The water cooled packaged DYNACIAT chillers-heaters LG
series of CIAT are specially designed to supply chilled water
or hot water with a middle capacity for air conditioning
applications systems encountered in collective and
commercial buildings , as well as industrial premises and
processes.
These packaged units must be settled in standard indoor in
a technical plant, sheltered against adverse weather and
frost.
To operate on COOLING mode, these units must be cooled
by a water circulation coming from an external source, like
underground water or city water if using a water flow control
valve, or connected to an external water drycooler or a
cooling tower.

On a water supply, the LGP series can be used as a heat


pump during winter time.
Connected to an heating or cooling floor, fan coil units or on
an air handling unit, an heat pump series LGP allows the
heating and the air conditioning of buildings thanks to a set
of valves located on the water circuit (not supplied).
Each unit is assembled, internally wired (logic and starting
box), charged with refrigerant, and is subject to a operation
test in the factory.
The installation work is simple, and the only operations
required on spot are field electrical wiring and water piping
connections.

RANGE
DYNACIAT LG - LGP series

DYNACIAT LGN series

Water cooled chillers or heat pump models

Chillers models without condenser (for split system)

DYNACIAT ILG series


models Water to Water reversible heat pumps

SPECIFICATIONS
DYNACIAT units LG series are supplied in standard with the
following components :
- water cooled condenser,
- chiller evaporator,
- capacity control system on outlet chilled or hot water,
- logic, control and starting electric box :
. Power supply : 3~50Hz 400V (+6%/-10%) + earth
. Logic circuit : 1~50Hz 230V (+6%/-10%)
(transformers are mounted on the unit as standard feature,),
- cabinet for indoor.

Conformity with the EC European directives


-

"LOW VOLTAGE" directive (LVD),


Machines 98 / 37 CEE
Electromagnetic EMC 89 / 336 CEE
Pressure vessels DESP 97 / 23 CEE
category 2 (except LGN models without condenser)
DESP is not applicable (LGN) unit not complete

Standards conformity
- EN 60-204 and EN 378-2

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

Water chillers

LG
TECHNICAL

AND ELECTRICAL CHARACTERISTICS

DynaCiat LG - LGP

120V

150V

200V

240V

300V

350V

400V

500V

540V

600V

753Z

900Z 1000Z

Cooling capacity

kW

34.7

45.6

61.5

69.0

91.3

105.1

119.3

147.8

159.6

182.4

208.0

249.0

272.0

Power input

kW

7.5

9.6

13.0

15.2

19.2

22.3

25.4

32.0

34.4

38.4

55.0

67.0

74.0

4.62

4.75

4.73

4.53

4.75

4.71

4.69

4.62

4.63

4.75

3.78

3.72

3.67

Efficiency EER
Heating capacity

kW

39.9

52.7

70.4

79.4

105.3

120.6

137.7

163.9

184.1

205.0

250.0

301.0

330.0

Power input

kW

9.3

11.9

16.4

18.8

23.9

27.4

31.3

39.1

42.6

48.2

68.0

83.0

92.0

4.29

4.42

4.29

4.22

4.40

4.40

4.39

4.19

4.32

4.25

3.67

3.62

3.58

67

70

69

70

73

74

75

76

75

76

74

75

75

COP
Noise power level

dB(A)

Compressor

Hermetic SCROLL 2900 rpm

Starting mode

Direct on line by step

Quantity

Oil quality
Oil volume

POE 3MAF (32 cst).

POE ISO32-160SZ

4.14

6.50

6.50

8.28

8.84

9.76

11.24

8.28

8.28

16.0

16.0

16.0

l (cir2)

6.50

8.28

8.0

16.0

16.0

2
R410A

R407C

kg (cir1)

3.9

6.5

7.8

9.7

11.3

13.0

16.0

7.8

9.7

6.7

12.3

13.3

kg (cir2)

9.7

9.7

13.3

13.3

13.3

ph/Hz/V

3~50Hz 400V (+6%/-10%) + Earth

Maxi rated current

23.0

28.0

41.0

46.0

56.0

64.0

73.5

91.0

102.0

112.0

142.6

172.4

190.0

Starting current

118.0

198.0

139.0

141.0

226.0

253.0

300.0

318.0

272.0

282.0

366.0

395.0

413.0

Breaking capacity

kA

50

100

Electric box protection


Maxi wires section
Control voltage
Capacity control

IP22
mm2

50

50

50

50

ph/Hz/V

50

95

Water content
Outlet water mini Maxi

100-0

100-0

2.7

3.6

4.8

5.3

9.9

m3/h

3.5

4.8

6.2

7.0

9.5

Maximum water flow

m /h

11.2

14.6

19.8

22.2

29.2

Water connections

Design pressure

bar

Outlet water mini Maxi

95

95

185

185

185

100
100 100-50- 100-72- 100-75- 100-66- 100-72- 100-7543-0
37-0
0
50-22-0 50-25-0 33-0 50-22-0 50-25-0
Brazed plates type
11.3

G 1"1/4

G 1"1/2

12.8

15.7

15.2

19.8

15.8

15.8

15.8

-8C / +12C

10.9

12.4

15.2

16.4

19.1

16.5

34.0

38.4

47.5

51.1

58.4

45

G 2"

G 2"1/2

DN80 PN16

20.0

20.0

60

60

DN100 PN16

10 bars WATER side

Condenser
Water content

95

-10C / +12C

Minimum water flow

95

1~50Hz 230V (+6%/-10%) transformer mounted


100-50- 100-50- 100-500
0
0

Evaporator

Brazed plates type


l

3.0

4.1

5.1

5.8

8.0

9.4

11.1

15.2

13.8

16.0

15.8

+30C / +55C

15.8

15.8

+30C / +50C

Minimum water flow

m3/h

3.1

4.1

5.4

6.1

8.2

9.4

10.7

13.1

14.3

16.3

16.5

20.0

20.0

Maximum water flow

m3/h

8.5

11.1

15.1

17.0

22.3

26.0

29.4

35.0

39.1

44.6

45

60

60

Water connections

Design pressure

bar

10 bars WATER side

Storage mini Maxi

-20C / +50C

Mini water pipes content

G 1"1/2

G 2"

G 2"1/2

DN80 PN16

DN100 PN16

226

299

197

222

292

286

279

454

217

274

457

364

457

Operating height

mm

1201

1201

1201

1201

1201

1201

1201

1201

1201

1201

1881

1881

1881

Length

mm

798

798

1492

1492

1492

1492

1492

1492

2380

2380

2200

2200

2200

Width

mm

883

883

883

883

883

883

883

883

883

883

880

880

880

Dry weight

kg

230

300

385

390

590

620

665

735

930

1125

1045

1223

1223

Operating weight

kg

240

312

400

406

617

650

703

780

990

1190

1128

1315

1315

0 4 . 5 3 8

Capacities based on :
a/ COOLING mode : +12C/+7C and +30C/+35C
b/ HEATING mode : +40C/+45C and +12C/+7C

3.25

Refrigerant type

Electric supply

l (cir1)

Refrig. circuit nb

Refrigerant weight

EER and COP are gross values


height without lifting accessories

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

DynaCiat LGN

LG

Water chillers

120Z

150Z

200Z

240Z

300Z

350Z

400Z

500Z

540Z

600Z

753Z

900Z 1000Z

Cooling capacity

kW

28.0

41.0

55.0

67.0

81.0

95.0

110.0

134.0

150.0

162.0

204.0

245.0

268.0

Power input

kW

7.0

11.0

15.0

19.0

22.0

27.0

30.0

37.0

41.0

45.0

55.0

67.0

73.0

Discharge capacity

kW

35.0

52.0

70.0

86.0

103.0

122.0

140.0

171.0

191.0

207.0

259.0

312.0

341.0

4.00

3.72

3.66

3.52

3.68

3.51

3.66

3.62

3.65

3.60

3.70

3.65

3.67

67

70

69

70

73

74

75

76

75

76

74

75

75

Efficiency EER
Noise power level

dB(A)

