Вы находитесь на странице: 1из 12

B4

Purchase Order and Instrument specification sheet criteria shall be


confirmed and compared with instrument stainless steel tags / labels
and nameplates, and shipment checked for damage, prior to acceptance
of the shipment
Schedule Q,
Att IV, Sec. 7.1.
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL
TRAVEL TIME
SAUDI ARAMCO USE ONLY
SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
PLANT NO. EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID.
CONTRACTOR / SUBCONTRACTOR
Intrinsically Safe Circuit- Design / Procurement Package-
Documentation Review
SAIC-J-6902 1-Oct-05 INST
REFERENCE PASS
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLIST
SAIC NUMBER DATE APPROVED QR NUMBER
PROJ ECT TITLE WBS / BI / J O NUMBER
FAIL
A. I.S. System Certification Information and Third Party Listing Requirements
N/A RE-INSP DATE
ITEM
No.
ACCEPTANCE CRITERIA
A1
A2
A System Control Drawing shall be provided including all Entity Concept
parameters for each component in the intrinsically safe system. I.S.
system control drawings shall be prepared in accordance with ISA
RP12.2.02
SAES-J -903, Sec
7.4
The standard (SAES-J -903) and check list shall be followed in its entirety
after obtaining prior permission to use an intrinsically safe system from
the General Supervisor, Process Instrumentation Division, P&CSD.
SAES-J -903, Sec
1.4
A4
The Certifying agency, Certificate number, and Date of certification shall
be supplied for each component in the intrinsically safe system.
SAES-J -903, Sec
1.4
A3
The I.S. system control drawing shall be included as a separate sheet of
the associated Instrument Loop Drawing (ILD)
SAES-J -903, Sec
1.4
SAES-J -903, Sec
7.4
A6
Only equipment, apparatus or devices that have been certified, labeled
or listed as intrinsically safe (I.S.) by a third party testing laboratory shall
be used or installed under this standard.
Exception: If the field device is classified as simple apparatus,
certification is not required.
SAES-J -903, Sec
5.1
A5
If the field device is classified as simple apparatus, certification of the
device itself is not required. However, all devices included in the
Intrinsically Safe loop, shall be shown on the System Control Drawing.
A7
As third party testing laboratories, only the agencies listed in SAES-P-
100, Table 1(Atttachment- 1) are acceptable under this standard.
For equipment, devices, or apparatus certified as intrinsically safe, only
those that are certified as category EEX or AEX "ia" shall be used.
Commentary Note: The identifying letter for intrinsic safety is "i" followed
by either "a" or "b," identifying whether the equipment is suitable for Zone
0 (ia) or Zone 1 (ib). Intrinsically safe systems are limited by this
standard to those certified "ia" to simplify the selection process and to
ensure that an I.S. system is safe to install in all locations (Zone 0, 1, or
2).
SAES-J -903, Sec
1.4
B1
The I.S. system design package shall consist of the following
documentation: (B2 -B10)
SAES-J -903, Sec
1.4
B3
The manufacturer's storage, handling and preservation instructions to be
followed.
Schedule Q,
Att, IV, Sec 5.
B 2
B General Material Requirements - I.S System Design Package
Electrical area classification drawing
SAES-J -903, Sec
7.1
Page 1 of 12
SAES-J -903, Sec
1.4
C. Design requirements - Classification based on Temp. / Densities
SAES-J -903, Sec
7.5.4
B10
B5
Plan drawing showing the overall I.S. system from the instruments in the
hazardous areas to the instruments in the non-hazardous area (usually
the control room). For sake of clarity, the drawing shall show the I.S.
system only.
Demarcation lines between the non-hazardous (safe) area and the
hazardous area portions of system shall be clearly shown. The
respective areas shall be labeled "non-hazardous (safe)" and "hazardous
area".
SAES-J -903, Sec
7.2
B6
Typical loop diagrams showing termination assignments in junction
boxes and marshalling panels.
SAES-J -903, Sec
7.4
C4
Mixtures of Gases or Vapors of Different Ignition Temperatures:
Where a mixture of gases or vapors is composed of gases/vapors of
different ignition temperature, designation of the ignition temperature of
the mixture shall be by any one of the following methods:
5.3.1 The ignition temperature of that gas/vapor in the mixture having the
lowest individual ignition temperature per NFPA 325.
