Вы находитесь на странице: 1из 1

Project: Keadue WWTP Upgrade Works Section:

Drawin g Ref:

Job No. :

Calculation Sheet No : Clarifier Design Calculations By:


Ken Geelan 1

Checked By:

Date:

Reference:

Calculations

Output

Clarifier Tank Design Calculations


INSERT RELEVANT DATA INTO HIGHLIGHTED AREAS

Inputs Population Eqivalent = Flow Per Person = Dry Weather Flow (DWF) = Flow, Q = OverFlowrate - OR = Clarifier Design MLLS, X = Return Sludge Mass Concentration, Xr = 15 1500 g/m
3

550

PE

225 l/person/day 6 743 m /d


3

8000

g/m

Calculations Area, A = therefore = 49.50 50.00 m2 m


2

Hydraulic Application Rate of 22 m3/m2.d Assumed at Average Flow (Table 8-7 [Range Between 16 - 28 m3/m2.d]) Diameter, D = 7.97 8.00 Height, H = R= 6.2 3.1 m m m m m2 m2

Area of Clarifier, A = therefore =

50.265 50.50

Solids Loading =

0.0

kg MLSS/m2.h

Aceptable Limits for Soilds Loading Range Between 4 - 6 kg/m2.d (Table 8-7) Equations used for Calculations: R = X / Xr - X

A = Q / OR

Solids Loading = (1 + R) (Q) (MLSS) / A