Compressor

Hermetic SCROLL 2900 rpm

Starting mode

Direct on line by step

Quantity

Oil quality
Oil volume

POE ISO32-160SZ

l (cir1)

3.8

6.2

7.6

10.0

12.4

14.2

16.0

16.0

12.4

12.4

16.0

16.0

16.0

l (cir2)

10.0

12.4

8.0

16.0

16.0

Refrig. circuit nb

Refrigerant type

R407C

Refrigerant weight
Electric supply

POE ISO32-160SZ

R407C

No refrigerant (nitogen charge)


ph/Hz/V

3~50Hz 400V (+6%/-10%) + Earth

Maxi rated current

19.5

30.0

39.0

49.0

59.0

68.0

77.0

95.0

108.0

118.0

142.6

172.4

190.0

Starting current

120.0

175.0

140.0

195.0

205.0

245.0

254.0

318.0

254.0

264.0

366.0

395.0

413.0

kA

50

50

50

50

50

50

50

50

50

50

100

100

100

mm2

50

50

50

50

50

95

95

95

95

95

185

185

185

Breaking capacity
Maxi wires section
Electric box protection

IP22

Control voltage

ph/Hz/V

1~50Hz 230V (+6%/-10%) - transformer mounted

Capacity control

100-0

100-0

10050-0

10040-0

10050-0

10043-0

2.3

2.3

4.5

5.7

5.7

6.8

Evaporator
Water content
Outlet water mini Maxi

10050-0

10050-0

100-72- 100-75- 100-66- 100-72- 100-7545-18-0 50-25-0 33-0 50-22-0 50-25-0

Brazed plates type


C

6.8

7.9

11.3

11.3

15.8

15.8

-10C / +12C

15.8

-8C / +12C

Minimum water flow

m3/h

3.2

4.7

6.2

7.7

9.4

11.0

12.8

15.7

17.2

18.8

16.5

20.0

20.0

Maximum water flow

m3/h

9.9

14.2

19.5

23.8

28.5

30.0

30.0

30.0

52.3

57.1

45.0

60.0

60.0

Water connections

Design pressure

bar

G 1"1/4

G 1"1/2

G 2"

Discharge circuit
Balance circuit 1 / circuit 2
Dischage connections
Liquid connections

G 2"1/2

DN80 PN16

DN100 PN16

10 bars WATER side


Without condenser (spit system)

%
(cir1)

100
1"1/8

1"1/8

1"3/8

1"3/8

1"5/8

1"5/8

2"1/8

54/46

50/50

67/33

56/44

50/50

2"1/8

1"3/8

1"5/8

2"1/8

2"1/8

2"1/8

(cir2)

1"5/8

1"5/8

1"3/8

2"1/8

2"1/8

(cir1)

7/8

7/8

7/8

1"1/8

1"1/8

1"1/8

1"3/8

1"3/8

1"1/8

1"1/8

1"3/8

1"1/8

1"1/8

(cir2)

1"1/8

1"1/8

1"1/8

1"3/8

1"3/8

Design pressure

bar

29.5 bar HP

29.5 bar HP

Storage mini Maxi

-20C / +50C

-20C / +50C

Mini water pipes content

158

233

153

148

227

227

309

376

144

221

370

293

368

Operating height

mm

1201

1201

1201

1201

1201

1201

1201

1202

1201

1201

1881

1881

1881

Length

mm

788

788

1482

1482

1482

1482

1482

1482

2370

2370

2200

2200

2200

Width

mm

873

873

873

873

873

873

873

873

873

873

880

880

880

Dry weight

kg

223

284

375

436

518

548

586

591

835

954

975

1135

1135

Operating weight

kg

232

296

390

452

543

577

621

636

883

1008

1017

1177

1177

Capacities based on :
COOLING mode : +12C/+7C and condensing +45C
EER is gross value
height without lifting accessories

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

Water chillers

LG
MAIN

COMPONENTS

Electronic control system

Framework

Microprocessor electronic control system from CIAT, with CPU,


with centralization of controls and monitoring of internal states.

- casing with removable sheets in galvanized steel,

Including :

- enameled painted colors RAL 7024 and RAL 7035

- Selector for Run, Stop, Reset or Remote,


- Running mode selector, COOLING or HEATING,

Hermetic SCROLL compressors

- Output. RS485 output for BMS control (ModBus-JBus),

- Integral motor cooled by suction gas

. output adapter for remote signal adaptator,

- Motor protection by a winding internal thermostat

. output adapter for the remote control (optional).

- Mounting on antivibratil mounts

- LCD screen for output or internal operation and LED,

Evaporator

Functions :

- Brazed plates exchanger (s)

- Monitoring of running informations by :

- End plates and internal plates in AISI 316 stainless steel

. direct display of clear messages in different languages

- High performance optimized plates profile

. direct display of temperatures and pressures

- Thermal insulation

- Global compressors control with starting sequence, counting


and equalization of compressors running times

Condenser

- Anti-short cycle protection

Series LG - LGP

- Autoadaptatives functions with a soft driving the adjustment


of the control system on the running parameters deviation

- Brazed plates exchanger (s)


- High performance optimized plates profile

- Capacity step control system on each compressor (multi


compressors) in accordance with the cooling or heating requirements controlled by the water temperatures

- Thermal insulation

- Control of the internal operating parameters

series LGN

- Second setting point control

- Chiller without condenser

- Direct display of water temperatures

- Possibility of connection on a removed air cooled condenser


EUROPA 2C or AIRIAL series

- Diagnosis of operating status and faults :

Control functions and safety devices

- Remote management and remote control

- End plates and internal plates in AISI 316 stainless steel

- Thermostatic expansion valve


- High and low refrigerant pressure switch functions,
- Safety relief valves on refrigerant circuit
- Temperature sensors and pressure transducers,

HP/LP, water flow, compressor(s) motor(s), anti-frost

OPTIONAL

EQUIPMENT (FIELD MOUNTING)

Optional equipment (Separately delivered)

- Chilled water flow switch

- Remote control box,

- Unit starting sequence,

- Remote signal adaptator assembly,

Electrical box

- Evaporator and condenser water rubber expansion joints,

The entire assembly electric box, containing all the electric


components and control process unit (CPU), provides a complete control of the functions of the machine and allows operation monitoring, adjustment of the water temperature settings, or interface with an external managing system.

- Water filter 600 microns, evaporator and condenser,

The electric box includes :


- Power circuit and remote control circuit
- Wiring numbering
- Main safety switch breaker on front panel with handle

- Condenser 2 ways control valve for city water use,


- Condenser 3 ways control valve for starting with low water
temperature,
- Phase rotation detecter (rotation, phase failure, over voltage,
under voltage),
- Soft starter,
- Refrigeration sleeves for LGN (without condenser).

- Control circuit transformer


- Circuit breakers protections on power and control circuits
- Compressor(s) motor(s) contactor(s)
- Main earthling strip
- Microprocessor electronic system
Micro Connect or Connect for 100 to 500
Connect for sizes 600 to 1000
- Free contacts for field wiring signals report.