5.3.2 The ignition temperature of the mixture as determined by a test
specified in NFPA 325.
5.3.3 The ignition temperature as determined by calculations that have
been reviewed and accepted by the Chief Fire Prevention Engineer,
Dhahran.
SAES-B-068, Sec
5.3
SAES-J -903, Sec
1.4
General Area Classification Drawings shall be developed for all
facilities where flammable liquids, gases, or vapors are produced,
processed, stored or handled. This applies to new facilities, or
extensions/additions to existing facilities.
SAES-B-068, Sec
5.1
B7
B8 Cable length, meters (feet)
SAES-J -903, Sec
7.5.2
Size of individual pair or triad, capacitance per unit length, and
inductance per unit length.
Single pair/triad interconnecting cables shall be specified with a
minimum conductor size of 16 AWG.
Exception: Multiconductor "home run" cables may be specified with 18
AWG conductor size.
SAES-J -903, Sec
7.5.1
CONTRACTOR / SUBCONTRACTOR
Intrinsically Safe Circuit- Design / Procurement Package-
Documentation Review
SAIC-J-6902 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLIST
SAIC NUMBER DATE APPROVED QR NUMBER
PROJ ECT TITLE WBS / BI / J O NUMBER
N/A RE-INSP DATE
B9
Insulation Rating: Interconnecting cables shall be specified with a
minimum insulation rating of 600 Volts.
SAES-J -903, Sec
7.5.3
ITEM
No.
ACCEPTANCE CRITERIA REFERENCE
B10 Cable manufacturer
PASS FAIL
B11 Grounding Plan: Overall control house grounding plan
SAES-J -903, Sec
7.6.1
C3
C2
The use of Intrinsic Safety as a protection method is required for all
instruments located within Class I, Zone 0 areas
C1
I.S. systems shall only be used where other methods of protection are
impractical (e.g., ship loading arms and inline analyzers).
I.S. system vendor recommended grounding method
SAES-J -903, Sec
7.6.2
Page 2 of 12
CONTRACTOR / SUBCONTRACTOR
Intrinsically Safe Circuit- Design / Procurement Package-
Documentation Review
SAIC-J-6902 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLIST
SAIC NUMBER DATE APPROVED QR NUMBER
PROJ ECT TITLE WBS / BI / J O NUMBER
N/A RE-INSP DATE
ITEM
No.
ACCEPTANCE CRITERIA REFERENCE PASS FAIL
D. Extent of Classification Locations
D1
For relief valves venting to atmosphere, the classified area shall be
determined by: (see Attachments 2-6)
a) Figure 20, or Figure 21, when the source is adequately ventilated and
the gas/vapor is heavier than air.
b) Figure 24, when the source is adequately ventilated and the gas/vapor
is lighter than air.
c) Figure 22, when the source is inadequately ventilated and the
gas/vapor is heavier than air.
d) Figure 25, when the source is inadequately ventilated and the
gas/vapor is lighter than air.
e) The termination of a relief valve discharge, the associated weep hole,
and the bonnet vent shall each be a "source".
f) A non-flowing pilot on a pilot-operated relief valve shall not be a
"source".
SAES-B-068, Sec
6.2.1
C8
Typical relationship between Zone classification and the presence of
flammable mixtures can be seen in the following rule-of thumb.
Zone Flammable Mixture Present
0 1000 or more hours/year (10%)
1 10 <hours/year <1000(.1% to 10%)
2 1 <hours/year <10 (.01% to .1%)
unclassified Less than 1 hour/year (.01%)
Refer to API RP 505 section 6.5.8 for further details.
SAES-B-068, Sec
5.7
C7
Electrical Area Classification Drawings: The drawings shall, as a
minimum, show the following information:
5.6.1 The demarcation of the Zone 0, 1, 2 and unclassified areas, both
vertically and horizontally via plan, elevation, and section views.
5.6.2 The minimum ignition temperature of the mixture of gases/vapors
creating each classified location.
5.6.3 The type of gas or vapor in each of the classified areas. This shall
be presented as the name (s) of the gas/vapor and by the Group IIA, B,
or C designations defined within NFPA 70 and API RP 505.
SAES-B-068, Sec
5.6
C6
Mixtures of Gases of Different Groups: Where a mixture contains
gases of different Groups per NFPA 70, the area classification shall
satisfy the requirements for every Group for which the aggregate volume
of gas constitutes 30% or more of the mixture composition.
