Вы находитесь на странице: 1из 67

KRISHNA ELECTRICAL INDUSTRIES LTD.

30- B, Industrial Area Banmore


As Per IS: 7098(Pt-II)/1985 with latest amendment & GTP

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005

Size:-1Cx300 Sqmm 3.3/3.3 kv(A2XY)


DESCRIPTION OF TEST
Overall Diameter of Cable (mm)

Drum No.

OBSERVATION Drum No.

Drum No.

SPECIFIED VALUE 31.0+/-2.0

A) TEST ON CONDUCTOR i)No. of wirtes ii)Dia over conductor (mm) III)Shape of conductor Dia over Core (mm)i.e below copper tape/wire screen B) THICKNESS (mm) Insulation Avg Min Eccentricity Ovality Copper Tape Copper Wire No. of wires & tapes
Outer Sheath(Type-ST2) FRLS Outer Sheath(Type-ST2) FRLS

36 No. wires(Nom) 20.6(Approx.) Cir.Stranded Compacted 25.2(Approx.)

2.2 (Nom) 1.88 (Min) 10%(Max) 2%(Max)


0.045x30mm(Nom.)

0.82(Nom.) 3&1 2.00(Nom) 1.6(Min) 25.7(Approx.)

Diameter below outer sheath (mm)

6 7
15 Drums

A-1877 A-1879

505 500 3445

Size:-3CX150 Sq.mm 3.3/3.3 KV (A2XY)

S.NO.

Drum No.

Offered Length (Mtrs)

Length Consumed in testing (Mtrs)

Final Length (Mtrs)

1 2
20 Drums

A-1768 A-1769

508 517 1025

Size:-1CX150 Sq.mm 3.3/3.3 KV (A2XY)


S.NO. Drum No. Offered Length (Mtrs) Length Consumed in testing (Mtrs) Final Length (Mtrs)

1 2 3 4 5 5 Drums

A-1748 A-1749 A-1750 A-1751 A-1752

512 509 500 495 490 2506


For Krishna Electrical Industries Ltd

As Per IS: 7098(Pt-II)/1985 with latest amendment & GTP Customer:- National Thermal Power Corporation,Noida Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005 Size:-3Cx150 Sqmm 11/11 kv(A2XY) Dt. Of Completion of Testing:24.01.06
Drum No. 1040 Min O/D=75mm,Max. O/D=77.0mm.Approx. O/D=75.75mm Approx.Dia over inner sheath=66.07mm Approx.Dia over laid up cores=61.6mm Dia over core(R)=28.70mm(Approx.),Min Dia= Dia over core(Y)=28.63mm(Approx.),Min Dia= Dia over core(Bl)=28.71mm(Approx.),Min Dia= 28.69 28.56 28.62 Max.Dia= Max.Dia= Max.Dia= 28.8 28.69 28.89 % Ovality= Max. Dia-Min Dia Max. Dia % Ovality= Max. Dia-Min Dia Max. Dia % Ovality= Max. Dia-Min Dia Max. Dia X100= X100= X100=

0.38 0.45 0.93

Approx.Dia over cond(R)=14.58mm,Y=14.48 & Blue=14.50

Insulation thickness (R)=5.70mm(Approx.),Min Thickness=

5.6

Max. Thickness=

5.8

% Eccentricity =

Max.thick -Min thick Max.thick Max.thick -Min thick Max.thick Max.thick -Min thick Max.thick

Insulation thickness (Y)=5.78mm(Approx.),Min Thickness=

5.7

Max. Thickness=

5.9

% Eccentricity =

Insulation thickness (Bl)=5.72mm(Approx.),Min Thickness=

5.6

Max. Thickness=

5.8

% Eccentricity =

Inner Semicon thickness (R)=0.55mm(Approx.),(Y)=0.50mm(Approx.),(Bl)=0.5 mm(Approx.) Inner Semicon thickness (R)=0.5mm(Approx.),(Y)=0.45mm(Approx.),(Bl)=0.5 mm(Approx.) Copper tape Diemension (R)=40x0.055mm(Approx.),(Y)=40x.06mm(Approx.),(Bl)=39.83x0.05 mm(Approx.) Shrinkage Test(Insulation)= {Length of Specimen before Test(T1)-Length of Specimen after test(T2)}/ Length of Specimen before Test(T1)100 Red Core=(200-199)/200*100=0.5% Yellow Core=(200-198)/200*100=1.0% Blue Core=(199-198)/199*100=0.5% Shrinkage Test(Outer Sheath)= {Length of Specimen before Test(T1)-Length of Specimen after test(T2)}/ Length of Specimen before Test(T1)100 .=100*(195-194)/195= 0.513 Thermal stability Test(Outer Sheath)=Average reading of 3 Specimens=113 Minutes Loss of mass test on outer sheath=(W1-W2)/A mg/cm2 Surface Area(A)=1256+180xt/100 cm2 Thickness of No.1 Specimen=3.65, Surface Area=19.13, So loss of mass=(2.7958-2.7947)/19.13=0.57mg/cm2 Thickness of No.2 Specimen=3.9, Surface Area=19.58, So loss of mass=(2.3127-2.3116)/19.58=0.56mg/cm2 Thickness of No.3 Specimen=3.8, Surface Area=19.40, So loss of mass=(2.8524-2.8515)/19.40=0.46mg/cm2 So actual loss of mass=0.56 mg/cm2 (After discardining min & max. value) Water Absorption test on XLPE Insulation={Avg.(W2-W1)/3}/Surface Area mg/cm2 R1= 0.0008 mg/cm2 W2= 0.0509 R2= 0.0002 mg/cm2 Avg= 0.0004 mg/cm2 W2= 0.0409 R3= 0.0002 mg/cm2 W2= 0.0508 Y1= Y2= Y3= Bl1= Bl2= Bl3= 0.0004 mg/cm2 0.0002 mg/cm2 0.0004 mg/cm2 0.0004 mg/cm2 0.0006 mg/cm2 0.0004 mg/cm2 W2= 0.0576 W2= 0.0471 W2= 0.0567 W2= 0.0830 W2= 0.0760 W2= 0.0792 A= W1= W1= W1= 50 0.0505 0.0408 0.0507

Avg=

0.0003 mg/cm2

W1= 0.0574 W1= 0.0470 W1= 0.0565 W1= 0.0828 W1= 0.0757 W1= 0.0790

Avg=

0.0005 mg/cm2

Hot Deformation Test=(T2-T1)/T2*100 T1= 4.35 T2= 4.6 So %Hot deformation=

5.43

Max. Smoke density rating:-50.78 Avg.reading 18.33 of 3 samples:25.67 34.3 43.3 47 54 57.3 60.3 60 60 60

Acid Gas Generation Test:- 36.5(B-A)*1000/200/m mg/gm % Acid Gas Generation :- = 11.78

A= 8.9

B= 15

m=

0.945 gm

Ageing Test (Tensile & Elongation Test) Of Insulation(Red)


Before Ageing(Red) Area(mm2) Breaking Tensile Strength(N/MM2) WidthxThicknes Load(Kg) Breaking load/Area 6 12 19.62 19.62 6.12 12.5 20.03 6.52 13 19.57 19.57 6.2 12 18.99 Tensile Strength 19.59 %Variation= -2.46 Elongation %Variation= 100.00 Elongation Initial Final 20 110 20 110 20 105 20 105 % Elongation
(Final-Initial)*100/Final

450 450 425 425

450

425 437.5

After Ageing(Red) Area(mm2) Breaking Tensile Strength(N/MM2) WidthxThicknes Load(Kg) Breaking load/Area 6.12 13.4 21.47 6.12 12.5 20.03 6.24 12.8 20.12 20.03 6.63 13.5 19.98 20.12 20.076

Ageing Test (Tensile & Elongation Test) Of Insulation(Yellow)


Before Ageing(Yellow) Area(mm2) Breaking Tensile Strength(N/MM2) WidthxThicknes Load(Kg) Breaking load/Area 6 12 19.62 6.32 11.7 18.16 18.16 6.2 11 17.40 6.32 12.4 19.25 19.25 Tensile Strength 18.70 %Variation= -1.98 Elongation %Variation= 100.00 Elongation Initial Final 20 105 20 105 20 110 20 110 % Elongation
(Final-Initial)*100/Final

425 425 450 450

425

450 437.5

After Ageing(Yellow) Area(mm2) Breaking Tensile Strength(N/MM2) WidthxThicknes Load(Kg) Breaking load/Area 6.2 12 18.99 18.99 6.44 12 18.29 6.40 12.5 19.16 19.16 6.2 12.5 19.78 19.07

Ageing Test (Tensile & Elongation Test) Of Insulation(Blue)