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

RANGE

Necessary Glycol
7

LG-LGP 753Z - 1000Z

Condenser water outlet C

Condenser water outlet C

LG-LGP 120V - 600V

Necessary Glycol

-3

Necessary Glycol

-4

Chilled water outlet C

EVAPORATOR

LGN 100Z - 1000Z

Condensating temperature C

OPERATING

LG

Water chillers

-4

Chilled water outlet C

Chilled water outlet C

LIMITS
Admissible water inlet/outlet difference C

The curves represent the minimum and maximun allowable


temperature difference of chilled water (or glycol) in accordance
with the outlet temperature

Water glycol R22 / R407C

Example :
For a water outlet : + 5 C
mini difference : 2,6 C
Water temp. : 7,6 / 5 C
Max. difference : 6 C
Water temp. : 11 / 5 C
For temperature differences not included between the 2 curves,
consult us.

Brazed plate
evaporator

Water outlet temperature (C)

WATER

GLYCOL COEFFICIENTS

Difference of temperature for performances calculation tables

CORRECTION

30 % concentration of glycol weight


Cooling capacity
Evaporator

Freezing point of the solution : -17,5 C.

Pf : Refrigeration power according to selection tables


Pa : Compressor absorbed power according to selection
tables
P : Water pressure drop according to curves for the
corresponding corrected flow rate value (Qc).
Corrected values according to calculations above :
Pfc : Corrected cooling capacity
Qc : Corrected chilled or hot water flow rate
Pc : Corrected water pressure drop, evaporator or condenser.

0,98

Pfc = Pf x 0,98
Pcf x 0.86

1,05

Qc =

1,15

Pc = P x 1,15
12 / 7 C

Cooling capacity

0,97

Pfc = Pf x 0,97

Chilled water
flow

1,05

Pressure drop

1,10

Average temp.
Cooling capacity
Evaporator + condenser

Reading valves in the brochure

Condenser

K : Correction cfficients

Chilled water
flow
Pressure drop
Average temp.

POSITIVE TEMPERATURE NEGATIVE TEMPERATURE


K
Calculation
K
Calculation

Qc =

x 1,05

1,00

see selection table

1,10

Qc =

Pcf x 0.86

x 1,10

T
Pc = P x 1,30
1,30
see operating limits

(Pcf+Pa) x 0.86
x 1,05
T

Pc = P x 1,10
35 / 40 C

0,95

Pfc = Pf x 0,95
Pcf x 0.86

0,97

Chilled water
flow

1,05

Pressure drop

1,15

Pc = P x 1,15

1,30

Hot water flow

1,05

(Pcf+Pa) x 0.86
Qc =
x 1,05
T

1,05

Condenser
pressure drop

1,10

Pc = P x 1,10

1,10

Qc =

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

x 1,05

N A

1,10

Pfc = Pf x 0,97
Qc =

Pcf x 0.86

x 1,10

Pc = P x 1,30
Qc =

(Pcf+Pa) x 0.86
x 1,05
T

Pc = P x 1,10

0 4 . 5 3 8

Water chillers

LG
MINIMUM

WATER PIPES VOLUME

The Connect controller is equipped with an anticipation logic allowing high flexibility in adjusting the set points according to the
parameters drifting, in particular for low water volume hydraulic installations.
An adapted management of the compressors operating periods avoids therefore the start of anti-short cycle functions, and in
most cases, the requirement of a buffer tank.
Models LG - LGP - ILG

120V

150V

200V

240V

300V

350V

400V

500V

540V

600V

753Z

900Z

1000Z

Minimum installation volume (liters)

226

299

197

222

292

286

279

454

217

274

457

364

457

Notes :
Industrial processes which require a high stability of water temperatures or installations with high thermal load variation can
privilege the installation of a water buffer tank.

NOISE

LEVELS

The DynaCiat LG-LGP-LGN range is a must by its design integrating the "noiseless" assembly process for attenuation of
vibrations and sound power sources :
Scroll compressor(s) mounted on antivibratil mounts
Anti-vibratil assembly of several compressors on structure isolated from the frame (120 to 600)
Piping dissociated from the unit structure
Double skin paneling with mineral wool insulation 25 mm (753 to 1000)
Antivibration mounts to be positioned between the ground and the unit as a standard feature (753 to 1000)

Sound power levels ref 2x10-12 Pa 3 dB


LG / LGP
LGN
120
150
200
240
300
350
400
500
540
600
753
900
1000

POWER LEVEL SPECTRUM (dB)


63 Hz
77
78
78
78
81
82
83
84
83
84
89
90
90

125 Hz
65
74
60
68
77
75
76
74
78
80
78
79
79

250 Hz
65
72
60
68
75
75
76
77
76
78
72
73
73

500 Hz
59
67
62
62
70
68
69
67
70
73
73
74
74

1000 Hz
59
60
62
62
63
64
67
69
66
66
68
69
69

2000 Hz
61
64
64
64
67
69
70
72
69
70
62
63
63

4000 Hz
59
57
62
62
60
63
64
66
64
63
62
63
63

Global level Lw
dB(A)
67
70
69
70
73
74
75
76
75
76
74
75
75

Sound pressure levels ref 2x10-5 Pa 3 dB

Measuring point :
in free field
10 meter from the unit, 1.50 meters from the ground
directivity 2
LG / LGP
LGN
120
150
200
240
300
350
400
500
540
600
753
900
1000

PRESSURE LEVEL SPECTRUM (dB)


63 Hz
46
47
47
47
50
51
52
53
51
52
57
58
58

125 Hz
34
43
28
37
46
43
44
43
46
48
46
47
47

250 Hz
34
41
29
37
44
43
45
45
44
47
40
41
41

500 Hz
28
35
31
31
38
37
37
36
39
41
41
42
42

1000 Hz
28
29
31
31
32
33
36
38
34
35
36
37
37

2000 Hz
29
33
33
32
36
38
39
40
37
39
30
31
31

4000 Hz
28
25
30
31
28
31
32
34
33
31
30
31
31

Global level Lp
dB(A)
35
39
38
38
42
42
44
45
43
45
42
43
43

NOTES : Acoustic pressure levels depend of installation conditions, and consequently are only indicative. It is reminded that
only the sound power levels are comparable and certified.
Compliance with ISO 3744 standard Lp = Lw - 10 log S

