MainswitchFlushmounting Partno.

Front IP65

Articleno. Deliveryprogramme
Product range Basic function

P1-25/EA/SVB 041097

Switch-disconnectors Main switches Maintenance switches Manual override switches P1 Flush mounting

Part group reference Design

Protection type Emergency stop Standards Locking facility Contact sequence

Front IP65 As an emergency switching off/emergency stop device With red rotary handle and yellow locking ring According to IEC/EN 60204-1, VDE 0113 Part 1 Lockable in the 0 (Off) position without auxiliary contacts

Front plate no.

Main conducting paths No. of poles Auxiliary contacts Max. motor rating AC-23A 400/415 V 50-60 Hz Rated uninterrupted current

P Iu

M N/O B kW A

3 0 0 13 25

Approvals

Product Standards UL File No. UL CCN CSA File No. CSA Class No. NA Certification Suitable for Degree of Protection

UL 508; CSA-C22.2 No. 14-05; IEC/EN 60947-3; CE marking E36332 NLRV 12528 3211-05 UL listed, CSA certified Branch circuits, suitable as motor disconnect IEC: IP65; UL/CSA Type 3R, 12

General
08/10/2012 HPL-ED2012 V1.1 EN 1/5

Standards

IEC/EN 60 947, VDE 0660, IEC/EN 60 204, CSA,UL Switch-disconnectors to IEC/EN 60 947-3 NEMA3R, NEMA12
6

Lifespan, mechanical Maximum operating frequency Climatic proofing Ambient temperature Open Enclosed Mounting position Mechanical shock resistance to IEC 60068-2-27

Operations Halfsinusoidal shock 20 ms Ue Uimp Iu Iu Iu

10

0.3

Operations/ 50 h C C C g Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclical, to IEC 60068-2-30 - 25 - 50 - 25 - 40 As required > 15

Contacts

Rated operational voltage Rated impulse withstand voltage Overvoltage category/pollution degree Rated uninterrupted current open Enclosed Load rating with intermittent operation, class 12 AB 25 % DF AB 40 % DF AB 60 % DF Short-circuit rating Fuse

V AC V AC A A A x Ie x Ie x Ie A gG/ gL Arms W mm mm Nm x Us A A A A A A A kW kW kW kW kW kW kW kW
2 2

690 6000 III/3 25 25 2 1.6 1.3 25

Rated short-time withstand current (1 s current) Switching angles Current heat loss per contact at Ie Solid or stranded

Icw Ie P P P P P P P P

640 90 1.1 1 x (1.5 - 6) 2 x (1.5 - 6) 1 x (1 - 4) 2 x (1 - 4) M4 1.6 240 190 150 170 150 25 5.5 7.5 7.5 7.5 7 13
2/5

Terminalcapacities

Flexible with ferrule to DIN 46228 Terminal screw

Switchingcapacity
AC Rated making capacity cos = 0.35 Rated breaking capacity, motor load switch cos = 0.35 230 V 400 V 500 V 690 V Rated operational current 440 V load-break switch AC-21A Rating, AC-3 motor load switch 220 V 230 V 380 V 400 V 500 V 660 V 690 V AC-23A Motor load switches (main switches maintenance switches) 230 V 400 V
08/10/2012

Tightening torque

HPL-ED2012 V1.1 EN

500 V 690 V DC DC-1, Load-break switches L/R = 1 ms Rated operational current Voltage per contact pair in series DC-23A, motor load switch L/R = 15 ms 24 V Rated operational current Contacts 48 V Rated operational current Contacts 60 V Rated operational current Contacts 120 V Rated operational current Contacts

P P Ie Ie Ie Ie Ie

kW kW x Us A V A A A A

11 11 25 60 25 25 25 12

Quantity 1

Quantity 2

Quantity 3

Auxiliarycontacts Notes
Standards

Quantity 3 According to IEC/EN 60204-1, VDE 0113 Part 1

NotesMain switch characteristics to IEC/EN 60204; positive opening of contacts, operator element positively located on shaft The rated uninterrupted current Iu is stated at max. connected cross-section. For terminal capacity solid, stranded and flexible: Max. 2 cross-section sizes difference admissible when using 2 conductors.

TechnicaldataETIM4.0

Number of auxiliary contacts as normally open contact Number of auxiliary contacts as normally closed contact Rated permanent current Iu Number of poles Conditioned rated short-circuit current Iq Degree of protection (IP), front side Number of auxiliary contacts as change-over contact Interlockable Motor drive integrated Connection type main current circuit Version as emergency stop installation Type of control element Version as main switch Version as switch disconnector compact Version as safety switch Version as maintenance-/service switch Rated operation power at AC-23, 400V Rated operation power AC-3, 400 V Suitable for ground mounting Suitable for front mounting Suitable for front mounting center Suitable for distribution board installation Suitable for intermediate mounting Max. rated operation voltage Ue AC Motor drive optional Voltage release optional Device construction

A kA kWh kWh V

0 0 25 3 0 IP55 0 YES No Screw connection YES YES YES No YES 13 7.5 No No No No No 690 No No Built-in device fixed built-in technique

08/10/2012

HPL-ED2012 V1.1 EN

3/5

Characteristics

For utilisation category AC-4 (extreme load: 100 % inching, reversing or plugging) The blocked rotor current of the motor should not exceed the rated current of the switch for AC-21A to ensure a reasonable device lifespan.

Dimensions

Label mount not included as standard

08/10/2012

HPL-ED2012 V1.1 EN

4/5

3 padlocks

Additionalproductinformation(links)
IL03802003Z (AWA1150-1890) SwitchDisconnectors for flush mounting

IL03802003Z(AWA1150-1890)Switch-Disconnectorsforflushmounting ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL03802003Z2011_06.pdf

http://ecat.moeller.net/flip-cat/?edition=HPLEN&startpage=4.87

08/10/2012

Eaton Industries GmbH http://www.moeller.net/en 05/2012 by Eaton Industries GmbH HPL-ED2012 V1.1 EN (UX111)

5/5