Вы находитесь на странице: 1из 9

Systemair A/S - Air handling unit design

SystemairCAD - Version C2013-12.04.D1


1/16/2014
Page 1
Project: ventilatii - cta Unit: Danvent DV80
Summary for unit no. 1, Danvent DV80
Unit size 80 Roof unit
Unit width 2170 mm
Weight 4566 kg
Supply Extract
Airflow (1,205 kg/m) 13280.40 m3/h 13280.40 m3/h
Face velocity (unit) 1.54 m/s 1.54 m/s
External pressure 382 Pa 436 Pa
Filter F7 F7
Fan speed 1123 RPM 1091 RPM
Motor 5.50 kW 4.00 kW
Voltage 3x400 V 3x400 V
Rated current 13.70 A 10.00 A
Heat recovery 58.7 %
SFP, clean filters including frequency converter 2.21 kW/(m/s)
SFP, clean filters excluding frequency converter 2.10 kW/(m/s)
Heating 32.00 kW - Air 8.3/15.5C - Water 70/50C - 0.8 kPa - 0.39 l/s
Pipe connections 1 1/2" / 1 1/2"
Cooling 36.72 kW - Air 26.0/18.6C - Water 6/12C - 28.0 kPa - 1.45 l/s
Pipe connections 1 1/4" / 1 1/4"
Eurovent energy efficiency class A
Sound power level 63 125 250 500 1k 2k 4k 8k Hz Total
Supply air 69 69 66 58 45 39 36 38 dB 61 dB(A)
Outdoor air 63 73 72 63 59 51 44 33 dB 67 dB(A)
Exhaust air 68 68 65 58 44 39 36 38 dB 60 dB(A)
Extract air 63 74 73 66 63 59 51 43 dB 69 dB(A)
Sound break out 62 71 60 50 51 48 42 37 dB 59 dB(A)
Systemair Rt Telephone : +40 314055588
Telefax : +40 213514482
www.systemair.ro
Systemair A/S - Air handling unit design
SystemairCAD - Version C2013-12.04.D1
1/16/2014
Page 2
Project: ventilatii - cta Unit: Danvent DV80
Plan view Access side
Systemair Rt Telephone : +40 314055588
Telefax : +40 213514482
www.systemair.ro
Systemair A/S - Air handling unit design
SystemairCAD - Version C2013-12.04.D1
1/16/2014
Page 3
Project: ventilatii - cta Unit: Danvent DV80
Right end Left end
Doors and panels dimensions
Systemair Rt Telephone : +40 314055588
Telefax : +40 213514482
www.systemair.ro
Systemair A/S - Air handling unit design
SystemairCAD - Version C2013-12.04.D1
1/16/2014
Page 4
Project: ventilatii - cta Unit: Danvent DV80
Technical specification
The supply unit consist of
Empty section
Pressure drop 1 Pa
Length 900 mm
Damper
Pressure drop 1 Pa
Damper blades Standard
Filter
Dimensioning pressure drop 117 Pa
Initial pressure drop/Final pressure drop 58/176 Pa
Velocity, face area 1.74 m/s
Velocity, filter area 0.09 m/s
Filter class F7
Filter size 4x[490x592] +4x[490x490]
Filter length 535 mm
Empty section
Pressure drop 1 Pa
Length 450 mm
Plate heat exchanger
With face and by-pass damper
Supply Extract
Air flow 13280 13280 m3/h
Pressure drop 77 77 Pa
WINTER Air temperature before/after -12.0/5.6 18.0/4.2 C
Air relative humidity before/after 80/21 50/97 %
Condensate 0.4 l/min
Capacity 78.85 kW
Temperature efficiency 58.7 %
Dry efficiency according to EN 308 at 13280 m3/h 53.3 %
SUMMER Air temperature before/after 29.2/26.8 24.6/27.1 C
Air relative humidity before/after 43/50 50/43 %
Condensate 0.0 l/min
Capacity 11.15 kW
Temperature efficiency 53.3 %
Heat exchanger type Aluminum heat exchanger
Temperature efficiency Standard efficiency
Drip tray Standard
Mixing damper
Supply Extract
Systemair Rt Telephone : +40 314055588
Telefax : +40 213514482
www.systemair.ro
Systemair A/S - Air handling unit design