Before Ageing(Blue) Area(mm2) Breaking Tensile Strength(N/MM2) WidthxThicknes Load(Kg) Breaking load/Area 6.32 12.7 19.71 19.71 6.2 12.0 18.99 5.93 12.2 20.20 6.2 12 18.99 18.99 Tensile Strength 19.35 %Variation= -0.18 Elongation %Variation= 100.00 Elongation Initial Final 20 110 20 105 20 110 20 115 % Elongation
(Final-Initial)*100/Final

450 425 450 475

450 450 450

After Ageing(Blue) Area(mm2) Breaking Tensile Strength(N/MM2) WidthxThicknes Load(Kg) Breaking load/Area 6.2 12.2 19.30 19.30 6.4 12.8 19.62 6.40 12.7 19.47 19.47 7 13.5 18.92 19.39

Ageing Test (Tensile & Elongation Test) Of Insulation(Blue)

Before Ageing(Blue) Area(mm2) Breaking Tensile Strength(N/MM2) WidthxThicknes Load(Kg) Breaking load/Area 9.22 20.5 21.81 21.81 9.945 17.0 16.77 16.77 11.02 17.8 15.85 15.85 11.4 18.5 15.92 15.92 Tensile Strength 35.17 %Variation= 54.78 Elongation %Variation= 100.00

Elongation Initial Final 20 55 20 60 20 60 20 60

% Elongation
(Final-Initial)*100/Final

175 200 200 200

200 200 200

After Ageing(Blue) Area(mm2) Breaking Tensile Strength(N/MM2) WidthxThicknes Load(Kg) Breaking load/Area 9.75 15.9 16.00 11.6 18.8 15.90 15.90 10.97 17.8 15.91 15.91 12.4 20 15.82 15.91

Size:-1Cx300 Sqmm 6.35/11 kv(E)(A2XWaY)

Dt. Of Completion of Testing:24.01.06

Ageing Test (Tensile & Elongation Test) Of Insulation(Natural)


Before Ageing(Insulation) Area(mm2) Breaking Tensile Strength(N/MM2) WidthxThicknes Load(Kg) Breaking load/Area 5.33 11 20.24 6.12 12.5 20.03 20.03 5.93 11.1 18.38 8.19 16.5 19.76 19.76 Tensile Strength 19.90 %Variation= 7.55 Elongation %Variation= 100.00 Elongation Initial Final 20 120 20 110 20 105 20 95 % Elongation
(Final-Initial)*100/Final

500 450 425 375

450 425 437.5

After Ageing(Insulation) Area(mm2) Breaking Tensile Strength(N/MM2) WidthxThicknes Load(Kg) Breaking load/Area 6.52 9.6 14.45 6.44 13.5 20.58 6.24 10.6 16.66 16.66 7.02 14.4 20.12 20.12 18.39

Ageing Test (Tensile & Elongation Test) Of Insulation(Outer Sheath)


Before Ageing(O/Sh) Area(mm2) Breaking Tensile Strength(N/MM2) WidthxThicknes Load(Kg) Breaking load/Area 6.8 12.5 18.03 6.63 12.0 17.76 17.76 6.24 11 17.29 17.29 6.32 11 17.07 Tensile Strength 17.52 %Variation= 6.01 Elongation %Variation= 100.00 Elongation Initial Final 20 70 20 70 20 65 20 65 % Elongation
(Final-Initial)*100/Final

250 250 225 225

250 225 238

After Ageing(O/Sh) Area(mm2) Breaking Tensile Strength(N/MM2) WidthxThicknes Load(Kg) Breaking load/Area 6.72 12 17.53 6.55 11 16.49 16.49 5.40 8.6 15.62 6.32 10.6 16.45 16.45 16.47

Water Absorption test on XLPE Insulation={Avg.(W2-W1)/3}/Surface Area mg/cm2 N1= 0.0026 mg/cm2 W2= 0.0793 N2= 0.0238 mg/cm2 Avg= 0.009 mg/cm2 W2= 0.0807 N3= 0.0004 mg/cm2 W2= 0.0813

A= W1= W1= W1=

50 0.0780 0.0688 0.0811

Max. Smoke density rating:-50.78 Avg.reading of 3 samples:7 9 13.67 20 28.67 34 37.67 41.67 43.67 46.67

Acid Gas Generation Test:- 36.5(B-A)*1000/200/m mg/gm % Acid Gas Generation :- = 13.06

A= 8.7

B= 15.3

m=

0.922

Eccentricity =(Max thic-Min Thick)/Maxthick*100 4.878

Ovality = (Max Odof core -Min Od of Core)/MaxOD of core*100 0.519

VR

=2*(22/7)*L*R*D108 Loge D/d

L= Length R=Measure of Resistance D= Overall Dia d= Conductor Dia Example:1Cx150 3.3/3.3 KV Sq.mm Conductor L= Length R=Measure of Resistance D= Overall Dia d= Conductor Dia

3.5 60x104 19.0 14.5

VR

x.thick -Min thick Max.thick

X100=

x.thick -Min thick Max.thick

X100=

x.thick -Min thick Max.thick

X100=

59.3

58.67

Elongation Initial Final 20 115 20 110 20 110 20 105

Elongation Initial Final 20 110 20 110 20 105 20 110

Elongation Initial Final 20 110 20 110 20 115 20 110

Elongation Initial Final 20 60 20 55 20 60 20 55

Elongation Initial Final 20 110 20 120 20 110 20 120

Elongation Initial Final 20 70 20 65 20 70 20 70

48

48.67

gm

KRISHNA ELECTRICAL INDUSTRIES LTD. 30-B, Industrial Area Banmore (M.P.) ROUTINE TEST CERTIFICATE Reference Specification IS 7098(Pt-II)/1985

Page 12 of 67

Customer:- National Thermal Power Corporation,Noida


NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005 Size:-1CX300 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Natural 1 2 3 4 5 6 7 A-1065 A-1066 A-1067 A-1068 A-1069 A-1070 A-1071 Natural Natural Natural Natural Natural Natural Natural
Conductor High Voltage test at Resistance at 28 kv ac for 20C in ohms/kms 5 minutes

Dt. Of testing:-11 & 12.05.06

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)


Partial Discharge test at 1.5 Uo 20 Pc (Max) <5Pc <5Pc <5Pc <5Pc -<5Pc <5Pc

0.100(MAX) 0.0927 0.0918 0.0918 0.0936 0.0946 0.0926 0.0985

No Break down observed Withstood Withstood Withstood Withstood Not Withstood Withstood Withstood

Size:-1CX150 Sq.mm 3.3/3.3 KV (A2XY)


S.no Drum no. Core Identification Natural 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1185 1186 1187 1188 1189 1190 1191 1192 1241 1242 1243 1244 1245 1246 Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural
Conductor Resistance at 20C in ohms/kms

High Voltage test at 10 kv ac for 5 minutes


No Break down observed

0.206(MAX) 0.187 0.188 0.187 0.191 0.185 0.183 0.188 0.184 0.188 0.185 0.186 0.186 0.187 0.185

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

15 16 17 18 19 20 20 DRUMS

1247 1248 1249 1250 1003 1004

Natural Natural Natural Natural Natural Natural

0.186 0.186 0.185 0.185 0.182 0.185

Withstood Withstood Withstood Withstood Withstood Withstood

Page 13 of 67

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- National Thermal Power Corporation,Noida

Dt. Of testing:-24 & 25.05.06

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 6.35/11 KV (A2XWAY)
S.no Drum no. Core Identification Natural 1 2 3 4 5 6 7 8 9 10 11 12 13 13DRUMS A-1118 A-1119 A-1120 A-1121 A-1122 A-1123 A-1124 A-1125 A-1126 A-1127 A-1128 A-1129 A-1130 Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0946 0.0940 0.0945 0.0953 0.0919 0.0940 0.0933 0.0932 0.0949 0.0926 0.0933 0.0937 0.0943 High Voltage test at 17 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Partial Discharge test at 1.5 Uo 20 Pc (Max) <5Pc <5Pc <5Pc <5Pc <5PC <5Pc <5Pc <5Pc <5Pc <5Pc <5Pc <5Pc <5Pc

Head(QA&I)

Page 14 of 67

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- National Thermal Power Corporation,Noida


Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) Dt. Of testing:-24 & 25.05.06

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX150 Sq.mm 11/11 KV (A2XY)
S.no Drum no. Core Identification Natural 1 A-1172 R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y Conductor Resistance at 20C in ohms/kms 0.206(MAX) 0.182 0.182 0.182 0.186 0.186 0.186 0.183 0.183 0.185 0.181 0.181 0.182 0.188 0.185 0.185 0.182 0.184 0.182 0.185 0.187 0.185 0.184 0.182 High Voltage test at 28 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Partial Discharge test at 1.5 Uo 20 Pc (Max) 6 6 6 6 6 6 5 5 5 8 7 8 6 6 6 6 6 6 6 6 6 6 6

