal.xls',energy,'LF',b); xlswrite('energy_cal.xls',cellstr(strcat('WASCO0',num2str(seq))),'LF',c); %xlswrite(strcat(header,num2str(seq),'.xls'),energy,'LF');
end
128
P_number=P_number(1); P_max=max(abs(c(find(b<180)))); N_number=size(find(b>180)); N_number=N_number(1); if N_number>0 N_max=max(abs(c(find(b>180)))); N_phi_min=min(b(find(b>180))); else N_max=0; N_phi_min=360; end Alltime=(max(a)-min(a))*0.02;% unit s P_power=sum(abs(c(find(b<180)).*d(find(b<180))))*1e-12*1000/Alltime*1000;% kv* pc*1000=mW N_power=sum(abs(c(find(b>180)).*d(find(b>180))))*1e-12*1000/Alltime*1000; current=sum(abs(c))*1e-12/Alltime*1000; P_phi_min=min(b(find(b<180))); Energy= (P_power+N_power)*Alltime/1000; c_1000=c(find(abs(c(find(b<180)))<1000)); d_1000=d(find(abs(c(find(b<180)))<1000)); %d_1000=find(abs(d(find(b<180))<=1000); P_Energy_1000=sum(abs(c(find(abs(c(find(b<180)))<1000)).*d(find(abs(c(find( b<180)))<1000))))*1e-12*1000*1000/1000;% kv* pc*1000=mW;mW*s=mJ N_Energy_1000=sum(abs(c(find(abs(c(find(b>180)))<1000)).*d(find(abs(c(find( b>180)))<1000))))*1e-12*1000*1000/1000;% kv* pc*1000=mW;mW*s=mJ Energy_1000=P_Energy_1000+N_Energy_1000; P_Energy_2000=sum(abs(c(find(abs(c(find(b<180)))<2000)).*d(find(abs(c(find( b<180)))<2000))))*1e-12*1000;% kv* pc*1000=mW;mW*s=mJ N_Energy_2000=sum(abs(c(find(abs(c(find(b>180)))<2000)).*d(find(abs(c(find( b>180)))<2000))))*1e-12*1000;% kv* pc*1000=mW;mW*s=mJ Energy_2000=P_Energy_2000+N_Energy_2000; P_Energy_3000=sum(abs(c(find(abs(c(find(b<180)))<3000)).*d(find(abs(c(find( b<180)))<3000))))*1e-12*1000;% kv* pc*1000=mW;mW*s=mJ N_Energy_3000=sum(abs(c(find(abs(c(find(b>180)))<3000)).*d(find(abs(c(find( b>180)))<3000))))*1e-12*1000;% kv* pc*1000=mW;mW*s=mJ Energy_3000=P_Energy_3000+N_Energy_3000; P_Energy_4000=sum(abs(c(find(abs(c(find(b<180)))<4000)).*d(find(abs(c(find( b<180)))<4000))))*1e-12*1000*1000/1000;% kv* pc*1000=mW;mW*s=mJ N_Energy_4000=sum(abs(c(find(abs(c(find(b>180)))<4000)).*d(find(abs(c(find( b>180)))<4000))))*1e-12*1000*1000/1000;% kv* pc*1000=mW;mW*s=mJ Energy_4000=P_Energy_4000+N_Energy_4000; P_Energy_5000=sum(abs(c(find(abs(c(find(b<180)))<5000)).*d(find(abs(c(find( b<180)))<5000))))*1e-12*1000*1000/1000;% kv* pc*1000=mW;mW*s=mJ N_Energy_5000=sum(abs(c(find(abs(c(find(b>180)))<5000)).*d(find(abs(c(find( b>180)))<5000))))*1e-12*1000*1000/1000;% kv* pc*1000=mW;mW*s=mJ Energy_5000=P_Energy_5000+N_Energy_5000; P_Energy_6000=sum(abs(c(find(abs(c(find(b<180)))<6000)).*d(find(abs(c(find( b<180)))<6000))))*1e-12*1000*1000/1000;% kv* pc*1000=mW;mW*s=mJ N_Energy_6000=sum(abs(c(find(abs(c(find(b>180)))<6000)).*d(find(abs(c(find( b>180)))<6000))))*1e-12*1000*1000/1000;% kv* pc*1000=mW;mW*s=mJ Energy_6000=P_Energy_6000+N_Energy_6000; Number_1000=size(find(abs(c)<1000)); Number_1000=Number_1000(1); Number_2000=size(find(abs(c)<2000));
129
Number_2000=Number_2000(1); Number_3000=size(find(abs(c)<3000)); Number_3000=Number_3000(1); Number_4000=size(find(abs(c)<4000)); Number_4000=Number_4000(1); Number_5000=size(find(abs(c)<5000)); Number_5000=Number_5000(1); Number_6000=size(find(abs(c)<6000)); Number_6000=Number_6000(1); fprintf(' fprintf(' fprintf(' fprintf(' fprintf(' %s\n\n',x); Allamplitude\t\t=%f\t\t\t\n',max(P_max,N_max)); Allnumber\t\t=%f\t\t\t\n',P_number+N_number); Allpower\t\t=%f\t\tmW\t\n',P_power+N_power); Allcurrent\t\t=%f\t\tmA\t\n\n',current);
fprintf(' P_max\t\t=%f\t\t\t\n',P_max); fprintf(' P_number\t\t=%f\t\t\t\n',P_number); fprintf(' P_phi_min\t\t=%f\t\t\t\n\n',P_phi_min); fprintf(' N_max\t\t=%f\t\t\t\n',N_max); fprintf(' N_number\t\t=%f\t\t\t\n',N_number); fprintf(' N_phi_min\t\t=%f\t\t\t\n\n',N_phi_min); %fprintf(' Energy \t\t=%f\t\tJ\t\n',Energy); fprintf(' Energy \t\t=%f\t\tJ\t\n',Energy_6000); fprintf(' Energy below 1000\t\t=%f\t\tJ\t\n',Energy_1000); fprintf(' Energy from 1000 to 2000\t\t=%f\t\tJ\t\n',Energy_2000Energy_1000); fprintf(' Energy from 2000 to 3000\t\t=%f\t\tJ\t\n',Energy_3000Energy_2000); fprintf(' Energy from 3000 to 4000\t\t=%f\t\tJ\t\n',Energy_4000Energy_3000); fprintf(' Energy from 4000 to 5000\t\t=%f\t\tJ\t\n',Energy_5000Energy_4000); fprintf(' Energy from 5000 to 6000\t\t=%f\t\tJ\t\n',Energy_6000Energy_5000); fprintf(' PD number fprintf(' PD number Number_1000); fprintf(' PD number Number_2000); fprintf(' PD number Number_3000); fprintf(' PD number Number_4000); fprintf(' PD number Number_5000); below 1000\t\t=%f\t\t\t\n',Number_1000); from 1000 to 2000\t\t=%f\t\t\t\n',Number_2000from 2000 to 3000\t\t=%f\t\t\t\n',Number_3000from 3000 to 4000\t\t=%f\t\t\t\n',Number_4000from 4000 to 5000\t\t=%f\t\t\t\n',Number_5000from 5000 to 6000\t\t=%f\t\t\t\n',Number_6000-
