Applied Thermal Engineering 23 (2003) 581592

www.elsevier.com/locate/apthermeng

Domestic air-conditioner and integrated water heater for subtropical climate


Jie Ji a, Tin-tai Chow
a

b,*

, Gang Pei a, Jun Dong a, Wei He

Department of Thermal Science and Energy Engineering, University of Science and Technology of China, Hefei, Anhui 230026, China b Division of Building Science and Technology, City University of Hong Kong, Tat Chee Avenue, Kowloon, Hong Kong Received 25 July 2002; accepted 15 November 2002

Abstract The technology of using a heat pump for space conditioning and domestic hot water heating in residences has been developed for half a century. The earlier air-to-water heat pumps and water-heating heat pumps suered from drawbacks like high costs, unreliable operation, and inexible applications. They were not well positioned in the market to attract customers. This paper introduces a novel air-conditioning product that can achieve the multi-functions with improved energy performance. The basic design principles and the laboratory test results are presented. The results showed that by incorporating a water heater in the outdoor unit of a split-type air-conditioner so that space cooling and water heating can take place simultaneously, the energy performance can be raised considerably. 2002 Elsevier Science Ltd. All rights reserved.
Keywords: Room air-conditioner; Heat pump; Domestic hot water heating; Refrigeration; Thermal design

1. Introduction Heat pumps were rst used in residences in 1950s for space heating and for domestic hot water heating. They were not reliable at that time and the maintenance cost was high. After the oil crises in the 1970s, the family-use heat pump has undergone rapid development. Desuperheaters, which worked for heat pumps and air conditioners, were introduced in the United States market by three manufacturers. They were then claimed to oer almost free water heating in summer whenever
*

Corresponding author. Tel.: +852-2788-7089; fax: +852-2788-9716. E-mail address: bsttchow@cityu.edu.hk (T.-T. Chow).

1359-4311/02/$ - see front matter 2002 Elsevier Science Ltd. All rights reserved. PII: S 1 3 5 9 - 4 3 1 1 ( 0 2 ) 0 0 2 2 8 - 4

582

J. Ji et al. / Applied Thermal Engineering 23 (2003) 581592

Nomenclature COP Q W s coecient of performance heat ow rate (W) power input (W) time period (s)

Subscripts 1 condenser 2 evaporator c space cooling h space heating w water heating avg averaged space cooling was required, and to reduce total domestic electricity demand in houses which otherwise had to rely on direct electric water heaters [1]. Further feasibility studies showed that air-source water-heating heat pumps were much more economical than solar systems, which were much more popular in application. Payback periods of 23 years were anticipated [2]. Air-conditioning units with an integral hot-water storage tank and immersed condenser, using ambient air as a heat source, were available [3]. In early 1980s, over 10,000 units of these air-to-water heat pumps for homes were sold every year in US. These early models were suered from high purchase prices, high maintenance costs, noisy, poor longevity, and limited installation options. These drawbacks led the market to collapse. As of 1995, the two surviving manufacturers were only selling about 2000 residential units per year. One of them was producing a high-end integrated heat pump/storage tank. And the other was producing a compact stand-along heat pump that retroted onto an electric resistance storage water heater [4]. Through all these years, the technology has been emphasizing on waste heat recovery and hot water production. Services water heating is the main task of the heat pump water heater; the additional air-conditioning and heat recovery ventilation are the by-products. As a matter of fact, a condensing temperature higher than 60 C is dicult to obtain with refrigerants like R-22 and R134a. Heat pump water heaters in their normal capacities can heat water at a rate 40100% of the electric resistance units, and 3050% of the gas units. To provide quick recovery, a household must have a large heat pump, an unusually large storage tank, and a control system that turns on the electric resistance backup heater whenever required. However, large water tanks are more expensive, take up more space, and use more energy to maintain a set point. A higher-capacity heat pump is undesirable as it costs more and the frequent startstop often results in lower eciency. Some designs let the small heat pump cater for most of the hot water load, but include control mechanism to activate the electrical heater in the tank when the demand is high. However, this increases peak electrical demand and reduces energy eciency. For some households, an option is to reduce peak demand by spreading out their hot water consumption over the day. Today, technological advancements have overcome the problems mentioned above. Heat pump water heater may turn out to be popular again. The air-to-water heat pump water heater oers an

J. Ji et al. / Applied Thermal Engineering 23 (2003) 581592

583

energy-saving alternative. A heat pump water heater can provide hot water two to three times more energy ecient than an electric-resistance heater. If installed properly, it can also provide useful by-productsspace cooling, dehumidication, or heat-recovery ventilation. The extended use of heat pump water heater in air-conditioning and heat-recovery ventilation has been reported [4]. In Europe, advanced heat pump technology has been already in place [5].