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

AND HEATING CAPACITIES

VI

RO

NME

N TA L LY F R
IE

ND
LY

EN

COOLING

LG

Water chillers

TE

EN

PR

HFC R 410 A

DYNACIAT LG - LGP

CT

IO N

D E L'E N VI RO

NN

EM

CONDENSER WATER OUTLET TEMPERATURE C

LG
LGP

30
Pa
kW

Pc
kW

Pf
kW

Pa
kW

Pc
kW

Pf
kW

Pa
kW

Pc
kW

Pf
kW

Pa
kW

Pc
kW

Pf
kW

Pa
kW

Pc
kW

-10 19.0
-8 20.5
Glycol water
-4 24.0

6.7
6.8
6.7

25.4
26.9
30.5

17.9
19.3
22.6

7.5
7.5
7.5

25
26.5
29.9

16.5
17.7
21.1

8.4
8.4
8.4

24.5
25.7
29.1

15.2
16.3
19.4

9.4
9.5
9.4

24.1
25.2
28.3

17.8

10.6

27.8

30.1
34.2
36.4
42.8

6.7
6.8
6.8
6.9

36.6
40.8
43.0
49.5

28.6
32.6
34.7
41.0

7.5
7.5
7.5
7.6

35.8
39.9
42.0
48.4

27.0
30.8
33.0
39.0

8.3
8.4
8.4
8.4

35
38.8
41.1
47.1

25.2
28.9
30.9
36.7

9.3
9.3
9.3
9.4

34.1
37.9
39.9
45.8

23.2
26.8
28.6
34.3

10.5
10.5
10.5
10.4

33.2
36.8
38.7
44.4

-10 25.5
-8 27.4
Glycol water
-4 31.6

8.4
8.4
8.5

33.6
35.5
39.8

24.2
26.2
30.2

9.3
9.4
9.5

33.1
35.2
39.3

22.8
24.6
28.6

10.4
10.4
10.5

32.7
34.6
38.7

21.3
23,0
26.9

11.5
11.6
11.7

32.1
34.0
38.1

21.1
24.8

12.8
13.1

33.2
37.2

39.3
44.6
47.5
55.9

8.6
8.7
8.7
9.0

47.6
53.1
56.0
64.7

37.7
42.9
45.6
53.8

9.5
9.6
9.6
9.8

46.9
52.1
55.0
63.3

35.9
40.8
43.5
51.4

10.6
10.7
10.7
10.8

46.1
51.1
53.8
61.9

33.8
38.6
41.2
48.7

11.8
11.9
11.9
12.0

45.2
50.0
52.7
60.4

31.5
36.0
38.6
45.8

13.2
13.3
13.3
13.4

44.2
48.8
51.4
58.7

-10 33.5
-8 36.5
Glycol water
-4 42.5

11.4
11.4
11.4

44.5
47.4
53.5

31.4
34.2
40.1

12.9
12.9
12.9

43.7
46.5
52.5

29.1
31.8
37.5

14.6
14.6
14.6

42.9
45.7
51.4

26.6
29.3
34.6

16.5
16.5
16.5

42.1
44.9
50.2

31.5

18.7

49.2

53.2
60.5
64.4
76.0

11.5
11.6
11.7
11.8

64.3
71.7
75.7
87.5

50.5
57.7
61.5
73.0

12.9
13.0
13.0
13.1

62.9
70.2
74.1
85.7

47.6
54.5
58.2
69.5

14.5
14.6
14.6
14.5

61.6
68.6
72.3
83.6

44.4
51.0
54.6
65.4

16.4
16.4
16.4
16.3

60.1
66.8
70.4
81.2

41.0
47.2
50.6
61.1

18.5
18.5
18.5
18.3

58.6
64.9
68.4
78.7

-10 37.8
-8 41.2
Glycol water
-4 47.9

13.4
13.4
13.4

50.6
54.1
60.9

35.6
38.8
45.3

15.0
15.0
15.0

49.8
53.1
59.7

32.8
36.0
42.3

16.8
16.8
16.8

48.8
52
58.3

30.1
33.1
39.2

18.9
18.9
18.9

47.8
51.0
57.1

35.7

21.2

55.8

59.7
67.7
72.2
84.9

13.5
13.6
13.7
13.9

72.9
80.9
85.6
98.5

56.8
64.6
69.0
81.4

15.0
15.1
15.2
15.3

71.3
79.2
83.7
96.4

53.6
61.1
65.3
77.3

16.8
16.8
16.8
17.0

69.7
77.4
81.6
93.8

50.0
57.3
61.3
73.0

18.8
18.8
18.8
18.8

68.0
75.3
79.4
91.2

46.1
53.1
56.9
68.1

21.1
21.0
21.0
21.0

66.2
73.2
77.1
88.3

-10 50.1
-8 54.2
Glycol water
-4 62.8

16.8
16.8
16.9

66.2
70.3
79.1

47.6
51.7
59.9

18.7
18.8
18.9

65.4
69.7
78.0

44.7
48.8
56.8

20.7
20.8
21.0

64.4
68.6
76.9

41.8
45.6
53.3

22.9
23.1
23.4

63.4
67.5
75.6

41.8
49.3

25.6
26.0

65.9
74.0

120V
Pure water

150V
Pure water

R410A

200V
Pure water

240V
Pure water

300V
Pure water

2
5
7
12

2
5
7
12

2
5
7
12

2
5
7
12

2
5
7
12

78.1
89.1
95.1
112.