SystemairCAD - Version C2013-12.04.D1
1/16/2014
Page 5
Project: ventilatii - cta Unit: Danvent DV80
Air flow 1833 13280 m3/h
Pressure drop 5 5 Pa
WINTER Air temperature before/after 5.6/18.0 20.0/20.0 C
Air relative humidity before/after 21.4/50.1 50.0/50.0 %
Mixing ratio 86 %
SUMMER Air temperature before/after 26.8/24.9 24.6/24.6 C
Air relative humidity before/after 49.6/50.0 50.0/50.0 %
Mixing ratio 86 %
Damper blades 3 dampers
Mixing damper type Standard
Humidifier
Air flow 13280 m3/h
Pressure drop - Panel 42.0 Pa
Pressure drop - Eliminator 29.0 Pa
Total Pressure 71.0 Pa
Evaporated water 1.7 g/kg
Efficiency 90.3 %
Max cooling temp decrease 4.1 C
Air temperature before/after 14.0/9.9 C
Air relative humidity before/after 55.0/94.7 %
Total Pressure Service side
Purge Connection 32 PVC
Filling connection 3/8" BSP
Width 2060 mm
Height 1160 mm
Depth 550 mm
Net area 1.6 m2
Face velocity 2.3 m/s
Pump - power 71.0 W
Frame material Stainless steel
Baffle material Hu-Cell
Baffle thickness 150 mm
Level detector 1 pcs
Droplet eliminator 1 pcs
Its necessary to connect the level detector before connection of water
pump. If not the unit doesnt work properly and connection must be
done by the installer.
Heating coil, Fluid
Air flow 13280 m3/h
Pressure drop 18 Pa
Air temperature before/after 8.3/15.5 C
Air relative humidity before/after 50/31 %
Capacity 32.00 kW
Face velocity 1.72 m/s
Fluid type Water
Fluid temperature inlet/outlet 70.0/50.0 C
Fluid flow rate 0.39 l/s
Fluid pressure drop 0.8 kPa
Fluid velocity 0.20 m/s
Coil volume 16.5 l
Connection side Service side
Connection size inlet/outlet 1 1/2" / 1 1/2"
Systemair Rt Telephone : +40 314055588
Telefax : +40 213514482
www.systemair.ro
Systemair A/S - Air handling unit design
SystemairCAD - Version C2013-12.04.D1
1/16/2014
Page 6
Project: ventilatii - cta Unit: Danvent DV80
Tube material Cu
Fin material Al
Fin spacing 2.1 mm
No. of rows 2
Coil code DVH-80-W-Z-2-27-1125-1905-2.1-CU-Al-H-1 1/2
Cooling coil, Fluid
Air flow 13280 m3/h
Pressure drop air, wet coil with condensate droplets 29 Pa
Air temperature before/after 26.0/18.6 C
Air relative humidity before/after 52/80 %
Total cooling capacity 36.72 kW
Sensible cooling in % of total cooling 90 %
Face velocity 1.72 m/s
Condensate 0.1 l/min
Fluid type Water
Fluid temperature inlet/outlet 6.0/12.0 C
Fluid flow rate 1.45 l/s
Fluid pressure drop 28.0 kPa
Fluid velocity 0.91 m/s
Coil volume 21.8 l
Connection side Service side
Connection size inlet/outlet 1 1/4" / 1 1/4"
Tube material Cu
Fin material Al
Fin spacing 2.1 mm
No. of rows 3
Drip tray material Standard
Coil code DVK-80-W-Z-3-22-1125-1905-2.1-CU-Al-H-1 1/4
Fan , Plug
Air flow 13280 m3/h
External pressure 382 Pa
Pressure drop 25 Pa
Static pressure 741 Pa
Total pressure 783 Pa
Absorbed power 3.75 kW
Fan speed 1123 RPM
Maximum fan speed 1230 RPM
Efficiency by static pressure 72.9 %
Efficiency by total pressure 77.0 %
K-factor (p=1,2 kg/m3) 490
Fan type M-RH71C
Operation frequency 58 Hz
Max. operating frequency 64 Hz
Direct drive
Motor
Motor type IE2
Motor types-size ABB-132MC
Motor protection Thermistor
Rated power 5.50 kW