130
Gas-in-total calculated Gas-in-total calculated Gas-in-total calculated Gas-in-total calculated Average GIT Generation GIT
131
Gas-in-total calculated Gas-in-total calculated Gas-in-total calculated Gas-in-total calculated Average GIT Generation GIT
C2H2 164.4
C2H6 0.7
4030
31.2
243.2
1.6
Gas-in-gas_TM8 2
4031
34.0
258.4
1.0
132
Gas-in-gas_TM8 3
12/10/12:4 2
4032
314. 5
34.2
260.4
1.6
6639. 0
122858. 7
127. 3
76. 0
15. 3
22. 3
Gas-in-total calculated
4029
33.0
188.0
1.8
304.5
20135.4
32.9
Gas-in-total calculated
4030
47.9
277.7
4.2
512.0
20070.3
51.3
Gas-in-total calculated
4031
52.5
297.0
2.6
519.7
20074.4
53.3
4032
Time 12/10/12:42
No. 4032
CO2 314.5
C2H4 34.2
C2H2 260.4
C2H6 1.6
H2 6639.0
O2 122858.7
CH4 127.3
CO 76.0
P 15.3
T 22.3
Gas-in-gas_TM8 1
12/10/13:42
4033
313.4
44.2
338.4
1.5
9645.4
121926.4
176.5
84.3
15.3
22.3
Gas-in-gas_TM8 2
12/10/14:42
4034
313.8
46.1
353.1
1.7
9536.6
121347.0
176.1
80.1
15.3
22.4
Gas-in-gas_TM8 3
12/10/15:42
4035
314.5
46.7
352.5
1.4
9474.8
120980.6
176.5
77.2
15.4
22.3
133
Gas-in-total calculated
12/10/12:42
4032
384.9
52.7
299.0
4.2
516.5
20034.0
52.7
11.7
Gas-in-total calculated
12/10/13:42
4033
383.6
68.2
388.5
4.0
750.4
19882.0
73.1
13.0
Gas-in-total calculated
12/10/14:42
4034
383.6
71.0
404.9
4.5
742.0
19780.8
72.8
12.3
12/10/15:42
4035
Time 13/10/09:40
No.
CO2
C2H4
C2H2
C2H6
H2
O2
CH4
CO
4053 Gas-in-gas_TM8 1 13/10/11:18 4054 Gas-in-gas_TM8 2 13/10/12:18 4055 Gas-in-gas_TM8 3 13/10/13:18 4056
313.2
43.9
333.3
2.0
7807.6
113151.5
166.4
83.8
15.7
21.9
315.3
52.6
404.9
1.9
9841.8
113234.0
205.7
88.9
15.7
22.2
317.0
54.8
416.2
2.5
9801.2
112841.4
209.5
99.5
15.6
22.4
319.7
55.4
420.5
2.2
9769.1
112704.1
213.2
87.9
15.6
22.6
134
Gas-in-total calculated
13/10/09:40
4053
395.2
69.8
394.5
5.4
623.0
18959.1
70.9
13.2
Gas-in-total calculated
13/10/11:18
4054
396.5
83.4
477.6
5.1
785.6
18953.7
87.4
14.0
Gas-in-total calculated
13/10/12:18
4055
395.1
86.1
486.7
6.7
777.6
18755.0
88.4
15.6
13/10/13:18
4056
Time 23/9/10:00
No. 3660
CO2 379.5
C2H4 0.0
C2H2 0.0
C2H6 0.0
H2 155.4
O2 143204.8
CH4 0.0
CO 44.7
P 11.9
T 24.6
Gas-in-gas_TM8 1
23/9/12:20
3662
379.8
9.8
41.2
0.0
2960.3
139280.7
27.2
379.9
12.2
25.4
Gas-in-gas_TM8 2
23/9/13:20
3663
381.1
10.4
45.1
0.4
3002.0
138406.2
27.3
404.5
12.4
25.7
Gas-in-gas_TM8 3
23/9/14:20
3664
381.5
10.9
46.3
0.6
2947.4
136897.9
26.6
394.9
12.5
25.9
Gas-in-total calculated
23/9/10:00
3660
471.0
0.0
0.0
0.0
10.2
20198.7
0.0
5.1
135
Gas-in-total calculated
23/9/12:20
3662
479.7
13.5
85.3
0.0
200.5
20281.2
8.5
44.9
Gas-in-total calculated
23/9/13:20
3663
487.9
14.6
94.5
0.7
207.1
20537.7
8.7
48.6
23/9/14:20
3664
No. 3665
C2H2 47.5
C2H6 0.6
CH4 25.4
3666
380.4
17.6
81.1
0.5
50.7
Gas-in-gas_TM8 2
3667
378.6
18.7
88.2
1.1
52.4
Gas-in-gas_TM8 3
3668
373.9
18.6
88.4
0.4
49.7
Gas-in-total calculated
23/9/15:2 0 23/9/16:2 0
3665
492.2 8 496.9 7
14.75
100.69
1.08
204.1 5 411.1 9
20528.8 4 20460.7 1
8.19 16.4 9
47.8 7 84.6 0
Gas-in-total calculated
3666
25.16
173.27
0.90
136
Gas-in-total calculated
23/9/17:2 0 23/9/18:2 0
3667
26.94
189.93
2.01
3668
Time 26/9/15:07
No. 3690
CO2 389.2
C2H4 16.3
C2H2 77.3
C2H6 0.6
H2 3191.1
O2 120188.8
CH4 37.7
CO 545.1
P 15.4
T 25.2
Gas-in-gas_TM8 1
23/9/16:07
3691
388.4
23.1
107.3
0.3
5323.6
118951.4
63.0
686.8
15.5
25.5
Gas-in-gas_TM8 2
23/9/17:07
3692
388.2
24.1
109.4
0.0
5094.4
118121.0
63.0
783.8
15.5
25.5
Gas-in-gas_TM8 3
23/9/18:07
3693
387.1
23.6
110.4
0.6
4977.1
117724.1
63.2
770.6
15.6
25.5
Gas-in-total calculated
26/9/15:07
3690
621.6
28.4
202.4
1.3
272.5
22053.2
14.9
81.3
Gas-in-total calculated
23/9/16:07
3691
622.7
40.5
281.8
0.7
458.5
22025.3
25.0
103.1
Gas-in-total calculated
23/9/17:07
3692
622.4
42.2
287.3
0.0
438.8
21871.5
25.0
117.7
137
23/9/18:07
3693
Test 4
Date 09/29/2011
V (V)
I (A)
Gas-in-total calculated Gas-in-total calculated Gas-in-total calculated Gas-in-total calculated Average GIT Generation GIT
138
FR3
10/03/2011
2570.00
0.00
Gas Type Gas in Gas_TM8-Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
Gas-in-total calculated Gas-in-total calculated Gas-in-total calculated Gas-in-total calculated Average GIT Generation GIT
No.
