Вы находитесь на странице: 1из 82

EtherNet/IP Embedded Switch Technology

Linear and Device-level Ring Topologies


Catalog Numbers 1756-EN2TR, 1783-ETAP, 1783-ETAP1F,
1783-ETAP2F, 1734-AENTR, 1738-AENTR, 1732E
Application Guide
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell
Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences
between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that
each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Allen-Bradley, ArmorBlock, ArmorPoint, CompactLogix, ControlLogix, POINT I/O, Rockwell Automation, RSLinx, RSLogix, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage,
or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may
be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach
dangerous temperatures.
3Publication ENET-AP005C-EN-P - May 2010 3
Summary of Changes
Introduction
This release of this document contains new and updated information. To find
new and updated information, look for change bars, as shown next to this
paragraph.
Updated Information
The document has been changed to provide the most accurate and common
topologies currently available with a DLR application. Refer to Common
Network Topologies on page 65, for more information.
4 Publication ENET-AP005C-EN-P - May 2010
Summary of Changes
Notes:
5Publication ENET-AP005C-EN-P - May 2010 5
Table of Contents
Preface Purpose of This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Who Should Use This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1
EtherNet/IP Embedded Switch
Technology Overview
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
EtherNet/IP Embedded Switch Technology. . . . . . . . . . . . . . . . . . . . 10
Linear Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Device-level Ring (DLR) Network . . . . . . . . . . . . . . . . . . . . . . . . . 11
Rockwell Automation Products with Embedded
Switch Technology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Features Common to Products with Embedded
Switch Technology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
DLR Network Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Supervisor Node . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Ring Node . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
DLR Network Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Number of Nodes on a DLR Network. . . . . . . . . . . . . . . . . . . . . . . . . 19
DLR Network Fault Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Chapter 2
Construct and Configure a
Device-level Ring Network
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Install Devices on a DLR Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Configure Supervisor Nodes on a DLR Network . . . . . . . . . . . . . . . . 22
Configure a Ring Supervisor in RSLogix 5000
Programming Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Enable Ring Supervisor in RSLogix 5000
Programming Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Configure and Enable a Ring Supervisor in RSLinx Classic
Communication Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Complete the Physical Connections of the Network . . . . . . . . . . . . . . 33
Verify Supervisor Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Chapter 3
Monitor a DLR Network Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Methods to Monitor a DLR Network. . . . . . . . . . . . . . . . . . . . . . . . . . 35
RSLogix 5000 Programming Software Status Pages . . . . . . . . . . . 36
RSLinx Communication Software Status Pages . . . . . . . . . . . . . . . 36
Device Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Programmatically Through the Use of a MSG Instruction . . . . . . 36
Monitor Status Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
RSLogix 5000 Programming Software Status Pages . . . . . . . . . . . 37
RSLinx Communication Software. . . . . . . . . . . . . . . . . . . . . . . . . . 38
Monitor Device Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Monitor Diagnostics via MSG Instructions . . . . . . . . . . . . . . . . . . . . . 42
Example Use of MSG Instruction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Use Specific Values on the Configuration Tab . . . . . . . . . . . . . . . 44
6 Publication ENET-AP005C-EN-P - May 2010
Table of Contents
Retrieve All Ring Diagnostic Information . . . . . . . . . . . . . . . . . . . 45
Request the Ring Participant List . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Enable and Configure a Ring Supervisor . . . . . . . . . . . . . . . . . . . . 48
Chapter 4
Troubleshoot a Linear or DLR
Network
General Solutions for Linear or DLR Networks . . . . . . . . . . . . . . . . . 49
Specific Issues on Your DLR or Linear Network . . . . . . . . . . . . . 50
Chapter 5
Additional 1783-ETAP,
1783-ETAP1F, and 1783-ETAP2F
EtherNet/IP Tap Features
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Use DIP Switches. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Internet Group Management Protocol (IGMP) Configuration
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
IGMP Snooping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
IGMP Querier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Device Port Debugging Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Replace a 1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F
Tap on the Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Port Buffer Utilization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Chapter 6
Common Network Topologies Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Standalone Linear Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Standalone DLR Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Expanding Beyond Simple Linear or DLR Networks . . . . . . . . . . 68
Appendix A
Network Usage Guidelines and
Recommendations
Appendix B
Network Recovery Performance
Index
7Publication ENET-AP005C-EN-P - May 2010 7
Preface
Purpose of This Manual
This manual describes how to install, configure and maintain linear and
Device-level Ring (DLR) networks using Rockwell Automation EtherNet/IP
devices with embedded switch technology.
Who Should Use
This Publication
You should use this manual if you develop applications that use EtherNet/IP
devices with the embedded switch technology.
You should also understand:
general EtherNet/IP networking concepts.
RSLogix 5000 programming software.
RSLinx Classic programming software.
8 Publication ENET-AP005C-EN-P - May 2010
4
9Publication ENET-AP005C-EN-P - May 2010 9
Chapter 1
EtherNet/IP Embedded Switch
Technology Overview
Introduction
Multiple topics affect your understanding of EtherNet/IP embedded
switch technology.
Prior to the introduction of products with embedded switch technology, the
traditional EtherNet/IP network topology has been a star, where end devices
are connected and communicate with each other via a switch. The diagram
below shows an EtherNet/IP star configuration.
Example EtherNet/IP Star Topology
The EtherNet/IP embedded switch technology offers alternative network
topologies for interconnecting EtherNet/IP devices by embedding switches
into the end devices themselves.
Topic Page
EtherNet/IP Embedded Switch Technology 10
Rockwell Automation Products with Embedded Switch Technology 12
DLR Network Elements 15
DLR Network Operation 18
Number of Nodes on a DLR Network 19
DLR Network Fault Management 19
10 Publication ENET-AP005C-EN-P - May 2010
Chapter 1 EtherNet/IP Embedded Switch Technology Overview
EtherNet/IP Embedded
Switch Technology
Embedded switch technology is designed to enable end devices to form linear
and ring network topologies.
Linear Network
A linear network is a collection of devices that are daisy-chained together. The
EtherNet/IP embedded switch technology allows this topology to be
implemented at the device level. No additional switches are required.
The graphic below shows an example of a linear network.
Example Linear Network
These are the primary advantages of a linear network.
The network simplifies installation and reduces wiring and installation
costs.
The network requires no special software configuration.
Embedded switch products offer improved CIP Sync application
performance on linear networks.
The primary disadvantage of a linear network is that any break of the cable
disconnects all devices downstream from the break from the rest of the
network.
IMPORTANT
Products with EtherNet/IP embedded switch technology have
two ports to connect to a linear or DLR network in a single
subnet.
You cannot use these ports as two Network Interface Cards
(NICs) connected to two different subnets.
Publication ENET-AP005C-EN-P - May 2010 11
EtherNet/IP Embedded Switch Technology Overview Chapter 1
Device-level Ring (DLR) Network
A DLR network is a single-fault tolerant ring network intended for the
interconnection of automation devices. This topology is also implemented at
the device level. No additional switches are required.
The graphic below shows an example of a DLR network.
Example DLR Network
The advantages of the DLR network include:
simple installation.
resilience to a single point of failure on the network.
fast recovery time when a single fault occurs on the network.
The primary disadvantage of the DLR topology is the additional effort
required to set up and use the network as compared to a linear or star network.
IMPORTANT
Products with EtherNet/IP embedded switch technology have
two ports to connect to a linear or DLR network in a single
subnet.
You cannot use these ports as two Network Interface Cards
(NICs) connected to two different subnets.
12 Publication ENET-AP005C-EN-P - May 2010
Chapter 1 EtherNet/IP Embedded Switch Technology Overview
Rockwell Automation
Products with Embedded
Switch Technology
The current Rockwell Automation products that you can use to construct a
DLR or linear network include:
1756-EN2TR ControlLogix EtherNet/IP 2-port module - Allows
ControlLogix controllers, I/O modules and communication modules to
connect to the DLR or linear network.
1783 EtherNet/IP taps - Allow devices that do not support embedded
switch technology to connect to a linear or a DLR network. Each tap
uses a device port on the front of the tap to connect to devices that do
not support the embedded switch technology to connect to linear or
DLR networks. The taps have two network ports to connect to linear or
DLR networks.
The network ports used to connect to linear or DLR networks are
different for each type of tap. The following table describes the types of
taps used with each tap:
The primary advantages of using fiber-optic networks are the availability
of increased distances between network nodes and greater noise
immunity on the network.
For an example of a 1783-ETAP tap using both the device port and
network ports to connect a device that does not support embedded
switch technology to a DLR network see graphic Example DLR
Network on page 11.
1734-AENTR, POINT I/O 2-port Ethernet adapter - Allows POINT
I/O modules to connect to the DLR or linear network.
1738-AENTR, ArmorPoint 2-port Ethernet adapter - Allows
ArmorPoint I/O modules to connect to the DLR or linear network.
Cat. No. Network Ports Description
1783-ETAP 2 copper Two copper network ports connect the tap
to copper linear or DLR networks.
1783-ETAP1F 1 copper
1 fiber
One copper network port connects the tap
to a copper linear or DLR network, and one
fiber-optic network port connects the tap
to a fiber-optic linear or DLR network.
This tap is commonly used to connect a
copper section with a fiber-optic section of
the same network.
1783-ETAP2F 2 fiber Two fiber-optic network ports connect the
tap to a fiber-optic linear or DLR network.
Publication ENET-AP005C-EN-P - May 2010 13
EtherNet/IP Embedded Switch Technology Overview Chapter 1
Any 1732E ArmorBlock I/O EtherNet/IP modules with a catalog
number ending in R, including:
1732E-IB16M12R
1732E-OB16M12R
1732E-16CFGM12R
1732E-IB16M12DR
1732E-OB16M12DR
1732E-8X8M12DR
1732E-IB16M12SOEDR
Features Common to Products with Embedded Switch Technology
The products described on page 12 have certain features in common.
Each product supports the management of network traffic to ensure
timely delivery of critical data, that is, QoS and IGMP protocols are
supported.
Each product is designed according to the ODVA specification for
EtherNet/IP. Because of this design, third-party products may be
designed, according to the ODVA specification, to operate on a DLR or
linear network. To see the ODVA specification, go to:
http://www.odva.org/
For DLR networks, ring recovery time is less than 3 ms for a 50 node
network. For more information about recovery time, see Network
Recovery Performance on page 75.
14 Publication ENET-AP005C-EN-P - May 2010
Chapter 1 EtherNet/IP Embedded Switch Technology Overview
Each product supports an IEEE 1588 transparent clock for CIP motion
and CIP Sync applications.