A-1174

A-1175

A-1176

A-1177

A-1178

A-1179

A-1180

A-1181

B R Y B

0.182 0.184 0.183 0.183

Withstood Withstood Withstood Withstood

6 6 6 6

Page 15 of 67

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- National Thermal Power Corporation,Noida


Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) Dt. Of testing:-24 & 25.05.06

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-1CX150 Sq.mm 6.35/11 KV (A2XY)
S.no Drum no. Core Identification Natural 1 2 3 3 DRUMS Head(QA&I) A-1108 A-1109 A-1173 Natural Natural Natural Conductor Resistance at 20C in ohms/kms 0.206(MAX) 0.187 0.187 0.185 High Voltage test at 17 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Partial Discharge test at 1.5 Uo 20 Pc (Max) <5Pc <5Pc <5Pc

LOT-5

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I (3X660 mw) Dt. Of testing:-04,05,13,14,19 & 20.07.06

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX150 Sq.mm 11/11 KV (A2XY)
S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206(MAX) 1 A-1184 R Y B 0.189 0.189 0.189 High Voltage test at 28 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Partial Discharge test at 1.5 Uo 20 Pc (Max) 3 3 2

A-1185

A-1227

A-1228

A-1246

A-1247

A-1263

A-1264

A-1265

10

A-1266

11

A-1267

12

A-1268

13

A-1269

14

A-1270

15

A-1271

16

A-1286

R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B

0.192 0.192 0.192 NIL 0.188 0.187 0.188 0.186 0.186 0.191 0.189 0.187 0.191 0.191 0.189 0.187 0.184 0.182 0.182 0.186 0.184 0.191 0.194 0.194 0.182 0.184 0.184 0.186 0.187 0.187 0.187 0.185 0.188 0.185 0.187 0.187 0.187 0.187 0.191 0.189 0.192 0.190 0.190

Withstood Withstood Withstood HV FAIL Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Head(QA&I)

2 2 4 .---2 2 2 2 2 2 3 2 2 2 2 2 6 6 6 2 2 2 2 2 2 2 4 2 4 2 3 2 4 4 8 12 8 2 2 2 2 2 2

Page 16 of 67

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) Dt. Of testing:-13 & 14.07.06

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX95 Sq.mm 3.3/3.3 KV (A2XY)
S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms High Voltage test at 10 kv ac for 5 minutes

0.320 (MAX) 1 A-1275 R Y B R Y B R Y B 0.292 0.296 0.292 0.291 0.296 0.291 0.296 0.298 0.296

A-1276

A-1277

No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Head(QA&I)

Page 17 of 67

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) Dt. Of testing:-13 & 14.07.06

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX150 Sq.mm 3.3/3.3 KV (A2XY)
S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206 (MAX) 1 A-1296 R Y B R Y B 0.185 0.187 0.187 0.181 0.187 0.188 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Head(QA&I)

A-1297

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Dt. Of testing:-13 & 14.07.06

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY)
S.no Drum no. Core Identification Natural 1 2 3 4 A-1260 A-1261 A-1262 A-1278 Natural Natural Natural Natural Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0957 0.0926 0.0926 0.0936 High Voltage test at 28 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Partial Discharge test at 1.5 Uo 20 Pc (Max) 2 2 2 2

5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A-1279 A-1280 A-1281 A-1282 A-1283 A-1284 A-1285 A-1287 A-1288 A-1289 A-1290 A-1291 A-1292 A-1293 A-1294 A-1295

Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural

0.0945 0.0927 0.0935 0.0944 0.0937 0.0954 0.0973 0.0942 0.0940 0.0935 0.0967 0.0948 0.0948 0.0952 0.0934 0.0936

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

2 2 4 2 2 2 2 2 3 3 3 3 2 2 2 2

Page 18 of 67

Head(QA&I)

Lot-6

Page 19 of 67

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Dt. Of testing:- 26 & 27.07.06

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY)
S.no Drum no. Core Identification Natural 1 2 3 4 5 6 7 8 9 A-1322 A-1323 A-1333 A-1334 A-1335 A-1336 A-1337 A-1338 A-1339 Natural Natural Natural Natural Natural Natural Natural Natural Natural Conductor High Voltage test Partial Resistance at at 28 kv ac for 5 Discharge test 20C in minutes at 1.5 Uo ohms/kms No Break down 0.100(MAX) 20 Pc (Max) observed 0.0944 Withstood 0.0954 0.0973 0.0961 0.0936 0.0952 0.0963 0.0935 0.0945 Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX150 Sq.mm 11/11 KV (A2XY)
S.no Drum no. Core Identification

Dt. Of testing:- 26 & 27.07.06


Partial Discharge test at 1.5 Uo

Conductor High Voltage test at Resistance at 28 kv ac for 5 minutes 20C in ohms/kms 0.206(MAX) No Break down observed

20 Pc (Max)

A-1312

A-1313

A-1314

R Y B R Y B R Y B

0.188 0.190 0.192 0.190 0.194 0.186 0.185 0.188 0.186

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

3 2 3 2 2 2 2 2 2

A-1315

A-1316

A-1317

A-1318

A-1319

A-1320

10

A-1321

R Y B R Y B R Y B R Y B R Y B R Y B R Y B

0.192 0.190 0.194 0.188 0.190 0.190 0.189 0.191 0.185 0.189 0.187 0.187 0.191 0.191 0.187 0.189 0.189 0.189 0.189 0.189 0.193

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

2 3 7 2 2 2 2 2 4 6 2 2 2 2 4 5 10 10 2 4 2

Page 20 of 67

Head(QA&I) 11.08.06 Lot 8

KRISHNA ELECTRICAL INDUSTRIES LTD. 30-B, Industrial Area Banmore (M.P.) ROUTINE TEST CERTIFICATE
Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) Dt.of testing:-10 & 11-08.06

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-1CX150 Sq.mm 3.3/3.3 KV (A2XY)
S.no Drum no. Core Identification Natural 1 2 3 4 5 6 7 8 9 A-1340 A-1341 A-1342 A-1343 A-1344 A-1345 A-1346 A-1347 A-1348 Natural Natural Natural Natural Natural Natural Natural Natural Natural Conductor Resistance at 20C in ohms/kms 0.206(MAX) 0.183 0.186 0.186 0.184 0.184 0.184 0.187 0.187 0.185 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

A-1349 A-1350 A-1351 A-1352 A-1353 A-1354 A-1355 A-1356 A-1357 A-1381 A-1382 A-1383 A-1384 A-1385 A-1386 A-1387

Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural

0.184 0.185 0.186 0.187 0.187 0.188 0.186 0.185 0.189 0.189 0.186 0.188 0.189 0.187 0.186 0.185

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

Page 21 of 67

KRISHNA ELECTRICAL INDUSTRIES LTD. 30-B, Industrial Area Banmore (M.P.) ROUTINE TEST CERTIFICATE
Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) Dt.of testing:-10 & 11-08.06

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX95 Sq.mm 3.3/3.3 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.320 (MAX) 1 A-1362 R Y B 0.291 0.291 0.289 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood

A-1363

A-1364

A-1365

A-1366

A-1367

A-1368

A-1369

A-1370

R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B

0.285 0.288 0.288 0.293 0.293 0.295 0.288 0.290 0.292 0.293 0.289 0.289 0.288 0.292 0.288 0.288 0.288 0.292 0.292 0.291 0.292 0.292 0.292 0.294

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Head(QA&I)

Page 22 of 67

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I (3X660 mw) Dt.of testing:-10,11 & 17-08.06

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX150 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206(MAX) 1 A-1358 R Y B R Y B R Y B R Y B R 0.188 0.186 0.188 0.187 0.187 0.186 0.186 0.184 0.188 0.186 0.187 0.189 0.187 High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 2 2 2 2 2 2 2 2 2 2 2

A-1359

A-1360

A-1361

A-1389

A-1390

A-1391

A-1392

A-1393

10

A-1394

11

A-1395

Y B R Y B R Y B R Y B R Y B R Y B R Y B

0.187 0.187 0.189 0.189 0.187 0.189 0.189 0.189 0.189 0.189 0.189 0.190 0.190 0.188 0.188 0.190 0.190 0.190 0.188 0.188

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Page 23 of 67

Head(QA&I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Dt.of testing:-10 & 11-08.06

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0937 0.0933 0.0953 0.0938 0.0926 0.0947 0.0929 0.0938 High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 2 2 2 2 2 2

Natural 1 2 3 4 5 6 7 8 A-1371 A-1372 A-1373 A-1376 A-1377 A-1378 A-1379 A-1380 Natural Natural Natural Natural Natural Natural Natural Natural

