Configuration of Direct Starters with the APL Channel Block FbSwtMMS in SIMATIC PCS 7
SIMATIC PCS 7 V8.0 Application Example October 2012

Applications & Tools


Answers for industry.

Siemens Industry Online Support This document is an article from the Siemens Industry Online Support. The following link takes you directly to the download page of this document: http://support.automation.siemens.com/WW/view/en/64182525

Caution: The functions and solutions described in this entry are mainly limited to the realization of the automation task. In addition, please note that suitable security measures in compliance with the applicable Industrial Security standards must be taken, if your system is interconnected with other parts of the plant, the companys network or the Internet. For further information on this issue, please refer to Entry ID 50203404. http://support.automation.siemens.com/WW/view/en/50203404

Copyright Siemens AG 2012 All rights reserved

Please also use our technical forum from the Siemens Industry Online Support actively in this context. Add your questions, suggestions and problems and discuss them in our large forum community: http://www.siemens.com/forum-applications

Configuration of Direct Starters V 1.0, Entry ID: 64182525

Description of the task and solution APL channel block Motor Management Starter (FbSwtMMS) Configuration Links History

1 2 3 4 5

SIMATIC PCS 7 V8.0 Configuration of Direct Starters with the APL Channel Block FbSwtMMS in SIMATIC PCS 7
Application Example

Copyright Siemens AG 2012 All rights reserved

Configuration of Direct Starters V 1.0, Entry ID: 64182525

Warranty and Liability

Warranty and Liability


Note The application examples are not binding and do not claim to be complete regarding configuration, equipment and any eventuality. The application examples do not represent customer-specific solutions. They are only intended to provide support for typical applications. You are responsible for ensuring that the described products are used correctly. The application examples do not relieve you of the responsibility to use sound practices in application, installation, operation and maintenance. When using these application examples, you recognize we will not be liable for any damage/claims beyond the liability clause described. We reserve the right to make changes to these application examples at any time without prior notice. If there are any deviations between the recommendation provided in this application example and other Siemens publications (e.g. catalogs), the contents of the other documentation shall have priority. We accept no liability for information contained in this document. Any claim against us based on whatever legal reason - resulting from the use of the examples, information, programs, engineering and performance data etc., described in this Application Example shall be excluded. Such an exclusion shall not apply in the case of mandatory liability, e.g. under the German Product Liability Act (Produkthaftungsgesetz), in cases of intent, gross negligence, or injury of life, body or health, guarantee for the quality of a product, fraudulent concealment of a deficiency or violation of fundamental contractual obligations (wesentliche Vertragspflichten). The damages for a breach of substantial contractual obligations are, however, limited to the foreseeable damage, typical for the type of contract, except in the event of intent or gross negligence or injury to life, body or health. The above provisions do not imply a change in the burden of proof to your detriment. Any form of duplication or distribution of these application examples or excerpts hereof is prohibited without the express consent of Siemens Industry Sector.

Copyright Siemens AG 2012 All rights reserved

Configuration of Direct Starters V 1.0, Entry ID: 64182525

Table of Contents

Table of Contents
Warranty and Liability ..............................................................................................4 1 Description of the task and solution .............................................................6 1.1 1.2 1.2.1 1.2.2 1.2.3 2 2.1 2.2 3 3.1 3.2 3.3 3.4 3.5 4
Copyright Siemens AG 2012 All rights reserved

Task ..................................................................................................6 Solution .............................................................................................6 Main contents....................................................................................6 Restriction .........................................................................................7 Validity ..............................................................................................7 Channel block....................................................................................8 Template .........................................................................................12 Requirement....................................................................................13 Importing the EDD/GSD file ............................................................. 13 Hardware configuration.................................................................... 14 CFC engineering .............................................................................18 OS-Runtime.....................................................................................24

APL channel block Motor Management Starter (FbSwtMMS) ...................8

Configuration................................................................................................13

Links .............................................................................................................25 History ..........................................................................................................25

Configuration of Direct Starters V 1.0, Entry ID: 64182525

1 Description of the task and solution

1
1.1

Description of the task and solution


Task
In modern automation projects, not all the components are supplied by the same company. You often have the situation that the supplier of the process control system is not the same as the supplier of the drives. Moreover, not every customer needs the complete and extensive range of functions for the drives, which can be retrieved by specifically tailored block libraries, most of them chargeable.

1.2

Solution
For the integration of the direct starter drives Siemens therefore offers a modern motor channel block FbSwtMMS, which is part of the PCS 7 standard library Advances Process Library (APL), allowing for an integration into PCS 7 of all the drives which support the standard profiles of the technical specification Profiles for Low Voltage Switchgear Devices.