2. Applications in subtropical region For a place in the subtropical region, like Hong Kong, most household families use air-conditioners merely for space cooling in summer. The use of heat pump is not popular because of the relatively short and mild winter. Instead, electric heaters are used during the cold days. To obtain hot water, the families rely on various types of water heaters, such as electric water heater, gasred water heater, etc. There are some limitations and problems as at present, viz.: (a) The air-conditioner is used only in summer for space cooling and remains idle in the rest of the year; the utilization is low. (b) A family buys both air-conditioner and water heater; this may not be economical in terms of cost and space. (c) The operating cost of the gas-red or electric water heater can be higher than that of the heat pump. (d) The gas-red water heater depends on the stability of water-pressure on its smooth operation; it also has the potential danger in life safety caused by the possible leakage of fuel gas or combustion products. (e) Condenser heat dissipation from the air-conditioners can be a source of heat pollution; this is elaborated below. For high-rise apartment buildings in Hong Kong and in the Mainland China, the building reentrantan open space where the kitchens receive daylight and ventilating airis a popular place to accommodate the outdoor units of the split-type air-conditioners. The presence of these aircooled condensing units however, introduces a thermal problemthe thermal buoyance as a result of heat dissipation leads to the development of a rising air plume; inadequate air exchange at this recessed space elevates the ambient temperature, and the insucient cooling signicantly aects the condenser performance, especially for those at the upper oor levels. The result could be an overall degradation of the capacity and the eciency of the air-conditioners at the entire building re-entrant. As most condensing units are unlikely to function properly at elevated on-coil temperature because of the abnormal condenser working pressure, the problem is therefore not only energy wastage but also equipment malfunction [6,7]. Similar problems occur in windowtype air-conditioners when they are placed at the building re-entrant [8]. Currently under our study is a novel air-conditioner that possesses multi-functions: space cooling, domestic hot water heating, and space heating. The design is expected to overcome the mentioned problems and limitations. Two prototypes have been produced. The following presents their basic design concepts and the laboratory test results that illustrate the operation and economic advantages.

584

J. Ji et al. / Applied Thermal Engineering 23 (2003) 581592

3. Design of novel air-conditioning units 3.1. General principles The proposed air-conditioner is designed for multi-task and for year round service. The device possesses the dual functions of space air-conditioning and water heating. It is designed as a splittype unit. A water tank with immersed condensing coils is integrated in the outdoor unit. In the warm seasons, the novel air-conditioner provides space cooling as its primary task, and produces domestic hot water through the water-bath heat-recovery condenser as its secondary task. In the process, the water temperature will rise. The performance will drop because of the elevated condenser working temperature and pressure. To overcome this limitation, an air-cooled condenser is connected in series with the immersed condenser. This is to overtake the duty of the immersed condenser when the water temperature reaches a high limit. And, because of the mixed eect of water- and air-cooling, the average performance in the cooling mode will be generally higher than the conventional split-type air-conditioner. The proposed product is able to work in one of the following three operation modes: 3.1.1. Provision of space cooling and domestic hot water As the rejected heat energy at the condenser is about 1520% more than the evaporator refrigerating eect, the recovery of all rejected heat for hot water production is not necessary. The hot water consumption depends on the needs of the individual family, say on the number of family members and their living habits. As the operation time for space cooling can be lengthy, the water heater is only to recover a part of the condensation heat energy. 3.1.2. Provision of domestic hot water as a heat pump water heater Other than the cooling season, the proposed air-conditioner is primarily used to produce domestic hot water. In this mode, the indoor unit is not in use. The air-cooler at the outdoor unit becomes the evaporator, which works together with the immersed condenser. In order to improve the heat exchange at the water tank, the other side-by-side condenser coil is to be put in service. The proposed product becomes a heat pump water heater in this case. Because of the mild winter in the subtropical region, the outdoor temperature will not drop below 0 C. In Hong Kong for example, the average temperature in winter is 15 C, there is minimum defrosting problem even when the ambient air is used as the heat pump heat source. 3.1.3. Provision of space heating In the cold season, space heating may be needed. The proposed air-conditioner then behaves like a conventional air-to-air heat pump. The air-cooler at the outdoor unit becomes the evaporator. The indoor unit will then provide space heating. In terms of economy in equipment operation, simultaneous space heating and domestic water heating is not recommended. 3.2. Performance denition The energy performance of a refrigeration device can be measured by its coecient of performance (COP), which carries dierent denitions depending on its specic appli-

