Sectionalizing Equipment
600 A 15, 25, and 28 kV Class Clr SecTER Cabinet
GENERAL
The versatile single- and three-phase
600 A Clr SecTER cabinets
from Cooper Power Systems are
designed as cable sectionalizing
centers. They can be used wherever
underground cable must be
sectionalized or connected. Functions
include sectionalizing cable, switching
cable, isolating cable and feeder taps.
Each Clr SecTER cabinet comes
complete with one Cooper Power
Systems exclusive 600 A, 15, 25,
or 28 kV Class Clr Loadbreak
Connector installed per phase.
The aesthetic low profile design
provides unobtrusive in stallations for
sectionalizing, tapping or terminating
underground cable.
The top hinged diagonally cut
removable cover and cabinet are
designed for easy one man opening
and improved access to interior
terminations. A door stop prevents the
door from accidentally closing.
All cover-to-cabinet seams are
designed to exceed ANSI


tamperproof standards. Munsell Green
(7YG3.29/1.5) TGIC powder coating
exceeds ANSI

coating requirements.
Continuous seam welding ensures a
sturdy smooth cabinet.
Standard Features
12 Gauge Mild Steel or Aluminum
Construction
One Clr Loadbreak Connector
per phase
Stainless Steel hardware and
hinges
Padlock hasp and pentahead
silicon bronze door bolt
Parking stands (two for Single-
phase, four for Three-phase)
Ground nuts (one per phase)
600 A 15, 25, and 28
kV Clr Loadbreak
Connector System
The Cooper Power Systems Clr
Loadbreak Connector System is a
600 A loadbreak device available in
ratings for operation on 15, 25, or 28
kV class systems. It is used to provide
a visible break and visible ground
on 600 A network and distribution
systems without having to remove
600 A terminations and move heavy
cable. The Clr Loadbreak Connector
System Is fully shielded, submersible
and meets the applicable requirements
of IEEE Std 386 -2006 standard
Separable Insulated Connector
Systems.
When isolating underground
cable, with the system energized
or de-energized, with or without
rated load current, with the use of a
clampstick, the loadbreak connector
(LCN) can be removed. A 600 A
loadbreak protective cap (LPC6__)
can then be installed on the two
exposed loadbreak interfaces. All
bushings of the connector system
are then insulated and deadfront.
If a 600 A termination with a 200 A
reducing tap plug is used on the IEEE
Std 386 -2006 standard 600 A
15/25 kV deadbreak interfaces of the
junction, a grounding elbow can be
installed, providing a visible ground.
It is then safe to perform work on the
underground cable.
0712 Supersedes 0312
Figure 1.
Three-Phase Clr SecTER Cabinet.
Electrical Ap pa ra tus
1000-20
Figure 2.
600 A, 15 kV Clr Square
Configuration.
600 A 15, 25, and 28 kV Class Clr SecTER Cabinet
2
Figure 3.
Single-phase SecTER cabinet, Catalog Number SEC1P_ _CLEERA2.
Note: Dimensions given are for reference only.
PADLOCK HASP AND
PENTAHEAD SILICON
BRONZE BOLT
GROUND
SLEEVE
OPTIONAL
Figure 4.
Three-phase SecTER cabinet, Catalog Number SEC3P_ _CLEERA2.
Note: Dimensions given are for reference only.
PADLOCK HASP AND
PENTAHEAD SILICON
BRONZE BOLT
GROUND
SLEEVE
OPTIONAL
GROUND
SLEEVE
OPTIONAL
DOOR STOP
GROUND
NUT
DOOR STOP
GROUND
NUT
Clr 600 A LOADBREAK
CONNECTOR
Clr 600 A LOADBREAK
CONNECTOR
1
7
.
0
0
2
4
.
4
0
19.79
23.50
8.10
22.00 66.00
3.18
3
0
.
0
0
PARKING
STAND
PARKING
STAND
1000-20
3
Figure 5.
Single-phase SecTER cabinet, Catalog Number SEC1P_ _CLEERA2DP.
Note: Dimensions given are for reference only.
Figure 6.
Three-phase SecTER cabinet, Catalog Number SEC3P_ _CLEERA2DP.
Note: Dimensions given are for reference only.
24.40
17.00
24.00 REF
30.00 REF
3
0
.
0
0