Copyright Siemens AG 2012 All rights reserved

In addition, this variant is also interesting for the integration of Siemens drives such as SIMOCODE pro. The complete performance range is not always needed. By interconnecting the motor channel block FbSwtMMS with the APL function block MotRevL, the complete function range of the PCS 7 operation, monitoring and supervision is available. The configuration, parameterization and commissioning of the drives takes place in the usual PCS 7 environment.

1.2.1

Main contents
The integration of a directly starting drive is explained and completely configured as an example with a SIMOCODE pro V and a prefabricated template, which is also a part of the PCS 7 Advanced Process Library (APL). The focus will be on the following issues: Channel block FbSwtMMS Structure of the standard profiles Integration of the template Hardware configuration CFC engineering Parameterization of the drives via PDM

Configuration of Direct Starters V 1.0, Entry ID: 64182525

1 Description of the task and solution

1.2.2

Restriction
This configuration instruction describes the integration of directly starting drives which support the standard protocol. As an example the Siemens drive SIMOCODE pro V is configured, all the other drives will be configured in exactly the same way. This application does not refer to the SIMOCODE library which is available separately for a fee and covers the complete performance range of the SIMOCODE drives.

1.2.3

Validity
This Application Example is valid for PCS 7 V 8.0 and higher.

All drives which support the standard profiles of the technical specification Profiles for Low Voltage Switchgear Devices and for which a compatible Electronic Device Description File (EDD) or a General Station Description (GSD) is available, can be integrated in PCS 7 V8.0.
Copyright Siemens AG 2012 All rights reserved

Configuration of Direct Starters V 1.0, Entry ID: 64182525

2 APL channel block

APL channel block Motor Management Starter (FbSwtMMS)


With the APL channel block Motor Management Starter all direct starter drives which support the standard profiles of the technical specification Profiles for Low Voltage Switchgear Devices can be integrated in the PCS 7. This enables you to integrate directly starting drives from different manufacturers into PCS 7. The channel block is part of the PCS 7 Advanced Process Library (APL). Therefore, there will be no further costs from buying an add-on or an external library. In addition the direct starters, wherever they come from, are configured in the same way in the PCS 7 environment.

2.1

Channel block
The channel block was developed according to the profiles for Motor Management Starter, which are described in the technical specification Profiles for Low voltage Switchgear Devices (LVSG).

Copyright Siemens AG 2012 All rights reserved

The Motor Management Starter profile prescribes that the format 0 has to be used for the data to the process control system and also for the data from the process control system. In case of the SIMOCODE pro V, this would be the basic type 2 with 4 bytes input and 2 bytes output data.

NOTICE

The connection of field devices into the PCS 7 via PROFINET is only entirely supported with PCS 7 V8.0 SP1.

Configuration of Direct Starters V 1.0, Entry ID: 64182525

2 APL channel block

Explanation The 4 bytes entry data are reflected in the channel block in the two inputs PZDIn1 and PZDIn2 with one word each. The 2 bytes output data are represented with the output PZDOut1 in the block.

Copyright Siemens AG 2012 All rights reserved

The input and output files are inverted as compared to the tables. In the following screenshot, the value 16#2400 is pending at the output PZDOut1, the value 24 being the higher byte and 00 the lower byte. The two individual bytes are read from right to left.

Configuration of Direct Starters V 1.0, Entry ID: 64182525

2 APL channel block

16#2400 24 2 4

Bits: (0-7 for byte constructions; 0-15 for word constructions) Byte 7 15 0 Reserved 6 14 Trip Reset 5 13 Auto Mode 4 12 Emergency Start 3 11 Self Test Reserved 2 10 Run Forward Reserved 1 9 Off 0 8 Run Reverse Reserved Higher Byte

24
Lower Byte

Manufacturer Manufacturer Manufacturer Manufacturer Specific4 Specific3 Specific2 Specific1

Reserved

00

0 00 16#2400
Copyright Siemens AG 2012 All rights reserved

In the table you can see that it is a directly starting motor, which currently runs forward in automatic mode (auto Mode and Run Forward).