J. Ji et al. / Applied Thermal Engineering 23 (2003) 581592

585

cations. Additional performance denitions can be used in the case of the novel air-conditioner. 3.2.1. Space cooling and water heating mode Because of the gradual change in water temperature, the COP of the novel air-conditioner varies with time, even when both indoor and outdoor thermal environments remain unchanged. At any time instance t, the COP for space cooling is given by: COPc t Q2 t W t Q2 t Qw t W t 1

and the overall COP value when the water waste heat for water heating is included is then: COPcw t 2

Their average values over a time period s is Rs Q2 t dt COPc avg R0s W t dt 0 Rs Q2 t Qw t dt COPcw avg 0 R s W t dt 0

In the above equations, Q2 t is the heat exchange rate at the indoor unit; Qw t is heat exchange rate at the immersed condenser; W t is the electric power input to the novel air-conditioner, and s is the time duration of the measurement. 3.2.2. Water-heating-only mode The water heating eciency can be dened as COPw t Qw t W t Rs Qw t dt R0s W t dt 0 5

COPw

avg

3.2.3. Space-heating-only Similarly, the COP for space heating can be dened as COPh t Q1 t W t Rs Q1 t dt R0s W t dt 0 7

COPh

avg

586

J. Ji et al. / Applied Thermal Engineering 23 (2003) 581592

where Q1 is the condenser heat energy released to the indoor space for a reversed cycle. This COPh for space heating is expected the same as the conventional air-to-air heat pump, when the water bath condenser is left idle.

4. The prototypes Two prototypes of slightly dierent design were fabricated for performance testing. Their features are described below. 4.1. Two-function air-conditioner The two-function air-conditioner is able to provide space cooling and water heating, but not space heating. This is especially suitable for applying in the tropic and subtropical areas where space heating is not essential. The water bath condenser consists of two heat transfer coils acting side by side. The two alternative working cycles are shown in Fig. 1. The white arrows in the gure indicate the direction of refrigerant ow in the space cooling and water heating mode (Mode 1), and the black arrows indicate the ow directions in the water-heating-only mode (Mode 2). The switching between these two modes is by means of the electromagnetic valves. In Mode l, Valve 1 and Valve 3 are closed and Valve 2 is open. The refrigerant discharged from the compressor passes through Coil 1 at the water bath condenser, then directly to the air-cooled condenser without passing through the

Water bath condenser


Coil 1 Valve 2 Air-cooled condenser

Valve1

Coil 2 Capillary tube 1

Compressor Evaporator

Valve 3

Indoor unit

Capillary tube 2

Fig. 1. Working cycles of the two-function air-conditioner.

J. Ji et al. / Applied Thermal Engineering 23 (2003) 581592

587

Water-bath condenser Four-way valve

Valve 1

Air-cooled condenser

Capillary tube 1 Valve 2

Capillary tube 1. In Mode 2, Valve 1 and Valve 3 are open and Valve 2 is closed. Both Coil 1 and Coil 2 of the water bath condenser are now in use to increase the heat capacity. 4.2. Three-function air-conditioner The three-function air-conditioner is able to provide space cooling, water heating and space heating. This is particularly suitable for applying in cold climatic regions where space heating is generally required. However, it should not be subject to extremely cold weather; otherwise the proposed product with a low-temperature heat source will suer from low eciency. Also defrosting can be a problem. The working cycles of the three-function air-conditioner are shown in Fig. 2. There are three modes of operation. Mode 1 is for simultaneous space cooling and water heating, Mode 2 is for water-heating-only, and Mode 3 is for space-heating-only. The directions of refrigerant ow in these three modes are indicated by the white, black and gray arrows respectively. The four-way valve allows the correct refrigerant ow across the compressor in all situations.

Compressor Valve3

Indoor unit
Evaporator Capillary tube 2

Fig. 2. Working cycles of the three-function air-conditioner.

5. Laboratory test 5.1. Laboratory set-up To examine the performance of the novel air-conditioner, the evaporative and condensation heat transfer in dierent modes and dierent thermal environment (i.e. the temperature and relative humidity of air) were measured.

