INERGENT DESIGN CALCULATION WORKSHEET

Volume Calculations: Area


Area Name : Control Room
Length : m
Width : m
Height : m
Area : m2
Volume : m3
Volume Reductions :
Structural Reduction: m3
Reduced Volume : m3
Movable object reduction :
(If more than 25% of Reduced Volume)
Total Reduced Volume : m3
Room Minimum Ambient Temperature :
Design Concentration : %
Flooring Factor :
(From Table )
Initial Inergent Quantity Calculation:
Inergent Quantity :
(Total Reduced Volume x Flooding Factor) formula from the design manuam
Altitude Correction:
Height above or below sea level : m
Factor :
(from design manual)
Actual Inergen Quantity : m3
(Initial inergen quantity x Altitude correction factor)
(Ingergen Qty. /Cylinder Capacity to next whole number (Cyl. Qty. x Cyl. Cap.)
Cylinder Requirement : Total Cylinder Capacity :
355 ft3 cylinder
266 ft3 cylinder
205 ft3 cylinder
200, 250, 350, 425, and 435 cu. ft.
(5.7, 7.1, 9.9, 12.0, and 12.3 cu. m.).
Cylinder Size Selected :
Inergen Supplied :
(Cyl. Qty. x Cyl. Cap.)
Actual Inergen Loading Factor :
(Inergen Agent Supplied / Alt. Correction Factor) + Total Reduced Volume
Concentration Range Check :
(Design concentration must be between 37.5% - 42.8% for occupied spaces)
Room Max. Ambient Temp. :
Design Concentration at Max. Temp. :
(locate actual Inergen conc. At Max. Temp. on Table or use calc in Design Manual.
(Total Reduced Volume x Flooding Factor) formula from the design manuam