Вы находитесь на странице: 1из 58

web: www.smar.com e-mail: smarinfo@smar.

com

smar Specifications and information are subject to change without notice.


December/99

BRAZIL ARGENTINA CHINA FRANCE


Smar Equipamentos Ind. Ltda. Smar Argentina Smar China Corp. Smar France S. A. R. L.
Rua: Dr. Antonio Furlan Jr., 1028 Soldado de La Independencia, 1259 3 Baishiqiao Road, Suite 30233 1, bld de l’Oise
Sertãozinho SP 14170-480 (1429) Capital Federal – Argentina Beijing 100873, P.R.C. Immeuble Les Maradas
Tel.: +55 16 645-6455 Telefax: 00 (5411) 4776-1300 / 3131 Tel.: +86 10 6849-8643 95031 Cergy – Pontoise
Fax: +55 16 645-6450 e-mail: smar@ciudad.com.ar Fax: +86 10 6849-9549 Tel.: +33 1 30 38-3888
e-mail: dncom@smar.com.br e-mail: smarchn@eastnet.com.cn Fax: +33 1 30 38-4110
e-mail: smar@wanadoo.fr
GERMANY MEXICO NORWAY SINGAPORE
Smar GmbH Smar Mexico Smar Norge A/S Smar Singapore Pte. Ltd.
Robert-Koch-Strasse 35 11, Poniente, No. 1314-1 PB Sandviksveien, 18 315 Outram Road
D 55129 Mainz Col. Centro C. P. 72000 N-5035 Sandviken Bergen #06-07, Tan Boon Liat Building
Tel.: +49 6131 582037 Ciudad de Puebla, Puebla Tel.: +47 55 13-3885 Singapore 169074
Fax: +49 6131 582249 Tel.: +52 22 46-4386 Fax: +47 55 13-3886 Tel.: +65 324-0182
e-mail: smar@taunus.de Fax: +52 22 46-4386 e-mail: smarno@online.no Fax: +65 324-0183
e-mail: smarrick@mexis.com e-mail: jberge@smar.com.sg
USA
Smar International Corporation Smar Laboratories Corporation Smar Research Corporation
Northwest Point Service Center 10960 Millridge North, Suite 107 4250 Veterans Memorial Hwy.
7240 Brittmoore, Suite 118 Houston, TX 77070 Unit 156
Houston, TX 77041 Tel.: +1 281 807-1501 Holbrook , NY 11741
Tel.: +1 713 849-2021 Fax: +1 281 807-1506 Tel: +1-631-737-3111
Fax: +1 713 849-2022 e-mail: smarlabs@swbell.net Fax: +1-631-737-3892
e-mail: cservice@smar.com e-mail: srcny@aol.com
sales@smarresearch.com
Index III

INTRODUCTION
The TT301 is a transmitter mainly intended for measurement of temperature using RTDs or thermocouples, but can also
accept other sensors with resistance or mV output such as: pyrometers, load cells, resistance position indicators, etc.
The digital technology used in the TT301 enables the choice of several output functions, an easy interface between the
field and the control room and several interesting features that reduce considerably the installation, operation and
maintenance costs.

The TT301, besides the normal functions offered by other smart transmitters, offers the following functions:

SPECIAL SENSOR : the output follows a mV or Ohm input according to a 16-point linearization table.

CONTROLLER : the process variable is compared to a setpoint. The deviation acts on the output signal
according to a PID algorithm (Optional).

BATCH : setpoint generator allowing pre-programmed recipes of up to 2-week duration in 16


points.

LOCAL ADJUST : not only for lower and upper value, sensor-type, operation mode, indication, setpoint,
PID parameters... as well. In other words you do not need a Hand-Held Terminal.

PASSWORD : three configurable levels for different functions.

CHANGE COUNTER : indicates the number of changes in each functions.

SPECIAL- SENSOR-UNIT : allows the digital output and reading to indicate one of over 100 standard engineering
units or any special unit with up to 5 characters.

Get the best result of the TT301 by carefully reading these instructions.
IV TT301 – Operation & Maintenance Instruction Manual

NOTE:

This Manual is compatible with version 2.XX, where 2 denotes software Version and XX
software "RELEASE". There indication 2.XX, the Manual is compatible with any
"RELEASE" of software version 2.
Index V

Table of Contents
1 INSTALLATION PAGE

GENERAL................................................................................................................................................................ 1.1
MOUNTING ............................................................................................................................................................. 1.1
ELECTRIC WIRING ................................................................................................................................................ 1.1

2 OPERATION
FUNCTIONAL DESCRIPTION - HARDWARE ....................................................................................................... 2.1
MUX-Multiplexer .......................................................................................................................................... 2.1
Signal Conditioner ....................................................................................................................................... 2.1
A/D Converter .............................................................................................................................................. 2.1
Signal Isolator.............................................................................................................................................. 2.1
CPU - Central Processing Unit & PROM .................................................................................................... 2.1
D/A Converter .............................................................................................................................................. 2.1
Output .......................................................................................................................................................... 2.1
Modem ......................................................................................................................................................... 2.1
Power Supply............................................................................................................................................... 2.1
Power Isolation ............................................................................................................................................ 2.1
Display Controller ........................................................................................................................................ 2.1
Local Adjustment ......................................................................................................................................... 2.2
FUNCTION DESCRIPTION - SOFTWARE ............................................................................................................ 2.2
Input ............................................................................................................................................................. 2.2
Digital Filter.................................................................................................................................................. 2.2
Input Trim..................................................................................................................................................... 2.2
Standard Sensor Linearization & Compensation ....................................................................................... 2.2
Special Sensor ............................................................................................................................................ 2.2
Ranging ....................................................................................................................................................... 2.2
Time Generator ........................................................................................................................................... 2.2
Setpoint........................................................................................................................................................ 2.2
PID (Optional) .............................................................................................................................................. 2.2
Auto/Manual................................................................................................................................................. 2.2
Limits............................................................................................................................................................ 2.2
Output .......................................................................................................................................................... 2.2
Current Trim................................................................................................................................................. 2.2
Display ......................................................................................................................................................... 2.2
TEMPERATURE SENSORS................................................................................................................................... 2.2
Thermocouples............................................................................................................................................ 2.2
THERMORESISTANCES (RTDs)........................................................................................................................... 2.4
THE DISPLAY.......................................................................................................................................................... 2.5
Monitoring .................................................................................................................................................... 2.5
ALARM..................................................................................................................................................................... 2.6