CO2
C2H4
C2H2
C2H6
H2
O2
CH 4
3930
384.4 389.3 9
9.5
48
11.8
3932
16.2
83.1
2.1
33.9
Gas in Gas_TM8 2
3933
393
16.9
86.9
1.7
35.9
139
Gas in Gas_TM8 3
05/10/16:1 7
3934
393.6
16.9
89.6
1.9
3098. 2
130596. 6
35.5
510. 7
13. 9
23. 2
Gas-in-total calculated
3930
568.6
15.3
117.3
4.1
21.4
21580.0
4.2
20.7
Gas-in-total calculated
3932
573.3
26.0
201.9
4.3
244.4
21388.6
12.1
68.4
Gas-in-total calculated
3933
577.6
27.0
210.6
3.5
239.9
21352.5
12.8
69.1
3934
Time 01/12/14:58
No.
CO2
C2H4
C2H2
C2H6
H2
O2
CH4
CO
4640 Gas in Gas_TM8 1 04/12/06:50 4657 Gas in Gas_TM8 2 04/12/10:50 4657 Gas in Gas_TM8 3 04/12/15:50 4657
336.9
128541.3
18
15.5
21.6
348
5.3
0.6
65.4
122568.1
43.3
15.3
19.1
348
5.3
0.6
65.4
122568.1
43.3
15.4
18.8
348
5.3
0.6
65.4
122568.1
43.3
15.2
18.7
140
Gas-in-total calculated
01/12/14:58
4640
421.2
0.0
0.0
0.0
0.0
21285.0
0.0
2.8
Gas-in-total calculated
04/12/06:50
4657
442.3
0.0
6.3
1.7
5.1
20205.4
0.0
6.7
Gas-in-total calculated
04/12/10:50
4657
446.8
0.0
6.4
1.7
5.1
20358.4
0.0
6.7
04/12/15:50
4657
Time 25/11/13:13
No. 4624
CO2 0.0
C2H4 0.0
C2H2 0.0
C2H6 0.0
H2 0.0
O2 119372.6
CH4 0.0
CO 35.9
P 12.6
T 22
Gas in Gas_TM8 1
29/11/10:45
4625
403.5
0.0
8.8
0.0
217.0
140225.6
8.3
54.6
15.5
20.6
Gas in Gas_TM8 2
29/11/11:45
4625
403.5
0.0
8.8
0.0
217.0
140225.6
8.3
54.6
15.6
21.2
Gas in Gas_TM8 3
29/11/12:45
4625
403.5
0.0
8.8
0.0
217.0
140225.6
8.3
54.6
15.6
21.5
141
Gas-in-total calculated
25/11/13:13
4624
0.0
0.0
0.0
0.0
0.0
16046.7
0.0
4.5
Gas-in-total calculated
29/11/10:45
4625
510.4
0.0
10.4
0.0
17.1
23298.9
3.5
8.5
Gas-in-total calculated
29/11/11:45
4625
510.1
0.0
10.4
0.0
17.2
23401.4
3.5
8.6
29/11/12:45
4625
Time 04/12/16:50
No.
CO2
C2H4
C2H2
C2H6
H2
O2
CH4
CO
4658 Gas in Gas_TM8 1 06/12/13:50 4661 Gas in Gas_TM8 2 06/12/14:50 4661 Gas in Gas_TM8 3 06/12/15:50 4661
350.6
6.6
60.4
123193
37.2
15.1
18.8
368.2
1.6
17.9
1.3
393.6
121610
22.2
61.2
15
20.1
368.2
1.6
17.9
1.3
393.6
121610
22.2
61.2
15
20.5
368.2
1.6
17.9
1.3
393.6
121610
22.2
61.2
15.1
20.8
Gas-in-total calculated
04/12/16:50
4658
441.4
0.0
7.8
0.0
4.6
20063.5
1.3
5.7
142
Gas-in-total calculated
06/12/13:50
4661
453.4
2.5
20.7
3.5
29.9
19587.4
9.1
9.3
Gas-in-total calculated
06/12/14:50
4661
451.3
2.5
20.6
3.5
30.0
19560.7
9.1
9.2
06/12/15:50
4661
No.