-10 57.0
-8 61.7
Glycol water
-4 71.9

350V
Pure water

Pure water

Pf : Cooling output
Pa : Compressor power input
Pc : Heating capacity

40

45

50

Pc
kW

21.1
24.5
26.3
31.6

11.8
11.7
11.7
11.7

32.3
35.7
37.5
42.8

29,0
33.3
35.7
42.6

14.8
14.8
14.9
15.0

43.0
47.5
49.9
56.9

37.2
43.1
46.4
56.4

21
20.9
20.9
20.5

57.1
63.0
66.3
76.2

41.9
48.6
52.2
62.8

23.7
23.6
23.5
23.5

64.4
71.0
74.6
85.4

21.2 91.7 67.2


21.3 102.0 76.9
21.4 107.6 82.3
21.6 123.9 97.8

23.7 90.0 62.7


23.8 99.8 72.0
23.9 105.3 77.1
24.0 121.0 91.7

26.5 88.0 57.6


26.6 97.5 66.6
26.6 102.7 71.4
26.8 117.6 85.3

19.3
19.4
19.5

21.4
21.5
21.6

74.1
78.9
88.9

50.5
55.2
64.3

23.8
23.8
24.0

73.1
77.9
87.3

47.0
51.4
60.4

26.4
26.6
26.8

71.9
76.6
85.9

47.2
56.0

29.6
29.9

75.1
84.3

2 90.0 19.8 109.3


5 103.0 20.1 122.6
7 110.2 20.3 129.9
12 130.3 20.8 150.7

85.7
98.4
105.1
124.6

21.9
22.2
22.3
22.7

106.6
119.9
126.8
146.8

81.5
93.3
99.9
118.8

24.3
24.5
24.6
25.0

104.9
117.0
123.7
143.1

76.5
88.0
94.2
112.3

27.1
27.3
27.4
27.7

102.5
114.3
120.6
139.1

71.4
82.3
88.2
105.3

30.3
30.4
30.5
30.8

100.3
111.5
117.5
135.1

22.0 85.3 60.9


22.1 91.4 66.4
22.3 102.8 77.6

24.5 84.3 57.2


24.6 89.9 62.5
24.7 101.3 73.5

27.3
27.4
27.6

83.0
88.7
99.8

52.9
58.1
68.6

30.2
30.4
30.7

81.5
86.9
97.8

53.1
63.3

33.8
34.2

84.9
95.7

22.6
22.9
23.1
23.7

25.0
25.3
25.4
25.9

27.8
28.0
28.1
28.5

119.5
133.3
141.0
162.7

87.5
100.3
107.6
128.0

31.0
31.2
31.3
31.5

117.2
130.4
137.7
158.5

81.4
93.8
100.6
120.2

34.6
34.8
34.8
35.1

114.4
127.1
134.0
154.1

101.9
116.6
124.3
147.4

Pa
kW

19.0 93.3 71.2


19.2 104.0 81.4
19.2 109.9 86.9
19.6 126.7 102.9

53.7
58.4
68.1

2
5
7
12

Pf
kW

17.1 94.7 74.9


17.3 105.9 85.5
17.4 112.0 91.3
17.9 129.5 107.
75.5
80.3
90.7

-10 64.2
-8 70.2
Glycol water
-4 81.4

400V

35

55

Evaporator water
outlet temperature Pf
C
kW

123.9
138.9
146.8
170.5

97.5
111.6
119.3
141.3

121.7
136.1
144.0
166.5

92.7
106.2
113.7
135.1

29.5 85.7
29.7 94.9
29.8 99.8
29.9 114.1

65.6
76.1
81.7
98.1

33.9 97.8
34.1 108.6
34.2 114.4
34.5 131.3

74.8
86.6
93.0
111.4

38.5
38.8
38.9
39.1

111.4
123.6
130.1
149.0

Zone where use of water / glycol is compulsory


Calculation fouling 0.00005 m2 C/W
Eurovent conditions

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

Water chillers

LG
ND

CT

IO N

D E L'E N VI RO

NN

T
TE

EN

PR

PR

TE

ND

HFC R 407c

HFC R 410 A

DYNACIAT LG - LGP

RO

LY

VI

N TA L LY F R
NME
IE

EN

RO

LY

VI

EN

AND HEATING CAPACITIES


EN

COOLING

N TA L LY F R
NME
IE

EM

CT

IO N

D E L'E N VI RO

NN

EM

CONDENSER WATER OUTLET TEMPERATURE C

LG
LGP

-10 78.8
-8 85.4
Glycol water
-4 99.6

27.3 105.0 74.4


27.4 111.7 80.9
27.6 126.2 94.8

30.3 103.4 69.9


30.5 110.1 76.0
30.7 124.3 89.6

33.7 101.9 64.5


33.9 108.2 70.7
34.1 122.3 83.7

37.5 99.9
37.8 106.4 64.3
38.0 119.9 77.0

41.9 103.7
42.3 117.1

28.1
28.5
28.7
29.4

31.1
31.4
31.6
32.3

34.5
34.8
35.0
35.5

38.4
38.6
38.7
39.2

42.8
43.0
43.1
43.5

R410A

500V
Pure water

2
5
7
12

125.2
143.6
153.3
182.1

Pa
kW

35
Pc
kW

152.4
171.3
181.3
210.8

Pf
kW

119.8
137.2
147.0
174.5

Pa
kW

40
Pc
kW

149.8
167.6
177.7
205.9

Pf
kW

113.8
130.9
139.9
166.5

-10 87.5 30.2 116.5 82.6 33.7 114.7 77.3


-8 95.5 30.3 124.6 90.0 33.8 122.3 84.6
Glycol water
-4 110.4 30.4 139.6 104.9 33.8 137.4 98.7

540V
Pure water

2
5
7
12

137.4
156.2
166.6
196.0

30.6
30.9
31.1
31.9

167.1
186.3
196.8
227.1

131.2
149.5
159.6
188.1

34.0
34.3
34.4
35.0

164.1
182.7
192.9
222.2

124.3
142.1
151.6
179.4

Pa
kW

45
Pc
kW

147.0
164.5
173.7
201.0

Pf
kW

107.3
123.5
132.2
157.5

Pa
kW

50
Pc
kW

144.1
160.7
169.6
195.4

Pf
kW

99.9
115.4
123.8
148.1

600V

R407C

140.7
156.7
165.2
190.0

41.8 111.1
42.0 118.2
42.3 132.4 84.8

47.2 129.5

38.0
38.1
38.2
38.6

42.5
42.6
42.6
42.8

47.5
47.6
47.7
47.7

160.9
179.0
188.6
216.8

116.8
133.7
143.0
170.2

157.5
174.7
184.1
211.6

108.5
124.5
133.4
159.1

153.8
170.1
179.2
205.2

189.4
211.6
224.0
258.9

149.8
170.9
182.4
215.4

38.0
38.3
38.4
39.2

186.6
208.1
219.7
253.6

142.5
163.0
173.9
206.0

42.5
42.6
42.8
43.2

183.4
204.2
215.3
248.0

134.5
154.0
164.5
195.4

47.4
47.6
47.7
48.0

179.9
199.8
210.5
241.9

125.4
144.0
154.1
183.7

52.9
53.2
53.3
53.5

175.9
195.1
205.3
235.3

-8
Glycol water -4
2
5
Pure water 7
12
-8
Glycol water -4

117
139

44
45

160
183

112
133

49
51

159
181

107
126

54
56

158
180

101
119

60
62

157
178

111

69

176

177
202
217
260
137
163

47
49
49
51
56
58

223
250
265
310
191
219

168
193
208
248
130
155

53
54
55
57
62
64

220
246
261
303
189
216

160
183
197
235
123
146

59
61
61
63
69
71

216
241
256
296
189
214

151
172
185
221
116
137

65
67
68
70
76
78

213
236
250
289
187
212

140
161
172
206

72
74
75
78

209
232
245
281

131

84

210

2
5
7
12

211
244
262
314

58
60
60
62

268
302
321
375

201
232
249
299

65
66
67
69

264
297
315
366

191
219
235
282

72
74
75
77

259
290
307
357

179
206
221
265

80
82
83
86

255
285
301
348

167
192
206
247

88
91
92
95

251
279
294
339

-8
Glycol water -4
2
5
Pure water 7
12

153
182

59
61

210
240

146
173

66
68

209
239

139
164

73
76

208
236

131
154

81
84

207
234

144

93

232

230
265
285
341

64
66
67
69

292
328
350
408

220
253
272
324

72
74
74
77

289
324
344
399

208
239
257
307

80
82
83
86

284
318
337
390

196
224
241
288

88
91
92
95

280
311
330
380

182
210
225
269

98
101
102
106

276
306
322
370

Pure water

Pf : Cooling output
Pa : Compressor power input
Pc : Heating capacity

Pf
kW

Pa
kW

Pc
kW

91.3
106.1
114.2
137.3

47.7
47.9
48.1
48.4

136.5
151.8
160.2
183.7

99.2
114.6
123.1
147.4

53.3
53.3
53.3
53.4

149.7
165.4
174.1
198.7

115.4
133.1
142.7
170.8

59.0
59.3
59.5
59.8

171.5
189.7
199.6
228.2

52.0 148.0

34.2
34.6
34.8
35.8

900Z

1000Z

Pc
kW

156.3
177.9
190.1
223.9

Pure water

2
5
7
12

Pa
kW

37.5 112.9 71.7


37.7 120.5 78.5
37.8 134.9 92.2

-10 100.1 33.6 132.3 95.1 37.3 130.7 89.5 41.4 128.8 83.5 45.8 126.8
-8 108.5 33.7 140.9 103.4 37.5 139.3 97.6 41.7 137.3 91.1 46.2 134.9
Glycol water
-4 125.6 33.9 158.3 119.8 37.7 156.1 113.5 42.1 153.7 106.4 46.8 151.0 98.7