3 PROGRAMMING USING TERMINAL


THE HAND-HELD TERMINAL ................................................................................................................................ 3.1
Fitting the Battery......................................................................................................................................... 3.1
Fitting the DATAPACK and RAMPACK ...................................................................................................... 3.1
Keyboard...................................................................................................................................................... 3.1
Turning the Unit On and Off ........................................................................................................................ 3.1
Use of <ON/CLEAR> key or the Function EXIT ......................................................................................... 3.2
TERMINAL PROGRAMMING TREE ...................................................................................................................... 3.2
ON LINE SINGLE UNIT CONFIGURATION ........................................................................................................... 3.2
INFORMATION - INFO............................................................................................................................................ 3.4
CONFIGURATION - CONF ..................................................................................................................................... 3.4
RERANGING THE TT301 ....................................................................................................................................... 3.5
RERANGING WITHOUT REFERENCE ................................................................................................................. 3.5
RERANGING WITH REFERENCE......................................................................................................................... 3.6
UNIT......................................................................................................................................................................... 3.8
DAMPING ................................................................................................................................................................ 3.8
OUTPUT .................................................................................................................................................................. 3.8
BURNOUT ............................................................................................................................................................... 3.9
DISPLAY.................................................................................................................................................................. 3.9
SENSOR - Sensor ................................................................................................................................................... 3.9
VI TT301 – Operation & Maintenance Instruction Manual

3 PROGRAMMING USING TERMINAL (Cont.) PAGE

Special Sensor Configuration....................................................................................................................................3.10


Special Sensor Special Unit Selection......................................................................................................................3.11
Special Sensor Table ................................................................................................................................................3.11
PID Module (Optional) ...............................................................................................................................................3.11
MONIT - Monitoring..............................................................................................................................................................3.13
CNTRL - CONTROL ............................................................................................................................................................3.13
Operation Mode - OP_MODE....................................................................................................................................3.13
INDIC - Indication.................................................................................................................................................................3.13
TUNING................................................................................................................................................................................3.14
SAF. LIMITS - Control Limits ...............................................................................................................................................3.14
SP-TABLE - Setpoint Table .................................................................................................................................................3.14
TRIM .....................................................................................................................................................................................3.14
Current TRIM (4-20 mA Output) ................................................................................................................................3.14
Reading TRIM (Input) ................................................................................................................................................3.15
MAINTENANCE - MAINT.....................................................................................................................................................3.16
FORMAT ..............................................................................................................................................................................3.16
SERIAL NUMBER................................................................................................................................................................3.16
CHANGE COUNTER - OP_COUNT ...................................................................................................................................3.16
PASSWORDS......................................................................................................................................................................3.17
CONFIGURATION LEVEL...................................................................................................................................................3.17
WP-PROT - WRITE PROTECT...........................................................................................................................................3.17
ALARM - ALARM .................................................................................................................................................................3.17
Configuring Alarms ....................................................................................................................................................3.18
ACKNOWLEDGING ALARMS.............................................................................................................................................3.18
ON-LINE MULTIDROP OPERATION..................................................................................................................................3.18
CONFIGURATING THE TT301 FOR MULTIDROP............................................................................................................3.19
CONFIGURATION IN MULTIDROP MODE........................................................................................................................3.19

4 PROGRAMMING USING LOCAL ADJUST


THE MAGNETIC TOOL .........................................................................................................................................................4.1
RERANGING USING THE LOCAL ZERO AND SPAN ADJUSTMENTS IN SIMPLE MODE .............................................4.1
COMPLETE LOCAL ADJUSTMENT .....................................................................................................................................4.2
LOCAL PROGRAMMING TREE............................................................................................................................................4.2
OPERATION - [OPER]...........................................................................................................................................................4.3
BATCH - [BATCH]..................................................................................................................................................................4.4
TUNING - [TUNE]...................................................................................................................................................................4.5
CONFIGURATION - [CONF]..................................................................................................................................................4.7
ESCAPE - [ESC] ....................................................................................................................................................................4.9

5 MAINTENANCE PROCEDURES
GENERAL ..............................................................................................................................................................................5.1
DIAGNOSIS WITH SMAR HAND-HELD TERMINAL ...........................................................................................................5.1
ERROR MESSAGES .............................................................................................................................................................5.1
TROUBLESHOOTING WITH TRANSMITTER .....................................................................................................................5.2
DISASSEMBLY PROCEDURE..............................................................................................................................................5.3
Sensor..........................................................................................................................................................................5.3
Electronic Circuits ........................................................................................................................................................5.3
REASSEMBLY PROCEDURE...............................................................................................................................................5.3
INTERCHANGEABILITY........................................................................................................................................................5.3
RETURNING MATERIALS ....................................................................................................................................................5.3
Exploded View........................................................................................................................................................................5.3
SPARE PARTS LIST FOR TRANSMITTER..........................................................................................................................5.4
ACESSORIES ........................................................................................................................................................................5.5
Index VII

6 TECHNICAL DATA
FUNCTIONAL SPECIFICATIONS............................................................................................................................................................6.1
Inputs...............................................................................................................................................................................................6.1
Output Signal ..................................................................................................................................................................................6.1
Power Supply ..................................................................................................................................................................................6.1
Load Limitation................................................................................................................................................................................6.1
Indication.........................................................................................................................................................................................6.1
Hazardous Location Certification ...................................................................................................................................................6.1
Zero and Span Adjustment .............................................................................................................................................................6.1
Temperature Limits .........................................................................................................................................................................6.1
Loss of Input (Burnout)/Failure Alarm ............................................................................................................................................6.1
Humidity Limits................................................................................................................................................................................6.1
Turn-on Time...................................................................................................................................................................................6.1
Update Time....................................................................................................................................................................................6.1
Damping..........................................................................................................................................................................................6.1
Configuration...................................................................................................................................................................................6.1
HHT Main Features.........................................................................................................................................................................6.1
PERFORMANCE SPECIFICATIONS.......................................................................................................................................................6.1
Accuracy..........................................................................................................................................................................................6.1
Ambient Temperature Effect...........................................................................................................................................................6.1
Power Supply Effect........................................................................................................................................................................6.1
Vibration Effect................................................................................................................................................................................6.1
Electro-Magnetic Interference Effect ..............................................................................................................................................6.1
PHYSICAL SPECIFICATION....................................................................................................................................................................6.2
Electrical Connection ......................................................................................................................................................................6.2
Material of Construction..................................................................................................................................................................6.2
Mounting .........................................................................................................................................................................................6.2
Weight .............................................................................................................................................................................................6.2
CONTROL CHARACTERISTICS (OPTIONAL) .......................................................................................................................................6.2
Alarm ...............................................................................................................................................................................................6.2
ORDERING CODE ...................................................................................................................................................................................6.3
Index 1.1