C2H2
C2H6
H2
O2 137518. 3
CH4
CO
4628
403.3
1.6
10.5
1.1
9.9
49.8
4629
401.5
5.7
31.9
2.8
135301
48.9
73
Gas in Gas_TM8 2
4629
401.5
5.7
31.9
2.8
135301
48.9
73
Gas in Gas_TM8 3
4629
401.5
5.7
31.9
2.8
135301
48.9
73
Gas-in-total calculated
29/11/13:4 5 30/11/11:3 5
4628
510.1 1 511.1 9
2.55
12.46
3.00
14.61
23057.5 3 22625.6 6
4.22 20.8 6
7.86 11.4 7
Gas-in-total calculated
4629
9.16
38.09
7.72
82.47
143
Gas-in-total calculated
30/11/12:3 5 30/11/13:3 5
4629
9.14
38.03
7.69
83.07
4629
Gas Type Gas in Gas_TM8-Background 1 Gas in Gas_TM8-Background 2 Gas in Gas_TM8-Background 3 Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
C2H4 0 0 0 0 0 0
C2H2 0 0 0 0 0 0
CH4 0 0 0 0 0 0
Gas-in-total calculated Gas-in-total calculated Gas-in-total calculated Gas-in-total calculated Average GIT Generation GIT
PD attitude 1000pC-2
Date 23/11/201 1
V (V)
I (A)
B 0.03
Gas Type Gas in Gas_TM8-Background 1 Gas in Gas_TM8-Background 2 Gas in Gas_TM8-Background 3 Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
Gas-in-total calculated Gas-in-total calculated Gas-in-total calculated Gas-in-total calculated Average GIT Generation GIT
145
PD attitude
Oil Type
Date
Headspace (ml)
V (V)
I (A)
2000pC-1
FR3
14/11/2011
2570.00
0.00
Time 14/11/11:00
No. 4407
CO2 384.9
C2H4 2.8
C2H2 6.7
C2H6 1.6
H2 301.7
O2 90419.7
CH4 8.0
CO 154.9
P 15.1
T 22.7
Gas in Gas_TM8 1
14/11/21:40
4419
390.3
4.1
10.1
2.1
646.6
88132.9
14.4
189.3
15.3
23.5
Gas in Gas_TM8 2
14/11/21:40
4419
390.3
4.1
10.1
2.1
646.6
88132.9
14.4
189.3
15.3
23.5
Gas in Gas_TM8 3
14/11/21:40
4419
390.3
4.1
10.1
2.1
646.6
88132.9
14.4
189.3
15.3
23.5
Gas-in-total calculated
14/11/11:00
4407
616.79
4.88
17.72
3.55
24.83
15915.94
3.10
22.51
14/11/21:40
4419
629.06
7.20
26.81
4.68
54.21
15829.67
5.65
27.93
14/11/21:40
4419
629.06
7.20
26.81
4.68
54.21
15829.67
5.65
27.93
14/11/21:40
4419
PD attitude 2000pC-2
Date 23/11/2011
V (V)
I (A)
Gas Type Gas in Gas_TM8-Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Generation GIT
Time 15/11/11:50
No. 4424
CO2 387.5
C2H4 4.6
C2H2 10.2
C2H6 1.5
H2 620.6
O2 89578.7
CH4 15.2
CO 204.5
P 15
T 21.5
Gas in Gas_TM8 1
15/11/19:50
4431
405.2
11.0
21.4
2.9
2387.7
86963.4
43.4
376.4
15.2
24
147
Gas in Gas_TM8 2
15/11/19:50
4431
405.2
11.0
21.4
2.9
2387.7
86963.4
43.4
376.4
15.2
24
Gas in Gas_TM8 3
15/11/19:50
4431
405.2
11.0
21.4
2.9
2387.7
86963.4
43.4
376.4
15.2
24
15/11/11:50
4424
623.75
8.04
27.19
3.34
50.31
15498.61
5.86
29.44
15/11/19:50
4431
645.83
19.12
56.10
6.40
199.57
15585.59
16.92
55.23
15/11/19:50
4431
645.83
19.12
56.10
6.40
199.57
15585.59
16.92
55.23
15/11/19:50
4431
Gas Type Gas in Gas_TM8Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
148
Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Generation GIT
Gas Type Gas in Gas_TM8Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
C2H2 0 28 28 28
149
17/11/20:4 0
4470
Gas Type Gas in Gas_TM8Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
C2H6 4.6 8 8 8
Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Generation GIT
Test Temperature 300.00 Gas Type Gas in Gas_TM8Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3 Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO
Test 1
Heating 20 mins CO2 440.80 556.30 521.00 514.30 408.20 477.53 484.40 487.16 483.03 470.30
Oil Headspace Volume (ml) (ml) 25/07/2011 2748.00 3.50 Date C2H4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 C2H2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 C2H6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
V (V) 0.40 H2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
11.80 23.80
151366.10 33.50 12.00 31.90 151752.00 36.50 12.10 26.40 152405.00 33.30 12.20 24.80 19187.01 18669.02 19377.88 19565.75 19204.22 19204.22 0.00 10.23 11.72 10.80 10.92 10.92
Test 2
151
Gas in Gas_TM8 2
7/25/16:44
3205
619.40
0.00
0.50
0.00
0.00
147760.70 99.40
12.50
27.70
Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO
Heating 20 mins CO2 514.30 589.30 581.40 576.90 486.68 590.23 594.81 590.90
Date 25/07/2011 C2H4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
I (A) 261.00 O2 CH4 P 12.20 12.90 13.00 13.10 T 24.80 24.80 24.30 24.20