753Z

55

Evaporator water
outlet temperature Pf
C
kW

30

Zone where use of water / glycol is compulsory


Calculation fouling 0.00005 m2 C/W
Eurovent conditions

NOTES
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
8

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

AND HEATING CAPACITIES REJECTED ON REMOTE CONDENSER

VI

RO

NME

N TA L LY F R
IE

ND

LY

EN

PR

HFC R 407c

DYNACIAT LGN

TE

EN

COOLING

LG

Water chillers

CT

IO N

D E L'E N VI RO

NN

EM

CONDENSING TEMPERATURE C

LGN

40

45

55

50

Pf
kW

Pa
kW

Pc
kW

Pf
kW

Pa
kW

Pc
kW

Pf
kW

Pa
kW

Pc
kW

Pf
kW

Pa
kW

Pc
kW

-8
-4

15.2
18.2

5.9
5.9

20.8
23.9

14.3
17.2

6.6
6.6

20.6
23.6

13.3
16.1

7.4
7.4

20.3
23.2

12.3
14.9

8.3
8.3

20.1
22.8

2
5
7
12

24.3
28.7
30.8
38.2

5.9
5.9
5.9
5.9

30.0
34.5
36.6
44.0

23.1
27.3
29.4
36.5

6.6
6.6
6.6
6.6

29.4
33.7
35.8
42.9

21.7
25.7
27.8
34.5

7.4
7.4
7.4
7.4

28.8
32.9
34.9
41.7

20.2
24.0
26.0
32.3

8.3
8.3
8.3
8.3

28.2
32.0
34.0
40.4

-8
-4

22.6
27.1

8.7
8.8

31.0
35.5

21.4
25.7

9.7
9.8

30.7
35.1

20.1
24.2

10.8
10.9

30.4
34.6

18.7
22.6

12.1
12.2

30.2
34.2

2
5
7
12

35.4
41.6
44.8
54.7

8.9
8.9
8.9
9.0

44.0
50.3
53.5
63.5

33.7
39.7
42.9
52.4

9.9
9.9
9.9
10.0

43.3
49.3
52.5
62.1

31.9
37.6
40.6
49.7

11.0
11.1
11.1
11.1

42.5
48.3
51.3
60.5

30.0
35.4
38.4
47.1

12.3
12.4
12.4
12.4

41.8
47.3
50.3
59.1

-8
-4

30.0
35.7

11.8
11.8

41.3
47.0

28.0
33.7

13.2
13.2

40.6
46.4

26.0
31.6

14.8
14.8

40.1
45.7

24.0
29.3

16.7
16.7

39.7
45.1

2
5
7
12

47.3
56.1
60.5
75.0

11.9
12.0
12.0
12.1

58.8
67.7
72.2
86.8

45.2
53.3
57.8
71.5

13.3
13.3
13.4
13.4

58.0
66.2
70.8
84.6

42.5
50.2
54.5
67.6

14.9
14.9
14.9
15.0

56.8
64.6
69.0
82.2

39.6
47.0
51.0
63.5

16.7
16.7
16.7
16.8

55.6
63.1
67.1
79.8

-8
-4

36.5
44.0

14.7
14.8

50.5
58.3

34.5
41.7

16.4
16.5

50.1
57.6

32.3
39.3

18.3
18.4

49.7
56.8

30.0
36.6

20.5
20.6

49.4
56.2

2
5
7
12

58.5
68.8
74.4
91.9

15.0
15.1
15.2
15.4

73.1
83.5
89.2
106.9

55.6
65.6
71.1
87.6

16.7
16.8
16.9
17.1

71.7
81.9
87.5
104.2

52.5
62.1
67.2
83.2

18.6
18.7
18.8
18.9

70.4
80.1
85.4
101.6

49.3
58.3
63.2
78.4

20.8
20.9
21.0
21.1

69.2
78.4
83.4
98.9

-8
-4

45.0
53.3

17.5
17.6

61.7
70.3

42.0
50.7

19.5
19.6

60.5
69.5

39.5
47.7

21.7
21.9

60.1
68.6

36.8
44.8

24.3
24.5

59.7
68.0

2
5
7
12

70.4
82.4
89.3
109.8

17.8
18.0
18.0
18.2

87.7
99.9
106.8
127.6

67.1
79.3
85.5
104.8

19.8
20.0
20.0
20.2

86.3
98.7
105.0
124.5

63.5
75.0
81.0
99.8

22.1
22.2
22.3
22.4

84.8
96.5
102.6
121.6

59.7
70.5
76.5
94.2

24.7
24.8
24.9
25.0

83.3
94.4
100.4
118.4

-8
-4

51.8
62.5

20.7
20.9

71.6
82.6

48.9
59.2

22.9
23.1

70.7
81.4

46.0
55.8

25.4
25.7

70.1
80.3

43.0
52.3

28.3
28.5

69.7
79.4

2
5
7
12

82.7
97.8
105.3
129.5

21.3
21.5
21.7
22.0

103.3
118.8
126.4
151.1

78.6
93.0
100.5
123.8

23.5
23.8
23.9
24.3

101.3
116.1
123.7
147.5

74.4
88.0
95.3
117.5

26.1
26.3
26.5
26.9

99.5
113.4
120.9
143.6

70.1
82.8
89.8
111.0

29.0
29.2
29.4
29.8

97.8
111.0
118.1
139.9

-8
-4

60.1
72.5

23.8
24.0

82.8
95.6

56.9
68.8

26.2
26.5

81.9
94.2

53.5
64.8

29.1
29.3

81.1
92.7

50.0
60.6

32.2
32.5

80.4
91.5

2
5
7
12

95.9
113.4
122.3
151.3

24.5
24.8
24.9
25.4

119.6
137.5
146.6
176.1

91.2
107.6
116.9
143.9

27.0
27.3
27.5
28.0

117.3
134.1
143.6
171.2

86.2
101.9
110.4
136.4

29.8
30.2
30.4
30.9

114.9
131.0
139.8
166.4

81.0
96.0
104.1
128.7

33.0
33.4
33.6
34.2

112.7
128.2
136.5
161.8

Glycol water

120Z
Pure water

Glycol water

150Z
Pure water

Glycol water

200Z

R407C

35

Evaporator water
outlet temperature
C

Pure water

Glycol water

240Z
Pure water

Glycol water

300Z
Pure water

Glycol water

350Z
Pure water

Glycol water

400Z
Pure water

Pf : Cooling output
Pa : Compressor power input
Pc : Heating capacity

Pf
kW

Pa
kW

Pc
kW

13.7
18.7
22.2
24.1
30.1

9.4
9.4
9.4
9.3
9.3

22.5
27.6
31.2
33.1
39.1

20.9
28.0
33.1
35.8
44.1

13.7
13.8
13.8
13.8
13.9

33.8
41.1
46.4
49.1
57.5

26.8
36.6
43.5
47.3
59.2

18.9
18.8
18.8
18.8
18.8

44.6
54.5
61.6
65.4
77.3

33.8
45.8
54.3
59.0
73.3

23.2
23.3
23.4
23.5
23.6

55.6
68.0
76.7
81.5
96.1

41.5
55.7
65.9
71.5
88.5

27.4
27.6
27.7
27.8
27.9

67.3
82.0
92.5
98.2
115.5

48.6
65.4
77.4
84.0
104.1

31.8
32.2
32.5
32.7
33.1

78.6
96.2
108.6
115.4
136.1

46.4
56.4
75.8
89.8
97.5
120.9

35.9
36.2
36.7
37.1
37.3
38.0

80.1
90.6
110.8
125.4
133.4
157.5

Zone where use of water / glycol is compulsory


Calculation fouling 0.00005 m2 C/W
Standard conditions

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

Water chillers

LG
COOLING

AND HEATING CAPACITIES REJECTED ON REMOTE CONDENSER

DYNACIAT LGN

CONDENSING TEMPERATURE C

LGN

Evaporator water
outlet temperature
C
Glycol water

500Z
Pure water

Glycol water

540Z

R407C

Pure water

Glycol water

600Z
Pure water

Glycol water

753Z
Pure water

Glycol water

900Z
Pure water

Glycol water

1000Z
Pure water

Pf : Cooling output
Pa : Compressor power input
Pc : Heating capacity

35

40

45

55

50

Pf
kW

Pa
kW

Pc
kW

Pf
kW

Pa
kW

Pc
kW

Pf
kW

Pa
kW

Pc
kW

Pf
kW

Pa
kW

Pc
kW

Pf
kW

Pa
kW

Pc
kW

-8
-4

73.75
89

27.97
28.3

100.6
116.3

70.1
84.9

31.2
31.7

99.9
115.3

67.1
80.3

34.7
35.3

100.1
114

63.2
75.7

38.5
39.2

99.7
113

2
5
7
12

115.9
135.9
146.1
178.9

28.9
29.3
29.6
30.2

144
164.4
174.9
208.4

110.9
130.2
140.7
172.1

32.4
32.9
33.1
33.8

142.2
162.0
172.9
205.1

105.4
123.9
133.9
164.3

36.1
36.6
36.9
37.7

140.2
159.3
169.7
200.9

99.7
117.3
126.9
155.9

40.2
40.8
41.1
41.9

138.2
156.6
166.4
196.5

58.9
70.8
93.5
110.1
119.1
146.7

42.7
43.4
44.6
45.2
45.6
46.5

99.1
112
136
153.5
162.9
191.6

-8
-4

80.3
98.2

32.0
32.3

110.9
129.3

76.1
93.2

35.7
36.0

110.1
127.8

71.7
87.9

40.0
