This guide is intended for a quick startup of the eVD4. You will get to know how to supply the integrated relay RBX615 and the required inputs to make the circuit-breaker operate. Moreover, you will see the functions of inputs and outputs, their related pins on the plug and their configurability.
Power supply
To supply the integrated relay refer to the following two steps. 1. Connect the power supply to pins number 2 (+) and 3 (-). In this way you supply the power supply card (-X100). In the picture below, a part of the related circuit diagram is shown.
2. Connect the power supply to pins number 48 (+) and 49 (-). In this way you supply the extension board (-X200) and you enable the two H bridges. In the picture below a part of the related circuit diagram is shown. In this example the H bridges (HB 1 and HB 2) supply the motor for operating the earthing switch (-MAE) and the motor for moving the truck (-MAT).
2 1 2
1 48 *E) *G)
48
101
202
XDB23 GN/BL
1 VH/RD
201 2
49
50
51
49
50
51
MAT
M
MAE
Inputs
In the table below it is possible to find the function of each input, depending on the version of your eVD4. If the input is configurable (inputs from 1 to 10) you can also find the respective pins in the plug.
Function Binary Input number Card Fixed version eVD4 Feeder Protection (F1, F2, F3) Ext. Protections Alarm Ext. Protections Trip MCB closed Available Enable to close Blocking OC inst. stage General Reset Emergency opening Earthing switch close Earthing switch open CB remote closing CB remote opening CB closed signalling CB open signalling Truck in test position Truck in service position Withdrawable version eVD4 Feeder Protection (F1, F2, F3) Ext. Protections Alarm Ext. Protections Trip MCB closed Enable truk moving Enable to close in insert pos. Blocking OC inst. stage General Reset Emergency opening Earthing switch close Earthing switch open CB remote closing CB remote opening CB closed signalling CB open signalling Truck in test position Truck in service position Fixed version eVD4 Motor Protection (M1, M2) Ext. Protections Alarm Ext. Protections Trip MCB closed Available Enable to close General Reset Emergency opening Earthing switch close Earthing switch open CB remote closing CB remote opening CB closed signalling CB open signalling Truck in test position Truck in service position Withdrawable version eVD4 Motor Protection (M1, M2) Ext. Protections Alarm Ext. Protections Trip MCB closed Enable truk moving Enable to close in insert pos. General Reset Emergency opening Earthing switch close Earthing switch open CB remote closing CB remote opening CB closed signalling CB open signalling Springs charged signalling Truck in test position Truck in service position Configurable Available in plug (pins)
BI 1 BI 2 BI 3 BI 4 BI 5 BI 6 BI 7 BI 8 BI 9 BI 10 BI 11 BI 12 BI 13 BI 14 BI 15 BI 16 BI 17
I/O expansion (-X200) I/O expansion (-X200) I/O expansion (-X200) I/O expansion (-X200) I/O expansion (-X200) I/O expansion (-X200) I/O expansion (-X200) I/O expansion (-X200) I/O expansion (-X200) I/O expansion (-X200) Basic Card (-X300) Basic Card (-X300) Basic Card (-X300) Basic Card (-X300) Basic Card (-X300) Power supply (-X100) Power supply (-X100)
yes yes yes yes yes yes yes yes yes yes no no no no no no no
yes (49-29) yes (49-32) yes (49-33) yes (49-34) yes (49-36) yes (49-37) yes (49-44) yes (49-45) yes (49-46) yes (49-47) yes yes no no no no no
In the circuit diagram below the pins on the plug for each output are highlighted.
29 29 32
32 33
33 34
34 36
36 37
37 44
44 45
45 46
46 47
47 48 215
48
207
208
209
210
211
212
213
214
215
205
BI 1
BI 2
BI 3
BI 4
BI 5
BI 6
BI 7
BI 8
BI 9
BI 10
205
49 49
To feed one input is sufficient to connect pin number 49 (common for all the inputs) to the negative pole and the positive pole to the corresponding pin. For example to feed input number 5 (BI5) supply pin 49 (-) and pin 36 (+). Its necessary to supply the following inputs to respect the relay logic: Input 3 (Micro Circuit-breaker Closed): it represents the status of the micro circuit-breakers in the low voltage compartment of the panel. If this input is not supplied, a red LED on the HMI will switch on. The circuit-breaker is anyway operable even with this LED on. Both for fixed and withdrawable version. Input 4 (Enable truck moving): to unlock the truck locking magnet (RLE2) and to be able to rack in the circuitbreaker. Only for withdrawable version. Input 5 (Enable to close in inserted position): to close the circuit-breaker once inserted. Both for fixed and withdrawable version.
Input 8 (Emergency opening): if not supplied, this input sends an emergency opening command. Both for fixed and withdrawable version. Input 10 (Earthing switch open): it represents the status of the earthing switch. It is possible to close the circuit-breaker only when this input number 10 is supplied, i.e. the earthing switch is open. If there is the earthing switch you need to wire it in the way that the input number 10 is supplied when the earthing switch is in the open position. If there is no earthing switch, just supply the input number 10 to be able to close the circuit-breaker. Both for fixed and withdrawable version.
Outputs
In the table below it is possible to find the function of each output, depending on the version of your eVD4. If the output is configurable (inputs from 1 to 6) you can also find the respective pins in the plug.
Card I/O expansion (-X200) I/O expansion (-X200) I/O expansion (-X200) I/O expansion (-X200) Power supply (-X100) Power supply (-X100) Power supply (-X100) Power supply (-X100) Power supply (-X100) Power supply (-X100) Power supply (-X100) Basic Card (-X300)
Function Protection with Auto-Reclose selected General operate indication General start indication Cumulative Alarm Unsuccess AR K86 tripped CBFP open upstream Locking electromagnet on operating mechanism (-RLE1) Shunt closing release (-MBC) Shunt opening release (-MBO1) Watchdog CB ready Locking electromagnet on truck (-RLE2) Protection without Auto-Reclose selected General operate indication General start indication Cumulative Alarm Available K86 tripped CBFP open upstream Locking electromagnet on operating mechanism (-RLE1) Shunt closing release (-MBC) Shunt opening release (-MBO1) Watchdog CB ready Locking electromagnet on truck (-RLE2)
Available in plug (pins) yes (20-21) yes (22-23) yes (24-26) yes (27-28) yes (12-13) yes (14-15) no no no yes yes no
In the circuit diagram below the pins on the plug for each output are highlighted.
To see the value of each output is sufficient to connect to the related pins on the plug.
20 20 22
22 24
24 27 221
27
217
219
223
BO 1
BO 2
BO 3
BO 4
218
220
220
21
23
26
21
23
26
28 28
ABB S.p.A. Power Products Division Unit Operativa Sace-MV Via Friuli, 4 I-24044 Dalmine Tel.: +39 035 6952 111 Fax: +39 035 6952 874 E-mail: info.mv@it.abb.com
ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone: +358 10 22 11 Fax: +358 10 22 41094 www.abb.com/substationautomation
ABB AG Calor Emag Medium Voltage Products Oberhausener Strasse 33 Petzower Strasse 8 D-40472 Ratingen D-14542 Glindow Phone: +49(0)2102/12-1230, Fax: +49(0)2102/12-1916 E-mail: powertech@de.abb.com www.abb.com
The data and illustrations are not binding. We reserve the right to make changes without notice in the course of technical development of the product. Copyright 2012 ABB. All rights reserved.