Вы находитесь на странице: 1из 12

Increasing Cooling Tower Water Efficiency

Chang Sub Kim


Mentor: Melany Hunt
Co-Mentors: J im Cowell, J ohn Onderdonk, Matthew Berbee

Abstract
In 2008, California Institute of Technology used 764,064,005 liters of water. Cooling towers
at the central and satellite plants consumed 319,951,956 liters of water through evaporation and
blowdown, contributing to over forty per cent of overall water usage on campus. In this Water
Efficiency Project, the amount of water loss due to evaporation and blowdown each month has been
studied and has demonstrated that on average, 83 per cent of water loss is due to evaporation and
the rest due to blowdown. This project aims to improve overall water efficiency of cooling towers by
examining two applicable systems that can recover vapor and reduce blowdown. An ozone
treatment reduces the use of chemicals and thus decreases the blowdown rate. A vapor recovery
system consisting of a circular fiber filter on top of cooling towers absorbs and condenses water
vapor coming out of the cooling towers. A feasibility experiment showed that approximately 10 per
cent of evaporated water could be recovered using this method. Further research should be carried
out to study corrosion problems from the ozone treatment, and the type of the fiber filter that
should be installed to optimize water vapor absorption without obstructing airflow.



Introduction
Water is one of the most vital
resources on the Earth, but is becoming
increasingly scarce. Numerous attempts to
conserve water and reduce water pollution
have been made by all kinds of organizations,
from the federal government of the United
States to research universities such as
California Institute of Technology. Caltech
currently employs various water-efficient
technologies in an attempt to reduce its water
consumption level through its Water
Efficiency Project. In 2008, Caltech used
764,064,004 liters of water. Over half of the
water was consumed through Caltechs own
central and satellite utility plants. Each plant
operates induced draft cooling towers with four
cells. The cooling towers are used to lower the temperature of the water from condensers. A
large fan pulls up cool and dry ambient air from below, and warm water sprayed near the top
(Fig. 2) cools from evaporation and heat transfer to the cooler air. Warm, saturated air comes out
of the cooling tower into the atmosphere (Fig. 1).
Figure1|SatellitePlantCoolingTowers
Eighty per cent of water
used by Caltechs central and
satellite plants is lost from the
cooling towers. One factor of
the water loss from cooling
towers is evaporation.
Concentration of chemicals
(ions, acids, and so on) that are
either originally present in
water or added to increase
cooling efficiency and reduce
microbes increases after each
cycle due to evaporation. As the
concentration increases, ions
might cluster together and form
solids, the number of bacteria
may increase significantly, thus
decreasing overall cooling efficiency. Therefore,
the concentration of solids should be
maintained below a certain limit. Blow-
down is used to adjust the concentration
by bleeding and refilling cooling water.
This process results significant water loss
in cooling towers and also results water
pollution.
Increasing water efficiency of
Caltechs cooling towers can lower overall
water consumption significantly. Facilities
employees currently attempt to decrease
blowdown rate by controlling pH setup
point cooling water pH at which
blowdown valve opens. The pH level of
cooling water increases as water
evaporates and the chemical concentration
increases. Setting higher pH tolerance
level up to a point at which cooling
efficiency of cooling towers does not decrease significantly increases the number of cycles of
cooling water per blowdown.
Ozone treatment of cooling water is another possible solution to reduce blowdown.
Ozone, a relatively unstable molecule composed of three oxygen atoms, acts as a strong biocide
by oxidizing living organisms. Traditional chemical treatment to control microbes and prevent
scaling requires frequent bleedoff of cooling water because of increase in concentration of
chemicals due to evaporation. This further requires frequent refill of treatment chemicals. An
alternative to the traditional chemical treatment is ozone treatment. As an effective microbial
controller, ozone can replace chemicals to control microbes.
Figure2b|Warmwatersprayinsidethecentralplantcooling
tower
Figure2a|CoolingTowerMechanism
Ozone treatment, an alternative to traditional chemical treatments, can improve water
efficiency substantially according to R.J . Strittmatter, et al
1
. Ozone treatment for cooling water
has several advantages over traditional controls: less or no use of chemicals (toxic and non-toxic),
water conservation due to less blowdown (as less or no chemicals are used, the concentration
level is much lower). However, there are several concerns about ozone treatment, including the
impact on corrosion, effectiveness, and lack of general guidelines. The experiments by
Strittmatter, et al show that ozone has a negligible impact on corrosion at typical use levels, does
not increase mineral scales, controls fouling, and is excellent for microbial controls. Caltech had
previously examined applicability of ozone treatment in its cooling towers, but did not introduce
the treatment due to corrosion problems.
Besides reducing blow, the amount of water used on campus can be reduced by reducing
the amount of evaporative losses. Attempts to recover evaporation loss can be found in two
Korean patents. Kyung Seok Kang uses hollow fiber membrane filter modules to recapture
cooling water vapor
2
and Hoogeun Lee uses honeycomb, pleated or web-like fiber filters to
absorb water vapor coming out of cooling towers
3
. However, the amount of vapor that can be
recovered from such systems is not indicated
The ultimate goal of the Water Efficiency Project is to find applicable mechanisms which
improve overall water efficiency of cooling towers. For this summer, a cooling tower prototype
a humidifier and two different types of filters were installed and tested how much vapor
dismissed from the humidifier can be absorbed by each filter.