INSTALLATION
GENERAL Using the brackets, the mounting may be done in
several positions, as shown on Fig. 1.3.
The overall accuracy of temperature and other mea- One of the conduit inlets for electrical connection is
surements depends on several variables. Although the used to mount the sensor integral to the temperature
transmitter has an outstanding performance, proper transmitter (see Fig. 1.2).
installation is essential, in order to maximize its perfor-
mance. For better visibility, the digital indicator may be rotated
in steps of 90( (see Section V, Maintenance).
Among all factors, which may affect transmitter accura-
cy, environmental conditions are the most difficult to ELECTRIC WIRING
control. There are, however, ways of reducing the Access the wiring block by removing the Electrical
effects of temperature, humidity and vibration. Connection Cover. This cover can be locked closed by
the cover locking screw (Fig. 1.1). To release the cover,
Temperature fluctuation effects can be minimized by rotate the locking screw clockwise.
locating the transmitter in areas protected from extreme
environmental changes.

In warm environments, the transmitter should be


installed to avoid, as much as possible, direct exposure
to the sun. Installation close to lines and vessels
subjected to high temperatures should also be avoided.
For temperature measurements, sensors with cooling-
neck can be used or the sensor can be mounted
separated from the transmitter housing.

Use of sun shades or heat shields to protect the


transmitter from external heat sources should be
considered, if necessary.

Humidity is fatal to electronic circuits. In areas subject-


ed to high relative humidity, the O-rings for the elec-
tronics cover must be correctly placed. Removal of the Fig. 1.1 – Cover Locking
electronics cover in the field should be reduced to the
Cable access to wiring connections is obtained by one
minimum necessary, since each time it is removed, the
of the two conduit outlets. Conduit threads should be
circuits are exposed to the humidity. The electronic
sealed by means of code-approved sealing methods.
circuit is protected by a humidity proof coating, but
The unused outlet connection should be plugged
frequent exposures to humidity may affect the protec-
accordingly.
tion provided. It is also important to keep the covers
tightened in place. Every time they are removed, the The wiring block has screws on which terminals type
threads are exposed to corrosion, since these parts fork or ring can be fastened, see Fig. 1.2.
cannot be protected by painting. Code-approved
sealing methods on conduit entering the transmitter For convenience there are three ground terminals: one
should be employed. inside the cover and two external, located close to the
conduit entries.
Measurement error can be decreased by connecting
the sensor as close to the transmitter as possible and
using proper wires (see Section II, Operation).

WARNING:

Do not remove the graphite grease from the covers, or


they may jam.

MOUNTING
The transmitter may be mounted in two basic ways, as
follows:

- Separated from the sensor, using optional


mounting brackets.
- Mounted on the sensor assembly.
Fig. 1.2 – Ground Terminal
1.2 TT301 – Operation & Maintenance Instruction Manual

Fig. 1.3 – Dimensional Drawing and Mounting Positions

Use of twisted pair (16 AWG) cables is recommended.

WARNING:

Do not connect the Power Supply to the sensor terminals


(Terminals 1, 2, 3 and 4).

Avoid routing signal wiring close to power cables or


switching equipment.

The TT301 is protected against reversed polarity.


Connection of the TT301 working as transmitter should
be performed as in Fig. 1.4.

Fig. 1.5 – Wiring Diagram for the TT301 Working as


Controller

Connection of the TT301 in multidrop configuration


should be done as in Fig. 1.8. Note that a maximum of
15 transmitters can be connected on the same line and
that they should be connected in parallel. When many
transmitters are connected to the same line, calculate
the voltage drop through the 250 Ohm resistor and
verify that the voltage of the power supply is enough
(Fig 1.6).

Fig. 1.4 – Wiring Diagram for the TT301 Working as Wiring diagram for the TT301 in multidrop.
Transmitter
ATTENTION:
Connection of the TT301 working as a controller
(Optional) should be as indicated in Figure 1.5. For proper operation, the Hand-Held Terminal requires a
minimum load of 250 Ohm between it and the power supply.
Index 1.3

The Hand-Held Terminal can be connected to the


communication terminals of the transmitter or at any
point of the signal line by using the interface with
alligator clips.

It is also recommended to ground the shield of shielded


cables at only one end. The not grounded end must be
carefully isolated.

NOTE:

Make sure that the transmitter is operating within the


operating area as shown on the load diagram (Fig. 1.6).
Communication requires a minimum load of 250 Ohm.

The sensor should be connected as per Fig. 1.7.

IMPORTANT:

When operating with dual sensor, the sensors can not be


both grounded. At least one has to be not grounded for
proper operation of TT301.

Fig. 1.7 – Sensor Wiring

Fig. 1.8 – Wiring Diagram for the TT301 in Multidrop Configuration


1.4 TT301 – Operation & Maintenance Instruction Manual
Operation 2.1

2 - OPERATION
The TT301 accepts signals from mV generators such RAM, the data in the RAM is lost if the power is
as thermocouples or resistive sensors such as RTDs. switched off, however the CPU also has an internal
The criteria is that the signal is within the range of the nonvolatile EEPROM where data that must be retained
input. For mV, the range is -50 to 500 mV and for is stored.Examples of such data are: calibration,
resistance, 0-2000 Ohm. configuration and identification data.

FUNCTIONAL DESCRIPTION-HARDWARE D/A Converter


Refer to the block diagram (Fig. 2.1). The function of Converts the digital output data from the CPU to an
each block is described below. analog signal.