40.2

109.6
126.3

67.4
82.4

44.8
45.0

109.6
125.1

2
5
7
12

129.2
154.3
167.0
204.6

32.6
32.8
32.9
33.2

160.8
186.3
199.1
237.0

123.3
146.9
158.7
195.8

36.3
36.5
36.6
36.9

158.4
182.3
194.2
231.7

116.5
139.2
150.4
185.3

40.5
40.7
40.8
41.0

155.6
178.5
190.0
225.2

110.0
130.9
142.0
175.2

45.3
45.5
45.6
45.8

153.5
174.8
186.0
219.6

76.3
102.5
122.2
132.3
163.7

50.4
50.8
51.0
51.0
51.2

124.0
150.9
171.0
181.3
213.2

-8
-4

88.0
106.9

34.9
35.2

121.3
140.8

83.3
101.3

38.9
39.2

120.3
138.9

77.8
95.3

43.4
43.8

119.0
137.1

72.9
89.3

48.6
48.9

118.8
135.7

2
5
7
12

140.8
162.8
178.5
220.1

35.7
35.9
36.0
36.3

175.4
197.7
213.6
255.6

134.4
157.2
170.4
210.5

39.7
39.9
40.1
40.3

172.7
195.9
209.3
249.8

127.2
149.6
161.8
200.1

44.2
44.5
44.6
44.9

169.7
192.6
205.0
243.8

119.2
140.4
152.3
189.1

49.4
49.6
49.8
50.1

166.5
188.2
200.3
237.6

83.1
111.1
131.5
143.0
177.6

54.7
55.2
55.5
55.6
55.9

134.7
163.7
184.7
196.4
231.5

-8
-4

116
138

42
42

156
179

111
133

47
48

155
178

105
126

52
53

155
177

99
119

58
59

154
175

2
5
7
12

178
206
222
268

43
44
44
45

220
248
265
312

171
197
214
257

48
49
49
50

218
245
261
306

163
188
204
246

54
55
55
56

215
241
257
300

154
178
193
233

60
61
61
62

212
237
252
294

92
111
144
167
181
220

64
65
67
68
68
69

153
173
208
232
247
287

-8
-4

137
165

52
52

186
215

130
157

57
58

185
213

123
149

64
65

184
211

116
141

71
72

183
209

2
5
7
12

214
249
270
325

53
54
54
55

266
301
322
379

205
238
258
312

59
60
60
61

262
296
316
371

195
226
245
297

66
66
67
68

258
291
310
363

184
214
231
281

73
74
74
75

254
285
303
354

108
131
172
200
217
269

79
80
81
82
83
84

182
207
250
279
297
350

-8
-4

151
181

56
56

205
236

145
174

62
63

204
234

138
165

69
71

204
233

130
156

77
78

203
231

2
5
7
12

234
271
293
352

57
58
58
59

290
327
349
410

224
260
281
339

64
65
66
67

287
323
345
404

214
248
268
323

72
73
73
74

283
318
339
396

202
235
254
307

80
81
82
83

279
313
333
387

121
146
190
220
239
289

86
87
89
90
91
92

202
229
275
307
326
378

Zone where use of water / glycol is compulsory


Calculation fouling 0.00005 m2 C/W
Standard conditions

NOTES
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
10

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

WATER

LG

Water chillers
PRESSURE DROP

LG - LGP 120 - 1000


Condenser and evaporator
(prohibited use outside limit applications)

Water pressure drop in mWG

EVAPORATOR

Water flow m3/h

Water pressure drop in mWG

CONDENSER

Water flow m3/h

Units conversion formulae


kPa

= bar x 100

Foot (ft)

= mm x 0.0032808

bar

= mH2O x 0.0981

Pounds (lb)

= kg x 2.205

kg/cm2

= bar x 1.0197

Cubic foot mn (cfm)

= m3/h x 0.5885

Pi (lbf/in2)

= bar x 14.504

US Gallons

= m3 x 264.2

Inches (in)

= mm x 0.0394

UK Gallons

= m3 x 220

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

11

Water chillers

LG
WATER

PRESSURE DROP

LGN 120 - 1000


Evaporator only
(prohibited use outside limit applications)
EVAPORATOR

00

24

30

60

54

35

40

00

12

53

15

10

00

50

Units conversion formulae


= bar x 100

Foot (ft)

= mm x 0.0032808

= mH2O x 0.0981

Pounds (lb)

= kg x 2.205

kg/cm

= bar x 1.0197

Cubic foot mn (cfm)

= m3/h x 0.5885

Pi (lbf/in2)

= bar x 14.504

US Gallons

= m3 x 264.2

Inches (in)

= mm x 0.0394

UK Gallons

= m3 x 220

kPa
bar
2

12

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

LG

Water chillers
DIMENSIONS
DYNACIAT LG - LGP 120 to 1000

a : Condenser cooling water outlet (LG)


Condenser hot water outlet (LGP)
b : Condenser cooling water inlet (LG)
Condenser hot water inlet (LGP)
c : Evaporator chilled water outlet
d : Evaporator chilled water inlet
e : Electrical supply

Antivibratil mounts

LG-LGP

120

Fig.

150

200

240

300

350

400

500

540

600

G 11/2

c-d

G 11/4

127

Mass Kg

G 11/2

900

1000

Connectors
a-b

753

Flange PN16

G 2

G 21/2

126

DN 80

DN 100

127

122

454

492

446

408

Empty

230

300

385

390

590

620

665

735

930

1125 1045 1223 1223

in
operation

240

312

400

406

617

650

703

780

990

1190 1128 1315 1315

N A

0 4 . 5 3 8

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

13

Water chillers

LG
DIMENSIONS
DYNACIAT LGN 120 to 1000

140 280 280

321

585 150 150 150

385

680

270

98

461

95

169 150 150 150 169

a : Discharge piping connection


b : Liquid return piping connection
c : Evaporator chilled water outlet
d : Evaporator chilled water inlet
e : electrical supply

LGN

Masse Kg

14

120

Figure
Circuit 2 Circuit 1

Antivibratil mounts

150

200

240

300

350

400

500

540

600

753

1000

4
Tube 21/8

11/8

13/8 13/8

15/8

21/8

15/8 15/8

7/8

7/8

11/8

11/8

11/8 11/8 13/8

11/8

900

11/8
Tube

13/8 15/8

13/8

21/8

11/8 11/8 11/8

13/8

c-d

G 11/4

A
B
C

127

G 11/2

G 2

G 21/2

PN 16 DN 80 Brides PN 16 DN 100

111
535
365

122
563
337

975

1135 1135

563
337

Vide

223

284

375

436

518

548

586

591

835

954

en
service

232

296

390

452

543

577

621

636

883

1008 1017 1117 1117

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

PIPING

LG

Water chillers
INSTALLATION EXAMPLE

COOLING installation with water dry-cooler

COOLING-HEATING installation on underground water

WINTER

SUMMER

chilled water circuit

air purge

hot water recovery circuit

water filter (compulsory)

water filling

flexibles (compulsory)

expansion tank
balance valve

thermometer wells
water discharge

drain

4 ways water valve

stop valve

accessible exchanger

temperature controller

relief valve

Note : the above piping diagrams examples are only indicative and do not purport to show the installation details necessary.