R
E
F
31.50
12.0
REF
30.00 REF 66.00 REF
17.00
24.40
3.18
19.79
3
0
.
0
0

R
E
F
31.50
12.0
REF
GROUND
SLEEVE
OPTIONAL
GROUND
SLEEVE
OPTIONAL
GROUND
NUT
GROUND
NUT
PARKING
STAND
PARKING
STAND
DOOR STOP
DOOR STOP
Clr 600 A LOADBREAK
CONNECTOR
Clr 600 A LOADBREAK
CONNECTOR
PADLOCK HASP AND
PENTAHEAD SILICON
BRONZE BOLT
GROUND
SLEEVE
OPTIONAL
600 A 15, 25, and 28 kV Class Clr SecTER Cabinet
4
ORDERING INFORMATION
TABLE 3
600 A 15 kV Class Clr SecTER Cabinet
kV Class
Dimensions (in.)
Phase Catalog Number H W D
SecTER Cabinet 12-Gauge Mid Steel
15
30 24 22 1 SEC1P15CLEERA2*
30 66 22 3 SEC3P15CLEERA2*
30 24 30 1 SEC1P15CLEERA2DP
30 66 30 3 SEC3P15CLEERA2DP
SecTER Cabinet Aluminum
15
30 24 22 1 SEC1P15CLEERA2L*
30 66 22 3 SEC3P15CLEERA2L*
30 24 30 1 SEC1P15CLEERA2DPL
30 66 30 3 SEC3P15CLEERA2DPL
Ground Sleeves
Fiberglass 18 24 22 1 00400L00K02G
Fiberglass 30 24 22 1 00400L00K05G
Mild Steel 24 24 22 1 0400L00K10GM
Fiberglass 18 66 22 3 00450L00K05G
Fiberglass 30 66 22 3 00450L00K08G
Mild Steel 24 66 22 3 0450L00K18GM
Fiberglass 18 24 30 1 00450L00K32G
Fiberglass 18 66 30 3 00450L00K35G
Accessory
600 A 15 kV Insulated Loadbreak Protective Cap LPC615
Clr Standoff Bushing PS625CLEER
Note:
Recessed base allows for an additional 1-1/2" stacking from backplate.
PRODUCTION TESTS
Tests are conducted in accordance
with IEEE Std 386

-2006 standard.
AC 60 Hz 1 Minute Withstand
34 kV
Minimum Partial Discharge
Extinction Voltage
11 kV (3pc Sensitivity)
Tests are conducted in accordance with
Cooper Power Systems re quire ments.
Physical In spec tion
Periodic Dissection
Periodic Fluoroscopic Analysis
TABLE 4
Voltage Ratings and Characteristics
Description kV
Standard Voltage Class 15
Maximum Rating Phase-to-
Phase
14.4
Maximum Rating Phase-to-
Ground
8.3
AC 60 Hz 1 Minute Withstand 34
DC 15 Minute Withstand 53
BIL and Full Wave Crest 95
Minimum Partial Discharge
Extinction Voltage
11
Voltage ratings and characteristics are in accordance
with applicable IEEE Std 386

-2006

standard
requirements.
TABLE 2
Current Ratings and Characteristics
Description Amperes
600 A Loadbreak Interface
Continuous
Current
600 A rms
Loadbreak
Switching
Ten make and break operations at 600 A at 14.4 kV Phase-Phase
Three make and break operations at 900 A at 14.4 kV Phase-Phase
Fault Closure
16 kA rms symmetrical at 14.4 kV Phase-Phase after ten 600 A loadbreak
switching operations for 0.17 seconds
16 kA rms symmetrical at 14.4 kV Phase-Phase after three 900 A loadbreak
switching operations for 0.17 seconds
4 Hour
Overload Current
900 A rms
Short Time
Current
16 kA rms symmetrical for 0.17 seconds (limited by fault closure rating)
10 kA rms symmetrical for 3.0 seconds
IEEE Std 386 -2006 standard 600 A, 15/25 kV Deadbreak Interface
Continuous
Current
600 A rms
4 Hour
Overload Current
900 A rms
Short Time
Current
16 kA rms symmetrical for 0.17 seconds
10 kA rms symmetrical for 3.0 seconds
Current ratings and characteristics are in ac cor dance with applicable IEEE Std 386