Page 24 of 67

Head(QA&I)
LOT - 9

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Dt. Of testing:-30.08.06

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 6.35/11 KV (A2XWaY)
S.no Drum no. Core Identification Natural 1 2 A-1425 A-1426 Natural Natural Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0952 0.0945 High Voltage test at 17 kv ac for 5 minutes No Break down observed Withstood Withstood Partial Discharge test at 1.5 Uo 20 Pc (Max) 2 8

Head(QA&I)

30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Dt. Of testing:-30.08.06

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 3.3/3.3 KV (A2XY)
S.no Drum no. Core Identification Natural 1 2 3 4 5 6 7 8 9 A-1063 A-1064 A-1407 A-1408 A-1427 A-1428 A-1429 A-1430 A-1431 Natural Natural Natural Natural Natural Natural Natural Natural Natural Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0967 0.0972 0.0939 0.0943 0.0919 0.0943 0.0932 0.0921 0.0933 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

Page 25 of 67 10 A-1445 Natural 0.0979 Withstood

Head(QA&I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) Dt.of testing:-30.08.06

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX95 Sq.mm 3.3/3.3 KV (A2XY) S.no Drum no.
Core Identification

Conductor Resistance at 20C in ohms/kms 0.320 (MAX) 0.297 0.291 0.291 0.292 0.291 0.291 0.292 0.301 0.292 0.292 0.294 0.292 0.296 0.296 0.298 0.292 0.290 0.296 0.293 0.293 0.293 0.296

High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

R,Y, & Bl 1 A-1432 R Y B R Y B R Y B R Y B R Y B R Y B R Y B R

A-1433

A-1434

A-1435

A-1436

A-1437

A-1438

A-1446

A-1447

10

A-1448

Y B R Y B R Y B

0.296 0.294 0.296 0.296 0.293 0.296 0.298 0.294

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Head(QA&I)

Page 26 of 67

LOT - 10

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

Page 27 of 67

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)

Dt.of testing:-13 & 14.09.06

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX150 Sq.mm 3.3/3.3 KV (A2XY)
S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206 (MAX) 1 A-1374 R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R 0.185 0.185 0.189 0.187 0.189 0.189 0.189 0.189 0.189 0.186 0.190 0.191 0.187 0.189 0.191 0.183 0.185 0.185 0.188 0.190 0.190 0.189 0.192 0.188 0.186 0.186 0.186 0.188 0.188 0.187 0.189 0.189 0.189 0.191 0.191 0.191 0.185 0.187 0.185 0.188 0.192 0.188 0.188 0.189 0.190 0.185 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

A-1375

A-1450

A-1451

A-1452

A-1454

A-1455

A-1456

A-1457

10

A-1458

11

A-1459

12

A-1460

13

A-1461

14

A-1466

15

A-1467

16

A-1468

17

A-1469

18

A-1470

19

A-1471

20

A-1472

Y B R Y B R Y B R Y B R Y B

0.189 0.190 0.189 0.191 0.188 0.190 0.189 0.192 0.190 0.190 0.190 0.188 0.188 0.190

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

Page 28 of 67

Head(QA&I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

Page 29 of 67

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Dt.of testing:-13 & 14.09.06

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0953 0.0933 0.0955 0.0964 0.0950 0.0967 0.0963 0.0964 0.0966 0.0969 High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 3 3 2 2 2 2 2 3 3 2

Natural 1 2 3 4 5 6 7 8 9 10 A-1473 A-1474 A-1475 A-1476 A-1477 A-1478 A-1479 A-1480 A-1481 A-1482 Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural

Head(QA&I)

LOT-11

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I (3X660 mw)

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX150 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms
Dt.of testing:- 05 & 06.10.06

High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo

Page 30 of 67

0.206(MAX) 1 A-1575 R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B 0.181 0.182 0.181 0.177 0.178 0.179 0.181 0.182 0.183 0.178 0.179 0.180 0.180 0.181 0.180 0.179 0.179 0.180 0.180 0.181 0.179 0.182 0.182 0.183 0.182 0.179 0.181 0.182 0.183 0.183 0.184 0.184 0.183 0.180 0.182 0.185 0.181 0.178 0.180 0.178 0.181 0.181 0.176 0.176 0.179

No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Head(QA&I)

20 Pc (Max) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

A-1576

A-1577

A-1578

A-1579

A-1580

A-1581

A-1589

A-1590

10

A-1591

11

A-1592

12

A-1593

13

A-1594

14

A-1595

15

A-1596

Lot 13

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Page 31 of 67

Customer:- N T P C, Noida

Dt.of testing:-12 & 13-12.06

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0909 0.0918 0.0901 0.0892 0.0898 0.0908 0.0904 0.0895 0.0892 0.0882 0.0882 0.0919 0.0894 0.0890 0.0900 0.0880 0.0880 0.0880 0.0870 0.0900 0.0870 High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 2 2 2 2 2 2 4 2 2 2 2 2 2 2 2 2 10 2 2

Natural 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 A-1768 A-1769 A-1770 A-1771 A-1772 A-1773 A-1774 A-1775 A-1776 A-1777 A-1778 A-1779 A-1780-A A-1780-B A-1825 A-1826 A-1827 A-1828 A-1829 A-1830 A-1831 Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural

Page 32 of 67

FOR NTPC LTD

P.V.Saxena/V.K Gupta/P.Sahoo Chief Manager/Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD. 30-B, Industrial Area Banmore (M.P.) ROUTINE TEST CERTIFICATE
Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
Dt.of testing:-12 & 13-12.06

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-1CX150 Sq.mm 3.3/3.3 KV (A2XY)
S.no Drum no. Core Identification Natural 1 2 3 4 5 A-1748 A-1749 A-1750 A-1751 A-1752 Natural Natural Natural Natural Natural Conductor Resistance at 20C in ohms/kms 0.206(MAX) 0.177 0.178 0.182 0.176 0.178 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood

FOR NTPC LTD

P.V.Saxena/V.K Gupta/P.Sahoo Chief Manager/Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I (3X660 mw)

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX150 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206(MAX) 1 A-1764 R Y B R Y B R Y B 0.182 0.179 0.184 0.181 0.181 0.182 0.182 0.182 0.182
Dt.of testing:-28.12.06 ,8.01,9.01& 10.01.07

High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 3 3 3 2 6 2 2 2 2

A-1765

A-1766

A-1767

A-1865

A-1866

A-1867

A-1868

A-1869

10

A-1870

11

A-1871

12

A-1880

13

A-1881

14

A-1882

15

A-1883

R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B

0.180 0.180 0.183 0.184 0.177 0.186 0.185 0.184 0.184 0.179 0.179 0.183 0.176 0.180 0.180 0.175 0.180 0.178 0.176 0.176 0.179 0.181 0.181 0.183 0.179 0.186 0.181 0.177 0.184 0.181 0.179 0.181 0.181 0.178 0.178 0.182

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

2 2 3 3 3 3 2 2 2 2 2 2 3 3 3 2 2 2 3 3 3 2 2 2 2 2 2 2 2 2 2 2 2 3 2 2

Page 33 of 67

FOR NTPC LTD

P.V.Saxena/V.K Gupta/P.Sahoo Chief Manager/Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0878
Dt.of testing:-28.12.06 ,8.01,9.01& 10.01.07

High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood 20 Pc (Max) 2

Natural 1 A-1872 Natural

Page 34 of 67

2 3 4 5 6 7

A-1873 A-1874 A-1875 A-1876 A-1877 A-1879

Natural Natural Natural Natural Natural Natural

0.0885 0.0888 0.0894 0.0884 0.0872 0.0896

Withstood Withstood Withstood Withstood Withstood Withstood

2 2 2 2 2 2

FOR NTPC LTD

P.V.Saxena/V.K Gupta/P.Sahoo Chief Manager/Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX150 Sq.mm 3.3/3.3 KV (A2XY)
S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206 (MAX) 1 A-1878 R Y B 0.178 0.179 0.180 Dt.of testing:-28.12.06 ,8.01,9.01& 10.01.07 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood

FOR NTPC LTD

P.V.Saxena/V.K Gupta/P.Sahoo Chief Manager/Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD. 30-B, Industrial Area Banmore (M.P.) ROUTINE TEST CERTIFICATE
Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-1CX150 Sq.mm 3.3/3.3 KV (A2XY)
S.no Drum no. Core Identification Natural 1 A-1884 Natural Conductor Resistance at 20C in ohms/kms 0.206(MAX) 0.177 Dt.of testing:-28.12.06 ,8.01,9.01& 10.01.07 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood

FOR NTPC LTD

P.V.Saxena/V.K Gupta Chief Manager/Manager(QA & I)