SAES-B-068, Sec
5.5
C5
Mixtures of Gases of Different Densities " For a gas or mixture of
gases composed entirely of lighter-than-air gases, the extent of the
classified location shall satisfy the requirements for lighter-than-air
vapors.
Where a mixture is composed of lighter-than-air and heavier-than-air
gases and the mixture density is less than 75% of the density of air at
standard conditions, the extent of the classified area shall satisfy the
requirements for lighter-than-air vapors.
Where the mixture has a density equal to or greater than 75% of air at
standard conditions, it shall be considered as a heavier-than-air vapor for
area classification purposes.
SAES-B-068, Sec
5.4
Page 3 of 12
CONTRACTOR / SUBCONTRACTOR
Intrinsically Safe Circuit- Design / Procurement Package-
Documentation Review
SAIC-J-6902 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLIST
SAIC NUMBER DATE APPROVED QR NUMBER
PROJ ECT TITLE WBS / BI / J O NUMBER
N/A RE-INSP DATE
ITEM
No.
ACCEPTANCE CRITERIA REFERENCE PASS FAIL
D5
For the manways and piping-to-vessel connections on process vessels
and the piping-to-equipment connections on process equipment, the
classified area shall be determined by:
a) Figure 22, when the source is inadequately ventilated and the
gas/vapor is heavier than air.
b) Figure 25, when the source is inadequately ventilated and the
gas/vapor is lighter than air.
c) When the source in 6.2.7 is adequately ventilated, the Class I, Zone 2
area shall extend for 3 m around it. This is for all gases/vapors,
irrespective of whether they are lighter than air or heavier than air.
d) Connections on adequately ventilated vessels and equipment
containing fuel gas at a maximum gauge operating pressure of 350 kPa
(50 psig) shall not be considered release sources.
e) Connections on furnaces, fired boilers, fired heaters, incinerators, and
other equipment containing open flames shall not be considered release
sources. See Note (f) of paragraph 6.2.7.
SAES-B-068, Sec
6.2.5
D4
For the atmospheric terminations of sample stations, the classified area
shall be determined by:
a) Figure 20, Figure 21, when the source is adequately ventilated and the
gas/vapor is heavier than air.
b) Figure 24, when the source is adequately ventilated and the gas/vapor
is lighter than air.
c) Figure 22, when the source is inadequately ventilated and the
gas/vapor is heavier than air.
d) Figure 25, when the source is inadequately ventilated and the
gas/vapor is lighter than air.
e) When sampling frequency is equal to or greater than once a week, the
space within 1.5 m of the termination (the "source") shall be classified as
Class I, Zone 0 in Figures 20, 21, 24, and 25.
SAES-B-068, Sec
6.2.4
D3
For threaded fittings that are not seal-welded, the classified area shall be
determined by:
a) Figure 20, Figure 21, when the source is adequately ventilated and the
gas/vapor is heavier than air.
b) Figure 24, when the source is adequately ventilated and the gas/vapor
is lighter than air.
c) Figure 22, when the source is inadequately ventilated and the
gas/vapor is heavier than air.
d) Figure 25, when the source is inadequately ventilated and the
gas/vapor is lighter than air.
e) Adequately ventilated threaded fittings that are not seal-welded shall
not be considered release sources when containing fuel gas with a
maximum gauge operating pressure of 350 kPa (50 psig).
SAES-B-068, Sec
6.2.3
D2
For packing glands or seals on pumps and compressors the classified
area shall be determined by:
a) Figure 20, Figure 21, when the source is adequately ventilated and the
gas/vapor is heavier than air.
b) Figure 24, when the source is adequately ventilated and the gas/vapor
is lighter than air.
c) Figure 22, when the source is inadequately ventilated and the
gas/vapor is heavier than air.
d) Figure 25, when the source is inadequately ventilated and the
gas/vapor is lighter than air.
SAES-B-068, Sec
6.2.2
Page 4 of 12
CONTRACTOR / SUBCONTRACTOR
Intrinsically Safe Circuit- Design / Procurement Package-
Documentation Review
SAIC-J-6902 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLIST
SAIC NUMBER DATE APPROVED QR NUMBER
PROJ ECT TITLE WBS / BI / J O NUMBER
N/A RE-INSP DATE
ITEM
No.