CIP Sync technology can be used in Logix control systems to
synchronize clocks across a system operating on the EtherNet/IP
network. This technology supports highly distributed applications that
require such functions as timestamping, sequence of events recording,
distributed motion control, and increased control coordination.
For example, with CIP Sync technology, a single ControlLogix
controller can establish a master time and then, using ControlLogix
Ethernet modules, propagate that time to all necessary devices on the
network.
For more information on how to use CIP Synch technology, see the
Integrated Architecture and CIP Sync Configuration Application
Solution, publication IA-AP003.
Each of the products described on page 12 have two ports to connect to
linear or DLR networks in a single subnet. You cannot use these ports as
two network interface cards (NICs) connected to two different subnets.
Publication ENET-AP005C-EN-P - May 2010 15
EtherNet/IP Embedded Switch Technology Overview Chapter 1
DLR Network Elements
A DLR network is made up of the following devices:
Supervisor Node
Active Supervisor Node
Back-up Supervisor Node (optional)
Ring Node
Each of these device types, and how they work in a DLR network, are
described in the following sections. The graphics below show examples of
devices connected to a DLR network with copper connections and with
fiber-optic connections. In the second example, all devices are connected to
the network via a 1783-ETAP2F EtherNet/IP tap.
Example DLR Networks
Active Supervisor Node Back-up Supervisor Node
Back-up Supervisor
Node
Ring Node
Ring Node Ring Node
Active Supervisor Node Back-up Supervisor Node
Back-up Supervisor
Node
Ring Node
Ring Node Ring Node
DLR Network with
Copper Connections
DLR Network with
fiber-optic Connections
16 Publication ENET-AP005C-EN-P - May 2010
Chapter 1 EtherNet/IP Embedded Switch Technology Overview
Supervisor Node
A DLR network requires at least one node to be configured as ring supervisor.
Currently, several Rockwell Automation products support the ring supervisor
functionality.
1756-EN2TR ControlLogix EtherNet/IP 2-port module
1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F EtherNet/IP tap
Active Ring Supervisor
When multiple nodes are enabled as supervisor, the node with the numerically
highest precedence value becomes the active ring supervisor; the other nodes
automatically become back-up supervisors.
The ring supervisor provides the following primary functions:
Verifies the integrity of the ring
Reconfigures the ring to recover from a single fault
Collects diagnostic information for the ring
IMPORTANT
Out of the box, the supervisor-capable devices have their
supervisor function disabled so they are ready to participate in
either a linear/star network topology, or as a ring node on an
existing DLR network.
In a DLR network, you must configure at least one of the
supervisor-capable devices as the ring supervisor before
physically closing the ring. If not, the DLR network will
not work.
Publication ENET-AP005C-EN-P - May 2010 17
EtherNet/IP Embedded Switch Technology Overview Chapter 1
Back-up Supervisor Node
At any point in time, there will be only one active supervisor on a DLR
network. However, we recommend that you can configure at least one other
supervisor-capable node to act as a back-up supervisor. During normal
operation, a back-up supervisor behaves like a ring node. If the active
supervisor node operation is interrupted, for example, it experiences a
power-cycle, the back-up supervisor with the next numerically highest
precedence value becomes the active supervisor.
If multiple supervisors are configured with the same precedence value (the
factory default value for all supervisor-capable devices is 0), the node with the
numerically highest MAC address becomes the active supervisor.
We recommend that you:
configure at least one back-up supervisor.
configure your desired active ring supervisor with a numerically higher
precedence value as compared to the back-up supervisors.
keep track of your networks supervisor-precedence values for all
supervisor-enabled nodes.
For more information about how to configure a supervisor, see Construct and
Configure a Device-level Ring Network on page 21.
Ring Node
A ring node is any node that operates on the network to process data that is
transmitted over the network or to pass on the data to the next node on the
network. When a fault occurs on the DLR network, these reconfigure
themselves and relearn the network topology. Additionally, ring nodes can
report fault locations to the active ring supervisor.
IMPORTANT
While a back-up supervisor is not required on a DLR network, it
is recommended that you configure at least one back up ring
supervisor for your ring network.
IMPORTANT
Do not connect non-DLR devices directly to the network.
Non-DLR devices should be connected to the network through
1783-ETAP, 1783-ETAP1F, or 1783ETAP2F EtherNet/IP taps.
18 Publication ENET-AP005C-EN-P - May 2010
Chapter 1 EtherNet/IP Embedded Switch Technology Overview
DLR Network Operation
During normal network operation, an active ring supervisor uses beacon, and
other DLR protocol frames to monitor the health of the network. Back-up
supervisor nodes and ring nodes monitor the beacon frames to track ring
transitions between Normal, that is, all links are working, and Faulted, that is,
the ring is broken in at least one place, states.
You can configure two beacon-related parameters:
Beacon interval - Frequency at which the active ring supervisor
transmits a beacon frame through both of its ring ports.
Beacon timeout - Amount of time that supervisor or ring nodes wait
before timing out the reception of beacon frames and taking appropriate
action.
These parameters impact Network Recovery Performance. For information on
these performance times, see page 75. For information on how to set these
parameters, see Construct and Configure a Device-level Ring Network on
page 21.
During normal operation, one of the active supervisor nodes network ports is
blocked for DLR protocol frames. However, the active supervisor node
continues to send beacon frames out of both network ports to monitor
network health. The graphic below shows the use of beacon frames sent from
the active ring supervisor.
Normal DLR Network Operation
A second category of ring nodes, known as announce frame ring nodes, can be
designed to participate in a DLR network. The active supervisor sends
announce frames out one of its ports once per second or on detection of a ring
fault. DLR networks with announce frame ring nodes have slightly longer
recovery times than beacon frame nodes.
Active Ring
Supervisor
Ring Node 1 Ring Node 2 Ring Node 3 Ring Node 4
Beacon Frame
Blocked Port
Beacon Frame
Control Traffic Control Traffic
Publication ENET-AP005C-EN-P - May 2010 19
EtherNet/IP Embedded Switch Technology Overview Chapter 1
Number of Nodes on a
DLR Network
Rockwell Automation recommends that you use no more than 50 nodes on a
single DLR or linear network. If your application requires more than 50 nodes,
we recommend that you segment the nodes into separate, but linked, DLR
networks.
With smaller networks:
there is better management of traffic on the network.
the networks are easier to maintain.
there is a lower likelihood of multiple faults.
Additionally, on a DLR network with more than 50 nodes, network recovery
times from faults are higher than those listed in Network Recovery
Performance on page 75.
DLR Network Fault
Management
Your network may occasionally experience faults that prevent the normal
transmission of data between nodes. Your DLR network can protect your
application from interruptions resulting from a single fault. To maintain the
resiliency of your ring, your application should monitor the health of the ring
itself, as the ring may be faulted while all higher-level network functions, such
as I/O connections, are operating normally.
You can obtain fault location information from the active supervisor. For
more information on how to obtain fault location information, see Monitor a
DLR Network on page 35.
After a fault occurs, the active supervisor reconfigures the network to continue
sending data on the network.
20 Publication ENET-AP005C-EN-P - May 2010
Chapter 1 EtherNet/IP Embedded Switch Technology Overview
The following graphic shows the network configuration after a failure occurs,
with the active ring supervisor passing traffic through both of its ports, thus,
maintaining communication on the network.
Network Reconfiguration After Fault
Active Ring
Supervisor
Ring Node 1 Ring Node 2 Ring Node 3 Ring Node 4
Failure
Unblocked Port
Beacon Frame
Control and Other Traffic
Beacon Frame
Control and Other Traffic
21Publication ENET-AP005C-EN-P - May 2010 21
Chapter 2
Construct and Configure a Device-level
Ring Network
Introduction
Use this chapter to learn how to construct and configure a DLR network.
Install Devices on a
DLR Network
The first step to configuring a DLR network is to connect all devices to the
network. You should leave at least one connection unmade, that is, temporarily
omit the physical connection between two nodes on the ring network, because
the factory default settings of DLR devices are set to operate in linear/star
mode or as ring nodes on existing DLR networks.
The graphic below shows an example of a new DLR network with one
physical connection left open.
Example Device-level Ring Topology with One Connection Left Unmade
Topic Page
Install Devices on a DLR Network 21
Configure Supervisor Nodes on a DLR Network 22
Complete the Physical Connections of the Network 33
Verify Supervisor Configuration 34
IMPORTANT
If you fully connect your DLR network without a supervisor
configured, a network storm may result, rendering the network
unusable until one link is disconnected and at least one
supervisor is enabled.
Last physical
connection is
not made.
22 Publication ENET-AP005C-EN-P - May 2010
Chapter 2 Construct and Configure a Device-level Ring Network
Use the installation instructions for each device to connect it to the network.
Configure Supervisor
Nodes on a DLR Network
After you have installed your devices on the DLR network, you must configure
at least one supervisor node. Ring nodes do not require any DLR network
configuration.
Before you can complete a DLR network, that is, install your devices on the
network and make all physical connections, you must configure and enable a
ring supervisor in:
RSLogix 5000 programming software
or
RSLinx Classic communication software
This section shows how to use RSLogix 5000 programming software,
beginning on page 23, and RSLinx Classic communication software, beginning
on page 29, to configure and enable a ring supervisor.
Cat. No. Description Installation
Instructions
1756-EN2TR ControlLogix EtherNet/IP Communication
module
1756-IN612
1783-ETAP EtherNet/IP tap with copper interface 1783-IN007
1783-ETAP1F,
1783-ETAP2F
EtherNet/IP taps with fiber-optic interfaces 1783-IN008
1734-AENTR POINT I/O 2-port EtherNet/IP adapter 1734-IN040
1738-AENTR ArmorPoint 2-port EtherNet/IP adapter 1738-IN028
Multiple 1732E
products (listed on
page 12)
ArmorBlock I/O EtherNet/IP modules 1732E-IN003
TIP
You can use DIP switch 3 on the 1783-ETAP (with firmware
revision 2.x or later), 1783-ETAP1F or 1783-ETAP2F taps to
enable the taps as ring supervisors instead of using using the
software options described in this section.
For more information on how to use the DIP switches, see
page 53.
Publication ENET-AP005C-EN-P - May 2010 23
Construct and Configure a Device-level Ring Network Chapter 2
Configure a Ring Supervisor in RSLogix 5000
Programming Software
To configure the 1756-EN2TR module or the 1783-ETAP, 1783-ETAP1F, or
1783-ETAP2F taps as a ring supervisor, use the devices Add-on Profile
(AOP) in RSLogix 5000 programming software, version 17.01.
IMPORTANT
To download an AOP, go to: http://support.rockwellautomation.com/controlflash/LogixProfiler.asp
Depending on the firmware revision of your product, you must use a specific AOP version.