152405.00 33.30 146967.30 89.80 145649.00 87.90 145468.80 84.90 19425.05 19950.23 20111.56 20093.43 10.77 30.80 30.72 29.69
Test Temperature 300.00 Gas Type Gas in Gas_TM8Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3 Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated
Test 3
Heating 40 mins CO2 547.20 729.10 708.10 696.40 589.16 757.82 757.80 752.25
Date 26/07/2011 C2H4 0.00 0.60 0.00 0.00 0.00 0.78 0.00 0.00
Oil Volume (ml) 2742.00 C2H2 0.00 0.60 0.00 0.80 0.00 0.59 0.00 0.81
Headspace (ml) 2.00 C2H6 0.00 0.00 0.00 0.40 0.00 0.00 0.00 0.92
V (V) 0.40 H2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
I (A) 265.00 O2 139369.50 138672.70 138120.10 137220.30 20127.01 20005.21 20113.96 20036.48 CH4 68.20 173.20 169.40 160.40 25.03 62.69 62.38 59.36 P 13.80 13.90 13.90 14.00 T 24.30 28.00 26.10 25.30
H2 15.1 4350. 7
O2 132161.8 127410.0
CO 1285. 9 2093. 0
P 14. 6 14. 7
T 28. 3 43
153
3368 3369
Gas Type Gas in Gas_TM8-Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO Generation GIT
50s
42.5
154
400.00
Mineral
16s
2732.00
0.00
470-510
Gas Type Gas in Gas_TM8-Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO Generation GIT Generation GIO
16s 16s
8.7 8.3
155
30 28.4 27.8
Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO Generation GIT Generation GIO
90 mins 90 mins
385.50 378.20
7/28/08:40
3262
1252.26
2.37
0.00
140.40
8.06
19205.16
44.54
185.51
156
Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO Generation GIT Generation GIO
3h 3h
457.25 447.71
Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO Generation GIT Generation GIO
3h 3h
269.17 263.66
157
Gas Type Gas in Gas_TM8Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO Generation GIT Generation GIO
1.5h 1.5h
843.26 825.65
Test Temperature
Test 2
Oil Type
Heating
Date
Headspace (ml)
V (V)
I (A)
158
400.00
FR3
3h
08/01/2011
2732.00
1.00
0.60
310.00
Gas Type Gas in Gas_TM8-Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
T 27 33.2 30 29.3
Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO Generation GIT Generation GIO
Heating 3h 1.5h
P 10.7 11 11.2
159
Gas in Gas_TM8 3
4/8/16:2 0
3398
1214.0
109.9
0.0
412.5
1064.1
100984.0
556.6
5491.1
11.3
29.6
Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO Generation GIT Generation GIO
20mins 20mins
1002.7 979.75
Test Temperature
Test 2
Heating
Date
V (V)
I (A)
500.00
30mins
08/05/2011
1.70
424.00
Gas Type Gas in Gas_TM8-Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
T 28.2 31 28.7 28
160
Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO Generation GIT Generation GIO
30mins 30mins
1466.42 1428.03
Gas Type Gas in Gas_TM8-Background Gas in Gas_TM8 1 Gas in Gas_TM8 2 Gas in Gas_TM8 3
Gas in total calculated Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO Generation GIT
90s
334.64
161
Generation GIO
90s
326.51
168.57
0.84
185.57
16.53
65.86
118.67
149.70
Test Temperature
Test 2
Heating
Date
V (V) 2.90
I (A)
600.00
1.5min
08/09/2011
554.00
Gas in total calculated Gas in total calculated Gas in total calculated Average GIT Average GIO Generation GIT Generation GIO
90s 90s
312.44 328.79
test 1
lf number Energy(J) hf number WASCO0144 1.68 Xiao0866 WASCO0145 1.85 WASCO0146 1.36
Energy(J) 0.00
162
test 2
test 3
BD 4 BD 5 BD 6 BD 7 BD 8 BD 9 BD 10 BD 11 BD 12 BD 13 BD 14 BD 15 BD 16 BD 17 BD 18 BD 19 BD 20 BD 21 BD 22 BD 23 BD 24 BD 25 BD 26 BD 27 BD 28 BD 29 BD 30 BD 1 BD 2 BD 3 BD 4 BD 5 BD 6
WASCO0147 WASCO0148 WASCO0149 WASCO0150 WASCO0151 WASCO0152 WASCO0153 WASCO0154 WASCO0155 WASCO0156
1.81 1.40 1.69 1.76 3.22 3.04 1.34 1.24 1.78 3.55
WASCO0157 WASCO0158 WASCO0159 WASCO0160 WASCO0161 WASCO0162 WASCO0163 WASCO0164 WASCO0165 WASCO0166 WASCO0167 WASCO0168 WASCO0169 WASCO0170 WASCO0171 WASCO0172 WASCO0173 WASCO0174 WASCO0175 WASCO0176
1.77 1.37 1.64 1.63 1.51 4.01 1.77 1.92 1.30 4.93 1.75 1.81 2.04 1.92 1.17 1.76 1.75 1.78 1.47 1.69
XIAO0875 XIAO0876 XIAO0877 XIAO0878 XIAO0879 XIAO0880 XIAO0881 XIAO0882 XIAO0883 XIAO0884 XIAO0885 XIAO0886 XIAO0887 XIAO0888 XIAO0889 XIAO0890 XIAO0891 XIAO0892 XIAO0893 XIAO0894
2.02 1.07 1.42 1.79 1.42 2.24 1.64 2.25 1.04 1.55 1.73 1.89 2.30 2.07 0.95 1.82 1.81 1.89 1.55 1.90