-2006

standard requirements.
15 kV Ratings, Characteristics and Ordering Information
*IMPORTANT: A 30" deep SecTER
cabinet is required if a 200 A fused
loadbreak elbow is installed.
1000-20
5
ORDERING INFORMATION
TABLE 6
600 A 25 kV Class Clr SecTER Cabinet
kV Class
Dimensions (in.)
Phase Catalog Number H W D
SecTER Cabinet 12-Gauge Mid Steel
25
30 24 22 1 SEC1P25CLEERA2*
30 66 22 3 SEC3P25CLEERA2*
30 24 30 1 SEC1P25CLEERA2DP
30 66 30 3 SEC3P25CLEERA2DP
SecTER Cabinet Aluminum
25
30 24 22 1 SEC1P25CLEERA2L*
30 66 22 3 SEC3P25CLEERA2L*
30 24 30 1 SEC1P25CLEERA2DPL
30 66 30 3 SEC3P25CLEERA2DPL
Ground Sleeves
Fiberglass 18 24 22 1 00400L00K02G
Fiberglass 30 24 22 1 00400L00K05G
Mild Steel 24 24 22 1 0400L00K10GM
Fiberglass 18 66 22 3 00450L00K05G
Fiberglass 30 66 22 3 00450L00K08G
Mild Steel 24 66 22 3 0450L00K18GM
Fiberglass 18 24 30 1 00450L00K32G
Fiberglass 18 66 30 3 00450L00K35G
Accessory
600 A 25 kV Insulated Loadbreak Protective Cap LPC625
Clr Standoff Bushing PS625CLEER
Note:
Recessed base allows for an additional 1-1/2" stacking from backplate.
PRODUCTION TESTS
Tests are conducted in accordance
with IEEE Std 386

-2006 standard.
AC 60 Hz 1 Minute Withstand
40 kV
Minimum Partial Discharge
Extinction Voltage
19 kV (3pc Sensitivity)
Tests are conducted in accordance with
Cooper Power Systems re quire ments.
Physical In spec tion
Periodic Dissection
Periodic Fluoroscopic Analysis
TABLE 7
Voltage Ratings and Characteristics
Description kV
Standard Voltage Class 25
Maximum Rating Phase-to-
Phase
26.3
Maximum Rating Phase-to-
Ground
15.2
AC 60 Hz 1 Minute Withstand 40
DC 15 Minute Withstand 78
BIL and Full Wave Crest 125
Minimum Partial Discharge
Extinction Voltage
19
Voltage ratings and characteristics are in accordance
with applicable IEEE Std 386

-2006

standard
requirements.
TABLE 5
Current Ratings and Characteristics
Description Amperes
600 A Loadbreak Interface
Continuous
Current
600 A rms
Loadbreak
Switching
Five make and break operations at 600 A at 26.3 kV Phase-Phase
One make and break operation at 900 A at 26.3 kV Phase-Phase
Fault Closure
10 kA rms symmetrical at 26.3 kV Phase-Phase after five 600 A loadbreak
switching operations for 0.17 seconds
10 kA rms symmetrical at 26.3 kV Phase-Phase after one 900 A loadbreak
switching operation for 0.17 seconds
4 Hour
Overload Current
900 A rms
Short Time
Current
10 kA rms symmetrical for 0.17 seconds (limited by fault closure rating)
10 kA rms symmetrical for 3.0 seconds
IEEE Std 386 -2006 standard 600 A, 15/25 kV Deadbreak Interface
Continuous
Current
600 A rms
4 Hour
Overload Current
900 A rms
Short Time
Current
10 kA rms symmetrical for 0.17 seconds
10 kA rms symmetrical for 3.0 seconds
Current ratings and characteristics are in ac cor dance with applicable IEEE Std 386

-2006

standard requirements.
*IMPORTANT: A 30" deep SecTER
cabinet is required if a 200 A fused
loadbreak elbow is installed.
25 kV Ratings, Characteristics and Ordering Information
600 A 15, 25, and 28 kV Class Clr SecTER Cabinet
6
ORDERING INFORMATION
TABLE 9
600 A 28 kV Class Clr SecTER Cabinet
kV Class
Dimensions (in.)
Phase Catalog Number H W D
SecTER Cabinet 12-Gauge Mid Steel
28
30 24 22 1 SEC1P28CLEERA2*
30 66 22 3 SEC3P28CLEERA2*
30 24 30 1 SEC1P28CLEERA2DP
30 66 30 3 SEC3P28CLEERA2DP
SecTER Cabinet Aluminum
28
30 24 22 1 SEC1P28CLEERA2L*
30 66 22 3 SEC3P28CLEERA2L*
30 24 30 1 SEC1P28CLEERA2DPL
30 66 30 3 SEC3P28CLEERA2DPL
Ground Sleeves
Fiberglass 18 24 22 1 00400L00K02G
Fiberglass 30 24 22 1 00400L00K05G
Mild Steel 24 24 22 1 0400L00K10GM
Fiberglass 18 66 22 3 00450L00K05G
Fiberglass 30 66 22 3 00450L00K08G
Mild Steel 24 66 22 3 0450L00K18GM
Fiberglass 18 24 30 1 00450L00K32G
Fiberglass 18 66 30 3 00450L00K35G
Accessory
600 A 28 kV Insulated Loadbreak Protective Cap LPC628
Clr Standoff Bushing PS625CLEER
Note:
Recessed base allows for an additional 1-1/2" stacking from backplate.
PRODUCTION TESTS
Tests are conducted in accordance
with IEEE Std 386