MUX-Multiplexer Output
The MUX multiplexes the sensor terminals to the signal Controls the current in the line feeding the transmitter.
conditioning section ensuring that the voltages are
measured between the correct terminals. It acts as a variable resistive load whose value depends
on the voltage from the D/A converter.
Signal Conditioner
Its function is to apply the correct gain to the input Modem
signals to make them suit the A/D - converter. Modulates a communication signal on the current line.
A "1" is represented by 1200 Hz and a "0", by 2200 Hz.
A/D Converter These signals are symmetric and do not affect the DC
The A/D converts the input signal to a digital format for level of the 4-20 mA signal.
the CPU.
Power Supply
Isolator Takes power of the loop-line to power the transmitters
Its function is to isolate the control and data signal circuit. This is, of course, limited to 3.9 mA.
between the input and the CPU.
Power Isolation
CPU - Central Processing Unit & PROM Its function is to isolate power supply between the input
The CPU is the intelligent portion of the transmitter, and the CPU.
being responsible for the management and operation of
all other blocks: linearization, cold junction Display Controller
compensation and communication. The program is Receives data from the CPU informing which segments
stored in the PROM as well as the linearization data for of the Liquid Crystal Display,should be turned on.
the temperature sensors.
For temporary storage of data, the CPU has an internal

Fig. 2.1 – TT301 Block Diagram


2.2 TT301 – Operation and Maintenance Instruction Manual

Local Adjustment PID (Optional)


Two switches that are magnetically activated. They can First the error is calculated as SP-PV or PV-SP
be activated by the magnetic tool without mechanical or depending on which action (direct or reverse) is
electrical contact. configured in ACTION.

FUNCTIONAL DESCRIPTION - SOFTWARE 1 dPV


Refer to the block diagram (Fig. 2.2). The function of
each block is described below.
MV = Kp (e +
Tr ∫ edt + Td .
dt
)

Input Auto/Manual (Optional)


Calculates the actual mV or Ohm from the value The Auto/Manual mode is toggled in INDIC . In Manual,
sensed by the input circuitry. MV may be adjusted by the user in the INDIC option.
The POWER-ON option is used here to determine in
Digital Filter which mode the controller should be upon powering it
The digital filter is a low-pass filter with an adjustable on.
time constant. It is used to smooth noisy signals. The
Damping value is the time required for the output to Limits (Optional)
reach 63.2% for a step input of 100%. This block makes sure that the MV does not go beyond
its minimum and maximum limits as established by the
Input Trim HIGH-LIMIT and LOW-LIMIT. It also makes sure that
Here, the value obtained by READING-TRIM is used to the Rate-of-Change does not exceed the value set in
correct the transmitter for long term drift. OUT-CHG/S. These values are adjusted in the SAFETY
LIMITS option.
Standard Sensor Linearization & Compensation
Here, the mV and Ohm measurements are linearized Output
and cold-junction compensated according to the sensor Calculates the current proportional to the process
characteristics stored in the CPU. The CPU contains variable or Manipulated variable to be transmitted on
data about most standard sensors available. the 4-20 mA output, depending if the PID Module is ON
or OFF. This block also contains the constant current
Special Sensor function configured in OUTPUT.
Here, the mV and Ohm measurements may be
linearized according to a customer specified Current Trim
linearization table stored in TABLE - X,Y. Sensor TYPE The 4 mA-TRIM and 20 mA-TRIM are used to make the
and CONNECTION is specified as well. In UNIT, the transmitter current comply with a current standard,
desired engineering unit is configured. This unit is used should a deviation arise.
in all communication with the transmitter and on the
display. The LRL, URL and MINimum Span are used to Display
limit the range that can be set, to be within the table Alternates two indications as configured in DISPLAY.
and device accuracy. The engineering unit for the process variable can be
selected in UNIT.
Ranging
It is used to set the process values corresponding to the TEMPERATURE SENSORS
output 4 and 20 mA in transmitter mode or process The TT301, as previously explained, accepts several
variable 0 and 100% in PID mode. In transmitter mode types of sensors. The TT301 is specially designed for
the LOWER-VALUE is the point corresponding to 4 mA, temperature measurement using thermocouples or
and UPPER-VALUE is the point corresponding to 20 thermoresistances (RTDs).
mA. In PID mode, the LOWER-VALUE corresponds PV
= 0% and UPPER-VALUE corresponds to PV = 100%. Some basic concepts about these sensors are
presented below.
Time Generator (Optional) Thermocouples
Counts the time to be used by the Setpoint generator Thermocouples are the mot widely used sensors in
function. It may be paused by using PAUSE and industrial temperature measurements.
reseted to zero by using RESET.
Thermocouples consist of two wires made from different
Setpoint (Optional) metals or alloys joined at one end, called measuring
Here, the setpoint is adjusted in INDIC. In this block, junction. The measuring junction should be placed at
Setpoint tracking may be activated in SP-TRACKING. the point of measurement. The other end of the
The setpoint may also be generated automatically by thermocouple is open and connected to the
turning the SP-GENERATOR ON. When running, the temperature transmitter. This point is called reference
setpoint generator will ramp and dwell the setpoint junction or cold junction.
according to a table (recipe) configured in SP-TABLE. For most applications, the Seebeck effect is sufficient
to explain thermocouple behavior:
Operation 2.3

Fig. 2.2 – Software Flow Chart


2.4 TT301 – Operation and Maintenance Instruction Manual

How the Thermocouple Works The TT301 permits a 2-wire connection which may
When there is a temperature difference along a metal cause measuring errors, depending on the length of
wire, a small electric potential, unique to every alloy, will connection wires and on the temperature to which they
occur. This phenomenon is called Seebeck effect. are exposed (see Fig. 2.3).