Results
1. Water Usage Data Analysis
Data analysis on cooling tower water usage and its relation with cooling degree days was
performed. Central cooling tower and satellite cooling towers monthly make-up and blowdown
levels are recorded in Utility Plants monthly reports. The reports show that the cooling water
make-up and blowdown levels are low during winter and increase during the summer (Fig. 3).


Figure 3 | Central and satellite plants cooling tower water make-up and blowdown each month from
J anuary 2008 to May 2009. Note that the Satellite plant consumed noticeably more water before September 2008.
Central plants cooling towers did not operate as much as Satellite plants as old chillers were being replaced by new
ones. CT: Central Plant Cooling Tower. ST: Satellite Plant Cooling Tower

A quantitative measure of how much cooling is needed each month is obtained in a form
of monthly Cooling degree days (CDD) data from the weather station ID KCAPASAD5 (North
Wilson Avenue, Pasadena, CA). Total cooling water make-up (central and satellite) correlates
with cooling degree days each month (Fig. 4).















Total MU (L) Total BD (L) Tot Evap Loss (L) Evap Loss (%)
1-08 15,681,702 3,326,936 12,354,766 78.78
2-08 14,855,822 2,798,660 12,057,162 81.16
3-08 15,661,875 3,733,099 11,928,776 76.16
4-08 21,863,949 4,283,935 17,580,014 80.41
5-08 26,068,764 5,368,045 20,700,720 79.41
6-08 30,981,472 3,100,954 27,880,518 89.99
7-08 34,708,885 7,476,796 27,232,089 78.46
8-08 39,378,625 6,009,274 33,369,351 84.74
9-08 41,802,806 6,060,792 35,742,014 85.50
10-08 37,020,676 5,407,563 31,613,113 85.39
11-08 25,162,689 3,682,414 21,480,275 85.37
12-08 16,764,691 2,264,479 14,500,212 86.49
1-09 19,689,875 2,837,459 16,852,415 85.59
2-09 11,335,177 1,759,709 9,575,468 84.48
3-09 17,027,879 1,602,960 15,424,919 90.59
4-09 23,111,629 3,468,847 19,642,782 84.99
5-09 26,247,090 3,743,130 22,503,960 85.74

Table 1 | Total water make-up (MU), blowdown (BD) and evaporation loss by central and satellite cooling
towers from J anuary 2008 to May 2009. The percentage of evaporation loss is quite significant between 76 and 91
per cent each month.