588

J. Ji et al. / Applied Thermal Engineering 23 (2003) 581592

The energy performance of the three-function air-conditioner was tested in a national-standard laboratory. In the absence of standard testing procedures for this innovative product, the measurements were making reference to the Chinese National Standard GB/T7725-1996 on space heating and cooling devices. The thermal environments of the performance tests on the cooling and heat modes respectively are listed in Table 1. All laboratory measurements were taken placed in a room-type test chamber, of which the key features and provisions are shown in Fig. 3. The entire chamber was provided with high quality thermal insulation, in that the heat exchange (including thermal radiation) across the external enclosure was not to exceed 300 W, based on a temperature dierence of 11 C. The two environmental chambers were separated by a well-insulated partition. Individual air-handling unit (AHU) was provided in each chamber to keep the air temperature and relative humidity to the controlled conditions. These two adjoining chambers, here referred as the indoor chamber and the outdoor chamber, were where the indoor and outdoor units of the novel air-conditioners were placed. Surrounding each of the two chambers was an equalizing temperature compartment, where the air temperature was maintained the same as that in either chamber. A pressure-balancing device was inserted to monitor the pressure dierence between the two chambers, and to facilitate the measurements of air leakage and air recirculating rates. For the water-heating-only mode, the performance tests were carried out solely in the outdoor chamber at four dierent dry bulb air temperature conditions. These were respectively 31, 25, 15 and 4.5 C. The measurements were stopped when the water bath temperature rose to 70 C. And for the space-heating-only mode, the 7 C testing conditions is regarded as a frost-free outside condition.
Table 1 Controlled testing environment of novel air-conditioner Heat pump testing conditions Controlled air temperature at indoor chamber (C) DB Indoor unit at cooling operating mode Indoor unit at heating operating mode 27 20 WB 19 15 (max) Controlled air temperature at outdoor chamber (C) DB 35 7 WB 24 6

Fig. 3. Key features of air-conditioner performance test chamber.

J. Ji et al. / Applied Thermal Engineering 23 (2003) 581592


3500 3000 2500 2000 1500 1000 500 0
0 15 30 45 75 60 Time(minute) 90 105

589

cooling rate(W) input po wer(W) COPcw100 water te mperature10(deg.C) COPc100

Fig. 4. Performance test results of three-function air-conditioner at space cooling and water-heating mode.

5.2. Performance test results Fig. 4 shows the testing results of the three-function air-conditioner when it operated with the space-cooling and water-heating mode. While both the input electric power and water temperature increased with time, the COPcw and COPc drop mildly. The COPcw avg is found to be 4.02 and the COPc avg 2.91. Fig. 5(a)(d) show the test results of the water-heating-only mode at four dierent controlled ambient temperatures. It can be seen that in each case COPw gradually decreases with time as the water bath temperature increases. During the four testing periods, the COPw avg dropped from 3.42 to 2.0 when the setting of the controlled ambient temperature shifted from 31 to 4.5 C. It should be noted that the listed COPw avg values are for reference only, since the initial water bath temperatures were not controlled in these trial tests. Table 2 lists the averaged testing results for Modes 1, 2 and 3. It should be noted that for Mode 3, the COPh remained constant (equal to COPh avg ) as far as the indoor and outdoor thermal environments were xed in accordance with the specied testing conditions stated in Table 1. The performance was close to a conventional air-to-air heat pump. For the two-function air-conditioner, the test results are expected to be more or less the same as the three-function air-conditioner. This is because the two prototypes are basically of the same design, except for the complexity in the refrigeration circuit.

6. Discussions The COPc of a conventional air-conditioner is in the range of 2.22.4. According to our test results, the novel air-conditioner has a higher COPc (2.91 in average) than the conventional

590
80 60 40 20 0 0

J. Ji et al. / Applied Thermal Engineering 23 (2003) 581592

input power/100(W ) wate r temperature(deg.C COPw1 0 5 9 13 Time(minute) 17 20 23

(a) Ambient temperature at 31oC


80 60 40 20 0 0 4 8 12 16 20 24 28 31 Time(minute ) input power/100(W) wate r temperature(deg.C) COPw1 0

(b) Ambient temperature at 25oC


80 60 40 20 0 0 4 8 12 16 20 24 28 32 Time(minute) input power/100(W) water temperature(deg.C) COPw*10