163
test 4
test 5
BD 7 BD 8 BD 9 BD 10 BD 11 BD 12 BD 13 BD 14 BD 15 BD 1 BD 2 BD 3 BD 4 BD 5 BD 6 BD 7 BD 8 BD 9 BD 10 BD 11 BD 12 BD 13 BD 14 BD 15 BD 1 BD 2 BD 3 BD 4 BD 5 BD 6 BD 7 BD 8 BD 9
WASCO0177 WASCO0178 WASCO0179 WASCO0180 WASCO0181 WASCO0183 WASCO0184 WASCO0185 WASCO0186 WASCO0187 WASCO0188 WASCO0189 WASCO0190 WASCO0191 WASCO0192 WASCO0193 WASCO0194 WASCO0195 WASCO0196 WASCO0197 WASCO0198 WASCO0199 WASCO0200 WASCO0201 WASCO0202 WASCO0203 WASCO0204 WASCO0205 WASCO0206 WASCO0207 WASCO0208 WASCO0209
1.76 5.13 1.71 1.45 1.54 1.80 1.72 1.82 1.83 1.71 1.78 1.69 1.93 1.80 0.00 0.00 1.82 1.62 1.65 1.86 1.70 1.80 1.73 1.77 1.80 1.84 1.84 1.84 1.87 1.47 1.80 1.38
XIAO0895 XIAO0896 XIAO0897 XIAO0898 XIAO0899 XIAO0900 XIAO0901 XIAO0902 XIAO0903 XIAO0904 XIAO0905 XIAO0906 XIAO0907 XIAO0908 XIAO0909 XIAO0910 XIAO0911 XIAO0912 XIAO0913 XIAO0914 XIAO0915 XIAO0916 XIAO0917 XIAO0918 XIAO0919 XIAO0920 XIAO0921 XIAO0922 XIAO0923 XIAO0924 XIAO0925 XIAO0926
1.89 1.94 1.91 1.45 1.60 1.87 1.75 2.11 1.96 2.08 1.97 1.69 2.04 2.01 2.29 1.52 2.00 1.89 1.74 1.81 1.73 1.93 1.66 2.04 2.21 2.12 2.12 2.00 1.32 1.77 1.32 1.97
164
BD 10 BD 11 BD 12 BD 13 BD 14 BD 15
AII.39 FR3 sparking tests energy BD Test number lf number BD 1 wasc0016 BD 2 BD 3 BD 4 BD 5 wasc0017 BD 6 wasc0018 BD 7 BD 8 wasc0019 1 BD 9 wasc0020 BD 10 wasc0021 BD 11 BD 12 BD 13 BD 14 BD 15 wasc0022 BD 16 wasc0023 BD 17 wasc0024 BD 18 wasc0025 BD 19 wasc0026 2 BD 20 wasc0027 BD 21 wasc0028 BD 22 wasc0029
Energy(J) hf number 1.78 XIAO0742 XIAO0743 XIAO0744 1.63 XIAO0745 1.47 XIAO0746 1.74 XIAO0747 1.67 XIAO0748 1.48 XIAO0749
BD 23 BD 24 BD 25 BD 26 BD 27 BD 28 BD 29 BD 30 BD 1 BD 2 BD 3 BD 4 BD 5 BD 6 BD 7 BD 8 BD 9 BD 10 BD 11 BD 12 BD 13 BD 14 BD 15 BD 1 BD 2 BD 3 BD 4 BD 5 BD 6 BD 7 BD 8 BD 9
wasc0030 wasc0031 wasc0032 wasc0033 wasc0034 wasc0035 wasc0036 wasc0037 wasc0038 wasc0039 wasc0040 wasc0041 wasc0042 wasc0043 wasc0044 wasc0045 wasc0046 wasc0047 wasc0048 wasc0049 wasc0050 wasc0051 wasc0052 wasc0054 wasc0055 wasc0057 wasc0058 wasc0059 wasc0061 wasc0062 wasc0063 wasc0064
1.61 1.77 1.59 1.63 1.69 1.60 1.69 1.43 1.56 1.57 1.45 1.67 1.55 1.50 1.44 1.60 1.56 1.36 1.54 1.59 1.42 1.65 1.57 1.62 1.46 1.54 1.62 1.49 1.46 1.76 1.58 1.66
XIAO0758 XIAO0759 XIAO0760 XIAO0761 XIAO0762 XIAO0763 XIAO0764 XIAO0765 xaio0766 xaio0767 xaio0768 xaio0769 xaio0770 xaio0771 xaio0772 xaio0773 xaio0774 xaio0775 xaio0776 xaio0777 xaio0778 xaio0779 xaio0780 XIAO0781 XIAO0782 XIAO0783 XIAO0784 XIAO0785 XIAO0786 XIAO0787 XIAO0788 XIAO0789
1.00 1.18
1.05 1.13
166
BD 10 BD 11 BD 12 BD 13 BD 14 BD 15 BD 1 BD 2 BD 3 BD 4 BD 5 BD 6 BD 7 BD 8 BD 9 BD 10 BD 11 BD 12 BD 13 BD 14 BD 15 BD 1 BD 2 BD 3 BD 4 BD 5 BD 6 BD 7 BD 8 BD 9 BD 10 BD 11
wasc0065 wasc0066 wasc0067 wasc0068 wasc0069 wasc0070 wasc0101 wasc0102 wasc0103 wasc0104 wasc0105 wasc0106 wasc0107 wasc0108 wasc0109 wasc0110 wasc0111 wasc0112 wasc0113 wasc0114 wasc0115 wasc0129 wasc0130 wasc0131 wasc0132 wasc0133 wasc0134 wasc0135 wasc0136 wasc0137 wasc0138 wasc0139
1.75 1.69 1.63 1.70 1.72 1.72 1.47 1.57 1.64 1.79 1.68 1.70 1.51 1.58 1.60 1.57 1.60 1.72 1.83 1.82 1.40 1.38 1.45 1.41 1.38 1.34 1.35 1.22 1.40 1.51 1.46
XIAO0790 XIAO0791 XIAO0792 XIAO0793 XIAO0794 XIAO0795 XIAO0822 XIAO0823 XIAO0824 XIAO0825 XIAO0826 XIAO0827 XIAO0828 XIAO0829 XIAO0830 XIAO0831 XIAO0832 XIAO0833 XIAO0834 XIAO0835 XIAO0836 XIAO0851 XIAO0852 XIAO0853 XIAO0854 XIAO0855 XIAO0856 XIAO0857 XIAO0858 XIAO0859 XIAO0860 XIAO0861
1.07 1.21 1.23 1.22 1.16 1.14 1.21 1.24 1.12 1.21 1.13 1.29 1.08 1.24 1.09 1.25 1.26 1.27 1.29 1.51 1.34 0.81 0.99 0.69 1.01 0.62 0.58 0.63 0.91 1.08 1.04 1.02 167
BD 12 wasc0140 BD 13 wasc0141 BD 14 wasc0142 BD 15 wasc0143 AII.40 Gemini X PD test -1 energy 1500pC Time PD Attitude PD number Power(mW) PD current Energy Energy below 1000 Energy from 1000 to 2000 Energy from 2000 to 3000 Energy from 3000 to 4000 Energy from 4000 to 5000 Energy from 5000 to 6000 AII.41 Gemini X PD test -2 energy 2000pc Time PD Attitude PD number Power(mW) PD current Energy 168 58kV