-2006 standard.
AC 60 Hz 1 Minute Withstand
45 kV
Minimum Partial Discharge
Extinction Voltage
21.1 kV (3pc Sensitivity)
Tests are conducted in accordance with
Cooper Power Systems re quire ments.
Physical In spec tion
Periodic Dissection
Periodic Fluoroscopic Analysis
TABLE 10
Voltage Ratings and Characteristics
Description kV
Standard Voltage Class 28
Maximum Rating Phase-to-
Phase
28
Maximum Rating Phase-to-
Ground
16.2
AC 60 Hz 1 Minute Withstand 45
DC 15 Minute Withstand 100
BIL and Full Wave Crest 125
Minimum Partial Discharge
Extinction Voltage
21.1
Voltage ratings and characteristics are in accordance
with applicable IEEE Std 386

-2006

standard
requirements.
TABLE 8
Current Ratings and Characteristics
Description Amperes
600 A Loadbreak Interface
Continuous
Current
600 A rms
Loadbreak
Switching
Five make and break operations at 600 A at 28.0 kV Phase-Phase
One make and break operation at 900 A at 28.0 kV Phase-Phase
Fault Closure
10 kA rms symmetrical at 28.0 kV Phase-Phase after five 600 A loadbreak
switching operations for 0.17 seconds
10 kA rms symmetrical at 28.0 kV Phase-Phase after one 900 A loadbreak
switching operation for 0.17 seconds
4 Hour
Overload Current
900 A rms
Short Time
Current
10 kA rms symmetrical for 0.17 seconds (limited by fault closure rating)
10 kA rms symmetrical for 3.0 seconds
IEEE Std 386 -2006 standard 600 A, 15/25 kV Deadbreak Interface
Continuous
Current
600 A rms
4 Hour
Overload Current
900 A rms
Short Time
Current
10 kA rms symmetrical for 0.17 seconds
10 kA rms symmetrical for 3.0 seconds
Current ratings and characteristics are in ac cor dance with applicable IEEE Std 386

-2006

standard requirements.
28 kV Ratings, Characteristics and Ordering Information
*IMPORTANT: A 30" deep SecTER
cabinet is required if a 200 A fused
loadbreak elbow is installed.
1000-20
7
Figure 7.
600 A Loadbreak Connector System with (2) BOL-T termina-
tions.
Figure 9.
600 A Loadbreak Connector System with (1) BOL-T and
(1) T-OP II or BT-TAP termination and (1) 200 A Loadbreak
Protective Cap.
BOL-T
TERMINATION
SOURCE LOAD
LOADBREAK
CONNECTOR (LCN)
SOURCE LOAD
T-OP II OR BT-TAP
TERMINATION
BOL-T TERMINATION
Typical Congurations
Figure 8.
600 A Loadbreak Connector System with (1) BOL-T, (1) T-OP
II or BT-TAP termination and (1) 200 A Loadbreak Elbow Tap.
Figure 10.
600 A Loadbreak Connector System with (1) BOL-T, (1) T-OP
II, or BT-TAP Termination and (1) 200 A Fused Loadbreak
Elbow.
Note: Fused elbow requires a 30" deep SecTER cabinet.
SOURCE LOAD
200 A
LOADBREAK
PROTECTIVE CAP
BOL-T
TERMINATION
200 A
LOADBREAK
ELBOW
SOURCE LOAD
T-OP II OR BT-TAP
TERMINATION
200 A FUSED
LOADBREAK
ELBOW
BOL-T
TERMINATION
T-OP II OR
BT-TAP
TERMINATION
600 A 15, 25, and 28 kV Class Clr SecTER Cabinet
8
Figure 11.
600 A Loadbreak Connector System with (1) BOL-T, (1)
T-OP II, or BT-TAP Termination and (1) M.O.V.E. Elbow Surge
Arrester.
SOURCE
LOAD
BOL-T
TERMINATION
M.O.V.E.
ELBOW
SURGE
ARRESTER
T-OP II OR BT-TAP
TERMINATION
2300 Badger Drive
Waukesha, WI 53188
2012 Cooper Industries. All Rights Reserved.
Cooper Power Systems, Clr, SecTER, BOL-T, T-OP, BT-TAP, and M.O.V.E.
are valuable trademarks of Cooper Industries in the U.S. and other countries.
You are not permitted to use the Cooper Trademarks without the prior written
consent of Cooper Industries.
IEEE Std 386-2006 standard is a trademark of the Institute of Electrical and
Electronics Engineers, Inc., (IEEE). This publication/product is not endorsed or
approved by the IEEE.
ANSI

is a registered trademark of the American National Standards Institute.