10

Configuration of Direct Starters V 1.0, Entry ID: 64182525

2 APL channel block

Input data from the field device to the controller


Table 2-1
Bits: (0-7 for byte constructions; 0-15 for word constructions) 7 Byte 15 23 31 0 default 1 2 default 3 default Warning 0
Manufacturer Specific4

6 14 22 30 Fault 0
Manufacturer Specific3

5 13 21 29 Auto Mode 1
Manufacturer Specific2

4 12 20 28 Lock-Out Time 0
Manufacturer Specific1

3 11 19 27 Overload Warning 0
Manufacturer Specific6

2 10 18 26 Run Forward 0
Manufacturer Specific5

1 9 17 25 Off 1 Reserved

0 8 16 24 Run Reverse 0 Reserved

Motor Current High (% / Is) Dont Care Motor Current Low (% / Is) Dont Care

Copyright Siemens AG 2012 All rights reserved

Output data from the controller to the field device


Table 2-2
Bits: (0-7 for byte constructions; 0-15 for word constructions) Byte 7 15 0 Reserved Manufactur er Specific4 6 14 Trip Reset Manufactur er Specific3 5 13 Auto Mode Manufactur er Specific2 4 12 Emergency Start Manufactur er Specific1 3 11 Self Test Reserved 2 10 Run Forward Reserved 1 9 Off 0 8 Run Reverse Reserved

Reserved

Configuration of Direct Starters V 1.0, Entry ID: 64182525

11

2 APL channel block

2.2

Template
The template provided by the Advanced Process Library (APL) represents a complete configured CFC plan, where the APL channel block FbSwtMMS is logically interconnected with the APL function block MotRevL, thus offering a ready-to-use automation solution with the following functions: APL faceplates for PCS 7-conform operator control & monitoring. Switching between local and remote control Display of the current in the faceplate The same operator control & monitoring no matter which motor manufacturer No additional libraries required.

The template is based exclusively on the PCS 7 APL blocks, which are available as a standard from PCS 7 V8.0 onwards.

Copyright Siemens AG 2012 All rights reserved

In the template, the channel block FbSwtMMS is interconnected with the motor block MotRevL for a motor that can be switched on in forward and reverse mode. Three interlock blocks are provided for the interlocking with acknowledgment (Protect), interlocking without acknowledgement (Interlock) and the permit for switching on (Permit). Where to get the template and the channel block The channel block and the template are part of the PCS 7 V8.0 and do not require an additional installation.
Configuration of Direct Starters V 1.0, Entry ID: 64182525

12

3 Configuration

3
3.1

Configuration
Requirement
A prepared PCS 7 project is required, where at least the CPU, the communication processor and the DP master line, and all the communication paths have already been configured.

3.2

Importing the EDD/GSD file


In the Siemens device catalog you will find a great variety of field devices. If you cannot find a field device you use in this catalog, you can install the EDD or GSD file for your field device. After the installation, the field device will be available in the device catalog with an object symbol, just as you know it. You can get the EDD or GSD file from your field device supplier almost always.

Difference between EDD and GSD files The General Station Description (GSD) contains DP slave transmission features in a standard form. The use of a GSD file facilitates the configuration and integration of field devices of different manufacturers in a DP master system. The Electronic Device Description (EDD) always contains the GSD file and adds the device features of the field device. The EDD files are read in by the configuration tools, e.g. SIMATIC PDM and simplify the configuration, commissioning and maintenance of the filed devices.

Copyright Siemens AG 2012 All rights reserved

NOTICE

When a direct starter is to be integrated by means of a GSD file, it cannot be configured by means of the PDM, but only by means of a configuration tool or on site by means of an input module.

Configuration of Direct Starters V 1.0, Entry ID: 64182525

13

3 Configuration

3.3

Hardware configuration
1. Open the hardware configuration (HW Config). 2. In the device catalog, change the profile to "Standard". The device tree then only lists those field devices which support the standard protocols.

Copyright Siemens AG 2012 All rights reserved

3. In the device catalog, choose the direct starter you use, e.g. PROFIBUS DP > Additional Field Devices > Switching Devices > SIMOCODE > SIMOCODE pro V (GSD V1.3).

4. Drag and drop your direct starter to the PROFIBUS master system.

14

Configuration of Direct Starters V 1.0, Entry ID: 64182525

3 Configuration

5. Assign the new PROFIBUS address.

6. Select the basic type 2 with 4 byte input data and 2 byte output data, and drag and drop it to the respective slot.

Copyright Siemens AG 2012 All rights reserved

7. Select the line with the input and output addresses, open Object Properties with the right mouse button and select Object Properties

Configuration of Direct Starters V 1.0, Entry ID: 64182525

15

3 Configuration

8. Assign the initial addresses of the input and output addresses.


NOTICE

Make sure that the initial addresses of the input and output addresses begin with the same start value.

