DPUMPUS0108
Data Sheet
General
Features
Ultrasonic sensor, hydrostatic pressure transmitter or 4 - 20 mA input. Standard measurement ranges from 0 -10 ft. up to 0 - 100 ft. in liquids / sludge. Measures and indicates level, numbers of starts, pump run time, calculates capacity and output for each pump and total capacity for the whole pumping station. Menu system with easy and logical functions. Start-up menu for first time operation, so that all parameters are correctly applied. The pump controller is operated by clearly marked keys. Simplified field installation due to user friendly logical functions. Pumps can be manually operated directly from the pump controller. Alternation of two to four pumps (first in first out). Two by two alternation of small and larger pumps. Alternation in sequences. Alternation by running hours. Choice of numbers of synchronous pumps in operation. A function which allows the complete draining of a well or pumping station. Automatic start of back-up pump. Pumps can be taken out of service. Manual start/stop of pumps. Free choice of delay of start for each pump, limiting current surge and water hammering. Alarms for level and system error. Delays on alarm outputs. The pump controller calculates both output and capacity of the individual pump, along with the total capacity of the pumping station. The calculation model is
English or metric measurement units Direct indication of elevation for use in flood plains or areas where USGS elevations are required. Text display for programming and reading of measurement values with all indications in plain language (English and Spanish). 4 relays for control and alarms. Lead/lag pump alternation.
Operation
Functions
Flow calculation
independent of the actual pump characteristics and does not require pump data programming.
Data Sheet
ULC 2500 Level Controller System Package 1
The Danfoss ULC 2500 Level Controller System Package is supplied with the SONOLEV Ultrasonic Sensor with a 0 - 30 ft. measuring range. The SONOLEV sensor provide a noncontact level measurement system, which is ideal for use in most water and wastewater level applications.
Features
Non-contact measuring method; no moving parts, no maintenance. Only 3 beam angle. The narrow beam angle provide high signal intensity and minimum sensitivity to foam and sludge on the surface.
Accidental submergance to 30 ft. Logic noise protection system ignores electrical disturbances, turbulence and interference from mixers.
Connections
SONOLEV 1100 Sensor No. No. No. No. No. 1= 2= 3= 4= 5= brown red orange yellow black
Voltage input
Relay out 1
Relay out 2
Relay out 3
Relay out 4
Specifications
0.4 "
Dimensions
Data Sheet
ULC 3000 Level Controller System Package 2
The Danfoss ULC 3000 Level Controller System Package is supplied with the PRESLEV 2100 Level Transmitter for measuring rages of up to 30 ft. The ULC 3000 Level Controller is ideal for applications where surface conditions make it difficult for ultrasonic measurements or where access for surface measurements is difficult.
Features
Sturdy pressure transmitter with 316L stainless steel membrane. The transmitter has a steel reinforced cable which can withstand a tensile stress up to 2,000 lbs.
The transmitter has a polyethylene equalizing tube in the cable. The transmitter housing is designed to prevent clogging.
Connections
Relay out 1
Relay out 2
Relay out 3
Relay out 4
Voltage input
Specifications
1%
+ 5 to + 150 F Polypropylene (grey) / POM (black), membrane from 316L stainless steel. 2 AWG 20, shielded, oil resistant PVC insulation. Length 40 ft. (can be extended) NEMA 6P, submersible up to 100 ft. EN50081-1, EN50082-1
Dimensions
Mounting Bracket
Data Sheet
Communication
Start and stop levels for pumps and alarms. Start and stop (blocking of pumps). Counters and time meters. Calculation of volume and throughput of one pump and pumping station.
Specifications
Height 7.28 ", width 9.45 ", depth 4.53 " Polystyrol with transparent lid, NEMA 4X UL-CUL listed, file # 194021 UL 508/c22: 2 No. 142-M1987
Dimensions
Data Sheet
Order numbers, standard
System Package 1, ULC 2500 Level Controller, including SONOLEV 1100 Sensor
192L9060: 192L9061: Level Controller, range 0 - 30 ft. Level Controller, range 0 - 30 ft., with galvanically isolated 4 - 20 mA output
System Package 2, ULC 3000 Level Controller, including PRESLEV 2100 Transmitter
192L9035: 192L9036: 192L9040: 192L9041: Level Controller, range 0 - 10 ft. Level Controller, range 0 - 10 ft., with galvanically separated 4 - 20 mA output Level Controller, range 0 - 30 ft. Level Controller, range 0 - 30 ft., with galvanically separated 4 - 20 mA output
Please use build-up code below for ordering special ULC systems
ULC 2500 - RF030 - G0 - CF040
PRESLEV 1100, 2100 or 3100 R010 = range 0 - 10 ft G0 G1 = no galvanic separation = galvanic separation
* Please check programmable range for transmitter
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.