reflex V in-line vessel Necessity reflex V in-line vessels protect the diaphragms of expansion vessels from impermissible temperature loads. According to DIN 4807 Part 3, the continuous temperature on the diaphragm must not exceed 70C. In cooling systems, temperatures of d 0C should be avoided, so as to eliminate the possibility of the diaphragm freezing to the vessel. Principle If the reflex V in-line vessel is connected from above, hot expansion water > 70C displaces cooler water into the diaphragm of the expansion vessel. If the reflex V in-line vessel is connected from below, cold expansion water d 0C displaces warmer water into the diaphragm of the expansion vessel.
In heating systems
t > 70C
In cooling circuits
t d 0C t > 0C
Vn t 70C
Vn
Selection No general formula exists for calculating the nominal volume Vn of V in-line vessels. Local conditions also vary too greatly. We would therefore like to refer you to our calculation program and the brochure for Pressurization, Degassing, and Make-up Systems Planning, Calculation, Equipment.
D A A
Technical data
A h
Type 10 bar / 120C V 6 V 12 V 20 V 40 V 60 V 200 V 300 V 350 6 bar / 120C V 500 V 750 V 1000 V 1500 V 2000 V 3000 V 4000 V 5000 10 bar / 120C V 1000 V 1500 V 2000 V 3000 V 4000 V 5000
Article No. 7403100 7403200 7402000 7403400 7402600 7701800 7701900 7702400 7852800 7851800 7851905 7852305 7852405 7852505 7853405 7854805 7400205 7400305 7400405 7400505 7400605 7400705
H mm 245 285 360 562 760 900 1200 1385 1660 2310 2020 2020 2480 2560 3130 3637 2055 2055 2055 2600 3180 3720
h mm ------113 174 142 142 210 210 210 305 305 305 340 340 340 285 285 285 315 315 315
A mm R R R R 1 R 1 DN 40/PN 16 DN 40/PN 16 DN 40/PN 16 DN 40/PN DN 40/PN DN 65/PN DN 65/PN DN 65/PN DN 65/PN DN 65/PN DN 65/PN 6 6 6 6 6 6 6 6
Weight kg 2 3 4 ? 23 43 48 51 79 325 560 780 940 1405 1930 2015 675 935 960 1685 2315 2420
750 750 1000 1200 1200 1500 1500 1500 1000 1200 1200 1500 1500 1500
Vn nominal volume/liters