Copyright Siemens AG 2012 All rights reserved

Note

The FbSwtMMS block must be incorporated in the same cycle (OB) as the respective hardware.

Assign a symbolic address 9. Select the line with the addresses again and open the Edit Symbols window with a click on the right mouse button.

10. Assign the symbolic names in the Symbol column.

16

Configuration of Direct Starters V 1.0, Entry ID: 64182525

3 Configuration

PDM When a motor starter is integrated via GSD, it cannot be configured by means of PDM, but only with a separate configuration tool. 11. For the configuration via PDM, select your motor starter, in this case SIMOCODE, and open the motor properties with the right mouse button Object Properties....

Copyright Siemens AG 2012 All rights reserved

12. Select the tab General and activate the option box Configuration via PDM.

13. After the activation, double-click on the symbol figure of the direct starter to open PDM. You can now configure the direct starter.

Configuration of Direct Starters V 1.0, Entry ID: 64182525

17

3 Configuration

3.4

CFC engineering
1. Switch to the SIMATIC Manager. 2. Select File > Open in the menu bar.

Copyright Siemens AG 2012 All rights reserved

3. In the window Open Project go to the tab Libraries and select the PCS 7 AP Library V80.

4. In the PCS 7 Library V80, select the Templates folder.

18

Configuration of Direct Starters V 1.0, Entry ID: 64182525

3 Configuration

5. Select the ManagedMotorStarter template, open the context menu and select Copy.

Copyright Siemens AG 2012 All rights reserved

6. Go to the technical hierarchy and add the copied template with the right mouse button by selecting paste. 7. Rename the template. 8. Open the template. 9. Select the MotRevL block, click on the right mouse button and select Object Properties.

Configuration of Direct Starters V 1.0, Entry ID: 64182525

19

3 Configuration

10. Assign a meaningful name under Name:

Interconnect a symbolic address 11. In the CFC plan, select the input PZDIn1 of the FbSwtMMS block. Open the context menu with the right mouse button, and select Interconnection to Address.

Copyright Siemens AG 2012 All rights reserved

20

Configuration of Direct Starters V 1.0, Entry ID: 64182525

3 Configuration

12. Select the first input word of the symbolic interconnection here, in this case IW512_SC. All the other input and output words are automatically connected by the driver wizard.

Copyright Siemens AG 2012 All rights reserved

Note

The telegram type used must also be stored in the direct starter. You can make this setting by means of the respective configuration tool or when you integrated the EDD via PDM. The driver wizard checks the number of input data, compares it with those stored in the device and if they dont match, it generates an error message.

Configuration of Direct Starters V 1.0, Entry ID: 64182525

21

3 Configuration

13. The output Imax for the maximum motor current with reference to the nominal current is interconnected with the input UserAna1 of the MotRevL. Select the input UserAna1 and open the context menu with the right mouse button, then select Object Properties.

Copyright Siemens AG 2012 All rights reserved

14. Select Value [REAL] Value, open the context menu and select Properties.

22

Configuration of Direct Starters V 1.0, Entry ID: 64182525

3 Configuration

15. Enter a meaningful name like Imax in the entry box Identifier. This name will later be displayed in the faceplate next to the Imax value.

Copyright Siemens AG 2012 All rights reserved

Compiling and loading of the AS and OS 16. Compile and load the AS. 17. Compile and load the OS.

Configuration of Direct Starters V 1.0, Entry ID: 64182525

23

3 Configuration

3.5

OS-Runtime
In OS Runtime you operate and monitor the field device via the usual faceplate of the MotRevL. The operator always sees and operates the same faceplates, no matter how many different drives of different manufacturers are integrated in the system operation. This guarantees a uniform operating concept, a clearer structure and avoids operating mistakes.

Faceplate of the MotRevL

Copyright Siemens AG 2012 All rights reserved

24

Configuration of Direct Starters V 1.0, Entry ID: 64182525

4 Links

Links
The following list is by no means complete and only provides a selection of appropriate information.

Table 4-1 Topic 1 2 3 Reference to this document Siemens Industry Online Support PCS 7 quick start (start page, landing page) Title

http://support.automation.siemens.com/ WW/view/en/64182525 http://support.automation.siemens.com http://support.automation.siemens.com/ WW/view/en/63481413

5
Copyright Siemens AG 2012 All rights reserved

History
Table 5-1 Version V1.0 Date 10/2012 First issue Change

Configuration of Direct Starters V 1.0, Entry ID: 64182525