Page 35 of 67

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0892 0.0878 0.0885 0.0900 0.0910 0.0892 0.0902 0.0896 0.0865 0.0883 0.0902 0.0884 0.0883 0.0901 0.0882 0.0883
Dt.of testing:-18 & 19.01.07

High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 5 2 2 2 2 2 2 2 2 2 2 2 2 6

Natural 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A-1919 A-1920 A-1921 A-1933 A-1934 A-1935 A-1936 A-1937 A-1938 A-1939 A-1940 A-1941 A-1942 A-1943 A-1944 A-1945

Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural

FOR NTPC LTD

P.V.Saxena/V.K Gupta Chief Manager/Manager(QA & I)

Page 36 of 67

LOT-16

08.02.07

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985 Dt.of testing:-08,09.02.07& 15.03.07 Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0879 0.0887 0.0875 0.0880 0.0891 0.0874 0.0864 0.0869 High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 4 2 2 2 2 2

Natural 1 2 3 4 5 6 7 8 A-2018 A-2019 A-2020 A-2021 A-2022 A-2023 A-2024 A-2025 Natural Natural Natural Natural Natural Natural Natural Natural

FOR NTPC LTD

For Krishna Electrical Industries Ltd (Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985 Dt.of testing:-08,09.02.07& 15.03.07 Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)

Page 37 of 67

NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005


Size:-3CX150 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206(MAX) 1 A-2063 R Y B R Y B 0.179 0.180 0.176 0.179 0.180 0.177 High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 3 3 3 8 3 3

A-2064

FOR NTPC LTD

For Krishna Electrical Industries Ltd (Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985 Dt.of testing:-08,09.02.07& 15.03.07 Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 3.3/3.3 KV (A2XY)
S.no Drum no. Core Identification Natural 1 2 3 A-2065 A-2066 A-2067 Natural Natural Natural Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0802 0.0889 0.0903 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood

FOR NTPC LTD

For Krishna Electrical Industries Ltd (Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985 Dt.of testing:-08,09.02.07& 15.03.07 Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005

Size:-3CX150 Sq.mm 3.3/3.3 KV (A2XY)


S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206 (MAX) 1 A-2061 R Y B R Y B 0.177 0.179 0.178 0.177 0.178 0.178 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood

Page 38 of 67

A-2062

FOR NTPC LTD

For Krishna Electrical Industries Ltd (Vinod Gupta) Manager(QA & I)

LOT-17(22.0307)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985 Dt.of testing:-15,16 & 22.03.07 Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 3.3/3.3 KV (A2XY)
S.no Drum no. Core Identification Natural 1 2 A-2135 A-2136 Natural Natural Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.088 0.089 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood

FOR NTPC LTD

For Krishna Electrical Industries Ltd

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985 Dt.of testing:-15,16 & 22.03.07 Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-3CX150 Sq.mm 11/11 KV (A2XY)

S.no

Drum no.

Core Identification

Conductor Resistance at 20C in ohms/kms 0.206(MAX)

Page 39 of 67

High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 2 4 2 2 3 3 2 2 3 3 3 3 3 2 2 2 3 2 3 2 2 2 2 2 2 3 2 2 3 3 3 4 2 2

A-2125

A-2126

A-2127

A-2128

A-2129

A-2130

A-2131

A-2132

A-2133

10

A-2134

11

A-2137

12

A-2138

R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B

0.182 0.193 0.181 0.167 0.166 0.165 0.181 0.181 0.181 0.177 0.176 0.178 0.177 0.183 0.179 0.167 0.165 0.166 0.165 0.166 0.166 0.163 0.166 0.166 0.181 0.181 0.180 0.163 0.165 0.166 0.165 0.165 0.165 0.181 0.181 0.181

FOR NTPC LTD

For Krishna Electrical Industries Ltd (Vinod Gupta) Manager(QA & I)

LOT -18 (09.04.07)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985 Dt.of testing:-19 & 20.04.07 Customer:- N T P C, Noida

Page 40 of 67

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-3CX150 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206(MAX) 1 A-3001 R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B 0.182 0.178 0.179 0.172 0.178 0.176 0.176 0.179 0.178 0.177 0.181 0.179 0.179 0.179 0.177 0.176 0.177 0.175 0.177 0.179 0.182 0.177 0.176 0.177 0.182 0.181 0.178 0.175 0.175 0.176 0.180 0.180 0.179 0.176 0.173 0.176 0.178 0.177 0.177 0.177 0.177 0.178 High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 3 3 3 2 2 2 3 3 3 2 2 2 2 3 2 3 3 3 3 2 3 2 2 3 3 3 3 3 3 2 2 2 2 2 2 2 2 3 2 2 2 2

A-3002

A-3003

A-3004

A-3005

A-3006

A-3007

A-3008

A-3009

10

A-3019

11

A-3020

12

A-3021

13

A-3022

14

A-3033

15

A-3034

16

A-3035

17

A-3036

18

A-3037

19

A-3038

20

A-3039

21

A-3040

R Y B R Y B R Y B R Y B R Y B R Y B R Y B

0.182 0.180 0.180 0.176 0.178 0.174 0.183 0.178 0.174 0.179 0.177 0.176 0.178 0.179 0.176 0.174 0.176 0.175 0.176 0.175 0.173

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

3 2 2 3 4 3 3 3 2 3 2 2 3 2 2 3 3 2 3 3 3

Page 41 of 67

FOR NTPC LTD

For Krishna Electrical Industries Ltd

(N.K. VYAS) Sr.Manager(QA)

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985 Dt.of testing:-19 & 20.04.07 Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY) S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0871 0.0873 0.0887 0.0879 0.0880 0.0911 High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 2 2 2 2

Natural 1 2 3 4 5 6 A-3023 A-3024 A-3025 A-3026 A-3027 A-3028 Natural Natural Natural Natural Natural Natural

Page 42 of 67

FOR NTPC LTD

For Krishna Electrical Industries Ltd

(N.K. VYAS) Sr.Manager(QA)

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985 Dt.of testing:-19 & 20.04.07 Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005
Size:-1CX150 Sq.mm 6.35/11 KV (A2XWaY) Conductor Core Resistance at S.no Drum no. Identification 20C in ohms/kms Natural 1 2 3 4 A-3029 A-3030 A-3031 A-3032 Natural Natural Natural Natural 0.206(MAX) 0.177 0.176 0.178 0.178 High Voltage test at 17 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Partial Discharge test at 1.5 Uo 20 Pc (Max) 2 2 2 2

FOR NTPC LTD

For Krishna Electrical Industries Ltd

(N.K. VYAS) Sr.Manager(QA)

(Vinod Gupta) Manager(QA & I)

30.04.07

LOT-19&20

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Page 43 of 67

Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)


NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY) Cable Dt. of Testing:-10,11.05.07&17,18.05.07 Conductor High Voltage Partial Core Resistance S.no Drum no. test at 28 kv ac Discharge test Identification at 20C in for 5 minutes at 1.5 Uo ohms/kms Natural 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 A-3049 A-3050 A-3051 A-3085 A-3086 A-3087 A-3088 A-3089 A-3090 A-3091 A-3092 A-3093 A-3094 A-3095 A-3096 A-3097 A-3098 A-3099 A-3100 A-3101 A-3106 Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural 0.100(MAX) 0.087 0.087 0.086 0.088 0.087 0.087 0.087 0.088 0.086 0.088 0.087 0.087 0.088 --0.086 0.086 0.087 0.086 0.086 0.086 0.087 No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Fail Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 9 2 2 3 2 3 3 10 2 3 2 2 --2 2 4 2 6 2 2

Page 44 of 67

22

A-3107

Natural

0.086

Withstood

FOR NTPC LTD

For Krishna Electrical Industries Ltd

(Vinod Gupta) Manager(QA & I)

08.05.07

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)


NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005
Size:-1CX300 Sq.mm 6.35/11 KV (A2XWaY) Cable

S.no

Drum no.