When two wires of dissimilar metals are joined in one In a 2-wire connection, the voltage V2 is proportional to
end, and left open in the other, a temperature difference the RTD resistance plus the resistance of the wires.
between the two ends will result in a voltage since the V2 = [RTD + 2.x R] x I
potentials generated by the dissimilar materials are
different and does not cancel each other out. Now, two
important things must be noted. First: the voltage
generated by the thermocouple is proportional to the
difference between the measuring-junction and the cold
junction temperatures. Therefore the temperature at the
reference junction must be added to the temperature
derived from the thermocouple output, in order to find
the temperature measured. This is called cold junction
compensation, and is done automatically by the TT301,
which has a temperature sensor at the sensor terminals
for this purpose. Secondly, if the thermocouple wires Fig. 2.3 – Two-Wire Connection
are not used all the way to the terminals of the In order to avoid the resistance effect of the connection
transmitter (e.g. copper wire is used from sensor-head wires, it is recommended to use a 3-wire connection
or marshalling box) new junctions with additional (see Fig. 2.4) or a 4-wire connection (see Fig. 2.5).
Seebeck effects will be created and ruin the
measurement in most cases, since the cold-junction In a 3-wire connection, terminal 3 is a high impedance
compensation will be done in the wrong point. input. Thus, no current flows through that wire and no
voltage drop is caused. The voltage V2-V1 is
The relation between the measuring junction tempera- independent of the wire resistances since they will be
ture and the generated millivoltage is tabulated in ther- canceled out, and is directly proportional to the RTD
mocouple calibration tables for standardized ther- resistance alone.
mocouple types, the reference temperature being 0(C. V2-V1 = [RTD + R] x I - R x I = RTD x I
Standardized thermocouple which are commercially
used, whose tables are stored in the memory of the
TT301, are the following:

 NBS (B, E, J, K, N, R, S, T)
 DIN (L, U)

THERMORESISTANCES (RTDs)
Resistance Temperature Detectors, most commonly
known as RTD's, are based on the principle that the
Fig. 2.4 – Tree-Wire Connection
resistance of a metal increases as its temperature
increases. In a 4-wire connection, terminals 2 and 3 are high
impedance inputs. Thus, no current flows through those
Standardized RTDs, whose tables are stored in the wires and no voltage drop is caused. The resistance of
memory of the TT301, are the following: the other two wires are not interesting since no
measurement is done on them. Hence the voltage V2
 JIS [1604-81] (Pt50 & Pt100) is directly proportional to the RTD resistance. (V2 =
 IEC, DIN, JIS [1604-89] (Pt50, Pt100 & Pt500) RTD x I).
 GE (Cu 10)
 DIN (Ni 120)

For a correct measurement of RTD temperature, it is


necessary to eliminate the effect of the resistance of the
wires connecting the sensor to the measuring circuit. In
some industrial applications, these wires may be
hundreds of meters long. This is particularly important
at locations where the ambient temperature changes a
lot.
Fig. 2.5 – Four-Wire Connection
Operation 2.5

A differential connection is similar to the two-wire Monitoring


connection and gives the same problem (see Fig. 2.6). During normal operation, the TT301 is in the monitoring
Terminal 3 is a high impedance input. Thus, no current mode. In this mode, indication alternates between the
flow through and no voltage drop is caused, but the primary and secondary variable as configured in
resistance of the other two wires will be measured and DISPLAY. See Fig. 2.8.
does not cancel each other out in a temperature
measurement, since linearization will affect them
differently.

Fig. 2.6 – Differential Connection Fig. 2.8 – Typical Monitoring Mode Display
THE DISPLAY The display indicates engineering units, values and
The digital indicator is able to display one or two parameters simultaneously with most status
variables which are user selectable. When two indicators. The monitoring mode is interrupted in two
variables are chosen, the display will alternate between situations:
the two with an interval of 3 seconds.
 user performs complete local adjustment.
The different fields and status indicators are explained  an alarm is activated.
in Fig. 2.7.

Fig. 2.7 - Display


2.6 TT301 – Operation and Maintenance Instruction Manual

ALARM
The two alarms are software alarms and have no
contacts available on the transmitter. The alarms are
acknowledged by using the Local Adjustment or the
Hand-Held Terminal, which can view and configure
alarms as well - see further Section III. During an alarm,
the display will indicate which alarm has been activated
and if it has been acknowledged or not.
The transmitter display also indicates the alarms status
as shown in Fig. 2.9.

AL H means High Alarm, AL L means Low Alarm and


ALO indicates Burnout failure. The ACK indicates that
the alarm has not yet been acknowledged.

When the alarm condition disappears, the "ACK" is


switched off and the display returns to monitoring
mode.
Fig. 2.9 – Typical Alarm Condition Display
For further information on alarm configuration, see
Section III - Programming Using Terminal.
Programming Using Terminal 3.1

3 PROGRAMMING USING TERMINAL


THE HAND-HELD TERMINAL Fitting the Battery
The HT2 uses any 9-Volt PP3 size battery, however for
Smar Hand-Held Terminal (HT2) is the human machine longer operating life, use of alkaline batteries is
interface used to maximize the advances of digital recommended.
technology. The terminal's front face is shown on Fig.
3.1. Remove the protective case by pulling it firmly
downwards. Pull the tab to remove the battery cover
and observe polarity.

WARNING:
Do not remove the battery in Hazardous Areas.

Fitting the DATAPACK and RAMPACK.


The datapack is the module where the TT301
configuration software for the HT2 is stored. Make sure
it is market TT301 and put it into slot B.

Keyboard

The Hand-Held Terminal (HT2) has double function


keys. The function labels are indicated on the keys
themselves, and above them. The following keys are
used for TT301 programming.

Is used to switch the HT2 on or to return to


the last decision level in the menu. The
display will show the menu - the list of built-in
applications available. If you cannot read the display, or
if it is difficult to read, you may have to adjust the
Fig. 3.1 – Smar Hand-Held Terminal contrast. To locate contrast adjustment, see Figure 3.1.

Smar Hand-Held Terminal (HT2) Software has the These keys are used to move the cursor.
following features:

 Transmitter identification and specification data. Is used to access the symbols and numbers
above the keys. Must be pressed
 Remote reranging. simultaneously with the desired key when the HT2 is in
the alphanumeric mode. To obtain the selection, just
 Special sensor parameter adjustments. press simultaneously <SHIFT> and the symbol or
number desired. For data entry that requires only
 Constant current adjustment between 3.9 and 21 mA numbers, the <SHIFT> key is not necessary.
for loop test.
Is used to delete characters wrongly typed.
 Monitoring of process variable in Engineering Units,
% and mA.
Is used to leave a space between characters.
 Controller monitoring for Setpoint, Process Variable,
Manipulated Variable and Auto/Manual status.