For both the 1756-EN2TR module and 1783-ETAP tap, make sure that the Major Revision configured on the
General tab of the devices RSLogix 5000 programming software configuration matches the major revision
of the physical module.
If the device configuration on the General tab does not match the physical module, the programming
software alerts you to this mismatch when you attempt to configure the Internet Protocol, Port
Configuration and Network tabs for that device.
Cat. No. Firmware Revision Required Add-On Profile
Revision
1756-EN2TR
2.1
(1)
(1)
You can use the ControlFLASH Firmware Upgrade software to upgrade a 1756-EN2TR module from firmware revision 2.1 to 3.x or later.
1.x or later
3.x or later 2.x or later
1783-ETAP
1.1
(2)
(2)
You can use the ControlFLASH Firmware Upgrade software to upgrade a 1783-ETAP tap from firmware revision 1.1 to 2.x or later.
To download new firmware, go to: http://www.rockwellautomation.com/support/americas/index_en.html
If you upgrade the firmware revision on your module or tap, you must use the required AOP revision listed above for that revision. For
example, if you upgrade your 1756-EN2TR module to firmware revision 3.x or later, you must use AOP revision 2.x or later in your RSLogix
5000 programming software.
Additionally, if you upgrade the firmware revision on your module or tap, you must also use the required RSLinx communication software
for that firmware revision. For more information on which RSLinx communication software version is required for each firmware revision,
see page 29.
1.x or later
2.x or later 2.x or later
1783-ETAP1F 2.x or later 2.x or later
1783-ETAP2F
24 Publication ENET-AP005C-EN-P - May 2010
Chapter 2 Construct and Configure a Device-level Ring Network
To configure a ring supervisor in RSLogix 5000 programming software, follow
these steps.
1. Add the module to your project.
a. Right-click 1756 Backplane and choose New Module.
IMPORTANT
The steps to configure a ring supervisor via software are
basically the same for the 1756-EN2TR module and the
1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F taps. This example
shows how to configure the 1756-EN2TR module.
You only need to configure the 1783-ETAP, 1783-ETAP1F, and
1783-ETAP2F taps in your I/O Configuration if you plan to
enable the tap as a ring supervisor. If you do not plan to use the
tap as a ring supervisor, we recommend that you do not add it
to your I/O Configuration.
Additionally, if you want to configure a 1783-ETAP,
1783-ETAP1F, or 1783-ETAP2F tap as a supervisor via software
or with its DIP switchs, you must first assign it an IP address.
The tap does not require an IP address if it is used as a ring
node or has its supervisor function enabled by DIP switch
For more information on how to use a taps switch to configure
it as a ring supervisor, see page 53.
a
Publication ENET-AP005C-EN-P - May 2010 25
Construct and Configure a Device-level Ring Network Chapter 2
b. Select the module.
c. Click OK.
2. Complete configuration information for the module in your
RSLogix 5000 project.
The graphic below shows the I/O configuration for an example DLR
network.
3. Download to your Logix controller.
4. Go online with the controller and leave it in Program mode.
b
c
26 Publication ENET-AP005C-EN-P - May 2010
Chapter 2 Construct and Configure a Device-level Ring Network
Enable Ring Supervisor in RSLogix 5000 Programming Software
After you have added your 1756-EN2TR module or 1783-ETAP,
1783-ETAP1F, or 1783-ETAP2F taps to your RSLogix 5000 programming
software project, you must enable the ring supervisor mode.
To enable the 1756-EN2TR module or 1783-ETAP, 1783-ETAP1F, or
1783-ETAP2F taps as a ring supervisor, follow these steps.
1. With your project online with the controller, double-click a
supervisor-capable device in the I/O configuration tree.
IMPORTANT
If you are using RSLogix 5000 programming software to
configure your ring supervisor and monitor diagnostics on your
DLR network, you must be online with your controller.
IMPORTANT
The steps to enable a ring supervisor are basically the same for
both the 1756-EN2TR module or 1783-ETAP, 1783-ETAP1F, or
1783-ETAP2F taps. This example shows how to do it for the
1756-EN2TR module.
Double-click the
module.
Publication ENET-AP005C-EN-P - May 2010 27
Construct and Configure a Device-level Ring Network Chapter 2
2. Click the Network tab to Enable Supervisor Mode.
Configuration takes effect immediately; you do not need to click Apply
or OK.
3. Click the Advanced button on the Network tab.
4. Configure supervisor-related parameters, as shown in the screen shot
below.
For these parameters, you must click Set after entering a value.
5. Click Set.
Click here to enable
Supervisor Mode.
IMPORTANT
For Beacon Interval, Beacon Timeout and Ring Protocol VLAN
ID, we recommend that you use the default values.
28 Publication ENET-AP005C-EN-P - May 2010
Chapter 2 Construct and Configure a Device-level Ring Network
Functionality Description Default Setting
Supervisor
Precedence
You may configure a supervisor precedence number for each device configured as a ring
supervisor. The highest possible supervisor precedence value is 255.
When multiple nodes are enabled as supervisor, the node with the highest precedence value is
assigned as the active ring supervisor; the other nodes automatically become back-up supervisors.
We recommend that you:
configure at least one back-up supervisor node.
set your desired Active Ring Supervisor with a relatively high supervisor-precedence value
compared to the back-up node(s).
keep track of your networks supervisor-precedence values.
If multiple supervisors are configured with the same precedence value (the factory default value
for all supervisor-capable devices is 0), the node with the numerically highest MAC address
becomes the active supervisor.
0
Beacon Interval Frequency of the active ring supervisor transmitting a beacon frame through both of its Ethernet
ports. This parameter is user configurable for any time between 200S and 100mS.
For more information on how this parameter relates to network performance, see page 75.
400 S
Beacon Timeout The beacon timeout is amount of time nodes wait before timing out the reception of beacon
frames and taking appropriate action. Supervisors support a range from 400S to 500mS.
For more information on how this parameter relates to network performance, see page 75.
1960 S
Ring Protocol
VLAN ID
Reserved for future use. 0
Publication ENET-AP005C-EN-P - May 2010 29
Construct and Configure a Device-level Ring Network Chapter 2
Configure and Enable a Ring Supervisor in RSLinx Classic
Communication Software
You can configure and enable a ring supervisor for your DLR network
through RSLinx Classic communication software.
IMPORTANT
Depending on the firmware revision of your product, you must use specific versions of RSLinx
communication software.
Cat. No. Firmware Revision Required RSLinx
Commmunication Software
Version
1756-EN2TR
2.1
(1)
(1)
You can use the ControlFLASH Firmware Upgrade software to upgrade a 1756-EN2TR module from firmware revision 2.1 to 3.x or later.
2.55 or later
3.x or later 2.56 or later
1783-ETAP
1.1
(2)
(2)
You can use the ControlFLASH Firmware Updgrade software to upgrade a 1783-ETAP tap from firmware revision 1.1 to 2.x or later.
To download new firmware, go to: http://www.rockwellautomation.com/support/americas/index_en.html
If you upgrade the firmware revision on your module or tap, you must use the required RSLinx communication software version listed
above for that firmware revision. For example, if you upgrade your 1756-EN2TR module to firmware revision 3.x or later, you must use
RSLinx communication software, version 2.56 or later.
Additionally, if you upgrade the firmware revision on your module or tap, you must also use the required AOP revision for that firmware
revision. For more information about which AOP revision is required for each firmware revision, see page 23.
2.55 or later
2.x or later 2.56 or later
1783-ETAP1F 2.x or later 2.56 or later
1783-ETAP2F
30 Publication ENET-AP005C-EN-P - May 2010
Chapter 2 Construct and Configure a Device-level Ring Network
This example is for the 1783-ETAP tap. Follow these steps.
1. Launch RSLinx communication software.
2. Browse to the DLR network that you are setting up.
3. Access the supervisor-capable nodes properties.
a. Right-click the node.
b. Choose Module Configuration.
The General tab appears with information about the module.
TIP
If you do not have the Electronic Data Sheet (EDS) file installed
on the module configured to be the ring supervisor, it will
appear with a question mark (?). To obtain and use the EDS file:
right-click the module and choose to upload the EDS file from the
device.
or
download the EDS file from:
http://www.rockwellautomation.com/resources/eds/
a
b
Publication ENET-AP005C-EN-P - May 2010 31
Construct and Configure a Device-level Ring Network Chapter 2
4. Click the Network tab to Enable Supervisor Mode.
Configuration takes affect immediately; you do not need to click Apply
or OK.
5. Click the Advanced button to configure supervisor-related parameters.
6. Click Set.
Click here to enable
Supervisor Mode.
IMPORTANT
For Beacon Interval, Beacon Timeout and Ring Protocol VLAN
ID, we recommend that you only use the default values.
32 Publication ENET-AP005C-EN-P - May 2010
Chapter 2 Construct and Configure a Device-level Ring Network
Functionality Description Default Setting
Supervisor
Precedence
You may configure a supervisor precedence number for each device configured as a ring
supervisor. The highest possible supervisor precedence value is 255.
When multiple nodes are enabled as supervisor, the node with the highest precedence value is
assigned as the active ring supervisor; the other nodes automatically become back-up supervisors.
We recommend that you:
configure at least one back-up supervisor node.
set your desired Active Ring Supervisor with a relatively high supervisor-precedence value
compared to the back-up node(s).
keep track of your networks supervisor-precedence values.
If multiple supervisors are configured with the same precedence value (the factory default value
for all supervisor-capable devices is 0), the node with the numerically highest MAC address
becomes the active supervisor.
0
Beacon Interval Frequency of the active ring supervisor transmitting a beacon frame through both of its Ethernet
ports. This parameter is user configurable for any time between 200S and 100mS.
For more information on how this parameter relates to network performance, see page 75.
400 S
Beacon Timeout The beacon timeout is amount of time nodes wait before timing out the reception of beacon
frames and taking appropriate action. Supervisors support a range from 400S to 500mS.
For more information on how this parameter relates to network performance, see page 75.
1960 S
Ring Protocol
VLAN ID
Reserved for future use. 0
Enable IGMP
Snooping
For more information on IGMP Snooping, see Additional 1783-ETAP, 1783-ETAP1F, and
1783-ETAP2F EtherNet/IP Tap Features on page 53.
Enabled
Enable IGMP
Querier
For more information on IGMP Querier, see Additional 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F
EtherNet/IP Tap Features on page 53.
Disabled
Enable Device
Port Debugging
Mode
For more information on Device Port Debugging Mode, see Additional 1783-ETAP, 1783-ETAP1F,
and 1783-ETAP2F EtherNet/IP Tap Features on page 53.