ACCEPTANCE CRITERIA REFERENCE PASS FAIL
D8
The interior of analyzer houses shall be classified as Class 1 Zone 1 and
group consistent with liquids or gases being handled.
SAES-B-068, Sec
6.4.1
D12
Laboratory hoods, ducting, and storage rooms shall be classified as
follows:
a) Enclosed space of fume hood: Class I, Zone 1.
b) Exhaust ducting associated: Class I, Zone 1 with fume hoods.
c) Vent for exhaust ducting: Per requirements of paragraph 6.2.7 for
vents.
d) Storage rooms for samples and chemicals: Per requirements of
paragraph 6.3.4.
SAES-B-068, Sec
6.4.5 and Sec
6.2.7 and Sec
6.3.4
D11
Pits, sumps, open trenches, and any other below-grade locations in
Class I, Zone 2 locations shall be classified as Class I, Zone 1.
SAES-B-068, Sec
6.4.4
SAES-B-068, Sec
6.4.3
D7
For the terminations of vents and drains (this includes vents and drains
on all instrumentation impulse lines containing volatile liquids or
combustible gas) that have to be opened to the atmosphere as part of
normal operation, the classified area shall be determined as follows:
a) Figure 20 and 21, when the source is adequately ventilated and the
gas/vapor is heavier than air.
b) Figure 24, when the source is adequately ventilated and the gas/vapor
is lighter than air.
c) Figure 22, when the source is inadequately ventilated and the
gas/vapor is heavier than air.
d) Figure 25, when the source is inadequately ventilated and the
gas/vapor is lighter than air.
e) Vents and drains that are installed solely for hydrotest, steam-out, and
maintenance and that are plugged or blinded, shall not be designated as
release points.
f) Vents and drains to the atmosphere on fired equipment and other
equipment having a continuous source of ignition shall be considered a
release source, irrespective of Note (e) of Paragraph 6.2.6 of this
Standard.
SAES-B-068, Sec
6.2.7
D6
For flanges, fittings, and valve stems, the classified area shall be
determined by:
a) Figure 22, when the source is inadequately ventilated and the
gas/vapor is heavier than air.
b) Figure 25, when the source is inadequately ventilated and the
gas/vapor is lighter than air.
c) When the source is adequately ventilated, it shall not create a
classified location.
SAES-B-068, Sec
6.2.6
D9
For interiors of unventilated battery rooms, electrical area classification
shall be Class I, Zone 1, Group IIC.
SAES-B-068, Sec
6.4.2
D10
Drainage ditches, swales, and associated remote impounding basins
(located in unclassified areas) for process location surface drainage shall
create a Class I, Zone 2 location, as follows:
a) Within ditches and swales.
b) The space between grade elevation and 0.6 m above the top of
ditches and swales. This shall extend from the centerline of the ditch or
swale at this elevation to points 4.5 m from the edges of the ditch or
swale.
c) Within an impounding basin, up to the top of its dike.
Page 5 of 12
CONTRACTOR / SUBCONTRACTOR
Intrinsically Safe Circuit- Design / Procurement Package-
Documentation Review
SAIC-J-6902 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLIST
SAIC NUMBER DATE APPROVED QR NUMBER
PROJ ECT TITLE WBS / BI / J O NUMBER
N/A RE-INSP DATE
ITEM
No.
ACCEPTANCE CRITERIA REFERENCE PASS FAIL
E. Material Specification and Certification
E6
Dedicated intrinsically safe field termination cabinets (junction boxes)
shall be provided to maintain positive separation of intrinsically safe from
non-intrinsically safe wiring.
SAES-J -903, Sec
8.2.3
E5
Mechanical protection of the conductors to each individual instrument
from the field-mounted instrument to the field junction box shall be
provided in the form of conduit or steel wire armor and cable tray/channel
per SAES-J -902.
SAES-J -903, Sec
8.2.2
E4
Conductors of intrinsically safe circuits shall not be placed in any
raceway, cable tray, or cable with conductors of any non-intrinsically safe
circuit.
SAES-J -903, Sec
8.2.1
E3
To assess the intrinsic safety of the interconnected equipment, the entity
parameters shall be compared (including the calculated interconnecting
cable capacitance and inductance) in accordance with ISA TR12.2.
SAES-J -903, Sec
7.4
E2
The interconnecting cables used in an intrinsically safe circuit must be
electrically compatible with the intrinsically safe components being used.