(c) Ambient temperature at 15oC


80 60 40 20 0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 Time(minute) input power/100(W) water temperature(deg.C) COP w10

(d) Ambient temperature at 4.5oC


Fig. 5. Performance test results of three-function novel air-conditioner at water-heating-only mode.

split-type air-conditioning unit. This is because of the water-cooling eect. If the novel air-conditioner is also used as a heat pump water heater, the COPcw avg of 4.02 becomes much attractive. This value is 38% higher than the COPc avg , and can be even higher if there is a continuous hot water consumption. Since once the water in tank has been consumed substantially and relled, the heat sink temperature will be lowered and the heat pump water heater will perform more eciently. In order to evaluate the eect of dierent hot water consumption modes on the energy performance, the variation of daily COP in dierent hot-water usage pattern should be further investigated. Furthermore, as a novel product, the equipment should be made cost eective by controlling well the initial cost and the maintenance cost. Over-sizing should be avoided.

J. Ji et al. / Applied Thermal Engineering 23 (2003) 581592 Table 2 Test performance of three-function novel air-conditioner in dierent operating modes Operating mode Mode 1: space-cooling and water-heating Mode 2: water-heating-only Averaged COP COPcw avg COPc avg COPw avg at 31 C 25 C 15 C 4.5 C COPh Test results 4.02 2.91 3.42 3.25 2.52 2.00 2.72

591

Mode 3: space-heating-only

According to an investigation of the China market in 1999, the annual sale volume of airconditioners in the country was 900,0000. Only 30% of the families living in cities owned airconditioners. The gure reduced to 10% for the rural area. Meanwhile, the annual output of gas water heaters was 400,000 and the annual output of solar water collectors was 250,0000. The sale volume of electric water heater shared 60% of the total water heater market. Following the economic growth of the country, it is expected that more and more families will have a demand on air-conditioners and water heaters. On the other hand, the available water heaters have problems like safety, reliability, and energy saving. At this end, the proposed air-conditioner integrated with water heater is functionally safe, exible, economical, and environmental friendly. It is expected to have a very good market in China, and even in other countries as well. Nishimura [9] gave a precise prediction about the trends of using heat pump in Asia and the Pacic.

7. Conclusions Heat pump oers a technology that reduces energy consumption, fuel cost, and global warming eect. By integrating a water-cooled condenser to the outdoor unit of a heat pump, there are a number of advantages, i.e. (a) By combining the air-conditioning unit and the water heater into one product, the novel airconditioner turns out to be exible, multi-functional, and economical. (b) Through the waste heat recovery process, the overall COP of the device can be much improved. (c) It can work independently as a domestic heat pump water heater; the heating eciency is much higher than that of the electric water heater. (d) The conventional air-conditioner only works in summer. In most time of a year, it becomes idle. The novel air-conditioner is suitable for use in any time of a year. (e) The laboratory test results on the prototype have been very much promising; the performance under the space-cooling mode can be jacked up by 38% through simultaneous water-heating. The energy performance of the space-heating mode is close to that of a conventional split-type unit.

592

J. Ji et al. / Applied Thermal Engineering 23 (2003) 581592

References
[1] E.F. Gorzelnik, Heat water with your air-conditioner, Electrical World 188 (11) (1977) 5455. [2] ONeal, et al., Energy and economic eects of residential heat pump water heaters. CONF-790107-2, Oak Ridge National Laboratory, USA, 1979. [3] R.D. Heap, Heat Pumps, Second ed., E.&F.N. Spon, London, 1983. [4] S. Bodzin, Air-to-water heat pumps for the home, Journal of Home Energy 14 (4) (1997). [5] H.J. Laue, Regional report Europe: heat pumpsstatus and trends, International Journal of Refrigeration 25 (2002) 414420. [6] T.T. Chow, Z. Lin, Prediction of on-coil temperature of condensers installed at tall-building re-entrant, Applied Thermal Engineering 19 (1999) 117132. [7] T.T. Chow, Z. Lin, J.P. Liu, Eect of condensing unit layout at building re-entrant on split-type air-conditioner performance, Energy and Buildings 34 (3) (2002) 237244. [8] M. Bojic, M. Lee, F. Yik, Flow and temperature outside a high-rise residential building due to heat rejection by its air-conditioners, Energy and Buildings 33 (2001) 737751. [9] T. Nishimura, Heat pumpsstatus and trends in Asia and the Pacic, International Journal of Refrigeration 25 (2002) 405413.