Disabled
Publication ENET-AP005C-EN-P - May 2010 33
Construct and Configure a Device-level Ring Network Chapter 2
Complete the Physical
Connections of the
Network
After you configure and enable your ring supervisor nodes, you must complete
the physical connection of your network to establish a complete and fully
functioning DLR network.
The figure below shows an example DLR network with all physical
connections complete.
Example Device-level Ring Topology with All Connections Complete
Last physical
connection is
made.
34 Publication ENET-AP005C-EN-P - May 2010
Chapter 2 Construct and Configure a Device-level Ring Network
Verify Supervisor
Configuration
You can verify your configuration and overall DLR network status in either
RSLogix 5000 programming software or RSLinx Classic communication
software.
1. Access the supervisor nodes properties as shown previously in
this chapter.
2. Click the Network tab.
3. Check the Network Topology and Network Status fields.
.
For a 1756-EN2TR module or the 1783-ETAP, 1783-ETAP1F, and
1783-ETAP2F taps, you can also verify the supervisor configuration through
the modules diagnostic web pages. For more information on monitoring
diagnostics via an EtherNet/IP modules web pages, see Monitor a DLR
Network on page 35.
If there
the Network Topology = Linear/Star is no supervisor configured for the
network.
the Network Topology = Ring is at least one node configured as a
supervisor.
the Network Status = Normal are no faults on the network.
Check these fields.
35Publication ENET-AP005C-EN-P - May 2010 35
Chapter 3
Monitor a DLR Network
Introduction
Use this chapter to learn how to monitor your DLR network.
Methods to Monitor a
DLR Network
You can retrieve network diagnostic information from the ring
supervisor-capable devices using the following:
RSLogix 5000 Programming Software Status Pages
RSLinx Communication Software Status Pages
Device Web Pages
Programmatically Through the Use of a MSG Instruction
Topic Page
Methods to Monitor a DLR Network 35
Monitor Status Pages 37
Monitor Device Web Pages 41
Monitor Diagnostics via MSG Instructions 42
36 Publication ENET-AP005C-EN-P - May 2010
Chapter 3 Monitor a DLR Network
RSLogix 5000 Programming Software Status Pages
You must use RSLogix 5000 programming software, version 17.01 or later and
have installed the appropriate AOPs to use the softwares profile status pages.
RSLinx Communication Software Status Pages
To monitor the network with this method, you must use RSLinx
communication software, version 2.55 or later.
Device Web Pages
The 1783-ETAP1F and 1783-ETAP2F taps support device web pages
out-of-the-box.
The 1783-ETAP tap, firmware revision 1.1 does not support device web
pages. If you upgrade the tap to firmware revision 2.1, you can use device web
pages with the tap.
Programmatically Through the Use of a MSG Instruction
For more information on how to monitor your DLR network via MSG
Instructions, see page 42.
Publication ENET-AP005C-EN-P - May 2010 37
Monitor a DLR Network Chapter 3
Monitor Status Pages
Both RSLogix 5000 programming software and RSLinx Classic
communication software offer status pages that you can use to monitor your
networks performance.
RSLogix 5000 Programming Software Status Pages
You can monitor your networks diagnostic information through the
RSLogix 5000 programming software when the software is online.
To monitor the network in RSLogix 5000 programming software, follow these
steps.
1. Verify that your project is online.
2. Access the active supervisor nodes properties.
a. Right-click the modules entry in the Controller Organizer.
b. Click Properties.
3. Use the Network tab to monitor diagnostics.
a
b
38 Publication ENET-AP005C-EN-P - May 2010
Chapter 3 Monitor a DLR Network
RSLinx Communication Software
To monitor the network in RSLinx communication software, follow
these steps.
1. Click RSWho to browse the network.
2. Access the property pages for the active supervisor node.
a. Open the driver that shows the nodes on your DLR network.
b. Right-click the node for which you want to monitor performance.
c. Click on the choice that you need to access.
Multiple choices appear.
These options are shown in the following sections.
a
b
c
Publication ENET-AP005C-EN-P - May 2010 39
Monitor a DLR Network Chapter 3
Module Configuration
This series of tabs provides:
general information.
connection information.
module information.
Internet protocol.
port configuration.
network information.
The example below shows a ring fault between nodes at IP addresses
10.88.80.21 and MAC ID 00-00-BC-02-48-D5.
There are multiple fields that you can use to monitor network
diagnostics.
Field Definition
Network Topology Possible values here can be Linear or Ring.
Network Status Displays if the network is operating normally (Normal) or has
experienced a fault (Ring Fault), as shown in the example screen
above.
Active Ring Supervisor Displays the IP address or MAC address of the active ring
supervisor.
Active Supervisor
Precedence
For more information on this field, see Active Ring Supervisor on
page 16.
Enable Ring Supervisor Configurable field that lets you to set the node as a ring
supervisor.
Ring Faults Detected Number of faults detected on the network since the last module
power cycle or counter reset.
40 Publication ENET-AP005C-EN-P - May 2010
Chapter 3 Monitor a DLR Network
Supervisor Status Displays whether this node is the active ring supervisor (Active),
a back-up supervisor (Back-up), a ring node, or part of a linear
network.
Last Active Node on
Port 1
The last node the active ring supervisor can communicate with
on Port 1. This value is an IP address or a MAC ID and remains
latched until the Verify Fault Location button is clicked.
Last Active Node on
Port 2
The last node the active ring supervisor can communicate with
on Port 2. This value is an IP address or a MAC ID and remains
latched until the Verify Fault Location button is clicked.
Status Displays whether a fault exists on the ring.
IMPORTANT
If the Network Topology field = Ring and the Network
Status field = Normal, the Last Active Node fields will
display the last fault information even though it has
been corrected.
To clear the last fault information from these fields, click
Verify Fault Location. You may see a message informing
you that the supervisor is no longer in fault mode and
the fields will be cleared.
Field Definition
Publication ENET-AP005C-EN-P - May 2010 41
Monitor a DLR Network Chapter 3
Monitor Device Web Pages
Another method to monitor network diagnostic information with
supervisor-capable nodes is to use the modules diagnostic web pages.
For example, to access your 1756-EN2TR modules diagnostic web pages,
follow these steps.
1. Open your web browser.
2. In the Address field, type your modules Internet Protocol (IP) address
and press Enter.
You can use the links on the left-most navigation bar to see each
available web page. The screen below shows Ring Statistics for a
1756-EN2TR module.
IMPORTANT
A 1783-ETAP tap using firmware revision 1.1 does not support
diagnostic web pages. You must upgrade the tap to firmware
revision 2.x or later to use diagnostic web pages.
Keep in mind, though, that upgrading your 1783-ETAP tap to
firmware revision 1.1 also requires that you upgrade your
RSLinx communication software to version 2.56 or later.
Ethernet/IP Module Internet Protocol (IP) Address
42 Publication ENET-AP005C-EN-P - May 2010
Chapter 3 Monitor a DLR Network
Monitor Diagnostics via
MSG Instructions
You can also obtain network diagnostic information programmatically via
MSG instructions in RSLogix 5000 programming software. For example, you
can:
get all ring diagnostic information.
get a ring participant list.
get the active supervisor.
clear rapid ring faults.
verify a fault location.
reset a fault counter.
enable and configure a ring supervisor.
This information can be displayed on an HMI device or manipulated in your
project code.
Example Use of
MSG Instruction
This example describes how to retrieve diagnostic information from your
DLR network. Follow these steps.
1. Enter a MSG instruction into your rung of logic.
2. Configure the MSG instruction to retrieve ring diagnostic information
service, as shown in the following screen shots.
IMPORTANT
Make sure the tag you create is sized appropriately to
hold all of the data you are reading or writing.
For more information, see page 44.
Publication ENET-AP005C-EN-P - May 2010 43
Monitor a DLR Network Chapter 3
3. Configure the MSG instructions communication path to point to the
active supervisor node.
The path on the following screen is one example path.
Click here to browse
to the active
supervisor node in
your project.
IMPORTANT
When using the Custom Get_Attributes_All (01) service,
if you point to an active supervisor node, you retrieve all
of the attributes listed in Retrieve All Diagnostic
Information Attribute Description on page 45.
If you point to a non-supervisor node, you retrieve only
the Network Topology and Network Status attribute
information.
If you point to backup supervisor node, you can retrieve
the current active supervisors IP address.
44 Publication ENET-AP005C-EN-P - May 2010
Chapter 3 Monitor a DLR Network
Use Specific Values on the Configuration Tab
Use the values on the Configuration tab of your MSG instruction to perform
specific services.
TIP
Sample DLR network diagnostic application code, for example,
Add-on Instruction or HMI faceplate graphics, is available on the
Rockwell Automation Sample Code Library.
For more information about the Rockwell Automation Sample Code
Library, see:
http://www.rockwellautomation.com/solutions/integratedarchitecture/r
esources5.html
Request Description Message
Type
Service
Type
Service
Code
(HEX)
Class
(HEX)
Instance Attribute
(HEX)
Source
Element
Source
Length
(Bytes)
Destination Destination
Length
(bytes)
Retrieve
All Ring
Diagnostic
Information
Information for
this request is
listed in Retrieve
All Ring
Diagnostic
Information on
page 45.
CIP
Generic
Custom 1 47 1 NA Left blank 0 Tag 50
or
54
(2)
Request
Ring
Participant
List
(1)
Information for
this request is
listed in Request
the Ring
Participant List on
page 47.
CIP
Generic
Get
Attribute
Single
e 47 1 9 NA NA Tag 10/node
Get Active
Supervisor
Obtain the IP
address and MAC
ID of the active
supervisor on the
DLR network
CIP
Generic
Get
Attribute
Single
e 47 1 a NA NA Tag 10
Acknowled
ge Rapid
Ring Faults
Condition
Request
supervisor to
resume normal
operation after
encountering a
rapid ring fault
condition
CIP
Generic
Custom 4c 47 1 NA NA NA NA
Verify a
Fault
Location
Request
supervisor to
update Last Active
Node values
CIP
Generic
4b 47 1 NA NA NA NA NA
Reset the
Ring Fault
Counter
Reset the number
of ring faults
detected on the
DLR network
CIP
Generic
Set
Attribute
Single
10 47 1 5 Tag 2 NA NA
Enable and
Configure a
Ring
Supervisor
Information for
this request is
listed in Enable
and Configure a
Ring Supervisor on
page 48.
CIP
Generic
Set
Attribute
Single
10 47 1 4 Tag 12 NA NA
(1)
This request only works if there are fewer than 40 nodes on the network. If there are more nodes than will fit in a single message, an error will be returned.