50kV 93691449174925902890369min 969min 1749min 2349min 2890min 3190min 1407 1486.9 1466.1 1528.49 1438.37 1466.1 7970 14044 6113 9778 4477 4350 0.032752 0.02018 0.017539 0.014433 0.013045 0.01302 0.000001 0 0 0 0 0 0.403727 0.727004 0.315035 0.511059 0.23461 0.234253 0.348365 0.564099 0.244025 0.384345 0.180944 0.178995 0.055363 0.162905 0.071009 0.126714 0.053666 0.055258
1241853372-62min 63-123min 184min 305min 1358min 1860.4 2208.01 2149.26 2286.34 2139.47 1421 3978 5686 10976 48040 0.02377 0.083638 0.123514 0.12023 0.059723 0 0.000001 0.000002 0.000002 0.000001 0.07564 0.300275 0.444146 0.86466 3.655812
Energy below 1000 Energy from 1000 to 2000 Energy from 2000 to 3000 Energy from 3000 to 4000 Energy from 4000 to 5000 Energy from 5000 to 6000 AII.42 Gemini X PD test -3 energy
3000pC Time PD Attitude PD number Power(mW) PD current Energy Energy below 1000 Energy from 1000 to 2000 Energy from 2000 to 3000 Energy from 3000 to 4000 Energy from 4000 to 5000 Energy from 5000 to 6000
0.043686 0.031954
50kV 321032153218322132253285334540474287435753573215min 3218min 3221min 3224min 3285min 3345min 4045min 4287min 4357min 5357min 5362min 2531.13 2100.3 2256.96 2403.84 3074.56 2413.63 3099.04 2922.79 2462.59 3148 2007.28 206 80 149 164 2204 1919 17440 5816 1532 19800 89 0.06484 0.04101 0.07387 0.08375 0.05598 0.04760 0.03725 0.03565 0.03197 0.02917 0.02555 2 7 2 2 1 9 4 1 4 5 1 0.00000 0.00000 0.00000 0.00000 0.00000 0.00000 0.00000 0.00000 0.00000 1 1 1 1 1 1 1 1 1 0 0 0.01926 0.00697 0.01315 0.01468 0.20142 0.17073 1.56448 0.13419 1.74960 0.00751 7 6 1 3 4 9 9 0.51348 6 2 9 0.00089 0.00076 0.00080 0.00952 0.14508 0.04569 0.01599 0.20944 0.00053 8 0.00076 5 9 1 0.01995 7 6 6 1 4 0.01668 0.00564 0.01211 0.01313 0.18150 0.14588 1.36821 0.45193 0.11499 1.48906 0.00685 6 6 2 2 5 5 8 1 3 3 7 0.00168 0.00027 0.00074 0.01018 0.00490 0.01585 0.00320 0.05061 0.00012 3 0.00057 5 2 8 4 0.05097 3 7 6 9 0.00021 0.00048 0.00021 4 2
4000pc Time PD Attitude PD number Power(mW) PD current Energy Energy below 1000 Energy from 1000 to 2000 Energy from 2000 to 3000 Energy from 3000 to 4000 Energy from 4000 to 5000 Energy from 5000 to 6000 PD number below 1000 PD number from 1000 to 2000 PD number from 2000 to 3000 PD number from 3000 to 4000 PD number from 4000 to 5000 PD number from 5000 to 6000
58kV 941251561861-31min 32-62min 63-93min 124min 155min 186min 1146min 3545.68 3545.68 3545.68 3545.68 3545.68 3545.68 4440.49 2496 1935 2388 2910 2533 2758 61255 0.166666 0.137344 0.165138 0.165928 0.145456 0.158171 0.130842 0.000002 0.000002 0.000002 0.000002 0.000002 0.000002 0.000002 0.300003 0.246909 0.297593 0.298259 0.261372 0.283743 7.528894 0.024767 0.007095 0.031721 0.06056 0.065623 0.087698 0.931736 0.174608 0.129074 0.154227 0.146039 0.116079 0.113735 3.534853 0.099446 0.108266 0.109014 0.090555 0.077525 0.08092 3.014477 0.001181 0.002475 0.002631 0.001106 0.002145 0.00139 0.044091 0.003736 287 1413 787 9 122 1146 657 10 279 1241 849 19 855 1276 769 10 751 1075 690 17 877 1096 771 14 9678 27831 23387 333 26
170
PD current Energy(J) Energy below 1000 Energy from 1000 to 2000 1000pc-1 Time PD Attitude PD number Power(mW) PD current Energy(J) Energy below 1000 Energy from 1000 to 2000
0.000011 0.027267 0.027168 0.0001 34kV 191min 1308.03 500 0.248928 0.000006 0.014796 0.011737 0.00306
0.000015 0.038067 0.037525 0.000543 210min 1228.13 570 0.285772 0.000006 0.017003 0.013617 0.003387
0.000012 0.031893 0.030285 0.001608 261min 1255.92 438 0.229005 0.000005 0.01363 0.010587 0.003043
0.00000 9 0.02453 2 0.02163 0.00290 1 281min 1255.92 498 0.24823 1 0.00000 6 0.01480 4 0.01212 1 0.00268 3
0.00000 9 0.02339 1 0.02040 4 0.00298 7 296min 1297.61 441 0.22833 4 0.00000 5 0.01364 5 0.01035 8 0.00328 7
0.00000 8 0.02174 4 0.01911 6 0.00262 8 310min 1269.82 488 0.25201 6 0.00000 6 0.01507 6 0.01186 8 0.00320 8
0.00000 7 0.01986 6 0.01649 9 0.00336 8 341min 1276.77 448 0.23712 4 0.00000 5 0.01418 9 0.01097 5 0.00321 4
0.00000 8 0.02088 5 0.01813 0.00275 6 357min 1314.98 476 0.23345 5 0.00000 5 0.01373 6 0.01139 0.00234 7
0.00000 7 0.01931 4 0.01552 5 0.00378 9 372min 1262.87 485 0.24800 6 0.00000 6 0.01477 1 0.01177 8 0.00299 3