Dt. of Testing:-10,11.05.07&17,18.05.07 Conductor High Voltage Partial Core Resistance test at 17 kv ac Discharge test Identification at 20C in for 5 minutes at 1.5 Uo ohms/kms Natural 0.100(MAX) 0.087 0.086 0.086 0.084 0.087 0.086 0.086 0.086 0.087 0.087 0.088 0.086 0.087 No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 2 2 2 2 2 2 2 2 2 2 2

1 2 3 4 5 6 7 8 9 10 11 12 13

A-3120 A-3121 A-3122 A-3123 A-3124 A-3125 A-3126 A-3127 A-3128 A-3129 A-3130 A-3131 A-3132

Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural

Page 45 of 67

14

A-3133

Natural

0.086

Withstood

FOR NTPC LTD

For Krishna Electrical Industries Ltd

(Vinod Gupta) Manager(QA & I)

LOT-21

25.05.07

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)


NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY) Cable Dt. Of Testing: 31.05,01.06.2007&06,07,08.06.2007 Conductor High Voltage Partial Core Resistance S.no Drum no. test at 28 kv ac Discharge test Identification at 20C in for 5 minutes at 1.5 Uo ohms/kms Natural 1 2 3 4 5 6 7 8 9 10 11 12 13 A-3178 A-3179 A-3180 A-3181 A-3182 A-3183 A-3184 A-3185 A-3186 A-3187 A-3188 A-3189 A-3190 Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural 0.100(MAX) 0.086 0.085 0.086 0.087 0.087 0.087 0.087 0.088 0.088 0.087 0.087 0.087 0.086 No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 2 5 2 2 2 2 2 2 2 2 10

FOR NTPC LTD

For Krishna Electrical Industries Ltd

Page 46 of 67

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)


NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005
Size:-3CX150 Sq.mm 11/11 KV (A2XY) Cable Dt. Of Testing: 31.05,01.06.2007&06,07,08.06.2007 Conductor Core Resistance S.no Drum no. Identification at 20C in ohms/kms 0.206(MAX) 1 A-3172 R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y 0.176 0.179 0.177 0.180 0.180 0.178 0.175 0.175 0.178 0.180 0.178 0.176 0.174 0.176 0.176 0.179 0.175 0.177 0.173 0.175 0.177 0.173 0.177 0.175 0.179 0.179 0.179 0.187 0.182 0.183 0.177 0.177

High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 8 6

A-3173

A-3174

A-3175

A-3176

A-3177

A-3191

A-3192

A-3193

10

A-3194

11

A-3195

12

A-3196

13

A-3197

14

A-3198

15

A-3199

16

A-3200

17

A-3201

18

A-3202

19

A-3206

20

A-3207

21

A-3208

22

A-3209

23

A-3210

24

A-3211

25

A-3212

B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B

0.177 0.177 0.177 0.175 0.180 0.180 0.180 0.177 0.177 0.179 0.177 0.177 0.177 0.175 0.175 0.175 0.178 0.182 0.176 0.178 0.178 0.180 0.177 0.177 0.177 0.178 0.178 0.178 0.182 0.179 0.184 0.176 0.183 0.179 0.176 0.176 0.178 0.178 0.178 0.180 0.175 0.175 0.180

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood
Outer Sheath damaged during Rewinding

Withstood Withstood Withstood

2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 2 2 2 2 2 3 2 2 2 2 3 2 2 2 2 2 2 2 2 2 2 2 2 3

Page 47 of 67

FOR NTPC LTD

For Krishna Electrical Industries Ltd

(Vinod Gupta) Manager(QA & I)

LOT-22

22.06.07

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Page 48 of 67

Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)


NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY) Cable

Dt. Of Testing:21 & 22.06.07


S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0870 0.0856 0.0859 0.0870 0.0861 High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 2 2 4

Natural 1 2 3 4 5 A-3260 A-3261 A-3262 A-3263 A-3264 Natural Natural Natural Natural Natural

FOR NTPC LTD

For Krishna Electrical Industries Ltd

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)


NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005
Size:-3CX150 Sq.mm 11/11 KV (A2XY) Cable

Dt. Of Testing:21 & 22.06.07


S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206(MAX) 1 A-3224 R Y B R Y B R Y B 0.176 0.177 0.180 0.179 0.179 0.175 0.176 0.179 0.176 High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 2 5 2 19 2 2 2

A-3225

A-3226

A-3258

A-3259

R Y B R Y B

0.178 0.178 0.180 0.178 0.178 0.181

Withstood Withstood Withstood Withstood Withstood Withstood

2 2 2 2 2 2

Page 49 of 67

FOR NTPC LTD

For Krishna Electrical Industries Ltd

(Vinod Gupta) Manager(QA & I)

LOT-23

31.07.07

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-3CX150 Sq.mm 3.3/3.3 KV (A2XY) Cable

Dt. of Testing:- 2& 3.08.07


S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206 (MAX) 1 A-3422 R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B 0.178 0.179 0.179 0.177 0.179 0.179 0.181 0.180 0.180 0.182 0.181 0.181 0.179 0.178 0.180 0.176 0.178 0.179 0.179 0.180 0.180 0.178 0.179 0.177 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

A-3423

A-3424

A-3425

A-3426

A-3427

A-3428

A-3429

FOR NTPC LTD

For Krishna Electrical Industries Ltd

Page 50 of 67 (Rajesh Sharma) Sr. Manager (IS) NTPC, Noida (Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-1CX150 Sq.mm 3.3/3.3 KV (A2XY) Cable

Dt. of Testing:- 2& 3.08.07


S.no Drum no. Core Identification Natural 1 2 3 4 5 6 7 8 9 10 11 12 A-3430 A-3431 A-3432 A-3433 A-3434 A-3435 A-3436 A-3437 A-3438 A-3439 A-3440 A-3441 Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural
Conductor Resistance at 20C in ohms/kms

High Voltage test at 10 kv ac for 5 minutes


No Break down observed

0.206(MAX) 0.178 0.177 0.175 0.176 0.175 0.176 0.177 0.180 0.179 0.179 0.181 0.177

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

FOR NTPC LTD

For Krishna Electrical Industries Ltd

(Rajesh Sharma) Sr. Manager (IS) NTPC, Noida

(Vinod Gupta) Manager(QA & I)

LOT-24

29.08.07

HOLD

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE

Reference Specification IS 7098(Pt-II)/1985

Page 51 of 67

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-3CX150 Sq.mm 3.3/3.3 KV (A2XY) Cable

Dt. of Testing:- 29.08.07 & 30.08.07


S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206 (MAX) 1 A-3610 R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R 0.181 0.179 0.179 0.178 0.180 0.179 0.181 0.184 0.184 0.179 0.181 0.182 0.181 0.178 0.181 0.180 0.179 0.181 0.177 0.181 0.179 0.180 0.178 0.179 0.175 0.174 0.176 0.178 0.179 0.176 0.178 0.181 0.178 0.182 0.181 0.184 0.175 0.179 0.176 0.181 0.181 0.182 0.180 0.177 0.178 0.179 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

A-3611

A-3612

A-3613

A-3614

A-3615

A-3616

A-3617

A-3618

10

A-3628

11

A-3629

12

A-3630

13

A-3631

14

A-3632

15

A-3633

16

A-3634

Y B

0.177 0.179

Withstood Withstood

Page 52 of 67

FOR NTPC LTD

For Krishna Electrical Industries Ltd

(N.K. VYAS) Sr.Manager(QA) LOT-25 26.11.07

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-1CX150 Sq.mm 3.3/3.3 KV (A2XY) Cable

Dt. of Testing:-26 & 27.11.07


S.no Drum no. Core Identification Natural 1 2 3 4 5 6 7 8 9 A-3851 A-3852 A-3853 A-3854 A-3855 A-3856 A-3857 A-3858 A-3859 Natural Natural Natural Natural Natural Natural Natural Natural Natural
Conductor Resistance at 20C in ohms/kms

High Voltage test at 10 kv ac for 5 minutes


No Break down observed

0.206(MAX) 0.176 0.176 0.175 0.175 0.176 0.175 0.176 0.178 0.176

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(R.K. Soni)

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-1CX300 Sq.mm 3.3/3.3 KV (A2XY) Cable

Page 53 of 67

Dt. of Testing:-26 & 27.11.07


S.no Drum no. Core Identification Natural 1 2 3 4 5 6 7 8 A-3860 A-3861 A-3862 A-3863 A-3864 A-3865 A-3866 A-3867 Natural Natural Natural Natural Natural Natural Natural Natural Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0869 0.0875 0.0878 0.0876 0.0873 0.0873 0.0874 0.0875 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(R.K. Soni)

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-3CX150 Sq.mm 3.3/3.3 KV (A2XY) Cable

Dt. of Testing:-26 & 27.11.07


S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206 (MAX) 1 A-3868 R Y B R Y B R Y B R Y B R 0.180 0.182 0.179 0.181 0.181 0.180 0.181 0.181 0.180 0.180 0.180 0.180 0.182 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

A-3869

A-3870

A-3871

A-3872

A-3873

A-3874

A-3875

Y B R Y B R Y B R Y B

0.186 0.180 0.182 0.181 0.181 0.182 0.181 0.180 0.182 0.181 0.181

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

Page 54 of 67

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(R.K. Soni)

(Vinod Gupta) Manager(QA & I)

03.12.07

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-3CX150 Sq.mm 11/11 KV (A2XY) Cable

Dt. of Testing:-03&04.12.07
S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206(MAX) 1 A-3890 R Y B R Y B R Y B R Y B R Y B R Y B 0.177 0.177 0.176 0.178 0.178 0.177 0.180 0.178 0.176 0.180 0.180 0.180 0.175 0.176 0.176 0.179 0.178 0.178 High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 3 2 2 2 3 2 3 2 2 2 3 2 2 3 2 3 2