Figure 4 | Total water make-up (MU), blowdown (BD) and evaporation loss by central and satellite Cooling
Towers and Cooling Degree Days (CDD). Water consumption by the cooling towers generally follows the trend of
CDD as expected. However, it is noticeable that the water consumption during the summer break (June, July and
August) does not increase as sharply as the CDD do.

Figures 3 and 4 show that cooling water is lost more through evaporation than through
blowdown. Numerical data of total make-up, blowdown and evaporative loss show that only 9 to
24 per cent of make-up water is lost through blowdown (Table 1).

2. Vapor Recovery Experiment
In order to estimate how much vapor can be absorbed by different filters and parameters,
a simple experiment was designed using an ultrasonic humidifier (Fig. 5) as a cooling tower
prototype.
Supply rate of vapor from the humidifier was calculated by dividing the difference of
water remaining in the tank of the humidifier by amount of time passed.

Time Passed Water Initial (ml) Water After (ml) Difference (ml) Rate (ml/min)
137 min 1000 738 262 1.912
308 min 20 sec 2000 1302 698 2.264
739 min 1 sec 2000 355 1645 2.226
Table 2 | Amount of water emitted by the ultrasonic humidifier over different periods of time

Table 2 shows that 1.9 to 2.2 g of vapor was
emitted by the humidifier per minute. This variation,
with changing temperature and humidity levels in the
laboratory, the source of error is estimated to be
around 15 per cent.
Two different types of filters fiber filter (Fig.
6) and pleated air filter (Figs. 7,8,9) are installed on
top of a humidifier and the amount of time passed and
according amount water (in grams) absorbed by each
filter is measured. For fiber filter pad, variations in
thickness and area were imposed. For pleated air filter,
different orientations were used.
Temperature of vapor coming out of the
humidifier 23.5C on average was measured in
order to compare with the temperature of vapor from
cooling towers estimated to be between 24C and
30C from cooling water temperature going into and
coming out of Caltechs cooling towers.
Attempts to measure air flow on top of the humidifier
and after going through each filter was not successful as the flow was not constant without a
filter on top, and filters in horizontal
orientation obstruct most of the air flow.

Figure 10 shows a relationship between the amount of time and the amount of vapor absorbed by
fiber filter 1. Vapor absorption is linear with time before saturation and concaves down
afterwards.
Figure5|VICKSUltrasonicHumidifier
Figure6|Clockwisefromleftuppercorner:fiberfilter1,2,3,
and4.Filters1,2,3areofsamesize.Filters1and2areabout1
cmthick.Filters3and4areofsamethickness,about2cmthick
Figure7|Pleatedairfilterinhorizontalorientation

Figure 10 | Vapor absorption versus time of fiber filter 1. The relationship is linear (solid line) before saturation and
concave down (dotted line) as the filter gets saturated.

Figure9|Multiplewalledpleatedairfilterinvertical
orientation
Figure8|Singlewalledpleatedairfilterinvertical
orientation

Figure 11 | Vapor absorption versus time of thin and thick fiber filters

Figure 11 shows that the vapor absorption by thin and thick filters is almost identical
before saturation. The slope of both curves is approximately 0.2 g/min in the linear region.
However, vapor absorption of thick filter concaves down more slowly than that of thin filter,
indicating higher saturation level. The thin filter seems to begin deviating from the linear relation
around 10 grams of water while the thick filter seems to deviate around 20 grams of water.
Hence, the filters may become saturation when they have absorbed 10 g of water per 1 cm of
filter.

Figure 12 | Vapor absorption versus time of large and small filters
There is no significant difference in vapor absorption between small and large filters
before saturation. Figure 12 shows that vapor absorption of large filters concaves down more
slowly than that of small filters, indicating higher saturation level.


Figure 13 | Vapor absorption versus time of horizontal and vertical pleated air filters

There is no significant difference in vapor absorption between vertical and horizontal
filters before saturation. Although there is not enough data points no points between 4 hours
and 14 hours to draw a conclusion, vapor absorption of horizontal filter concaves down more
slowly than that of thin filter, indicating higher saturation level. Since both horizontal and
vertical filters have same filter size, differing saturation levels seem to be due to filters
orientations.