(2)
You can use a Destination Length of 54 bytes if you use firmware revision 3.x or later for the 1756-EN2TR module or firmware revision 2.x or later for the 1783-ETAP,
1783-ETAP1F, or 1783-ETAP2F taps.
Publication ENET-AP005C-EN-P - May 2010 45
Monitor a DLR Network Chapter 3
Retrieve All Ring Diagnostic Information
When you perform the Retrieve All Ring Diagnostic Information request on
an active supervisor, the MSG instruction returns the following information.
Retrieve All Diagnostic Information Attribute Description
Destination Tag Attribute Name Description Possible Values
SINT [0] Network Topology Current network
topology mode
0 = Linear
1 = Ring
SINT [1] Network Status Current status of the
network
0 = Normal
1 = Ring Fault
2 = Unexpected Loop Detected
3 = Partial Network Fault
4 = Rapid Fault/Restore Cycle
SINT [2] Ring Supervisor Status Ring supervisor active
status flag
0 = Node is functioning as a backup
1 = Node is functioning as the active ring supervisor
2 = Node is functioning as a normal ring node
3 = Node is operating in a non-DLR topology
4 = Node cannot support the currently operating ring
parameters, that is, Beacon Interval and/or Beacon Timeout
Ring Supervisor Config Ring Supervisor
configuration
parameters
SINT [3] Ring Supervisor
Enable
Ring supervisor enable
flag
0 = Node is configured as a normal ring node (default
configuration)
1 = Node is configured as a ring supervisor
SINT [4] Ring Supervisor
Precedence
Precedence value of a
ring supervisor
(2)
Valid value range = 0255
0 = Default value
SINT [5-8] Beacon Interval Duration of ring
beacon interval
Valid value range = 200 s100 ms
Default = 400 s
SINT [9-12] Beacon Timeout Duration of ring
beacon timeout
Value value range = 400 s500 ms
Default value = 1960 s
SINT [13-14] DLR VLAN ID Valid ID to use in ring
protocol messages
Valid value range = 04094
Default value = 0
SINT [15-16] Ring Faults Count Number of ring faults
since power up
(2)
46 Publication ENET-AP005C-EN-P - May 2010
Chapter 3 Monitor a DLR Network
Last Active Node on
Port 1
Last active node at the
end of the chain
through port 1 of the
active ring supervisor
during a ring fault
SINT [17-20]
Device IP address
(2)
Any valid IP address value
A value = 0 indicates no IP address has been configured for the
device.
SINT [21-26] Device MAC
address
(2)
Any valid Ethernet MAC address
Last Active Node on
Port 2
Last active node at the
end of the chain
through port 2 of the
active ring supervisor
during a ring fault
SINT [27-30]
Device IP address
(2)
Any valid IP address value
A value = 0 indicates no IP address has been configured for the
device.
SINT [31-36] Device MAC
address
(2)
Any valid Ethernet MAC address
SINT [37-38] Ring Protocol
Participants Count
Number of devices in
the ring protocol
participants list
Active Supervisor
Address
IP and/or Ethernet
MAC address of the
active ring supervisor
SINT [39-42] Supervisor IP address Any valid IP address value
A value = 0 indicates no IP address has been configured for the
device.
SINT [43-48] Supervisor MAC
address
Any valid Ethernet MAC address
SINT [49] Active Supervisor
Precedence
Precedence value of
the active ring
supervisor
SINT [50-53]
(1)
Capability Flags Alerts you that the
device is capable of
operating as a
supervisor and
beacon-based ring
node.
0x22
(1)
This destination tag is available only with the 1756-EN2TR module, firmware revision 3.x or later, 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F taps, firmware revisions 2.x
or later. If you are using the 1783-ETAP tap, firmware revision 1.x, your program does not include this destination tag.
(2)
RSLogix 5000 programming software may display the value in this field as negative numbers. To better understand the value, we recommend you view it in HEX format.
Retrieve All Diagnostic Information Attribute Description
Destination Tag Attribute Name Description Possible Values
Publication ENET-AP005C-EN-P - May 2010 47
Monitor a DLR Network Chapter 3
Request the Ring Participant List
When you request the Ring Participant List service on your DLR network, the
MSG instruction returns the following information.
Request the Ring Participant List Attribute Description
Destination Tag Attribute Name Description Possible Values
Ring Protocol
Participants List
(1)
List of devices
participating in ring
protocol
SINT [0-3]
Device IP address
(2),

(3)
Any valid IP address value
A value = 0 indicates no IP address has been configured for the
device.
SINT [4-9] Device MAC
address
(3)
,
(4)
Any valid Ethernet MAC address
(1)
This attribute will return an array of the data shown, one entry for each node. The Ring Protocol Participants Count attribute determines the number entries.
(2)
This tag displays only IP addresses for ring participants that have been configured with one. For example, you may have a 1783-ETAP tap connected to the network that has
not been assigned an IP address. In that case, no address is shown for the 1783-ETAP tap.
(3)
RSLogix 5000 programming software may display the value in this field as negative numbers. To better understand the value, we recommend you view it in HEX format.
(4)
Unlike destination tag SINT [0-3], where IP addresses are displayed only for ring participants configured with an IP address, this tag displays MAC addresses for all ring
participants because every ring participant has a MAC address.
48 Publication ENET-AP005C-EN-P - May 2010
Chapter 3 Monitor a DLR Network
Enable and Configure a Ring Supervisor
When you perform the Enable and Configure a Ring Supervisor request on a
supervisor-capable device, configure the MSG instruction with the following
information.
Enable and Configure a Ring Supervisor Attribute Description
Source Tag Attribute Name Description Possible Values
Ring Supervisor Config Ring Supervisor
configuration
parameters
SINT [0] Ring Supervisor
Enable
Ring supervisor enable
flag
0 = Node is configured as a normal ring node (default
configuration)
1 = Node is configured as a ring supervisor
SINT [1] Ring Supervisor
Precedence
Precedence value of a
ring supervisor
(1)
Valid value range = 0255
0 = Default value
SINT [2-5] Beacon Interval Duration of ring
beacon interval
Valid value range = 200 s100000 s
Default = 400 s
SINT [6-9] Beacon Timeout Duration of ring
beacon timeout
(1)
Value value range = 400 s500000 s
Default value = 1960 s
SINT [10-11] DLR VLAN ID Valid ID to use in ring
protocol messages
(1)
Valid value range = 04094
Default value = 0
(1)
RSLogix 5000 programming software may display the value in this field as negative numbers. To better understand the value, we recommend you view it in HEX format.
49Publication ENET-AP005C-EN-P - May 2010 49
Chapter 4
Troubleshoot a Linear or DLR Network
General Solutions for
Linear or DLR Networks
Before you attempt to correct specific faults on your linear or DLR network,
we recommend that you first take the following actions when a fault appears.
For a DLR network:
verify that you have configured at least one node as a supervisor on
the network and that Network Topology = Ring.
verify that all cables on the network are securely connected to each
device.
verify that all devices that require an IP address have one assigned
correctly.
check the Network Status field on the active supervisor nodes status
page to determine the fault type.
For a linear network:
verify that none of the nodes are configured as a supervisor on
the network and that Network Topology = Linear.
If any nodes on a linear network are configured as a supervisor, it may
impact communication to other devices connected to the network.
verify that all cables on the network are securely connected to each
device.
verify that all devices that require an IP address have one assigned
correctly.
If the fault is not cleared once you have completed the actions listed above, use
the tables in the rest of this chapter to troubleshoot issues specific to a DLR
network or a linear network.
50 Publication ENET-AP005C-EN-P - May 2010
Chapter 4 Troubleshoot a Linear or DLR Network
Specific Issues on Your DLR or Linear Network
Use the table below to troubleshoot possible specific issues on your DLR or
linear network that are not solved by the actions described on the previous
page.
Issue Description Solution
Supervisor
Reports a Ring
Fault
A link on the DLR network may be broken:
intentionally, for example, because you are adding or deleting nodes but
have not made all physical connections to restore the set up of the network
with/without the node.
unintentionally, for example, because a cable is broken or a device
malfunctions.
When this fault occurs, the adjacent nodes to the faulted part of the network
are displayed in the Ring Fault group and the Network Status field = Ring Fault.
The screen shot below shows the Ring Fault section with IP addresses
appearing for the last active nodes. The faulted node is between nodes
10.88.80.115 and 10.88.80.208. If the IP address of either node is not available,
the software will display the nodes MAC ID.
Once the fault is corrected, the ring is automatically restored, and the Network
Status field returns to Normal.
Determine where the fault condition
exists and correct it.
You may need to click the Refresh
Communication link to update the
Ring Fault information to determine
where the fault condition exists.
Finally, you may want to use
DevicePort Debugging Mode
functionality on the 1783-ETAP tap to
analyze a suspicious node.
For more information, refer to Device
Port Debugging Mode on page 60.
Publication ENET-AP005C-EN-P - May 2010 51
Troubleshoot a Linear or DLR Network Chapter 4
Rapid Ring Fault When a Rapid Ring Fault occurs, the following events occur:
The active supervisor will block traffic on port 2, resulting in possible
network segmentation, that is, some nodes may become unreachable.
The Link 2 status indicator on the active supervisor is off.
As soon as the fault occurs, for both RSLogix 5000 programming software
and RSLinx communication software, the Status field = Rapid Fault/Restore
Cycles.
Any of the following may cause a Rapid Ring Fault:
5 intentional disconnections/reconnections of a node from the network
within 30 seconds
A duplex mismatch between two connected devices
Electromagnetic noise on the network
Unstable physical connections, such as intermittent connectors
Given the nature of a Rapid Ring Fault, the Last Active Node information may
not be accurate when a Rapid Ring Fault condition is present
Multiple possible solutions exist.
For the disconnections and
reconnections issue, no solution is
required.
Clear the fault when you have
reconnected the device to the
network permanently.
For the duplex mismatch issue,
reconfigure the duplex parameters
to make sure they match between
the devices.
For the electromagnetic noise
issue, determine where the noise
exists and eliminate it or use a
protective shield in that location.
For the unstable connections
issue, determine where they exist
on the network and correct them.
Check the media counters for all
devices on the network. The
device with the highest media
counter count is most likely
causing the Rapid Ring Fault.
Remove devices from the network
one by one. When you see the
Rapid Ring Fault disappear after a
device is removed, that device is
causing the fault.
You may want to use DevicePort
Debugging Mode functionality on
the 1783-ETAP tap to analyze a
suspicious node.
For more information, refer to
Device Port Debugging Mode on
page 60.
Finally, your Beacon Interval or
Timeout configuration may not be
appropriate for your network.
However, if you think you need to
change these values, we
recommend that you call Rockwell
Automation technical support.