SAES-J -903, Sec
8.2
E1
The intrinsically safe instrument enclosure shall be sealed to provide
adequate ingress protection (NEMA 4X or IP 65).
SAES-J -903, Sec
8.1
D18
In tank farm areas, pumps which are located at the edge of a pipe way
and which are bordered on the other three sides by dikes or walls of 1 m
height or more shall create classified locations as follows:
- Class I, Zone 1: When the linear dimension between opposite walls is
less than 30 m.
- Class I, Zone 2: When the linear dimension between opposite walls is
30 m or greater.
SAES-B-068, Sec
6.4.12
D17
Sanitary sewer systems shall be classified as follows: Class I, Zone 2
a) Space between 1.5 m and 3 m of termination of vents from lift
stations.
b) 0.6 m from the edge and 0.6 m above the cover of a sanitary sewer lift
station.
SAES-B-068, Sec
6.4.7.2
D16
Sanitary sewer systems shall be classified as follows: Class I, Zone 1
a) Inside lift stations.
b) Space within 1.5 m of termination of vent from lift stations.
SAES-B-068, Sec
6.4.7.1
D15
Oily water sewer systems shall be classified as follows :I, Zone 2 within
1.5 m and 3 m from the vents of the following: manholes, lift stations,
sumps, underground piping systems.
SAES-B-068, Sec
6.4.6.3
D14
Oily water sewer systems shall be classified as follows : Class I, Zone 1
within .5 m and 1.5 m from the vents of the following: manholes, lift
stations, sumps, underground piping systems.
6.4.6.3 Class I, Zone 2 within 1.5 m and 3 m from the vents of the
following: manholes, lift stations, sumps, underground piping systems.
SAES-B-068, Sec
6.4.6.2
D13
Oily water sewer systems shall be classified as follows: Class I, Zone 0
locations shall be:
a) Within manholes.
b) Within catch basins.
c) Within lift stations and sumps.
d) Within all underground piping.
e) Within all vents.
f) Within .5 m of the termination of vents from the following: manholes,
lift stations, sumps, underground piping systems.
SAES-B-068, Sec
6.4.6.1
Page 6 of 12
CONTRACTOR / SUBCONTRACTOR
Intrinsically Safe Circuit- Design / Procurement Package-
Documentation Review
SAIC-J-6902 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLIST
SAIC NUMBER DATE APPROVED QR NUMBER
PROJ ECT TITLE WBS / BI / J O NUMBER
N/A RE-INSP DATE
ITEM
No.
ACCEPTANCE CRITERIA REFERENCE PASS FAIL
E8
The field termination cabinet will serve as a transition point from
individual pair/triad to a multi-pair/triad cable.
SAES-J -903, Sec
8.2.3
E20
The minimum clearances between terminals of intrinsically safe circuits
and any grounded metal shall be 3 mm ( inch), unless that terminal is
intended to be grounded. The clearance between two terminals of
different intrinsically safe circuits shall be at least 6 mm ( inch).
SAES-J -903, Sec
8.3.4
E19
All spare wires shall be terminated at terminal blocks and grounded to
the intrinsic safety ground bus. Unused wires shall also be insulated at
their hazardous area ends.
SAES-J -903, Sec
8.3.3
E17
The I.S. cables from the field instrument shall be terminated on the
"hazardous area" terminations of the associated apparatus and shall be
secured or tie-wrapped separately from the non-intrinsically safe cables
terminated on the opposite end "safe area" terminals of the associated
apparatus. A minimum of 2 inches (50 mm) shall be maintained
between the I.S. and non-I.S. cables within the cabinet that contains the
associated apparatus.
SAES-J -903, Sec
8.3.2
E17
Cabinets that contain the associated apparatus shall be located within air-
conditioned analyzer shelters, process interface buildings, or control
rooms.
SAES-J -903, Sec
8.3.1
E16
I.S. cables shall enter the cabinet through cable entries completely
separate and opposite from the non-intrinsically safe connecting cables
to the control system.
SAES-J -903, Sec
8.3.1
E15
I.S. system wiring shall be terminated in dedicated marshalling cabinets
or compartments within marshalling cabinets that house the associated
apparatus. I.S. cables shall enter the cabinet through cable entries
completely separate and opposite from the non-intrinsically safe
connecting cables to the control system.