A-3891

A-3892

A-3893

A-3894

A-3895

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

Page 55 of 67 (R.K. Soni) Dy. Manager (IS) (Vinod Gupta) Manager(QA & I)

LOT-27

23.01.08

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-1CX150 Sq.mm 3.3/3.3 KV (A2XY) Cable

Dt. of Testing:- 23 & 24.01.08


S.no Drum no. Core Identification Natural 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 A-4090 A-4091 A-4092 A-4093 A-4094 A-4095 A-4096 A-4097 A-4098 A-4099 A-4100 A-4101 A-4102 A-4103 A-4105 A-4106 A-4107 A-4108 Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural
Conductor Resistance at 20C in ohms/kms

High Voltage test at 10 kv ac for 5 minutes


No Break down observed

0.206(MAX) 0.175 0.175 0.175 0.171 0.173 0.175 0.179 0.175 0.172 0.174 0.173 0.173 0.176 0.174 0.174 0.173 0.172 0.173

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

19 20

A-4109 A-4110

Natural Natural

0.175 0.176

Withstood Withstood

Page 56 of 67

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(Rajesh Sharma) Sr. Manager (IS)

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-1CX300 Sq.mm 3.3/3.3 KV (A2XY) Cable

Dt. of Testing:- 23&24.01.08


S.no Drum no. Core Identification Natural 1 A-3984 Natural Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0860 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(Rajesh Sharma) Sr. Manager (IS)

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T PC, Noida


Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-3CX95 Sq.mm 3.3/3.3 KV (A2XY) Cable

Dt. of Testing:- 23&24.01.08


S.no Drum no.
Core Identification

Conductor Resistance at 20C in ohms/kms 0.320 (MAX) 0.275 0.279 0.279 0.279

High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood

R,Y, & Bl 1 A-4111 R Y B R

A-4112

A-4113

A-4114

A-4115

A-4116

Y B R Y B R Y B R Y B R Y B

0.277 0.274 0.277 0.275 0.279 0.276 0.272 0.276 0.274 0.275 0.277 0.275 0.272 0.273

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

Page 57 of 67

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(Rajesh Sharma) Sr. Manager (IS)

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-3CX150 Sq.mm 3.3/3.3 KV (A2XY) Cable

Dt. of Testing:- 23&24.01.08


S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206 (MAX) 1 A-4086 R Y B R Y B R Y B R Y B R Y B R Y B R 0.180 0.180 0.180 0.174 0.173 0.173 0.176 0.176 0.175 0.176 0.176 0.175 0.179 0.179 0.178 0.174 0.173 0.173 0.179 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

A-4087

A-4088

A-4089

A-4117

A-4118

A-4119

A-4120

A-4121

10

A-4122

11

A-4123

12

A-4124

13

A-4125

Y B R Y B R Y B R Y B R Y B R Y B R Y B

0.177 0.177 0.179 0.178 0.178 0.175 0.175 0.175 0.177 0.176 0.175 0.174 0.174 0.174 0.173 0.176 0.176 0.176 0.175 0.175

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

Page 58 of 67

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(Rajesh Sharma) Sr. Manager (IS) LOT NO. 28

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)


NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005
Size:-1CX300 Sq.mm 11/11 KV (A2XY) Cable Dt. of Testing:- 07& 08.02.08 Conductor High Voltage Partial Core Resistance S.no Drum no. test at 28 kv ac Discharge test Identification at 20C in for 5 minutes at 1.5 Uo ohms/kms Natural 1 2 3 4 5 6 7 A-4127 A-4128 A-4129 A-4130 A-4131 A-4132 A-4133 Natural Natural Natural Natural Natural Natural Natural 0.100(MAX) 0.0896 0.0884 0.0871 0.0878 0.0863 0.0869 0.0859 No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 7 3 2 3 3 2 3

Page 59 of 67

8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35

A-4134 A-4135 A-4136 A-4137 A-4138 A-4139 A-4140 A-4141 A-4142 A-4143 A-4144 A-4145 A-4146 A-4147 A-4148 A-4149 A-4150 A-4151 A-4152 A-4153 A-4154 A-4155 A-4156 A-4157 A-4158 A-4159 A-4160 A-4161

Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural

0.0884 0.0875 0.0873 0.0883 0.0886 0.0875 0.0895 0.0890 0.0894 0.0868 0.0877 0.0884 0.0873 0.0872 0.0921 0.0888 0.0873 0.0877 0.0888 0.0881 0.0874 0.0867 0.0884 0.0881 0.0871 0.0863 0.0872 0.0876

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

3 3 2 2 2 2 2 3 3 2 2 2 3 2 3 2 2 3 2 3 2 2 3 3 2 3 2 2

Page 60 of 67

36 37

A-4162 A-4163

Natural Natural

0.0875 0.0869

Withstood Withstood

3 2

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(Rajesh Sharma) Sr. Manager (IS) LOT-29 14.02.08

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-3CX150 Sq.mm 3.3/3.3 KV (A2XY) Cable

Dt. of Testing:- 14&15.02.2008


S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206 (MAX) 1 A-4164 R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B 0.176 0.178 0.179 0.177 0.178 0.177 0.178 0.175 0.178 0.179 0.178 0.177 0.177 0.177 0.177 0.180 0.181 0.179 0.179 0.177 0.180 0.179 0.179 0.177 0.175 0.176 0.176 0.182 0.178 0.178 High Voltage test at 10 kv ac for 5 minutes No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

A-4165

A-4166

A-4167

A-4168

A-4169

A-4170

A-4171

A-4172

10

A-4173

11

A-4174

12

A-4175

13

A-4176

R Y B R Y B R Y B

0.178 0.177 0.177 0.176 0.176 0.175 0.176 0.176 0.177

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

Page 61 of 67

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(R.K. Soni) Dy. Manager (IS)

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)


NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005
Size:-1CX300 Sq.mm 6.35/11 KV (A2XWaY) Cable

Dt. of Testing:- 14&15.02.2008 S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0867 0.0887 0.0896 0.0862 0.0869 0.0856 0.0865 0.0863 0.0866 0.0866 0.0867 0.0868 High Voltage Partial test at 17 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 3 2 2 2 2 3 2 2 3 2 3 2

Natural 1 2 3 4 5 6 7 8 9 10 11 12
A-4177 A-4178 A-4179 A-4180 A-4181 A-4182 A-4183 A-4184 A-4185 A-4186 A-4187 A-4188

Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural

13 14 15 16 17 18 19 20 21 22 23

A-4189 A-4190 A-4191 A-4192 A-4193 A-4194 A-4195 A-4196 A-4197 A-4198 A-4199

Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural Natural

0.0885 0.0863 0.0865 0.0885 0.0869 0.0865 0.0650 0.0867 0.0864 0.0864 0.0870

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

2 2 2 2 2 2 2 3 2 2 2

Page 62 of 67

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(R.K. Soni) Dy. Manager (IS)

(Vinod Gupta) Manager(QA & I)

LOT-30 17.05.08

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-3CX150 Sq.mm 11/11 KV (A2XY) Cable

Date of Testing:- 28,29 & 30.05.08


S.no Drum no. Core Identification Conductor Resistance at 20C in ohms/kms 0.206(MAX) 1 A-1136 R Y B R Y B R Y 0.184 0.179 0.186 0.184 0.186 0.185 0.180 0.180 High Voltage Partial test at 28 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 3 2 2 2 3 3 2 3

A-1137

A-1138

A-1139

A-1140

A-1141

A-1142

A-1143

A-1144

10

A-1145

11

A-1176

12

A-1177

13

A-1178

14

A-1179

15

A-1180

B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B

0.181 0.181 0.181 0.188 0.187 0.188 0.188 0.181 0.179 0.180 0.176 0.179 0.179 0.175 0.175 0.176 0.181 0.188 0.188 0.179 0.180 0.180 0.181 0.185 0.182 0.180 0.181 0.180 0.188 0.180 0.180 0.179 0.179 0.179 0.185 0.189 0.189

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

2 3 2 2 3 2 2 3 2 2 2 2 3 2 2 2 2 3 2 2 2 2 2 3 2 2 3 2 2 2 2 2 3 2 2 2 2

Page 63 of 67

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(Siddhartha Singh) Manager (IS)

(Vinod Gupta) Manager(QA & I)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida

Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)


NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005
Size:-1CX300 Sq.mm 6.35/11 KV (A2XWaY) Cable

Date of Testing:- 28,29 & 30.05.08

S.no

Drum no.