 Controller parameters adjustment. Is used to confirm an action or complete an


input.
 Setpoint generator parameters adjustment. Turning the Unit On and Off
When the HT2 is turned on the first time or with a new
 Diagnosis and determining of faults in the processor battery, the following message is on the display:
or in the transmitter.

The operations which take place between the HT2 and SELECT LANGUAGE
the transmitter does not interrupt the measurement, English Français
and does not disturb the output signal. The HT2 can be Deutsch
connected on the 4-20 mA line up to 2 km away from
the transmitter.
3.2 TT301 - Operation and Maintenance Instruction Manual

The cursor is blinking under English, which is the only ON LINE SINGLE UNIT CONFIGURATION
language available for the software version 1.00. To configure the transmitter on line, certify that it is
Press the <EXE> key. correctly installed, with a suitable power supply and the
minimum 250 Ω load required.
11:23a
With the cursor blinking under the "On line single unit"
Tt301 Off option, press the <EXE> key. The display will show:

Moving the cursor to function OFF and pressing the Searching for XMTR
<EXE> key or pressing the Key <O> will turn the unit
off. If the terminal is ON for five minutes without any
keys being pressed, it will switch itself OFF.
With the cursor blinking under TT301, press the <EXE> XMTR = means transmitter
key. The operational system is transferred from the
plug-in EPROM memory (DATAPACK) to the HT2 RAM
memory, and the display will show the following >>>> SMAR TT301 <<<<
message. Output:
Temperature XMTR
Version 2.XX
HAND HELD TERMINAL
MODEL HT2
The display flashes a message informing that the
Version 1.XX transmitter is working as a temperature transmitter
(XMTR) and its software version is 2.xx. Immediately
After a few seconds, the following menu will show the after that, the main menu is displayed.
three configuration options.
/ (TAG) XMTR
INFO CONF MONIT
SMAR-HT2
TRIM MAINT ALARM
ON_LINE_SINGLE_UNIT
EXIT
ON_LINE_MULTIDROP
EXIT
or
Use of <ON/CLEAR> Key or the Function EXIT
Both <ON/CLEAR> key and the EXIT function allow the / (TAG) PID
user to leave the MENU in use and return to the next INFO CONF MONIT
higher MENU in the hierarchy. CNTRL TRIM MAINT
ALARM EXIT
The key or the function are also useful for returning to
a familiar menu when the user is lost in an unfamiliar / - indicates the main menu options.
operation.
TERMINAL PROGRAMMING TREE X M T R
The Programming tree is a tree-shaped structure with
a menu of all the available software resources, as
Indicates that the transmitter works also as a
shown in Figure 3.2.
transmitter
On Line Single Unit is used when the HT2 is
connected in parallel to a single transmitter and this or
transmitter has the address 0.
P I D (Optional)
WARNING:
Indicates that the transmitter works as a controller.
All transmitters are factory configured with no passwords.
TAG - is the space reserved for the transmitter TAG
To avoid operation by nonauthorized persons in some
critical levels of the Programming Tree, it is recommended (8 characters).
to configure all passwords and configuration levels prior to INFO - is the option where the main information about
operation. See "PASSWORD" option in Maintenance
section.
the transmitter can be accessed.
CONF - is the option where the output related
On Line Multidrop is used when the HT2 is connected parameters are configured: Lower Value,
in parallel to several transmitters (up to 15) and these Upper Value, Unit, Damping, Output Function,
transmitters are configured with different addresses Sensor Type, Burnout,XMTR/PID-mode and
(see Multidrop). Display.
Programming Using Terminal 3.3

Fig. 3.2 – Terminal P`rogramming Tree


3.4 TT301 - Operation and Maintenance Instruction Manual

MONIT - is the option that allows the user to monitor 4 INTEGRAL METER*: Indicates if a display is fitted or
of the transmitters dynamic variables and not.
output current.
SENSOR TYPE*: Shows sensor type and
CNTRL - is the option where all control parameters may respective connection, as
be adjusted and monitored. selected in CONF.

TRIM - is the option used to match the transmitter SENSOR RANGE*: Shows the TT301 range for this
indication with an Ohm/mV and/or a current particular type of sensor.
standard.
MAINT - is the option used to change Passwords, to
establish the password level attributed to each *NOTE:
configuration operation and to read the
These items cannot be changed at this point of the
operation counters.
menu. Please refer to configuration.
EXIT - is the option used to go back to the previous
menu. The <ON> key can be used as well.

INFORMATION - INFO
If the INFO option is selected, the display will show:

/INFO (TAG) XMTR

Tag:
XXXXXXXX

> and <


Using the < > keys all information items can
be accessed. If you intend to change one item, press
the <EXE> key.

/INFO (TAG) XMTR


Tag:
XXXXXXXX
Change it? Y / N
Fig. 3.3 – Terminal Information Tree
If you press <N>, the display will show the item again.
CONFIGURATION - CONF
If you press <Y>, you may select the new content and This function affects the 4-20 mA output of the
send it to the transmitter by pressing the <EXE> key. transmitter and the transmitter display indication. Here
The following items are available with the respective the transmitter can be reranged, having the damping
options. adjusted or the burnout mode changed. The
TAG - Eight character alphanumeric field for Engineering Units displayed on the transmitter and on
identification of the transmitter. Remember to the HT2 can also be changed.
use the <SHIFT> key for numbers and RERANGING THE TT301
symbols. To rerange a transmitter is to change the input values
DESCRIPTOR - 16-character alphanumeric field for related to 4 mA and to 20 mA. There are four ways to
additional identification of the do it with the TT301:
transmitter. May be used to identify 1 - Using the HT2 (without reference mode) where
service or location. calibration input is not required.
DATE MODIFIED - The date may be used to identify a 2 - Using the HT2 with an input signal or calibrator
relevant date as the last calibration, as reference (with reference mode).
the next calibration or the installation.
The date is presented in the form of 3 - Using the local adjustment with input signal as
Month, Day, Year. Month should be reference (simple mode, XMTR).
entered as a number 1 -12. Year with
4 - Using the local adjustment with input signal as
all four digits, e.g., 1992.
reference (complete mode, with reference).
MESSAGE: 32-character alphanumeric field for any
5- Using the local adjustment where a calibration
other information, such as the name of
input is not required (complete mode, without
the person who made the last calibration,
reference).
some special care to be taken, etc.
In transmitter mode, the Lower Value always
corresponds to 4 mA and the Upper Value to 20 mA. In
Programming Using Terminal 3.5