SAES-J -903, Sec
8.3.1
E14
Care shall be taken to avoid locating interconnecting cables containing
intrinsically safe circuits close to overhead power distribution lines or
heavy current carrying cables. Refer to SAES-J -902 for minimum
spacing requirements between parallel cable runs of different signal
types.
SAES-J -903, Sec
8.2.5
E13
The standard practice of separating thermocouple, 4-20 milliamp, and
digital alarm signals shall be observed. This segregation shall be
maintained in the field via dedicated, intrinsically safe field junction
boxes. Signal segregation shall be maintained up to the marshalling
panels, where signals may be consolidated to the extent specified in
SAES-J -902.
SAES-J -903, Sec
8.2.5
E12
Multi-pair/triad cables shall be routed from the field termination cabinets
(junction boxes) to the control room or process interface building in cable
trays, in conduits, or by direct burial cable provided the cable is approved
for cable tray use or for direct burial.
SAES-J -903, Sec
8.2.4
E11
Cables shall be sealed against the passage of gas and vapors as
required by the National Electrical Code NFPA 70, SAES-B-008, and
SAES-O-126.
SAES-J -903, Sec
8.2.4
E10
Field termination cabinets (junction boxes) shall be NEMA Type 4X or IP
65 (reference NEMA Standards Publication No. 250).
SAES-J -903, Sec
8.2.3
E9
Multi-core cables shall not combine intrinsically safe and non-intrinsically
safe signals.
SAES-J -903, Sec
8.2.3
E7
Where several intrinsically safe instrumentation loops are involved,
individual pair/triad from each instrument located in the field may be
routed to a common field termination cabinet.
SAES-J -903, Sec
8.2.3
Page 7 of 12
CONTRACTOR / SUBCONTRACTOR
Intrinsically Safe Circuit- Design / Procurement Package-
Documentation Review
SAIC-J-6902 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLIST
SAIC NUMBER DATE APPROVED QR NUMBER
PROJ ECT TITLE WBS / BI / J O NUMBER
N/A RE-INSP DATE
ITEM
No.
ACCEPTANCE CRITERIA REFERENCE PASS FAIL
4. SAES-J -902, Electrical Systems for Instrumentation, 31 J uly 2004
1. Schedule G -- Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), J uly 1993
2. Schedule Q -- Quality Requirements (Pro Forma Contract), November 2003
REFERENCE DOCUMENTS:
3. ISA-RP 12.2.02-1996 Recommendations for the Preparation , Content and Orga. Of Intrinsic Safety Control Drawings, 15 May 1996
6. SAES-B-068, Electrical Area Classification, 31 May, 2003.
7. NEC 2002- National Electric Code 2002
E29
Light blue color coding shall be used to identify intrinsically safe wiring.
The preferred practice is to specify intrinsically safe interconnecting
cables with a blue outer jacket. Alternatively, blue sleeves slipped over
the jacket at all points of termination may be used to identify I.S. wiring.
SAES-J -903, Sec
8.5.3
E28
All junction boxes, cable trays, conduits, cables, cabinets, and
instrument housings shall be labeled as containing intrinsically safe
circuits or equipment. The means of identification shall be visible after
installation. Label spacing on cable tray, conduit, and interconnecting
cables shall not exceed 25 feet (8 meters).
SAES-J -903, Sec
8.5.2
E27 All intrinsically safe system components shall be so identified.
SAES-J -903, Sec
8.5.1
E26
Cable protective armor, if used, shall be grounded to plant grounding
system at the field junction box.
SAES-J -903, Sec
8.4.6
E25
All metal cable trays used for intrinsically safe wiring shall be grounded
to the plant grounding system with a minimum of #4 AWG copper wire
with green insulation.
SAES-J -903, Sec
8.4.5
E24
All metal enclosures for intrinsically safe circuits shall be grounded to the
plant grounding system with a minimum of #4 AWG copper wire with
green insulation.
SAES-J -903, Sec
8.4.4
E23
When zener diode type barriers are used, the maximum resistance
between the farthest point on the intrinsic safety barrier ground and the
plant grounding system (the point at which the incoming electricity supply
neutral is grounded) shall not exceed 1 Ohm.
SAES-J -903, Sec
8.4.3
E22
Where screens/shields are used, they shall be covered by an outer
insulating sheath. They shall be grounded at the associated apparatus
intrinsic safety ground point and insulated at the hazardous area end.