Once the fault is fixed, click Clear
Fault.
Issue Description Solution
52 Publication ENET-AP005C-EN-P - May 2010
Chapter 4 Troubleshoot a Linear or DLR Network
Partial Fault
Condition
A partial network fault occurs when traffic is lost in only one direction on the
network because a ring member is not forwarding beacons in both directions
for some reason, such as because of a component failure.
The active ring supervisor detects a partial fault by monitoring the loss of
Beacon frames on one port and the fault location appears in the Ring Fault
section of the Network tab.
When a partial fault is detected, the active ring supervisor blocks traffic on one
port. At this point, the ring is segmented due to the partial fault condition. The
nodes adjacent to the faulted part of the network are displayed in the Ring
Fault group with either IP addresses or MAC IDs for each node displayed.
When this fault occurs the Network Status field = Partial Fault Condition.
Once the fault is corrected, it automatically clears, and the Network Status
field returns to Normal.
Determine where the fault condition
exists and correct it.
Additionally, you may want to use
DevicePort Debugging Mode
functionality, also known as Port
Mirroring, on a 1783-ETAP,
1783-ETAP1F, or 1783-ETAP2F tap to
analyze a suspicious node.
For more information, refer to Device
Port Debugging Mode on page 60.
Media Counter
Errors or
Collisions
The media counters screen displays the number of physical layer errors or
collisions. The screen below indicates where to check for errors encountered.
Error levels are displayed depending on what caused the error. For example, an
Alignment Error is displayed in the Alignment Error field.
On a DLR network, it is not uncommon to see low levels of media counter
errors. For example, if the network breaks, a low level of media counter errors
appear. With a low level of media counter errors, the value typically does not
continuously increase and often clears.
A high level of media counter errors typically continues to increase and does
not clear. For example, there is a mismatchof speedbetween two linked nodes,
a high level of media counter errors appears, steadily increasing and not
clearing.
To access the RSLinx screen above, browse the network, right-click on the
device, select Module Properties and click the Port Diagnostics tab.
Some example solutions include:
Check for a mismatch of speed
and/or duplex between two linked
nodes.
Verify that all cables on the
network are securely connected to
each device.
Check for electromagnetic noise
on the network. If you find it,
eliminate it or use a protective
shield in that location.
Issue Description Solution
53Publication ENET-AP005C-EN-P - May 2010 53
Chapter 5
Additional 1783-ETAP, 1783-ETAP1F, and
1783-ETAP2F EtherNet/IP Tap Features
Introduction
This chapter explains the additional features of the 1783-ETAP,
1783-ETAP1F, and 1783-ETAP2F EtherNet/IP tap.
Use DIP Switches
Follow this procedure to set the DIP switches on your 1783-ETAP,
1783-ETAP1F, or 1783-ETAP2F tap.
Topic Page
Use DIP Switches 53
Internet Group Management Protocol (IGMP) Configuration
Parameters
58
Device Port Debugging Mode 60
Replace a 1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F Tap on the
Network
62
Port Buffer Utilization 63
54 Publication ENET-AP005C-EN-P - May 2010
Chapter 5 Additional 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F EtherNet/IP Tap Features
1. Move the switches to the desired position and power cycle the tap.
IMPORTANT
Switch settings take effect only at power-up. If you change a
taps switch settings after it is in operation, there is no change
to the taps behavior until power is cycled to the tap.
Additionally, when you are setting the DIP swithes on your
EtherNet/IP tap, you should consider the following:
If you are using a 1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F
tap in a linear network, make sure switch 3 is set to the Off
position.
In many switch configurations, if switch 3 is set to the On
position, the tap is automatically configured to be a ring
supervisor. In a linear network, none of the nodes should be
configured as a ring supervisor.
With regard to using switch 3 to automatically configure the
tap to be a ring supervisor, the behavior described in table
DIP Switch Settings and Results on page 55 applies for any
1783-ETAP1F or 1783-ETAP2F tap. However, the settings
only cause the described power-up behavior for 1783-ETAP
taps using firmware revision 2.x or later. If you set the
switches as described on a 1783-ETAP tap with firmware
revision 1.x, the described power-up behavior does not
occur.
For more information, see page 55.
Publication ENET-AP005C-EN-P - May 2010 55
Additional 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F EtherNet/IP Tap Features Chapter 5
2. Refer to graphic below and table on page 55 for DIP switch settings.
DIP Switches
Off On
Switch 3
Switch 2
Switch 1
DIP Switch Settings and Results
Switch Power-up Behaviors for the 1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F tap
1 2 3
Off Off Off The tap uses the Internet Protocol settings, that is, IP address, determined by one of the
following:
- The RSLogix 5000 programming software configuration stored in the taps non-volatile
storage (NVS) memory
- Factory default setting of 169.254.1.1
For other configuration settings, the tap uses what is stored in its NVS memory.
Off Off On The tap uses the Internet Protocol settings, that is, IP address, determined by one of the
following:
- The RSLogix 5000 programming software configuration stored in the taps NVS memory
- Factory default setting of 169.254.1.1
The tap is automatically configured to be a ring supervisor.
For other configuration settings, the tap uses what is stored in its NVS memory.
(1)
On Off Off The tap uses the Internet Protocol settings, that is, IP address, determined by the BOOTP
server.
For other configuration settings, the tap uses what is stored in its NVS memory.
On Off On The tap uses the Internet Protocol settings, that is, IP address, determined by the BOOTP server.
The tap is automatically configured to be a ring supervisor.
For other configuration settings, the tap uses what is stored in its NVS memory.
(1)
Off On Off The tap uses the Internet Protocol settings, that is, IP address, determined by the DHCP server.
For other configuration settings, the tap uses what is stored in its NVS memory.
Off On On The tap uses the Internet Protocol settings, that is, IP address, determined by the DHCP server.
The tap is automatically configured to be a ring supervisor.
For other configuration settings, the tap uses what is stored in its NVS memory.
(1)
56 Publication ENET-AP005C-EN-P - May 2010
Chapter 5 Additional 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F EtherNet/IP Tap Features
3. Observe these guidelines when using the DIP switches:
Out-of-box, all three switches are in the Off position.
This is the software settable position. The tap uses either the default IP
address or the IP address last programmed with RSLogix 5000
programming software.
When a switch is pushed to the left, it is in the Off position.
When a switch is pushed to the right, it is in the On position.
To select DHCP, move switch 2 to the On position.
To select BOOTP, move switch 1 to the On position.
On On Off The taps factory default settings are restored and then halted with the OK status indicator flashing
red.
On On On The taps factory default settings are restored and then halted with the OK status indicator flashing
red.
(1)
These switch settings cause the described power-up/reset behavior for any 1783-ETAP1F or 1783-ETAP2F tap. However, the settings cause the described power-up/reset
behavior only for 1783-ETAP taps using firmware revision 2.x or later. If you set the switches as described here on a 1783-ETAP tap with firmware revision 1.x, the
described power-up/behavior does not occur.
DIP Switch Settings and Results
Switch Power-up Behaviors for the 1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F tap
1 2 3
Publication ENET-AP005C-EN-P - May 2010 57
Additional 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F EtherNet/IP Tap Features Chapter 5
To enable ring supervisor function, move switch 3 to the On position.
However, the change in tap behavior to operate as a ring supervisor only
takes effect after the next tap power-cycle or reset.
To restore factory default settings, move the middle switch (switch 2 in
the figure) and the switch closest to the tap front panel (switch 1 in the
figure) both to the right, that is the On, position. For more information,
see page 62.
When both the middle switch (switch 2 in the figure) and the switch
closest to the tap front panel (switch 1 in the figure) are in the position,
the tap resets all configuration settings stored in NVS to factory
defaults, suspends operation, and the OK status indicator blinks red.
To resume normal operation, move the switches to the desired positions
and cycle power to the module.
IMPORTANT
For all 1783-ETAP1F and 1783-ETAP2F taps, the ring supervisor
function is enabled when switch 3 is in the On position.
However, for the 1783-ETAP tap, the ring supervisor function is
enabled when switch 3 is in the On position if the tap uses
firmware revision 2.x or later. If you move switch 3 on a
1783-ETAP tap with firmware revision 1.x to the On position,
the tap is not enabled as a ring supervisor.
58 Publication ENET-AP005C-EN-P - May 2010
Chapter 5 Additional 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F EtherNet/IP Tap Features
Internet Group
Management Protocol
(IGMP) Configuration
Parameters
The 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F taps support two Internet
Group Management Protocol (IGMP) functions.
IGMP Snooping - Enabled by default
IGMP Querier - Disabled by default
You can use either RSLogix 5000 programming software or RSLinx
communication software to configure these parameters.
IGMP Snooping
This functionality is enabled by default in the 1783-ETAP, 1783-ETAP1F, and
1783-ETAP2F taps, and is commonly used to manage multicast traffic on the
network. When in use, this functionality allows the tap to multicast data to only
those devices that need the data rather than to all devices connected to the
network.
The graphic below shows a ControlLogix controller receiving multicast data
from I/O modules via a 1783-ETAP tap. The second ControlLogix controller
does not receive unwanted multicast traffic.
IGMP Snooping
IMPORTANT
For snooping to work, there must be a device present that is
running a querier. Typically, the device is a router or a switch,
such as the Stratix 6000, Stratix 8000, or Stratix 8300 managed
switch.
1756-L63 Controller
1756-EN2T
1756-EN2T
1756 I/O Modules
Data Transmission
1783-ETAP Tap
1756-L63 Controller
1756-EN2T
Publication ENET-AP005C-EN-P - May 2010 59
Additional 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F EtherNet/IP Tap Features Chapter 5
IGMP Querier
This functionality is disabled by default. The IGMP Querier functionality
enables a 1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F tap or switch, such as
a Stratix managed switch, to send out a query to all devices on the network to
determine what multicast addresses are of interest to a specific node or a
group of nodes.
However, for all devices that you configure on the network with the IGMP
Querier parameter enabled, you must also set an IP address other than the
factory default value for those devices. If multiple devices on the network
enable this functionality, only the node with the lowest IP address becomes the
active IGMP Querier node.
IGMP Version
If you enable IGMP Querier, you must select a Querier Version. The default
version is Version 2.
IMPORTANT
You should enable the IGMP Querier functionality for at least
one node on the network. The 1783-ETAP, 1783-ETAP1F, or
1783-ETAP2F taps, managed switches, and routers are
examples of devices that support IGMP Querier functionality.
If you do not enable the IGMP Querier functionality for at least
one node on the network, multicast traffic on the network may
eventually create network performance issues.
Enable IGMP Querier here.
Select Querier Version here.