Figure 14 | Vapor absorption versus time of single and multiple concentric vertical pleated air filters

The data presented in figure 14 demonstrate that the results are similar for the single
walled and multiple walled filters before saturation. Vapor absorption of multiple walled filter
concaves down more slowly than that of single walled filter, indicating higher saturation level.
Figures 10, 11, 12, 13, and 14 show that vapor absorption is linear with time until
saturation, thickness and area do not scale proportionally with vapor absorption, vertical
orientation results lower saturation than horizontal orientation, and multiple walled filter absorbs
much faster than singled walled one.
From the data points, around 10 per cent of vapor emitted from the humidifier was
captured by the fiber filters and between 3 and 6 per cent by pleated air filter before getting
saturated. Applying to Caltechs cooling towers, such filters can save around 16 million liters per
year.

Discussion
Caltech cannot use seawater for cooling purposes due to its location over thirty miles from the
ocean and fresh water is becoming scarcer every year. Cooling towers recycles their cooling
water while keeping high cooling efficiency, yet takes up forty two per cent of Caltechs total
water consumption. Recovering a small amount of vapor dismissed from Caltechs cooling
towers by use of fiber filters can improve overall water efficiency significantly. Further research
should be carried on to find optimal thickness, area, and orientation of filter extensive
parameter study. Efficient ways to extract condensed vapor from saturated filters and practical
application to cooling towers should be studied thereafter.

Methods
Acquisition of Cooling Water Data. Daily readings of central utility plant (cooling) tower and
satellite plant (cooling) tower blowdown, water softners, central plants condensate tank make up,
chilled water, chilled water expansion tank, and demineralizers are recorded at between 23:00
and 24:00 in Central Utility Plant Operation Log. The amount of water make up for SP cooling
tower is same as the amount of water softeners produced from SP, and the amount of water make
up for CUP cooling tower is the amount of condensate tank make up, chilled water, water going
into chilled water expansion tank and amount of demineralizers subtracted from water softeners
produced from CP.
Acquisition of Cooling Water Data. Central Utility Plant WaterLab provided Monthly
Chemical Usage Report. Each report shows the amount of chemicals (inhibitor,
dispersant/surfactant, biocides, antifoam and bromine) used for CUP, SUP, and IMSS cooling
towers.
Acquisition of Cooling Fan Speed and Temperature Data. The speeds of four cooling fans of
CUP, supply temperature (supplying to condensers from cooling towers) of CUP, and supply and
return (returning from cooling towers to condensers) temperatures of SP are recorded every
minute by computer. Averaging into hourly, daily, weekly, and monthly data was performed by
Matlab 2009a. Daily, weekly, and monthly Cooling degree days (CDD) data of weather station
ID KCAPASAD5 (North Wilson Avenue, Pasadena, CA) are obtained from
www.degreedays.net.
Experiment tools. VICKS Ultrasonic Humidifier V5100NS (cooling tower prototype),
Marineland Rite-Size Bonded Filter Pad (fiber filter), Flanders extended surface area Pleated Air
Filter (pleated air filter), OHAUS PRECISION Standard Model TS120S (scale), Dwyer Model
471 Digital Thermo Anemometer.



References
1. Strittmatter, R. J ., B. Yang, et al. (1992). "Application of Ozone in Cooling Water Systems." 17.
2. Homel Co., Ltd. Kang, K.S, inventor; Recovery System for Cooling Water at Cooling Tower,
Capable of Reducing Water Consumption by Improving Recovery Ratio of Vapor and Mist.
Korea Patent 10-0756384. Aug. 31, 2007.
3. Lee, Hoogeun. Cooling Water Recovery System Using Fiber Filter and its Operating Methods.
Korea Patent 10-0473388. Feb. 16, 2005.

Вам также может понравиться