Where screened multipair/multitriad cables interconnect within field
junction boxes with individual screened pair/triad cables, insulated
terminals shall be provided for the ongoing continuity of the
screens/shields.
SAES-J -903, Sec
8.4.2
E21
In cabinets housing the associated apparatus, the intrinsic safety ground
bus shall be connected to a node in the overall plant ground grid by
dedicated, redundant, insulated copper cables not smaller than #4 AWG.
To identify the intrinsically safe grounding conductors as being different
from other ground connections, the grounding conductor insulation color
shall be green with blue tracer (or banded with blue tape)
SAES-J -903, Sec
8.4.2
5. SAES-J -903 Intrinsically Safe System, 28 November, 2001.
REMARKS:
Page 8 of 12
CONTRACTOR / SUBCONTRACTOR
Intrinsically Safe Circuit- Design / Procurement Package-
Documentation Review
SAIC-J-6902 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLIST
SAIC NUMBER DATE APPROVED QR NUMBER
PROJ ECT TITLE WBS / BI / J O NUMBER
N/A RE-INSP DATE
ITEM
No.
ACCEPTANCE CRITERIA REFERENCE PASS FAIL
QC Record Reviewed Work Verified
Name, Sign and Date:
Quality Record Approved:
Name, Organization,
Initials and Date:
T&I Witnessed
QC Supervisor Proponent and Others
Name, Initials and Date:
Performed Inspection
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified
Work Verified T&I Witnessed QC Record Reviewed
QC Inspector PID Representative
indicates compliance with appropriate standards or performance in a specified manner.
Construction Representative*
Name, Initials and Date:
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
Attachment -3 Adequately Ventilated Process Location with Heavier Than Air- Gas or Vapor Source located Above Grade (Fig. 21)
NOTES:
Attachment -4 In adequately Ventilated Process Location with Heavier Than Air- Gas or Vapor Source located Above Grade (Fig. 22)
Attachment 5: Adequately Ventilated Process Location with Lighter-Than Air- Gas or Vapor Source located Above Grade (Fig. 24)
Attachment 6: Inadequately Ventilated Process Location with Lighter-Than Air- Gas or Vapor Source located Above Grade (Fig. 25)
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
Attachment -2 Adequately Ventilated Process Location with Heavier Than Air- Gas or Vapor Source located near grade
Work Verified
Saudi Aramco
with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the
f
PMT Representative
T&I Witnessed Work is Complete and Ready for Inspection:
Name, Initials and Date:
Contractor / Third-Party
QC Record Reviewed
*Person Responsible for Completion of Quality Work / Test Y =YES N =NO F =FAILED
ATTACHMENTS:
Attachment -1 Certification Agencies for Equipment in Hazardous Areas
Work / Rework May Proceed
Name, Initials and Date:
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization
Page 9 of 12
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLIST
SAIC NUMBER DATE APPROVED QR NUMBER
Where Figure 20, 21 or 22 is referenced in this Standard, the " additional Zone 2 area" is mandatory.
Intrinsically Safe Circuit- Design / Procurement Package-
Documentation Review
SAIC-J-6902 1-Oct-05 INST
Attachment -2 Adequately Ventilated Process Location with Heavier Than Air- Gas or Vapor S
Attachment -1 Certification Agencies for Equipment in Hazardous Areas
Page 10 of 12
Intrinsically Safe Circuit- Design / Procurement Package-
Documentation Review
SAIC-J-6902 1-Oct-05 INST
Where Figure 20, 21 or 22 is referenced in this Standard, the " additional Zone 2 area" is mandatory.
Attachment -4 In adequately Ventilated Process Location with Heavier Than Air- Gas or Vapor
Where Figure 20, 21 or 22 is referenced in this Standard, the " additional Zone 2 area" is mandatory.
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLIST
SAIC NUMBER DATE APPROVED QR NUMBER
Attachment -3 Adequately Ventilated Process Location with Heavier Than Air- Gas or Vapor S
Page 11 of 12
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLIST
SAIC NUMBER DATE APPROVED QR NUMBER
Attachment 6: Inadequately Ventilated Process Location with Lighter-Than Air- Gas or Vapor S
Intrinsically Safe Circuit- Design / Procurement Package-
Documentation Review
SAIC-J-6902 1-Oct-05 INST
Attachment 5: Adequately Ventilated Process Location with Lighter-Than Air- Gas or Vapor So
Page 12 of 12

Вам также может понравиться