0.00000 6 0.01501 0.01261 6 0.00239 4 390min 1321.93 474 0.26017 1 0.00000 6 0.01450 2 0.01071 6 0.00378 6
171
Energy below 1000 Energy from 1000 to 2000 1000pc-2 Time PD Attitude PD number Power(mW) PD current Energy(J) Energy below 1000 Energy from 1000 to 2000
0.00838 0.00869 0.00861 0.01018 0.00858 0.00979 0.00904 0.00955 0.00789 3 4 9 3 4 3 7 7 8 0.00887 0.00009 0.00098 0.00119 0.00133 0.00121 0.00099 0.00077 0.00083 0.00091 4 9 8 1 8 5 0.0008 2 9 5 34kV 151min 166min 181min 226min 241min 301min 316min 331min 346min 361min 1155.17 1266.34 1224.65 1221.18 1280.24 1214.23 1231.6 1221.18 1210.76 1207.28 336 311 292 335 342 406 358 370 320 331 0.14869 0.13575 0.16023 0.16284 0.19350 0.18053 0.18401 0.15551 0.16411 0.14575 8 9 5 3 1 5 8 6 8 0.00000 0.00000 0.00000 0.00000 0.00000 0.00000 0.00000 0.00000 0.00000 0.00000 3 3 3 4 4 4 4 4 4 4 0.00873 0.00884 0.00806 0.00959 0.00972 0.01157 0.01083 0.00924 0.00978 8 8 7 2 5 1 9 0.01096 4 5 0.00828 0.00804 0.00818 0.00814 0.01015 0.00887 0.00953 0.00778 0.00810 8 6 0.00712 7 2 8 4 6 6 6 0.00080 0.00094 0.00140 0.00158 0.00141 0.00196 0.00142 0.00145 0.00167 0.00045 2 6 5 3 3 5 4 8 9
16min
2076.1 1 760 0.7045 29 0.0000 13
31min
2089.9 8 674 0.6288 6 0.0000 11
46min
2270.2 1 680 0.6144 38 0.0000 11
61min
2089.9 8 698 0.6392 45 0.0000 12
76min
2166.2 3 562 0.5227 78 0.0000 1
91min
2076.1 1 694 0.6175 14 0.0000 11
106mi n
2270.2 1 776 0.6894 08 0.0000 12
121mi n
2103.8 4 638 0.5721 35 0.0000 1
136mi n
1992.9 3 651 0.5664 72 0.0000 1
151mi n
2058.7 8 791 0.6830 62 0.0000 12
166mi n
2311.8 802 0.6927 68 0.0000 12
181mi n
2166.2 3 912 0.7589 6 0.0000 14
0.0475 13 0.0207 33
0.0417 34 0.0179 32
0.0381 24 0.0163 89
0.0362 26 0.0171 29
0.0382 92 0.0163 31
0.0308 86 0.0141 95
0.0374 08 0.0167 79
0.0415 14 0.0199 47
0.0340 95 0.0155 79
0.0338 03 0.0167 19
0.0408 86 0.0208 5
0.0415 3 0.0212 02
0.0458 76 0.0246 59
172
0.0264 1 0.0003 7
0.0237 73 0.0000 28
0.0215 28 0.0002 06
0.0189 2 0.0001 77
0.0218 33 0.0001 27
0.0165 07 0.0001 84
0.0205 4 0.0000 9
0.0214 61 0.0001 05
0.0183 14 0.0002 02
0.0170 83
0.0198 6 0.0001 76
0.0202 68 0.0000 6
0.0209 8 0.0002 37
AII.48 FR3 PD test -5 energy 3000pc-1 Time PD Attitude PD number Power(mW) PD current Energy(J) Energy below 1000 Energy from 1000 to 2000
Energy from 2000 to 3000 Energy from 3000 to 4000 AII.49 FR3 PD test -6 energy
3000pc-2 Time PD Attitude PD number Power(mW) PD current Energy(J) Energy below 1000 Energy from 1000 to 2000 Energy from 2000 to 3000 Energy from 3000 to 4000
0.03686 0.041724 0.039785 0.03551 0.03552 0.000058 0.00074 0.000773 0.001481 0.003442
57kV 1min 3500.5 3284 3.133418 0.000044 0.186918 0.147386 0.020772 0.018033 0.000727
3min 3451.54 2978 2.944347 0.000042 0.180206 0.138484 0.020565 0.020801 0.000357
16min 3412.37 3495 3.725295 0.000053 0.223178 0.167518 0.031543 0.022418 0.001698
31min 3387.89 3289 3.377506 0.000048 0.20066 0.153773 0.026743 0.018876 0.001268
46min 76min 91min 105min 120min 3559.25 3441.75 3368.31 3451.54 3451.54 3320 3194 3009 3119 3135 3.534698 3.492992 3.134563 3.344037 3.448978 0.00005 0.00005 0.000045 0.000047 0.000049 0.212876 0.210771 0.190181 0.199089 0.206235 0.157311 0.151758 0.140483 0.148291 0.150484 0.031572 0.034984 0.029602 0.03264 0.035384 0.022068 0.021818 0.018991 0.016888 0.018123 0.001924 0.002211 0.001106 0.00127 0.002244
174
AII.52 Sparking test laboratory comparison Oil type FR3 TM8 sample Laboratory sample Laboratory / TM8 Gas-in-oil (ppm) C2H6 H2 3.0 80.4 3 59 99.84% 73.43%
CO 53.5 34 63.60%
CO2
C2H4
C2H2
C2H6
H2
O2
CH4
CO
175
TM8 sample Laboratory sample 1 Laboratory sample2 Laboratory average Laboratory / TM8
12 17 13 15 125.35%
41 44 27 36 86.98%
12 10 7 9 71.07%
46 58 57 58 124.14%
23 24 19 22 91.55%
9 10 9 10 105.69%
AII.54 Thermal test laboratory comparison Oil type Mineral TM8 sample Laboratory sample 1 Laboratory sample2 Laboratory average Laboratory / TM8 CO2 1163.82 1058 933 995.5 85.54% C 2 H4 6149.45 6798 5889 6343.5 103.16% C2H2 58.56 67 55 61 104.17% Gas-in-oil(ppm) C2H6 1060.74 961 836 898.5 84.70% H2 945.86 928 924 926 97.90% O2 14751.58 29506 20823 25164.5 170.59% CH4 2956.23 4033 3614 3823.5 129.34% CO 186.84 99 77 88 47.10%
176