PID mode, the Lower Value corresponds to PV=0% and


the Upper Value to PV=100%.
/CONF (TAG) XMTR
[Lower Range Adjust]
RERANGING WITHOUT REFERENCE
WITHOUT REFERENCE
The TT301 may be adjusted to give 4 and 20 mA cor- WITH REFERENCE
responding to given temperature values. The TT301
has the expected input, from several standard sensors
output at different temperatures, programmed in its As the cursor is blinking under "WITHOUT
memory. Therefore, the zero and span input does not REFERENCE", as desired, press <EXE>.
have to be generated when the TT301 is reranged, thus
there is no need to connect it to a calibrator for The display will show the range limits, for example, for
reranging purposes. Suppose that the transmitter is a IEC Pt100:
calibrated from -100 to 300 (C and the range must be
changed to 0 to 100(C. To rerange the transmitter, set /CONF (TAG) XMTR
the cursor blinking under CONF by using the < > <
> Range Limits:
<> <
> keys. Lo= -200.00 ºC
Hi= 850 ºC

/ (TAG) XMTR
INFO CONF MONIT
and ask for the new Lower Value:
TRIM MAINT ALARM
EXIT
/CONF (TAG) XMTR
Type Lower Range
Press <EXE>. Lo(C) = _

/CONF (TAG) XMTR The new Lower Value can be typed and entered with
Lower= -100.00 ºC the <EXE> key. If the typed value is below the Lower
Upper= 300.00 ºC
Unit = ºC
Limit Value or the span narrower than the minimum
span, an alarm message is shown on the display and
the value is not accepted.
To change the Lower Value, press <EXE>.
As the new Lower Value is 0(C. Type <0> and <EXE>:
/CONF (TAG) XMTR
[Lower Range Adjust] /CONF (TAG) XMTR
Lower= -100.00 ºC
Change it? Y / N Loop may be returned
to AUTO ! [EXE]
If you press <N> (No), you will return to the previous
screen. If you press <Y> (Yes): Press <EXE> to proceed:

/CONF (TAG) XMTR /CONF (TAG) XMTR


Lower= 0.00 ºC
Control loop should Upper= 300.00 ºC
be in MANUAL ! [EXE] Unit = ºC

This is a warning message. Be sure that changes in the To change the Upper Value, move the cursor to Upper
output signal will not disturb plant operation. and press <EXE>.

Press <EXE> key to proceed.


/CONF (TAG) XMTR
[Upper Range Adjust]
/CONF (TAG) XMTR Upper= 300.00 ºC
Change it? Y / N
Enter your Password
PSW = _
Press <Y> (Yes). A warning message will be on the
display. Press <EXE>.
If a password was programmed to this operation, you
must enter it (see MAINTENANCE).
/CONF (TAG) XMTR
After entering the password and pressing the <EXE> [Upper Range Adjust]
key: WITHOUT REFERENCE
WITH REFERENCE
3.6 TT301 - Operation and Maintenance Instruction Manual

The cursor is blinking under "WITHOUT REFERENCE". considering that the Minimum Span IEC Pt100 is 10(C,
Press <EXE> key. The display will show the sensor you must change the settings as follows:
limits for a while:
a) Set the LOWER VALUE = 90, i.e. (100-10)
b) Set the UPPER VALUE = 0(C
/CONF (TAG) XMTR c) Set the LOWER VALUE = 100(C
Range Limits:
Lo= -200.00 ºC
Hi= 850.00 ºC
RERANGING WITH REFERENCE
This is almost the conventional way to rerange or to
calibrate a transmitter. Apply the input to which you
and then, ask for the change: want to set the 4 mA/PV=0% point. If, through the HT2,
you tell the transmitter that this is the 4 mA/PV=0%
point, this input is set as the Lower Value and the
/CONF (TAG) XMTR
Type Upper Range span is maintained.
Up(C) =
The same procedure is applied for the Upper Value.

Type <1> <0> <0> and <EXE>. Example: A transmitter with resistance input is ranged,
so that:
The warning message will tell you that the loop may be
returned to AUTO. Press <EXE>. LOWER VALUE  0 Ohm
UPPER VALUE  100 Ohm

/CONF (TAG) XMTR After installation, the potentiometer residual may give a
Lower= 0.00(C reading of, for instance, 5 Ohm when the resistive
Upper= 100.00(C position indicator is at zero.
Unit =(C
The zero suppression is easily accomplished with the
The transmitter will generate a signal that varies from reranging with reference.
4-20 mA when the temperature varies from 0 to 100 (C.
Select CONF and press <EXE>.
Observe that both LOWER and UPPER VALUES are
completely independent. Adjustment of one does not
affect the other. Although, the following rules must be /CONF (TAG) XMTR
Lower= 0.00ohm
observed: Upper= 100.00ohm
Unit = ohm
a) Both LOWER and UPPER VALUES should not
be smaller than lower range or greater than high
range. As the cursor is blinking under Lower, press <EXE>..

b) The span, [(UPPER VALUE)-(LOWER


/CONF (TAG) XMTR
VALUE)], should be greater than the MINIMUM [Lower Range Adjust]
SPAN. Lower=
Change it? Y / N
If you intend to reverse a signal, i.e., to have the
UPPER VALUE smaller than the LOWER VALUE, Press <Y> (Yes).
proceed as follows:
/CONF (TAG) XMTR
Make the Lower Value as close to the Upper Value as
possible or vice-versa, observing the minimum span Control loop should
allowed , set the Upper Value to the desired setting and be in MANUAL ! [EXE]
then, set the Lower Value.
Press <EXE>.
Example: If the transmitter is ranged, so that:

LOWER VALUE  4 mA = 0(C /CONF (TAG) XMTR


UPPER VALUE  20 mA = 100(C
Enter your Password
PSW = _
and you want to change the settings to:

LOWER VALUE  4 mA = 100(C


/CONF (TAG) XMTR
UPPER VALUE  20 mA =0(C [Lower Range Adjust]
WITHOUT REFERENCE
WITH REFERENCE
Programming Using Terminal 3.7

Fig. 3.4 – Terminal Configuration Tree


3.8 TT301 - Operation and Maintenance Instruction Manual

Move the cursor to "WITH REFERENCE", since the For thermocouple and RTD input:
desired input is applied, and press <EXE>. degrees Celsius
degrees Fahrenheit
degrees Rankine
/CONF (TAG) XMTR Kelvins
[Lower Range Adjust]
Apply lower range
DAMPING
and wait few seconds
The CONF function enables the electronic damping
adjustment.
After a while, waiting for the input to stabilize, the
display will show: The damping may be adjusted between 0 and 32 sec.

