Equipment CT SIDE
Date 06.04.10
Cursor-1 55.6
Cursor-2 38.2
Analysis & Recommendation:- R temp. is in semi critical range so close monitoring is needed. Should be attended in the next priority.
Client Representative:-
THERMOGRAPHY REPORT Report No. :- 02 MAIN LOCATION: - SWITCH YARD (400 KV), BAY-05
Equipment CT SIDE
Date 21.02.2011
Cursor 1 53.2
Cursor 2 35.2
Analysis & Recommendation:- B temp is in semi critical range and may create problem in near future so it should be attended in next priority .
Client Representative:-
THERMOGRAPHY REPORT Report No. :- 03 MAIN LOCATION:- SWITCH YARD (400 KV), BAY-02
Equipment CENTRE
Date 06.04.10
Cursor-1 69.2
Cursor-2 43.4
Analysis & Recommendation:- B temp. is in semi critical range and may create problem in near future so close monitoring is needed.
Client Representative:-
THERMOGRAPHY REPORT Report No. :- 04 MAIN LOCATION:- SWITCH YARD (400 KV), BAY-03
Date 06.04.10
Cursor-1 67.3
Cursor-2 35.6
Analysis & Recommendation:- :- R temp. is in semi critical range so it should be under regular monitoring .Check the loose connection .
Client Representative:-
THERMOGRAPHY REPORT Report No. :- 05 MAIN LOCATION: - SWITCH YARD (400 KV), BAY-07
Date 22.02.2011
Cursor 1 53.3
Cursor 2 34.8
Analysis & Recommendation: - Y temp is in semi critical range and may create problem in near future so it should be attended in next priority.
Client Representative:-
Equipment FAN G
Date 02.05.2011
Analysis & Recommendation:- R temp is in semi critical range and may create problem in near future so it should be attended in next priority .
Client Representative:-
Equipment FAN - K
Date 22.12.2010
Cursor 1 126.8
Cursor 2 80.3
Analysis & Recommendation:- R ,Y temp. is in critical range so it should be attended as soon as possible.
Client Representative:-
Date 30.01.10
Cursor-1 55.5
Cursor-2 42.9
Analysis & Recommendation:- R transformer bushing Temp is high so it should be attended with next priority .
Client Representative:-