Speed (nominal) 965 RPM
Current, Amp. 13.70 A
Systemair Rt Telephone : +40 314055588
Telefax : +40 213514482
www.systemair.ro
Systemair A/S - Air handling unit design
SystemairCAD - Version C2013-12.04.D1
1/16/2014
Page 7
Project: ventilatii - cta Unit: Danvent DV80
Efficiency 86.1 %
Efficiency, actual working point 86.0 %
Voltage 3x400 V
Consumed power from mains power supply, excluding frequency converter 4.36 kW
Consumed power from mains power supply, including frequency converter 4.59 kW
Sound attenuator
Pressure drop 13 Pa
63 125 250 500 1k 2k 4k 8k Hz
Sound attenuation 5 11 17 25 36 39 36 28 dB
Cleaning of the material Standard
The extract unit consist of
Empty section
Pressure drop 1 Pa
Length 450 mm
Inspection section
Pressure drop 1 Pa
Length 300 mm
Empty section
Pressure drop 1 Pa
Length 150 mm
Damper
Pressure drop 1 Pa
Damper blades Standard
Filter
Dimensioning pressure drop 117 Pa
Initial pressure drop/Final pressure drop 58/176 Pa
Velocity, face area 1.74 m/s
Velocity, filter area 0.09 m/s
Filter class F7
Filter size 4x[490x592] +4x[490x490]
Filter length 535 mm
Empty section
Pressure drop 1 Pa
Length 450 mm
Empty section
Pressure drop 1 Pa
Length 900 mm
Systemair Rt Telephone : +40 314055588
Telefax : +40 213514482
www.systemair.ro
Systemair A/S - Air handling unit design
SystemairCAD - Version C2013-12.04.D1
1/16/2014
Page 8
Project: ventilatii - cta Unit: Danvent DV80
Inspection section
Pressure drop 1 Pa
Length 600 mm
Mixing damper
Data are stated on supply.
Plate heat exchanger
Data are stated on supply.
Fan , Plug
Air flow 13280 m3/h
External pressure 436 Pa
Pressure drop 25 Pa
Static pressure 683 Pa
Total pressure 725 Pa
Absorbed power 3.45 kW
Fan speed 1091 RPM
Maximum fan speed 1110 RPM
Efficiency by static pressure 73.1 %
Efficiency by total pressure 77.6 %
K-factor (p=1,2 kg/m3) 490
Fan type M-RH71C
Operation frequency 57 Hz
Max. operating frequency 58 Hz
Direct drive
Motor
Motor type IE2
Motor types-size ABB-132MA
Motor protection Thermistor
Rated power 4.00 kW
Speed (nominal) 960 RPM
Current, Amp. 10.00 A
Efficiency 85.3 %
Efficiency, actual working point 85.1 %
Voltage 3x400 V
Consumed power from mains power supply, excluding frequency converter 4.05 kW
Consumed power from mains power supply, including frequency converter 4.27 kW
Sound attenuator
Pressure drop 13 Pa
63 125 250 500 1k 2k 4k 8k Hz
Sound attenuation 5 11 17 25 36 39 36 28 dB
Cleaning of the material Standard
Systemair Rt Telephone : +40 314055588
Telefax : +40 213514482
www.systemair.ro
Systemair A/S - Air handling unit design
SystemairCAD - Version C2013-12.04.D1
1/16/2014
Page 9
Project: ventilatii - cta Unit: Danvent DV80
Other parts
Sections
Product Dimensions (width x height x length) Weight
AHU1-5410 2270 x 2910 x 5410 mm 2458 kg
AHU2-3990 2270 x 2910 x 3990 mm 2118 kg
The unit sections are delivered mounted on base frame.
Duct connections
Product Dimensions (width x height)
Outdoor 2100x1150 mm
Supply 2100x1150 mm
Extract 2100x1150 mm
Exhaust 2100x1150 mm
Systemair Rt Telephone : +40 314055588
Telefax : +40 213514482
www.systemair.ro

Вам также может понравиться