60 Publication ENET-AP005C-EN-P - May 2010
Chapter 5 Additional 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F EtherNet/IP Tap Features
Device Port
Debugging Mode
This functionality is disabled by default. You can use Device Port Debugging
mode, which is similar to port mirroring, to monitor data received on the
1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F taps two network ports over
the device port to a device, such as a personal computer running a protocol
analyzer application for advanced network debugging or analysis.
When device port debugging is used on a 1783-ETAP, 1783-ETAP1F, or
1783-ETAP2F tap, the device connected to the 1783-ETAP taps front port
receives all of the data traversing the ring (both directions).
When using the Device Port Debugging mode functionality, you insert the
1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F tap, with the network analyzer
connected to the device port, at the spot on the ring network where the node
in question is located. The graphic below shows a 1783-ETAP tap inserted in
the network.
Device Port Debugging Example Network
IMPORTANT
This functionality should be used only when troubleshooting
the network and not in normal network operation.
Personal Computer
Analyzing Network Traffic
1783-ETAP Tap With Device
Port Debugging Enabled
Break and
insert
Publication ENET-AP005C-EN-P - May 2010 61
Additional 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F EtherNet/IP Tap Features Chapter 5
Combined total network bandwidth of the traffic received on the two
1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F taps ports connected to the
network should not exceed the taps device port capacity. The speed setting
determines the device ports capacity.
You can configure the device port on a 1783-ETAP, 1783-ETAP1F, or
1783-ETAP2F tap to either of two speed settings:
100 Mbps - default setting
10 Mbps
If the bandwidth exceeds the capacity of the taps device port, some frames
from the ring will be dropped before reaching the device port. These dropped
frames do not impact the traffic on the rest of the DLR network.
The device port setting determines how much network traffic the 1783-ETAP,
1783-ETAP1F, or 1783-ETAP2F tap can handle before dropping frames. The
circled section in the graphic below shows the Device Port Port Buffer
Utilization. In this example the value is zero because a ring fault existson the
network.
62 Publication ENET-AP005C-EN-P - May 2010
Chapter 5 Additional 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F EtherNet/IP Tap Features
Replace a 1783-ETAP,
1783-ETAP1F, or
1783-ETAP2F Tap on the
Network
There may be times when you need to replace a 1783-ETAP, 1783-ETAP1F,
or 1783-ETAP2F tap on your network. In these instances, we recommend that
you use a tap that is set to factory default settings. If you are unsure of a
replacement tap's configuration, we recommend that you return the tap to its
factory default configuration.
The following example shows how to return a 1783-ETAP tap to its factory
default configuration. Follow these steps.
1. Power up the 1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F tap with
switches 1 and 2 set to On and switch 3 to Off as shown below.
2. Power off the tap.
3. Adjust the switches back to necessary setting to set the IP address. For
more information on switch settings, see Use DIP Switches on page 53.
4. Power up the tap.
Switch 3
Switch 2
Switch 1
OFF ON
Publication ENET-AP005C-EN-P - May 2010 63
Additional 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F EtherNet/IP Tap Features Chapter 5
Port Buffer Utilization
When you monitor the Port Buffer Utilization values on a 1783-ETAP,
1783-ETAP1F, or 1783-ETAP2F tap, you can monitor the values for:
Port 1.
Port 2.
Device Port.
You can monitor these fields from the Network tab for a 1783-ETAP,
1783-ETAP1F, or 1783-ETAP2F tap, as shown in the screen shot below.
If the values for any of these fields exceed 90% consistently, you should
analyze and adjust your network design.
Do not use a single 1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F tap to
connect a large number, that is hundreds, of nodes on each port with a large
amount of traffic flowing through this single tap. Doing so will significantly
impact the taps ability to transmit the data between nodes.
We recommend that you connect a large number of devices by using managed
switches. We also recommend that in your network design, you do not use
more than 50 nodes on a single DLR network.
For more information on topology recommendations, see Common Network
Topologies on page 65
64 Publication ENET-AP005C-EN-P - May 2010
Chapter 5 Additional 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F EtherNet/IP Tap Features
Notes:
65Publication ENET-AP005C-EN-P - May 2010 65
Chapter 6
Common Network Topologies
Introduction
Multiple common network topology combinations are shown in this chapter.
The intention of this chapter is to offer you a series of common topologies.
Your use of these networks/topologies is not limited to these examples.
Topic Page
Standalone DLR Networks 67
Expanding Beyond Simple Linear or DLR Networks 68
Connecting to External Switches 68
Working with STP, RSTP, or MSTP 69
Working with Other Rings (Resilient Ethernet Protocol) 70
Other Non-device-level Ring Redundant Media Topologies 71
66 Publication ENET-AP005C-EN-P - May 2010
Chapter 6 Common Network Topologies
Standalone Linear Networks
The graphics below show two example standalone linear networks. We
recommend that you do not use more than 50 nodes on a single linear
network.
The example graphic uses Rockwell Automation products that support
embedded switch technology, including 1783-ETAP taps, to construct a
copper linear network.
The example graphic uses Rockwell Automation products that support
embedded switch technology, including 1783-ETAP and 1783-ETAP1F
taps, to connect copper and fiber-optic sections of a linear network.
1783-ETAP1F
Connection to
fiber-optic
section of the
linear network
1783-ETAP
Publication ENET-AP005C-EN-P - May 2010 67
Common Network Topologies Chapter 6
Standalone DLR Networks
The graphics below show two standalone DLR networks. We recommend that
you do not use more than 50 nodes on a single DLR network.
The example graphic shows how to use Rockwell Automation products
that support embedded switch technology, including 1783-ETAP taps
to construct a copper DLR network.
The example graphic shows how to use 1783-ETAP2F taps to connect
Rockwell Automation products to a fiber-optic DLR network.
Active Supervisor Node Back-up Supervisor Node
Back-up Supervisor Node Ring Node
Ring Node Ring Node
DLR Network with
Copper Connections
Active Supervisor Node Back-up Supervisor Node
Back-up Supervisor Node Ring Node
Ring Node Ring Node
DLR Network with
fiber-optic Connections
68 Publication ENET-AP005C-EN-P - May 2010
Chapter 6 Common Network Topologies
Expanding Beyond Simple Linear or DLR Networks
This section shows the following topologies:
Connecting to External Switches
Working with STP, RSTP, or MSTP
Working with Other Rings (Resilient Ethernet Protocol)
Other Non-device-level Ring Redundant Media Topologies
Connecting to External Switches
In this example, the 1783-ETAP taps on the DLR network can be connected
to managed or unmanaged switches with star or linear topologies. Make sure
you segment your network properly and limit the traffic sent between
1783-ETAP taps. For example limit the traffic from network A to network B.
To monitor how much the network traffic is using of a 1783-ETAP taps port
capacity, check the Port Buffer Utilization values. For more information on
Port Buffer Utilization, see page 63.
1783-ETAP
1783-ETAP
DLR Network
Stratix
2000
1783-ETAP
1783-ETAP
Network A Network B
Network C Network D
Stratix
2000
Stratix
2000
Stratix
2000
1738-AENT 1738-AENT 1756-EN2T
1756-EN2T 1756-EN2T
1734-AENT
1734-AENT 1734-AENT
Publication ENET-AP005C-EN-P - May 2010 69
Common Network Topologies Chapter 6
Working with STP, RSTP, or MSTP
In this example, the managed switches that are used must support Spanning
Tree Protocol (STP), Rapid Spanning Tree Protocol (RSTP) or Multiple
Spanning Tree Protocol (MSTP) and have that protocol enabled.
If a fault occurs on any of the redundant links between the managed switches,
the recovery time is dependent on the protocol being used on the managed
switches.
1783-ETAP
DLR Network DLR Network
DLR Network DLR Network
Stratix
8000
1783-ETAP
1783-ETAP 1783-ETAP
Linear Network
Stratix
8000
Stratix
8000
Stratix
8000
Linear Network
Stratix 2000
CompactLogix with
1783-ETAP
CompactLogix with
1783-ETAP
CompactLogix with
1783-ETAP
CompactLogix with
1783-ETAP
1734-AENTR
1783-ETAP 1783-ETAP
1738-AENT 1738-AENT
1738-AENTR 1738-AENTR
1734-AENTR 1734-AENTR
1734-AENTR 1734-AENTR
1734-AENTRs
70 Publication ENET-AP005C-EN-P - May 2010
Chapter 6 Common Network Topologies
Working with Other Rings (Resilient Ethernet Protocol)
If a fault occurs on a non-DLR ring network, the recovery time is
protocol-dependent.
1783-ETAP
DLR Network DLR Network
DLR Network DLR Network
Stratix
8000
1783-ETAP
1783-ETAP 1783-ETAP
1783-ETAP
1783-ETAP
Linear network
Stratix
2000
Stratix
8000 Stratix
8000
Stratix
8000
REP Network
1738-AENTR 1738-AENTR
CompactLogix with
1783-ETAP
CompactLogix with
1783-ETAP
Linear network
1738-AENT
1756-EN2TR
1734-AENTRs
1734-AENTR 1734-AENTR
1734-AENTR
1734-AENT
1734-AENTR 1734-AENTR
1734-AENTRs
Publication ENET-AP005C-EN-P - May 2010 71
Common Network Topologies Chapter 6
Other Non-device-level Ring Redundant Media Topologies
If you are using either of the following topologies, consider the following:
The managed switches that are used must support STP, RSTP, or MSTP
protocol and have that protocol enabled.
Any supervisor-capable devices used in these example topologies should
not be configured as supervisors. If the devices are configured as
supervisors, the network beacons will cause network disruptions.
In both examples, if a fault occurs on any of the redundant links
between managed switches, the recovery time depends on the protocol
being used.
Graphic 1
Graphic 2
Stratix
8000
Connections to other devices that
may or may not be on DLR networks
Any Rockwell Automation products that support
embedded switch technology can be used at this
spot in the topology.
For a full list of products that support embedded
switch technology, see page 12.
1756-EN2TR
Stratix
8000
Stratix
8000
1734-AENTR 1734-AENTR
Any Rockwell Automation products that support embedded
switch technology can be used at this spot in the topology.
For a full list of products that support embedded switch
technology, see page 12.
72 Publication ENET-AP005C-EN-P - May 2010
Chapter 6 Common Network Topologies
Notes:
Publication ENET-AP005C-EN-P - May 2010 73
Appendix A
Network Usage Guidelines and
Recommendations
Consider the following guidelines and recommendations when using a DLR or
linear network.
Guideline/Recommendation Explanation
Use fewer than 50 nodes on a single DLR
network.
If your application requires more than 50
nodes, we recommend that you break the
nodes into separate, but linked, DLR
networks.