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

15

Water chillers

LG
DYNACIAT LG - LGP - LGN

SERIES

Installation recommendations
Instructions for water quality criteria
WARNING : A water filter (600 microns) must be mounted on the unit inlet by the installer.
Correct and specified operation along with the assurance of reasonable life expectancy from the chiller-heater is significantly
dependent on the water circuits, specially if the water quality is allowed to cause scaling, corrosion, the formation of algae
growth or the establishment of micro-organic growth.
The water quality must be absolutely analyzed to ensure that it is suitable for use on the machine, and to establish that
chemical treatment will be sufficient to hold the water quality to acceptable limits and if it will be necessary to install a
softening/demineralision process.
This water analysis must confirm or not the compatibility of the water used on the spot with the following schedule of the
different materials existing on the machine CIAT :
- copper tubes 99.9% brazed with copper and silver filler,
- depending from models, bronze threaded connexions or steal flange couplings,
- exchangers with plates and connexions in stainless steal AISI 316 - 1.4401 brazed with copper and silver filler.
Caution : the no respect of these instructions will avoid immediately the warranty of the chiller.

Lifting and handling operations


Work with the best safety conditions for people during the lifting and handling operations.
Follow absolutely the lifting instructions provided on the machine and the Installation, Operating, Commissioning and
Maintenance instructions manual.
Properly plan to ensure an accessible route to the place of installation before moving the machine.
Always lift the unit in a vertical manner, and In any case the machine can be bent or put on an horizontal position.

Location of the machine


DYNACIAT units are designed to be positioned indoor in a technical plant.
Frozen protections have to be included.
A great attention must be paid to accessing the unit for the service space necessary for the maintenance, also on the top.
The machine has to be mounted on a level, non combustible flat and horizontal floor with a foundation capable of supporting
the operation weight.
Countermeasures against the noise level of the auxiliaries like pumps are recommended.
So before the installation, prevent with a sound specialist the different possible sources of noise transmission, depending of the
machine room and its design.
Its NECESSARY to fit the pipework with rubber expansion joints (optional equipment).

Venting of technical plant


In accordance with the regulations on the installation spot, a fresh air supply system may be installed to avoid dangerous
situation or no comfort in case of refrigerant leakage from the cicuit of the machine.

Installation of the accessories :


Several optional accessories can be separately delivered from the unit, to be mounted on spot on the machine.
Follow absolutely the instructions of the Installation, Operating, Commissioning and Maintenance manual

Field electrical wiring :


Follow absolutely the Installation, Operating, Commissioning and Maintenance instructions manual.
All necessary instructions for electrical connections are detailed on the wiring diagrams attached to the unit.
(They must be strictly followed)
The connections must respect the good engineering practices and be conform to norms and regulations in force.
Field electrical wiring on the spot :
. main electric power supply,
. remote control of the machine (if necessary)
. free contacts informations (optional).
It is important to note that the unit is not protected against lightning transients on the electrical supply.
Accordingly, the installation must be fitted of apparatus to furnish an adequate transient protection, and such devices must be
incorporated in the field power electric box.

16

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

LG

Water chillers
Piping connections :
Follow absolutely the Installation, Operating, Commissioning and Maintenance instructions manual.
All piping shall be properly aligned and graded to a drain valve to permit complete drainage of the system. All pipes must be
installed and connected to the machine ensuring that complete access for service is provided and that all panels, then covered
with a thermal insulation.
Adequately support and brace the piping independently of the unit to avoid vibrations and strain on the piping connections.
Isolating valves and manual valves for water flow adjustment must also be installed.
- Field water connections required on the spot :
. water supply of the pipes installation check-pressure reducing valve,
. evaporator, condenser and water drain,
- Provide the accessories necessary for all hydraulic circuits, for example :
. a cooling water flow control valve, thermostatic type, mounted on the inlet side or outlet side of the condenser,
. water expansion tank,
. drain valves on pipes bottom points to extract all the water,
. exchangers stop valves and water filter,
. air purge valves on pipes top points,
. check that there is a sufficient water volume in the installation (if necessary provide a storage tank),
. rubber expansion joints on the exchangers inlet and outlet water side.
. thermowells at each inlet and outlet connection for measurement during commissioning and maintenance procedure.
Caution :
- Water circuit pressure do not exceed 4.0 bar,
- Expansion tank mounted before water pump,
- Do not install any valve on the expansion tank.
- Be sure to install the water circulating pumps immediately on the exchangers water inlet side.
- Be sure that the water pressure at the suction of each circulating pump is equal or higher than the minimum pressure NPSH
required, particularly in case of an "open" type circuit.
- Referring the technical conditions, the water quality criteria have to be analyzed.
- The frozen protection of the unit and the hydraulic piping is necessary, like the possibility of a water drain of the circuit.
In case of use of glycol for a protection against freezing, it is absolutely necessary to control the physical properties and the
concentration before commissioning.
- Before making final connection to the chiller-heater, the piping must be flushed with clean water to remove debris in the circuit.

Start up
The commissioning of DynaCiat machines must be made by CIAT or by a company agreed by CIAT.
Follow absolutely the Installation, Operating, Commissioning and Maintenance instructions manual.
Non exhaustive list of operations to be carried out during commissioning :
- Check the correct location of the machine
- Verification of the electrical supply protection- Verification of the phases and correct rotation direction
- Verification of the electrical connections on the unit
- Verification of correct sense of water circulation on the unit
- Verification of the water circuit cleanliness
- Water flow adjustment to the specified value
- Verification of the refrigeration circuit pressures
- Verification of the correct compressors rotation direction
- Verification of the water pressure drops and water flows
- Completion of running parameters check list

Maintenance operations
The machine require specific routine maintenance operations which must be provided by authorized service agents agreed by
CIAT.
A report of the running parameters must be completed on a special form "CHECK LIST" which may be directed to CIAT.
For this operation, refer and follow absolutely the instructions of the Installation, Operating, Commissioning and Maintenance
instructions manual.
It is necessary to take out a maintenance contract of the unit with a specialist on refrigerating machines agreed by CIAT,
including the period of warranty.

DYNACIAT LGN

SERIES

Refrigeration connections
- Follow absolutely the installation, Operating, Commissioning and Maintenance instructions manual.
- The pipes must be realised in refrigerant quality copper and following the stat of the art..
- As those units has been designed for a connection to a removed condenser not supplied by CIAT, refrigerant connections as
well as commissioning will not be carried out by us.
- The pipe runs should be designed carefully and bearing in mind the requirements to facilitate the oil return to the compressor and
pressure drops which can impair the performances.

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

17

Water chillers

LG

DRYCOOLERS
AIR

COOLED CONDENSERS

The CIAT drycoolers and air cooled condensers series


EUROPA
AIRIAL
are
compatible
with
the
DYNACIAT LG units with water cooled condensers or DYNACIAT LGN units without condenser.

Available in a large choice of sizes and 6 ventilation speeds,


EUROPA and AIRIAL units are adapted to the
dimensional or acoustic constraints of the site.

18

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

LG

Water chillers
NOTES
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -

N A

0 4 . 5 3 8

19

Non contractual document. With the thought of material improvement always in mind, CIAT reserves the right, without notice, to proceed with any technical modification.

Sige social & Usines


Avenue Jean Falconnier - B.P. 14
01350 Culoz - France
Tl. : 04 79 42 42 42 - Fax : 04 79 42 42 10
Internet : http://www.ciat.com

Dpartement Rfrigration
Tl. : 04 79 42 42 30 - Fax : 04 79 42 40 11

Export Department
Tl. : 33 4 79 42 42 20 - Fax : 33 4 79 42 42 12

Compagnie Industrielle dApplications Thermiques


S.A. au capital de 26 000 000 - R.C.S. Belley B 545 620 114

20

A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -