BG0428 Rev. A3
Every effort has been made to ensure that the material herein is complete and accurate. However, the manufacturer is not responsible for any mistakes in printing or faulty instructions contained in this book. Notification of any errors or misprints will be received with appreciation. For further information regarding a particular installation, operation or maintenance of equipment, contact the manufacturer or your local representative or distributor.
REVISION HISTORY
A1 A2 Nov 2007 Mar 2008 Release F/W versions 11.1.6 or higher. Added functions 7 Immediate Freeze and 8 Immediate FreezeNo Acknowledgement. Added DNP 16-bit and 32-bit frozen binary counter and analog input objects. Added DNP Object 50 Time and Date to the Class 0 point list. F/W versions 11.3.3 or higher. Added kVAh import/export and 4-quadrant kvarh registers.
A3
Jun 2010
Table of Contents
1 GENERAL ..........................................................................................................5 2 DNP 3.0 PROTOCOL IMPLEMENTATION ........................................................6
2.1 2.2
2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6 2.2.7
2.3
3.5
3.6
3.7
3.8
DEVICE SETUP.......................................................................................................................27
Basic Setup.......................................................................................................................................... 27 Communication Ports Setup ................................................................................................................ 27 Device Options Setup .......................................................................................................................... 28
3.9
APPENDIX A DNP APPLICATION MESSAGES ................................................35 APPENDIX B DNP DEVICE PROFILE ................................................................37
1 General
This document specifies a subset of the DNP3 communications protocol used to transfer data between a master computer station and the PM130. The document provides the complete information necessary to develop third-party communications software capable of communication with the Series PM130 instruments. Additional information concerning operating the device, configuring the communication parameters, and communication connections may be found in the "PM130 PLUS Installation and Operation Manual". Refer to Configuring DNP in the PM130 PLUS Installation and Operation Manual for information on how to configure Class 0 responses via the supplemental PAS software. The document is applicable to the PM130P, PM130E and PM130EH devices.
IMPORTANT
In 3-wire connection schemes, the unbalanced current and phase readings for power factor, active power, and reactive power will be zeros, because they have no meaning. Only the total three-phase power values will be shown. Most of the advanced features are configured using multiple setup parameters that can be accessed in a number of contiguous registers. When writing the setup registers, it is recommended to write all the registers at once using a single request, or to clear (zero) the setup before writing into separate registers.
Designations used in the guide: E - available in the PM130E and PM130EH EH - available in the PM130EH
The Direct-Operate, SBO/Operate or Direct-Operate-No-Acknowledge requests for reset/clear registers and setpoint changing are immediately confirmed.
The freeze command copies the corresponding Analog Input points to a freeze buffer with the time of freeze. The device provides a local freeze buffer for every communication port and every TCP/IP connection socket, so the Frozen Analog Input points must be requested via the same connection through which a freeze command was sent; otherwise the device may not guarantee that the frozen values are correlated with the corresponding freeze command. The objects that were frozen can be requested by asking for 16-bit or 32-bit Frozen Analog Input objects with variations 0 through 6, with the time of freeze or without time. 16-bit Frozen Analog Input objects may be scaled to avoid over-range errors if this option is enabled in the device (see Section 2.2.6, Scaling 16-bit Analog Inputs). The response contains the last frozen values of the corresponding Analog Input points if the freeze command was executed before, or immediate values of the corresponding Analog Input points in the event the freeze command has never been executed. Requesting Frozen Analog Input points with time of freeze without the freeze command can be used to get immediate values of the Analog Input points with timestamps. Frozen Analog Inputs requested with variation 0 are responded with the variation specified for the requested points in the Class 0 point list.
EXAMPLE If you have read a value of 201 for point AI:3 that shows the I1 current (see Section 3.1) and the CT primary current is 200A (the high current scale is 2200 = 400A), then the current reading in engineering units is as follows: (201 - 0) (400 - 0)/(32767 - 0) + 0 = 2.45A
10
Description I1 I2 I3 I1 I2 I3 Current Current Current Current Current Current THD THD THD TDD TDD TDD 0-9999 0-9999 0-9999 0-1000 0-1000 0-1000
Options/Range2
R/W R R R R R R
Notes 3-sec 3-sec 3-sec 3-sec 3-sec 3-sec value value value value value value
Energy and power demand readings and total harmonics are only available in the PM130EH meters.
1
Voltage and voltage harmonics readings: when the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. All analog input points except of harmonics are 1-second average values. For volts, amps and power scales and units, refer to Section 4 Data Scales and Units. For analog input scaling formulas and examples, see Section 2.2.6, Scaling Analog Input Objects. Any of the analog input points listed in the table can be frozen using functions 7 or 8 with object 30 and variation 0. See Section 2.2.5 for details.
11
12
13
Object : Var.1 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var 21:var NOTE
1
Object : Point FBC:38659 FBC:38660 FBC:38661 FBC:38662 FBC:38663 FBC:38664 FBC:38665 FBC:38666 FBC:38667 FBC:38668 FBC:38669 FBC:38670 FBC:38671 FBC:38672 FBC:38673 FBC:38674 FBC:38675 FBC:38676 FBC:38677 FBC:38912 FBC:38913 FBC:38914 FBC:38915 FBC:38916 FBC:38917 FBC:38918 FBC:38919 FBC:38920
Description Not used kvarh import kvarh export Not used Not used kVAh total Not used Not used kVAh import kVAh export Not used Not used Not used Not used Not used kvarh Q1 kvarh Q2 kvarh Q3 kvarh Q4 Phase Energies - Extended Set E kWh import L1 kWh import L2 kWh import L3 kvarh import L1 kvarh import L2 kvarh import L3 kVAh total L1 kVAh total L2 kVAh total L3
0-999,999,999
kVAh
0-999,999,999 0-999,999,999
kVAh kVAh
0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999
kvarh kvarh kvarh kvarh kWh kWh kWh kvarh kvarh kvarh kVAh kVAh kVAh
Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R R
Notes
For object variation, see DNP Options setup (see Section 3.9).
14
Notes
2-cycle value 2-cycle value 1 2-cycle value 2-cycle value 2-cycle value 2-cycle value 2-cycle value
1 1
15
Object : Var. 3 30:4 30:4 30:4 30:4 30:4 30:3 30:3 30:3 30:3 30:3 30:3 30:4 30:4 30:4 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:4 30:4 30:4 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3
Object : Point AI:35865 AI:35866 AI:35867 AI:35868 AI:35869 AI:35870 AI:35871 AI:35872 AI:36608 AI:36609 AI:36610 AI:36611 AI:36612 AI:36613 AI:36614 AI:36615 AI:36616 AI:36617 AI:36618 AI:36619 AI:36620 AI:36864 AI:36865 AI:36866 AI:36867 AI:36868 AI:37120 AI:37121 AI:37122 AI:37123 AI:37124 AI:37125 AI:37126 AI:37127 AI:37128 AI:37129 AI:37130 AI:37131 AI:37132 AI:37133
Description I2 K-Factor I3 K-Factor I1 Current TDD I2 Current TDD I3 Current TDD V12 Voltage V23 Voltage V31 Voltage 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Total PF lag Total PF lead Total kW import Total kW export Total kvar import Total kvar export 3-phase average L-N/L-L voltage 3-phase average L-L voltage 3-phase average current 1-Cycle Auxiliary Values Not used In (neutral) Current Frequency Voltage unbalance Current unbalance 1-Second Phase Values V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage I1 Current I2 Current I3 Current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2
Options/Range2 10-9999 10-9999 0-1000 0-1000 0-1000 0-Vmax 0-Vmax 0-Vmax -Pmax-Pmax -Pmax-Pmax 0-Pmax -1000-1000 0-1000 0-1000 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Vmax 0-Vmax 0-Imax
Type UINT16 UINT16 UINT16 UINT16 UINT16 UINT32 UINT32 UINT32 INT32 INT32 UINT32 INT16 UINT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT16 UINT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 INT32 INT32 INT32 INT32 INT32 UINT32 UINT32
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
3 3 3 3 3 3 1, 3 3 3
0-Imax 0-Fmax 0-3000 0-3000 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax
1 1 1
16
Object : Var. 3 30:3 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:3 30:3 30:3 30:3 30:3 30:3 30:4 30:4 30:4 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:4 30:4 30:4
Object : Point AI:37134 AI:37135 AI:37136 AI:37137 AI:37138 AI:37139 AI:37140 AI:37141 AI:37142 AI:37143 AI:37144 AI:37145 AI:37146 AI:37147 AI:37148 AI:37149 AI:37150 AI:37151 AI:37152 AI:37888 AI:37889 AI:37890 AI:37891 AI:37892 AI:37893 AI:37894 AI:37895 AI:37896 AI:37897 AI:37898 AI:37899 AI:37900 AI:38144 AI:38145 AI:38146 AI:38147 AI:38148
30:3 30:3
AI:38400 AI:38401
Description kVA L3 Power factor L1 Power factor L2 Power factor L3 V1/V12 Voltage THD V2/V23 Voltage THD V3/V31 Voltage THD I1 Current THD I2 Current THD I3 Current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 Current TDD I2 Current TDD I3 Current TDD V12 Voltage V23 Voltage V31 Voltage 1-Second Total Values Total kW Total kvar Total kVA Total PF Total PF lag Total PF lead Total kW import Total kW export Total kvar import Total kvar export 3-phase average L-N/L-L voltage 3-phase average L-L voltage 3-phase average current 1-Second Auxiliary Values Not used In (neutral) Current Frequency Voltage unbalance Current unbalance Present Volt, Ampere and Power Demands V1/V12 Volt demand V2/V23 Volt demand
Options/Range2 0-Pmax -1000-1000 -1000-1000 -1000-1000 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 10-9999 10-9999 10-9999 0-1000 0-1000 0-1000 0-Vmax 0-Vmax 0-Vmax -Pmax-Pmax -Pmax-Pmax 0-Pmax -1000-1000 0-1000 0-1000 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Vmax 0-Vmax 0-Imax
Units2 U3 0.001 0.001 0.001 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1 0.1 0.1 0.1% 0.1% 0.1% U1 U1 U1 U3 U3 U3 0.001 0.001 0.001 U3 U3 U3 U3 U1 U1 U2
Type UINT32 INT16 INT16 INT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT32 UINT32 UINT32 INT32 INT32 UINT32 INT16 UINT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT16 UINT16 UINT16
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
Notes
3-sec value 3-sec value 1 3-sec value 3-sec value 3-sec value 3-sec value 3-sec value 3-sec value 3-sec value 3-sec value 3-sec value 3-sec value
1 1
3 3 3 3 3 3 1, 3 3 3
0-Vmax 0-Vmax
U1 U1
UINT32 UINT32
R R
1 1
17
Object : Var. 3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:4 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5
Object : Point AI:38402 AI:38403 AI:38404 AI:38405 AI:38406 AI:38407 AI:38408 AI:38409 AI:38410 AI:38411 AI:38412 AI:38413 AI:38414 AI:38415 AI:38416 AI:38417 AI:38418 AI:38419 AI:38420 AI:38421 AI:38422 AI:38423 AI:38424 AI:38425 AI:38426 AI:38427 AI:38428 AI:38429 AI:38430 AI:38431 AI:38432 AI:38433 AI:38434 BC:38656 BC:38657 BC:38658 BC:38659 BC:38660 BC:38661 BC:38662 BC:38663
Description V3/V31 Volt demand I1 Ampere demand I2 Ampere demand I3 Ampere demand kW import block demand kvar import block demand kVA block demand kW import sliding window demand kvar import sliding window demand kVA sliding window demand Not used Not used Not used kW import accumulated demand kvar import accumulated demand kVA accumulated demand kW import predicted sliding window demand kvar import predicted sliding window demand kVA predicted sliding window demand PF (import) at Max. kVA sliding window demand kW export block demand kvar export block demand kW export sliding window demand kvar export sliding window demand kW export accumulated demand kvar export accumulated demand kW export predicted sliding window demand kvar export predicted sliding window demand Not used Not used Not used Not used In Ampere demand Total Energies E kWh import kWh export Not used Not used kvarh import kvarh export Not used Not used
Options/Range2 0-Vmax 0-Imax 0-Imax 0-Imax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax
Units2 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3
0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-1000 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax
U3 U3 U3 U3 U3 U3 0.001 U3 U3 U3 U3 U3 U3 U3 U3
Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
Notes
1
U2 kWh kWh
0-999,999,999 0-999,999,999
kvarh kvarh
18
Object : Var. 3 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 20:5 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4
Object : Point BC:38664 BC:38665 BC:38666 BC:38667 BC:38668 BC:38669 BC:38670 BC:38671 BC:38672 BC:38673 BC:38674 BC:38675 BC:38676 BC:38677 BC:38912 BC:38913 BC:38914 BC:38915 BC:38916 BC:38917 BC:38918 BC:38919 BC:38920 AI:39168 AI:39169 AI:39107 AI:39424 AI:39425 AI:39463 AI:39680 AI:39681 AI:39719 AI:39936 AI:39937
Description kVAh total Not used Not used kVAh import kVAh export Not used Not used Not used Not used Not used kvarh Q1 kvarh Q2 kvarh Q3 kvarh Q4 Phase Energies E kWh import L1 kWh import L2 kWh import L3 kvarh import L1 kvarh import L2 kvarh import L3 kVAh total L1 kVAh total L2 kVAh total L3 V1/V12 Harmonic Distortion EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion V2/V23 Harmonic Distortion EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion V3/V31 Harmonic Distortion EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion I1 Harmonic Distortion EH H01 Harmonic distortion H02 Harmonic distortion ...
Options/Range2 0-999,999,999
Units2 kVAh
0-999,999,999 0-999,999,999
kVAh kVAh
0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00
kvarh kvarh kvarh kvarh kWh kWh kWh kvarh kvarh kvarh kVAh kVAh kVAh 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01%
Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16
R/W R R R R R R R R R R R R R R R R R R R R R R R
Notes
R R R
1
R R R
1
R R R R R
19
Object : Var. 3 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:4 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:4 30:4 30:4 30:3 30:3 30:3 30:4 30:3 30:3 30:3 30:3 30:3 30:3
Object : Point AI:39975 AI:40192 AI:40193 AI:40231 AI:40448 AI:40449 AI:40487 AI:43264 AI:43265 AI:43266 AI:43267 AI:43268 AI:43269 AI:43270 AI:43271 AI:43272 AI:43273 AI:43274 AI:43275 AI:43276 AI:43277 AI:43278 AI:43279 AI:43280 AI:43281 AI:43520 AI:43521 AI:43522 AI:43523 AI:44032 AI:44033 AI:44034 AI:44035 AI:44036 AI:44037
Description H40 Harmonic distortion I2 Harmonic Distortion EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion I3 Harmonic Distortion EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion Fundamental (H01) Phase Values EH V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage I1 Current I2 Current I3 Current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 Fundamental (H01) Total Values EH Total fundamental kW Total fundamental kvar Total fundamental kVA Total fundamental PF Minimum 1-Cycle Phase Values V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage I1 Current I2 Current I3 Current
Options/Range2 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax 0-Pmax -1000-1000 -1000-1000 -1000-1000 -Pmax-Pmax -Pmax-Pmax 0-Pmax -1000-1000 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax
Units2 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3 U3 U3 U3 0.001 0.001 0.001 U3 U3 U3 0.001 U1 U1 U1 U2 U2 U2
Type UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 INT32 INT32 INT32 INT32 INT32 UINT32 UINT32 UINT32 INT16 INT16 INT16 INT32 INT32 UINT32 INT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R/W R R R R R R R
Notes
2-cycle values R R R R R R R R R R R R R R R R R R R R R R R R R R R R
1 1 1 1 1 1
2-cycle values
20
Object : Var. 3 30:3 30:3 30:3 30:4 30:3 30:3 30:4 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:4 30:3 30:3 30:4 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3 30:3
Object : Point AI:44288 AI:44289 AI:44290 AI:44291 AI:44544 AI:44545 AI:44546 AI:46080 AI:46081 AI:46082 AI:46083 AI:46084 AI:46085 AI:46336 AI:46337 AI:46338 AI:46339 AI:46592 AI:46593 AI:46594 AI:46848 AI:46849 AI:46850 AI:46851 AI:46852 AI:46853 AI:46854 AI:46855 AI:46856 AI:46857 AI:46858 AI:46859 AI:46860 AI:46861 AI:46862 AI:46863 AI:46864
Description Minimum 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Minimum 1-Cycle Auxiliary Values Not used In Current Frequency Maximum 1-Cycle Phase Values V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage I1 Current I2 Current I3 Current Maximum 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Maximum 1-Cycle Auxiliary Values Not used In Current Frequency Maximum Demands V1/V12 Maximum volt demand V2/V23 Maximum volt demand V3/V31 Maximum volt demand I1 Maximum ampere demand I2 Maximum ampere demand I3 Maximum ampere demand Not used Not used Not used Maximum kW import sliding window demand Maximum kvar import sliding window demand Maximum kVA sliding window demand Not used Not used Not used Maximum kW export sliding window demand Maximum kvar export sliding window demand
Units2 U3 U3 U3 0.001
Type INT32 INT32 UINT32 UINT16 UINT32 UINT32 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 INT32 UINT32 UINT16 UINT32 UINT32 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
Notes
Absolute value
0-Imax 0-Fmax 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-1000
U2 0.01Hz U1 U1 U1 U2 U2 U2 U3 U3 U3 0.001
1 1 1
Absolute value
U2 0.01Hz U1 U1 U1 U2 U2 U2
1 1 1
U3 U3 U3
0-Pmax 0-Pmax
U3 U3
21
Description Not used Not used Not used Not used In Maximum ampere demand
Options/Range2
Units2
0-Imax
U2
R/W R R R R R
Notes
Energy and power demand readings are only available in the PM130E and PM130EH meters. Total harmonics readings are only available in the PM130EH meters.
1 2
Voltage and voltage harmonics readings: when the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. For volts, amps, power and frequency scales and units: refer to Section 4 Data Scales and Units. For analog input scaling formulas and examples, see Section 2.2.6, Scaling Analog Input Objects. Any of the analog input points listed in the table can be frozen using functions 7 or 8 with object 30 and variation 0. See Section 2.2.5 for details.
22
1100-1199 1-99
Two higher decimal digits = major version number, two lower decimal digits = minor version number
30:4 AI:271 30:3 AI:272-AI:274 Factory Device Settings 30:4 AI:275 30:4 AI:276 30:3 AI:277-AI:278 30:4 AI:279 30:4 AI:280 30:4 AI:281-AI:288 Device Identification (alias) 30:4 AI:1023 30:4 AI:1024 AI:1025 30:3 AI:1026 30:3 Port Identification 30:4 AI:1027
1-99
1-99 1100-1199 F2
Two higher decimal digits = major version number, two lower decimal digits = minor version number
0=COM1, 1=COM2
UINT16
23
0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON
Returns zero PULSE ON 1 Returns zero PULSE ON 1 Returns zero PULSE ON 1 Returns zero PULSE ON 1 Returns zero PULSE ON 1 Returns zero PULSE ON 1 Returns zero PULSE ON 1 Returns zero PULSE ON 1 Returns zero PULSE ON 1 Returns zero PULSE ON 1 Returns zero PULSE ON 1 Returns zero PULSE ON 1
2 2 2 2 2 2
0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON
24
Object : Var. Object : Point 12:1(write) CROB:69 10:2(read) BI :70 12:1(write) CROB:70 10:2(read) B0 :71 12:1(write) CROB:71 10:2(read) B0:72 12:1(write) CROB:72 10:2(read) B0:73 12:1(write) CROB:73 10:2(read) B0:74 12:1(write) CROB:74 10:2(read) B0:75 12:1(write) CROB:75 10:2(read) B0:76 12:1(write) CROB:76 10:2(read) B0:77 12:1(write) CROB:77 10:2(read) B0:78 12:1(write) CROB:78 10:2(read) B0:79 12:1(write) CROB:79 Remote Relay Control 10:2(read) BO:80 12:1(write) CROB:80 10:2(read) BO:81 12:1(write) CROB:81 NOTES:
1
Description Reserved Software watchdog reset Loss of power (power down) Device reset (cold restart) Configuration reset
3 3 3
Options/Range 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON 0/1 = state OFF/ON
Units
Type
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
Notes
2 2 2 2 2 2 2 2 2 2
RTC fault (time synchronization required) Reserved Reserved Reserved EEPROM fault
R/W R/W
4 4
The following restriction should be noted when using object 12 to control the listed points. The Count byte is ignored. The Control Code byte is checked: - Pulse On (1) is valid for all points; other codes are invalid and will be rejected. The On Time and Off Time fields are ignored. The status byte in the response will reflect the success or failure of the control operation: - Request Accepted (0) will be returned if the command was accepted; - Request not Accepted due to Formatting Errors (3) is returned if the Control Code byte was incorrectly formatted or if an invalid code was present in the command; - Control Operation not Supported for this Point (4) is returned if the Control Point was out of control.
The alarm indication points indicate possible problems with the device hardware or setup configuration. The hardware problems are indicated by the appropriate points, which are set whenever the instrument fails self-test diagnostics, or in the event of loss of power. The dedicated binary point indicates the setup configuration problems, which is set when either
25
configuration register is corrupted. In this event, the instrument will use the default configuration. The configuration corrupt bit may also be set as a result of the legal changes in the setup configuration since the instrument might implicitly change or clear other setups if they are affected by the changes made. Issuing the Direct-Operate, SBO/Operate or Direct-Operate-No-Acknowledge command using the Control-Relay-Output-Block object (with the code operation Latch-Off) to points 64-75 can reset hardware fault points. The configuration corrupt status point is also reset automatically when you change setup either via the front panel or through communications. The following restrictions should be noted when using Object 12 to control the listed points: The Count byte is ignored. The Control Code byte is checked: - Latch Off is valid for all points; other codes are invalid and will be rejected. The On Time and Off Time fields are ignored. The status byte in the response will reflect the success or failure of the control operation: - Request Accepted (0) is returned if the command was accepted; - Request not Accepted due to Formatting Errors (3) is returned if the Control Code byte was incorrectly formatted or if an invalid Code was present in the command.
3 4
These self-check alarms are doubled with the corresponding internal indication bits. To manually operate a relay, use the Direct-Operate, SBO/Operate or Direct-Operate-No-Acknowledge command to point 80 or 81 of the Control-Relay-Output-Block object with the Control Code value Latch On. To manually release Relay #1, use the Direct-Operate, SBO/Operate or Direct-Operate-No-Acknowledge command to point 80 or 81 of the Control-Relay-Output-Block object with the Control Code value Latch Off. The following restrictions should be noted when using object 12 to control the listed points: The Count byte is ignored. The Control Code byte is checked: - Pulse On, Pulse Off, Latch On (Pulse On/Close) and Latch Off (Pulse On/Trip) are valid for all points; other codes are invalid and will be rejected; - Clear sub-field is valid; other sub-fields are ignored. The On Time specifies in ms the amount of time the digital point is to be turned on. The minimal value of the On Time is 500 ms and the actual value may differ from the specified value by up to 50 ms. The Off Time specifies in ms the amount of time the digital point is to be turned off. The minimal value of the Off Time is 500 ms and the actual value may differ from the specified value by up to 50 ms. The Status byte in the response reflects the success or failure of the control operation: - Request Accepted (0) will be return if the command was accepted; - Request not Accepted due to Formatting Errors (3) will be returned if the Control Code byte was incorrectly formatted or an invalid Code was present in the command; - Control Operation not Supported for this Point (4) will be returned if the Control Point was out of control.
26
Units
Type UINT16
Notes
0.1 A min
If the external synchronization is selected, the DI1 input is considered a pulse or KYZ input. The pulse edge restarts the power demand block accumulation interval.
40:2 (read) AO:4 41:2 (write) 40:1 (read) AO:5 40:1 (read) AO:6 40:1 (read) AO:7 40:2 (read) AO:8 41:2 (write) 40:1 (read) AO:9-AO:10 40:2 (read) AO:11 41:2 (write) 40:2 (read) AO:12 41:2 (write) 40:1 (read) AO:13-AO:19 40:2 (read) AO:20 41:2 (write) Communication Ports Setup 40:2 41:2 40:2 41:2 40:1 41:1 (read) (write) (read) (write) (read) (write) AO:64 AO:65 AO:66 AO:67
Volt/ampere demand period Reserved Reserved Reserved Number of blocks in a sliding window Reserved Nominal line frequency Maximum demand load current Reserved PT ratio multiplication factor
0 to 1800
sec
UINT16 UINT32 UINT32 UINT32 UINT16 UINT32 UINT16 UINT16 UINT32 UINT16
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W Read as 65535 Read as 65535 Read as 65535 Read as 65535
1 to 15
Read as 65535
Hz A
COM1 Setup Communication protocol Interface Device address Baud rate 0=SATEC ASCII, 1=Modbus RTU, 2=DNP3.0 2=RS-485 SATEC ASCII: 0-99 Modbus RTU: 1-247 DNP3.0: 065532 1=300 bps, 2=600 bps, 3=1200 bps, 4=2400 bps, 5=4800 bps, 6=9600 bps, 7=19200 bps, UINT16 UINT16 UINT32 UINT16 R/W R/W R/W R/W
27
Object:Var.
Object:Point Description
40:2 (read) 41:2 (write) 40:2 41:2 40:2 41:2 40:2 41:2 40:2 41:2 40:2 41:2 40:1 41:1 (read) (write) (read) (write) (read) (write) (read) (write) (read) (write) (read) (write)
Data format Flow control RTS mode ASCII compatibility mode COM2 Setup
Options/Range 8=38400 bps, 9=57600 bps, 10=115200 bps 0=7 bits/even parity, 1=8 bits/no parity, 2=8 bits/even parity
Units
Type
R/W
Notes
Format 0 is not allowed in DNP3.0 N/A for COM1 (read as 65535) N/A for COM1 (read as 65535)
0=disabled, 1=enabled
UINT16
AO:83
Baud rate
40:2 (read) AO:87 41:2 (write) Device Options Setup 40:2 (read) AO:92 41:2 (write) 40:2 (read) 41:2 (write) 40:2 (read) AO:93 AO:94
0=SATEC ASCII, 1= Modbus RTU, 2=DNP3.0, 5=Profibus DP 0=RS-232, 1=RS-422, 2=RS-485, 6=Ethernet, 7=Profibus SATEC ASCII: 0-99 Modbus RTU: 1-247 DNP3.0: 065532 Profibus DP: 0-126 1=300 bps, 2=600 bps, 3=1200 bps, 4=2400 bps, 5=4800 bps, 6=9600 bps, 7=19200 bps, 8=38400 bps, 9=57600 bps, 10=115200 bps 0=7 bits/even parity, 1=8 bits/no parity, 2=8 bits/even parity 0=no flow control 1=software (XON/XOFF) 2=hardware (CTS) 0=not used, 1=RTS is permanently asserted 2=RTS is asserted during the transmission 0=disabled, 1=enabled
UINT16
R/W
R/W R R
UINT16
R/W
E E
0=using reactive power: S=f(P,Q), 1=using non-active power: Q=f(S,P) 0=1104, 1=1105, 2=1106, 3=1107, 4=1108, 5=1x109 0=disabled, 1=enabled
28
Object:Var. 41:2 (write) 40:2 (read) 40:2 (read) 41:2 (write) 40:2 (read) 41:2 (write) 40:2 (read) 40:2 (read) 41:2 (write)
Object:Point Description AO:95-AO:101 Reserved AO:102 Energy LED test mode AO:103 AO:104AO:105 AO:106
Options/Range
Units
Notes Read as 65535 LED pulse rate is 10,000 pulses/kWh Default 1.5% Read as 65535 Default 0
Starting voltage, percent of FS voltage Reserved Device resolution (see Section 4 for details)
UINT16 UINT16
UINT16
29
Notes
1
1 1
Default Frozen Binary Counter object variation F3 (default=4) Reserved Default Analog Input object variation Reserved 16-bit BC scaling 16-bit AI scaling Reserved Select/Operate Timeout Multi Fragment Interval Reserved Time Sync Period Voltage scale, secondary volts Current scale, secondary amps Read as 65535 F3 (default=3) Read as 65535 0=1 (default), 1=10, 2=100, 3=1000 0=disabled, 1=enabled (default) Read as 65535 2 to 30 (default=10 sec) 5 to 500 (default=10 ms) Read as 65535 0 to 86400 (default=86400 sec) 60 to 828V (default=144V) 10 to 100 (default 2CT secondary)
5 2
sec V 0.1A
DNP object and variation Start point number Number of points in a range DNP Class 0 Point Range 1
30
Object:Var.
Object:Point
Options/Range
Units
Type
R/W
Notes
NOTES:
1 2
The default variation indicates the variation that is used for requests with qualifier code 06 (variation 0) when no specific variation is requested by a master station. Scaling 16-bit AI objects (see Section 2.2.6) lets accommodate 32-bit analog input readings to 16-bit object format. Scaling is enabled by default. It is not applied to 32-bit AI objects (object 30, variations 1 and 3). The Select Before Operate command causes the device to start a timer. The following Operate command must be sent before the value specified by the Select/Operate Timeout expires. The device requests time synchronization by bit 4 in the first octet of the internal indication word being set when the time specified by the Time Sync Period elapses. The master should synchronize the time in the device by writing the Time and Date object. The meter does not request time synchronization if the Time Sync Period is set to 0. Scaling 16-bit Binary Counters (see Section 2.2.7) allows changing a counter unit in powers of 10 to accommodate a 32-bit counter value to 16-bit BC object format.
3 4
31
Wiring 4LN3, 3LN3, 3BLN3 Wiring 4LL3, 3LL3, 3BLL3, 3OP2, 3OP3, 3DIR2 Fmax Nominal frequency 25, 50 or 60 Hz Nominal frequency 400Hz Data Units Low Resolution Option U1 U2 U3 Data Units High Resolution Option U1 PT Ratio = 1 PT Ratio > 1 U2 U3 PT Ratio = 1 PT Ratio > 1
See Device Options Setup for information on selecting the device resolution option.
1 CT Ratio = CT primary current/CT secondary current 2 The default Voltage scale is 144V (120V +20%). You can change it via the DNP Options setup (see Section 3.9) or via the
it via the DNP Options setup (see Section 3.9) or via the Device Options setup in PAS.
4 Pmax is rounded to whole kilowatts. With PT=1.0, if Pmax is greater than 9,999,000 W, it is truncated to 9,999,000 W.
32
5 Data Formats
Format Code Wiring Mode F1 Value 0 1 2 3 4 5 6 8 9 Instrument Options F2 Bit 0=1 Bit 1=1 Bits 2-5 Bit 6=1 Bit 7=1 Bit 8=1 Bit 9=1 Bit 10=1 Bit 11=1 Bit 12=1 Bits 13-15 Bits 16-18 Bits 19-22 Bits 23-24 Bits 25-31 DNP Object Variations F3 0 1 0 1 2 3 0 1 2 3 4 5 0 1 2 3 DNP Class 0 Objects F4 0x1E01 0x1E02 0x1E03 0x1E04 0x1F01 0x1F02 0x1F03 0x1F04 0x1F05 Description 3OP2 - 3-wire open delta using 2 CTs (2 element) 4LN3 - 4-wire WYE using 3 PTs (3 element), line-toneutral voltage readings 3DIR2 - 3-wire direct connection using 2 CTs (2 element) 4LL3 - 4-wire WYE using 3 PTs (3 element), line-to-line voltage readings 3OP3 - 3-wire open delta using 3 CTs (2 1/2 element) 3LN3 - 4-wire WYE using 2 PTs (2 1/2 element), line-toneutral voltage readings 3LL3 - 4-wire WYE using 2 PTs (2 1/2 element), line-toline voltage readings 3BLN3 - 3-wire broken delta using 2 PTs (2 1/2 element), line-to-neutral voltage readings 3BLL3 - 3-wire broken delta using 2 PTs (2 1/2 element), line-to-line voltage readings 120V Option 690V Option Reserved Analog output 0/4 or 4/20mA Analog output 0-1mA Analog output 1mA RO option DI option Reserved Setup is secured by a password (authorization required) Reserved Number of RO - 1 Number of DI 1 Number of AO - 1 Reserved Static Binary Input Objects Single-Bit Binary Input Binary Input With Status Static Binary Counters 32-bit Binary Counter 32-bit Binary Counter Without Flag 16-bit Binary Counter 16-bit Binary Counter Without Flag Frozen Binary Counters 32-bit Frozen Counter 32-bit Frozen Counter Without Flag 32-bit Frozen Counter With Time of Freeze 16-bit Frozen Counter 16-bit Frozen Counter Without Flag 16-bit Frozen Counter With Time of Freeze Static Analog Input Objects 32-bit Analog Input 32-bit Analog Input Without Flag 16-bit Analog Input 16-bit Analog Input Without Flag Analog Input 30:01 Analog Input 30:02 Analog Input 30:03 Analog Input 30:04 Frozen Analog Input Frozen Analog Input Frozen Analog Input Frozen Analog Input Frozen Analog Input Notes
33
Format Code 0x1F06 0x2801 0x2802 0x0101 0x0102 0x0A01 0x0A02 0x1401 0x1402 0x1405 0x1406 0x1501 0x1502 0x1505 0x1506 0x1509 0x150A 0x3201
Value
Description Frozen Analog Input 31:06 Analog Output 40:01 Analog Output 40:02 Binary Input 01:01 Binary Input 01:02 Binary Output 10:01 Binary Output Status 10:02 Binary Counter 20:01 Binary Counter 20:02 Binary Counter 20:05 Binary Counter 20:06 Frozen Counter 21:01 Frozen Counter 21:02 Frozen Counter 21:05 Frozen Counter 21:06 Frozen Counter 21:09 Frozen Counter 21:10 Time and Date 50:01
Notes
34
20 20 20 20 21 21 21 21 21 21 21 30
1 2 5 6 0 1 2 5 6 9 10 0
30 30 30 30 31 31 31 31 31 31 31 40 40 40 41 41 41 41 50 60 80 N/A N/A
1
1 2 3 4 0 1 2 3 4 5 6 0 1 2 1 2 1 2 1 1 1 N/A N/A
35
2 3 4
For this object only point index 7 is allowed. Responds with time object 50 variation 2 indicating time until device availability. The default object variation used in device responses to master requests with no specific variation specified can be selected via the DNP Options Setup (see Section 3.9, DNP Protocol setup). Functions Immediate Freeze (7) and Immediate Freeze-No Acknowledgement (8) copy the Analog Input points listed in the Class 0 point list as Frozen Analog Input objects (see Section 3.9, DNP Protocol setup) to a freeze buffer. In the event Class 0 doesnt contain Frozen Analog Input points, the device responds to function Immediate Freeze (7) with the IIN2.1 bit set - Outstation does not support requested operation for objects in the request. The response contains the last frozen values of the corresponding Analog Input points if the freeze command was executed before, or immediate values of the corresponding Analog Input points in the event the freeze command has never been executed. Frozen Analog Inputs requested with variation 0 are responded with the variation specified for the requested points in the Class 0 point list. Any Frozen Analog Input point can be requested except points AI:256AI:288 and AI:1024-AI:1027. See Section 2.2.5 for more information on Frozen Analog Inputs. Qualifier Hex Codes for each category: A - 00,01,03,04,07,17,27,08,18,28 B - 06 only C - Qualifier echo D - 00,01,03,04,17,27,18,28 N/A - Not Available N/R - Null Response
36
For Responses L1 Device supports READ of each object using either all points (Qualifier = 6) or specific points using qualifier defined in Basic 4 Documentation Set: 00, 01, 03, 04, 07, 17, 27, 08, 18, 28. Control Relay Block requires specific parameters described in this manual. Treats range field of qualifier 07 and 08 to mean point range [0N-1]. Maximum Data Link Frame Size (octets): Transmitted Received 292 292 Maximum Application Fragment Size (octets): Transmitted Received 2048 249
Maximum Data Link Retries: None Fixed at____________________ Configurable, range ___ to_____ Requires Data Link Layer Confirmation: Never Always Sometimes Configurable
Maximum Application Layer Retries: None Configurable, range ____ to _______ (Fixed is not permitted)
Requires Application Layer Confirmation: Never Always (not recommended) When reporting Event Data (Slave devices only) When sending multi-fragment responses (Slave devices only) Sometimes Configurable If 'Sometimes', when? ______________________________ If 'Configurable', how? ______________________________
37
Timeouts between fragments of the multi-fragment responses. Configurable: 50-500 ms (50 ms by default). ___________________________________________________________________ Attach explanation if 'Variable' or 'Configurable' was checked for any timeout Sends/Executes Control Operations: WRITE Binary Outputs SELECT/OPERATE DIRECT OPERATE DIRECT OPERATE NO ACK Count > 1 Pulse On Pulse Off Latch On Latch Off Queue Clear Queue
1
Select timeout period is configurable: 2s to 30s used to activate the Reset function associated with points 0 to 21 2, 3, 4 used to control Relays associated with points 80 to 81 3 used to reset the self-check alarm registers associated with points 64 to 75
Reports Binary Input Change Events when no specific variation requested: Never Only time-tagged Only non-time-tagged Configurable to send both, one or the other (attach explanation)
Reports time-tagged Binary Input Change Events when no specific variation requested: Never Binary Input Change With Time Binary Input Change With Relative Time Configurable (attach explanation)
38
Default Counter Object/Variation: No Counters Reported Configurable (attach explanation) Counters requested with variation 0 are responded with the default variation specified for the Counter object in the DNP Options Setup. Default Object Default Variation Point-by-point list attached Sends Multi-Fragment Responses: Yes
Counters Roll Over at: No Counters Reported Configurable (attach explanation) 16 Bits 32 Bits Other Value Counters Point-by-point list attached See Sections 3.3-3.5.
No
39