If you use more than 50 nodes on a single DLR network:
your network has a greater chance of multiple faults occurring on the network.
network recovery times from faulted DLR network are higher.
Do not configure a supervisor on a linear
network.
If your linear network includes non-DLR nodes and has a supervisor-enabled node on the
network, it may impact communication to non-DLR devices connected to the linear network.
If you must connect a device that is running
at 10 Mbps to a DLR or linear network, do
so through a 1783-ETAP, 1783-ETAP1F, or
1783-ETAP2F tap device port.
The 1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F taps can operate at 100 Mbps on the DLR
network; this is the optimal speed for a network. If you connect a 10 Mbps device directly to
the network, instead of through a tap, the linear or DLR network traffic slows to 10 Mbps.
Additionally, if the 10 Mbps device is connected to the network without a 1783-ETAP tap,
network recovery times are significantly impacted.
Configure multiple supervisor nodes
per ring.
If your DLR network only has one supervisor and the supervisor experiences a fault, none of
the other nodes become the active supervisor. In this case, the network becomes a linear
network until the fault is corrected and the DLR network restored.
Another reason to configure multiple supervisor nodes is that if you need to replace an
active supervisor node with an out-of-box replacement, the new device will not be enabled
as a supervisor (by default) and there would still be no supervisor on the network.
Connect switches to a DLR network via
1783-ETAP, 1783-ETAP1F, or 1783-ETAP2F
taps.
If switches are connected to the DLR network without the use of a 1783-ETAP, 1783-ETAP1F,
or 1783-ETAP2F tap, the network may experience unpredictable behavior and network
performance is unknown.
Run all nodes on the DLR network at 100
Mbps and in Full-Duplex mode.
These configuration values provide the best performance for your network.
Additionally, we recommend that you:
use auto-negotiate for all nodes on the DLR network.
do not use auto-negotiate on one node and then force speed on the next node linked
to it.
74 Publication ENET-AP005C-EN-P - May 2010
Appendix A Network Usage Guidelines and Recommendations
In a linear network, the number of nodes to
use is application specific, based on the
considerations described in the next box.
When determining the number of nodes to use on a linear network, consider the following:
There is a delay per node as information is transmitted to each successive node used on
the network.
- The typical delay on a linear network with 100 m copper segments between nodes is
30 S.
- The typical delay on a linear network with 2 kM fiber-optic segments between nodes
is 40 S.
The greater the number of nodes on the network, the longer the total time for
information to be transmitted across the entire network.
The single point of failure possibility is greater with each additional connection.
Troubleshooting the network may be more difficult with a higher number of nodes.
Do not physically close a DLR network
without a supervisor configured on the
network.
A DLR network without a supervisor node results in a network storm.
If you do close the DLR network without a supervisor configured, break the ring and
configure at least one supervisor before physically reconnecting the network.
Use the default values for the following:
Beacon Interval
Beacon Timeout
Ring Protocol VLAN ID
Changing the default values for the parameters Beacon Interval, Beacon Timeout and Ring
Protocol VLAN ID, can result in unpredictable network behavior and negatively impacted
network performance.
The default values are optimized for a network with:
50 or fewer nodes are on the network.
all nodes are operating at 100 Mbps and full-duplex mode.
at least 50% of the network traffic bandwidth being EtherNet/IP traffic
If you think you need to change the values of the Beacon Interval, Beacon Timeout or Ring
Protocol VLAN ID, for example, if any node on ring is not operating at 100 Mbps and
full-duplex mode, we recommend that you first call Rockwell Automation technical support.
Guideline/Recommendation Explanation
IMPORTANT
The total time for information to be transmitted across the entire
network, and its effect on how many nodes to use on a linear
network, is related to the Requested Packet Interval (RPI).
You should verify that the total time to transmit information from
the first node to the last node on the network is less than the RPI.
Make sure the network is not loaded beyond 90% of capacity.
Publication ENET-AP005C-EN-P - May 2010 75
Appendix B
Network Recovery Performance
When you measure your networks performance, with regard to dealing with
fault conditions, you should consider the network recovery time. Network
recovery is the time for all of the following to take place:
1. The supervisor node recognizes that a fault exists on the network.
2. The supervisor node reconfigures the network appropriately because
of the fault.
3. The supervisor node communicates to the network nodes that a fault
condition exists.
4. The network nodes reconfigure themselves appropriately because of
the fault.
With the default beacon interval value of 400 S and beacon timeout value of
1960 S, the worst-case time for network recovery times are:
2890 S for a copper DLR network. This recovery time is based on
100 m copper segments between nodes on the network.
3140 S for a fiber-optic DLR network. This recovery time is based
on 2 kM fiber-optic cable segments between nodes on the network.
When considering the values listed above, keep in mind:
Recovery time may actually occur faster than the times listed.
The recovery times listed above assume that your networks nodes are
operating at 100 Mbps speed and full-duplex mode. We recommend
that your nodes generally operate in this mode for DLR networks.
If other node conditions exist, such as a node operating at 10 Mbps
full-duplex, or 10/100 Mbps half-duplex, the recovery times will vary
from the times listed above.
If this is the case for your application, you will need to change the
beacon interval and beacon timeout. If you think you need to change
these parameters, we recommend that you first call Rockwell
Automation technical support.
The value assumes that the majority of the traffic on your network is
EtherNet/IP traffic.
76 Publication ENET-AP005C-EN-P - May 2010
Appendix B Network Recovery Performance
Notes:
Publication ENET-AP005C-EN-P - May 2010 77
Index
Numerics
1732E modules 13
1734-AENTR adapter 12
1738-AENTR adapter 12
1756-EN2TR module 12
1783-ETAP, 1783-ETAP1F, and
1783-ETAP2F taps 12, 53-63
device port debugging mode (port
mirroring) 60
DIP switches 53
IGMP Querier 59
IGMP Snooping 58
IGMP Version 59
port buffer utilization 63
replace on a network 62
A
active ring supervisor 39
active supervisor precedence 39
add-on profile 23
required revision with specific firmware
revisions 23
B
back-up supervisor node 17
beacon interval 18, 28, 32, 74
beacon timeout 18, 28, 32, 74
C
common network topologies 65-71
connecting to external switches 68
DLR 11, 67
expanding beyond simple linear or DLR
networks 68-71
linear 10, 66
other non-device level ring redundant
media topologies 71
star 9
working with other rings (resilient
Ethernet protocol) 70
working with STP, RSTP, or MSTP 69
configure
a ring supervisor in RSLinx
communication software 29-32
a ring supervisor in RSLogix 5000
programming software 23-25
beacon interval 28, 32
beacon timeout 28
Ring Protocol VLAN ID 28, 32
construct and configure a DLR network
21-34
D
device port debugging mode 32, 60
device web pages 41
minimum firmware revision for
1783-ETAP tap 41
monitor a DLR network 36
DIP switches
on 1783-ETAP, 1783-ETAP1F, and
1783-ETAP2F taps 53
DLR network
common topologies 11, 67
construct and configure 21-34
monitor 35-48
troubleshoot 49-52
E
elements of DLR network 15-17
enable
a ring supervisor in RSLinx
communication software 29-32
a ring supervisor in RSLogix 5000
programming software 26-28
EtherNet/IP embedded switch
technology overview 9-20
F
fault management on DLR network 19
I
IGMP Querier 32, 59
IGMP Snooping 32, 58
IGMP Version 59
install devices on a DLR network 21
L
last active node on port 1 40
last active node on port 2 40
linear network
common topologies 10, 66
troubleshoot 49-52
78 Publication ENET-AP005C-EN-P - May 2010
Index
M
media counter error or collisions 52
monitor a DLR network 35-48
active ring supervisor 39
active supervisor precedence 39
device web pages 41
enable ring supervisor 39
last active node on port 1 40
last active node on port 2 40
methods 35
network status 39
network topology 39
programmatically 36, 42-48
ring faults detection 39
supervisor status 40
using device web pages 36
using RSLinx communication software
36, 38
using RSLogix 5000 programming
software 36, 37
MSG instruction
enable and configure a ring supervisor 48
request the ring participant list 47
retrieve all ring diagnostic information 45
N
network recovery times 75
network status 39
network usage guidelines and
recommendations 73-74
node
active ring supervisor 39
back-up supervisor node 17
enable ring supervisor 39
number on a DLR network 19
number on a linear network 74
ring node 17
supervisor 16
supervisor status 40
P
partial fault condition 52
port buffer utilization
1783-ETAP, 1783-ETAP1F, and
1783-ETAP2F taps 63
port mirroring 60
programmatically monitoring a DLR
network 36, 42-48
R
rapid ring fault 51
replace 1783-ETAP, 1783-ETAP1F, and
1783-ETAP2F taps 62
ring faults detection 39
ring node 17
Ring Protocol VLAN ID 28, 32, 74
ring supervisor
enable in RSLinx communication
software 29-32
enable in RSLogix 5000 programming
software 26-28
RSLinx communication software 22
configure beacon timeout 32
configure Ring Protocol VLAN ID 32
configure supervisor precedence 32
enable device port debugging mode 32
enable ring supervisor 29-32
IGMP Querier 32
IGMP Snooping 32
monitor a DLR network 36, 38
verify supervisor configuration 34
RSLogix 5000 programming software 22
configure beacon timeout 28
configure Ring Protocol VLAN ID 28
configure supervisor precedence 28
enable ring supervisor 26-28
monitor a DLR network 36, 37
verify supervisor configuration 34
Publication ENET-AP005C-EN-P - May 2010 79
Index
S
software
RSLinx communication software 22
RSLogix 5000 programming software 22
star topology 9
supervisor node 16
active ring supervisor 16
beacon interval 28, 32
beacon timeout 28, 32
configure 22-32
Ring Protocol VLAN ID 28, 32
status 40
supervisor precedence 28, 32
verify configuration 34
supervisor precedence 32
T
troubleshoot 49-52
actions to take before correcting specific
network faults 49
media counter errors or collisions 52
partial fault condition 52
rapid ring fault 51
supervisor reports a ring fault 50
V
verify configuration 34
80 Publication ENET-AP005C-EN-P - May 2010
Index
Publication ENET-AP005C-EN-P - May 2010 82
Supersedes Publication ENET-AP005B-EN-P - January 2010 Copyright 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and
application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the
best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect
support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience an anomoly within the first 24 hours of installation, review the information that is contained in this manual.
You can contact Customer Support for initial help in getting your product up and running.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility.
However, if your product is not functioning and needs to be returned, follow these procedures.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
United States or Canada 1.440.646.3434
Outside United States or
Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html,
or contact your local Rockwell Automation representative.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number
above to obtain one) to your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.

Вам также может понравиться