Core Identification

Conductor Resistance at 20C in ohms/kms 0.100(MAX) 0.0925 0.0918 0.0912 0.0910

Page 64 of 67

High Voltage Partial test at 17 kv ac Discharge test for 5 minutes at 1.5 Uo No Break down observed Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 2 2

Natural 1 2 3 4
A-1146 A-1147 A-1148 A-1149

Natural Natural Natural Natural

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(Siddhartha Singh) Manager (IS)

(Vinod Gupta) Manager(QA & I)

LOT-31 20.06.08

KRISHNA ELECTRICAL INDUSTRIES LTD.


30-B, Industrial Area Banmore (M.P.)

Page 65 of 67

ROUTINE TEST CERTIFICATE


Reference Specification IS 7098(Pt-II)/1985

Customer:- N T P C, Noida
Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw)
NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 09.05.2005

Size:-3CX150 Sq.mm 11/11 KV (A2XY) Cable

Date of Testing:- 22,23.07.2088 & 29.07.2008


S.no Drum no. Core Identification Conductor High Voltage Partial Resistance test at 28 KV ac Discharge test at 20C in for 5 minutes at 1.5 Uo ohms/kms 0.206(MAX) 1 A-1288 R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B 0.178 0.179 0.178 0.185 0.185 0.185 0.181 0.181 0.181 0.181 0.182 0.182 0.181 0.178 0.180 0.181 0.180 0.181 0.184 0.183 0.182 0.181 0.182 0.182 0.184 0.184 0.184 0.182 0.181 0.182 0.181 0.182 0.182 0.181 0.181 0.182 No Break down observed Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood 20 Pc (Max) 2 2 3 2 3 2 3 3 2 2 2 3 3 2 2 3 2 2 2 2 3 2 3 2 2 2 2 3 2 3 2 3 2 2 3 2

A-1289

A-1290

A-1291

A-1292

A-1293

A-1294

A-1348

A-1349

10

A-1350

11

A-1351

12

A-1352

13

A-1353

14

A-1354

15

A-1355

16

A-1356

17

A-1357

18

A-1358

19

A-1359

20

A-1360

21

A-1361

R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B

0.181 0.183 0.182 0.180 0.181 0.180 0.182 0.181 0.181 0.181 0.180 0.182 0.183 0.182 0.184 0.182 0.182 0.181 0.182 0.183 0.182 0.182 0.184 0.181 0.181 0.181 0.180

Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood Withstood

2 3 2 2 3 2 3 3 3 2 2 3 2 2 3 2 3 2 2 3 3 2 2 3 2 3 2

Page 66 of 67

FOR NTPC LTD.

For Krishna Electrical Industries Ltd

(N.K. VYAS) Sr.Manager(QA)

(R.K. Gulati) Head (Tech. & QA)

KRISHNA ELECTRICAL INDUSTRIES LTD.


30- B, Industrial Area Banmore Acceptance Test Report
As Per IS: 7098(Pt-II)/1985 with latest amendment & GTP Customer:- N T P C, Noida Project:-Sipat Super Thermal Power Project,Stage-I(3X660 mw) CHP NO:- 01012808 NOA NO. & Date:-CS-9518-212-2(PT-B)-FC-COA-4555 Dt. 24.05.2005 Size:-3Cx150 Sqmm 11/11 KV (A2XY) Cable Date of Testing: 22.07.2008, 23.07.2008, 29.07.2008& 30.07.2008 OBSERVATION DESCRIPTION OF TEST SPECIFIED VALUE
Drum No.A-1348 Drum No.A-1351 Drum No.A-1356 Overall Diameter of Cable (mm) R 19

74.95
Y 19 14.60 B 19 R 19

74.50
Y B 19 19 14.60 Circular Stranded Compacted 28.37 R 5.63 5.50 5.17 0.25 0.60 0.50 28.47 Y 5.65 28.56 B 5.70 R 19

75.09
Y 19 14.60 B 19

74+/-2 19 Nos Wires(Nom.) 14.5(Approx.)


Cir.Stranded Compacted

A) TEST ON CONDUCTOR i)No. of strands ii)Dia over conductor (mm) III)Shape of conductor Dia over Core (mm)i.e below copper tape/wire screen B) THICKNESS (mm) Insulation Nom Min Eccentricity Ovality Inner Semicon
Outer Semicon Copper Tape/Overlap

28.62 R 5.68 5.50 5.17 0.38 0.50 0.50

28.28 Y 5.60

28.51 B 5.65

28.53 R 5.65 5.50 5.17 0.28 0.60 0.50

28.60 Y 5.70

28.83 B 5.80

28.1(Approx.) 5.5 (Nom) 4.85 (Min) 10%(Max) 2%(Max) 0.3(Min) 0.3(Min)


0.045x40mm/20%(Min.)

Copper Wire No. of wires & tapes Inner Sheath Outer Sheath(Type-ST2) FRLS Outer Sheath(Type-ST2) FRLS Diameter under the sheath Dia over laid up cores
C) On XLPE Insulation

5.50 5.50 3.50 5.17 0.14 0.18 0.50 0.50 0.50 0.50 0.05x40/22-24% 3 x 0.82 to 0.83 3&1 0.95 4.29 3.70 63.80 61.85

5.50 5.60 5.17 3.44 0.25 0.24 0.60 0.50 0.50 0.50 0.05x40/22-23% 3 x 0.82 to 0.83 3&1 0.83 4.26 3.18 64.10 61.69

5.60 5.70 3.45 3.38 0.17 0.28 0.50 0.60 0.50 0.60 0.05x40/23-25% 3 x 0.82 to 0.83 3&1 0.80 4.22 3.15 64.55 61.88

0.82(Nom.) 3&1 0.7 (Min) 3.40(Nom) 2.52(Min) 63.80 (Approx) 61.80 (Approx)

a i)Tensile Strength (N/mm) ii) Elongation at break % b) On outer sheath (ST2) i) Tensile Strength (N/mm) ii)Elongation at break %
D) AGEING TEST
(Expressed as % variation after 168 hrs.)

19.60 500

18.89 500 15.25 237.5

18.23 512.5

20.04 500

19.74 487.5 14.62 212.5

19.28 462.5

19.24 500

18.47 487.5 15.13 200

17.73 500

12.5(Min) 200(min) 12.5(Min) 150(Min)

a) On Insulation at 1350C i) Tenslie Strength (N/mm2) ii) % Variation iii) Elongation at break % iv) % Variation
b) On Outer Sheath (ST2) at 1000C

19.53 0.38 512.5 -2.5

18.39 2.67 525 -5.0 15.12 0.82 250 -5.26

18.37 -0.795 525 -2.43

---------

---------

-.+/- 25% Max -.+/- 25% Max 12.5(min) .+/- 25% Max 150 (min) .+/- 25% Max

i) Tenslie Strength (N/mm2) ii) % Variation iii) Elongation at break % iv) % Variation
E) HOT SET TEST ON XLPE INSULATION i) Elongation under load ii)Permanent Elongation after cooling F) VOLUME RESISTIVITY on XLPE insulation (ohm-cm) at 27 c at 90 c 5.6x1014 1.5x1013

75 1.45

85 2.65

90 2.15

85 2.0

80 2.6

75 1.4

70 2.85

85 2.2

95 1.5

175%(Max) 15%(Max)

6.1x1014 1.4x1013 >90

6.1x1014 1.4x1013

6.7x1014 1.5x1013

6.4x1014 1.5x1013 --

6.1x1014 1.4x1013

6.4x1014 8.4x1012

6.4x1014 1.4x1013 --

6.1x1014 1.5x1013

1.0 x 10 1.0 x 10

14 12

(Min) (Min)

G) THERMAL STABILITY TEST On Outer Sheath at 2000C Special Tests On FRLS Outer Sheath H) FLAMMABILITY TEST a) As per IEC-332-Pt-3(Cat-B)

80 minutes (min)

Unaffected length 2.1 Mtr from top of sample

---

---

The affected portion of cable shall not exceed 2.5 mtr above the bottom edge of the burner.

b) Oxygen index test as per 32.8 ASTMD-2863 on outer sheath c) Halogen Acid Gas Generation 18.54 Test on outer sheath as per IEC 754-1 d) Smoke Density Test on outer sheath as per ASTMD -2843 50.17 i) Max Smoke Density Rating 49.83 ii)Min Light Transmission I) High Voltage Test at 3 U0 for 4 hrs.at 33 KV Embossing :-KRISHNA/MPCAB 11/11 KV ELECTRIC 3CX150 MM2 FRLS 2008 FOR NTPC LTD.

29% (min) 20% (max)

--

--

---Withstood

----

60% (max) 40% (min) To Withstand

For Krishna Electrical Industries Ltd

(N.K. VYAS) Sr.Manager(QA)

(R.K. Gulati) Head (Tech. & QA)