/CONF (TAG) XMTR


[Lower Range Adjust]
OUTPUT
Set that reference The output can be set to any desired value between 3.9
as lower range? Y/N and 21 mA regardless of input. This feature is very
useful for loop test.
Confirm by pressing <Y>,
To activate one of these options, just move the cursor
to OUTPUT and press <EXE> key. The display will
/CONF (TAG) XMTR show:

Loop may be returned


to AUTO ! [EXE] /CONF (TAG) XMTR
[ Changing Function]
Function = Linear
Press <EXE> to proceed. Change it? Y / N

/CONF (TAG) XMTR Press <Y> yes.


Lower= 5.00ohm
Upper= 105.00ohm
Unit = ohm /CONF (TAG) XMTR

Control loop should


Observe that the Upper Value shifted, and the same be in MANUAL ![EXE]
span was maintained.

The Lower Value is the transmitter reading of the Press <EXE> key.
applied input.
/CONF (TAG) XMTR
The Upper Range Value may be changed in the same
way. As mentioned before, the transmitter reading in Enter your password
Engineering Units of the 4-20 mA points may differ PSW = _
slightly from your plant standard. If password is configured, enter the password and
press <EXE> key.
Although the 4-20 mA setpoints will operate properly
within these applied settings, the transmitter reading, in
Engineering Units, may indicate a slightly different /CONF (TAG) XMTR
value. Choose new Function
.linear .const
The function TRIM-READING can be used to match the EXIT
transmitter reading in Engineering Units to your plant
standard, thereby eliminating any eventual differences. Move the cursor to "CONST" option and press <EXE>
key.
UNIT
The Engineering Units of the transmitter display and of
the HT2 display may be changed when the option /CONF (TAG) XMTR
"UNIT", of the CONF function, is selected.
Enter current value
3.9 =< I(mA) =< 21
The following units are available;

For mV input: always mV


/CONF (TAG) XMTR
For Ohm input: always ohm Enter current value
I(mA) = _
Programming Using Terminal 3.9

Type the desired current value for example: 12.00 mA.


/CONF (TAG) XMTR
[ Meter Indication ]
/CONF (TAG) XMTR First Var. = PV
Second Var. = TAmb
Enter current value
I(mA)= 12.00_
Press <EXE> key.
Press <EXE> key.
/CONF (TAG) XMTR
This options is intentionally volatile, i.e., if the [ First Variable ]
transmitter is switched off, it will come back with Out PV Tamb
LINEAR output. PV% Exit

BURNOUT Move the cursor to PV% and press <EXE> key.


The output may be programmed to go to the maximum
limit, 21.00 mA (UP-SCALE) or to the minimum limit,
3.9 mA (DOWN-SCALE), should the transmitter fail, /CONF (TAG) XMTR
e.g., over range due to open sensor. If the TT301 [ Meter Indication ]
operates as a controller, the safety-out in CNTRL First Var. = PV%
should be used instead. Second Var. = TAmb

The cursor automatically moves to Second Variable,


DISPLAY press <EXE> key.
The transmitter display may alternate between two of
the following indications:
/CONF (TAG) XMTR
[ Second Variable ]
OUT Output in milliamperes
Out PV Tamb
*MV% Output in percent PV% Exit
PV Process variable in engineering units
TAmb. Ambient temperature
Move the cursor to OUT and press <EXE> key.
PV % Process variable in percent
*SP% Setpoint in percent /CONF (TAG) XMTR
*SP Setpoint in engineering units Disp. = PV% OUT
*TIME Time for setpoint generator Sensor = Pt100 I 3W
*ER Error in percent (PV% - SP%) PID Module is OFF

The indication will always alternate between the First If you do not want the display to alternate indications,
and the Second Variable. select the same indication in both variables, or select
NONE in the second variable.
* Note:
SENSOR - Sensor
These display items can only be selected in PID mode. Is used to configure the TT301 input for the sensor that
is used and the form of connection.
EXAMPLE:Set the first variable indication to PV%, and Select SENSOR and the display will show:
the second to OUT.

/CONF (TAG) XMTR


/CONF (TAG) XMTR [Sensor Selected]
[ Meter Indication ] Pt100 I 3 wire
Disp.= PV Tamb Change it? Y / N
Change it? y / N

Press <N> if you do not want to change or <Y> to


Press <Y> yes. change. The display will show:

/CONF (TAG) XMTR /CONF (TAG) XMTR


[Choose new Sensor]
Enter your password Rtd Ohm
PSW = _ Tc mV

If a password was programmed to this operation, you > key to see the last option.
Use the <
must enter it, and press <EXE> key.
3.10 TT301 - Operation and Maintenance Instruction Manual

RTD: Resistive Temperature Detectors


Cu10 (GE) VARIABLES UNITS
Ni120 (DIN)
Pt50, 100, 500 (IEC) inH2O, InHg, ftH2O, mmH2O, mmHg,
Pt50, 100 (JIS) psi, bar, mbar, g/cm2, Pa, KPa, Ton,
Configurable for 2, 3, 4 wires or differential PRESSURE ATM
ft3/m, gal/m, I/min, Gal/m, m3/h, gal/s,
Ohm: Linear Resistance Measurement I/s, MI/d, ft3/s, ft3/d, m3/d, Gal/h, Gal/d,
0 - 100 Ohm VOLUMETRIC ft3/h, m3/m, bbl/s, bbl/m, bbl/h, bbl/d,
0 - 400 Ohm FLOW gal/h, Gal/s, I/h, gal/d
0 - 2000 Ohm
SPEED ft/s, m/s, m/h
Configurable for 2, 3 ,4 wires or differential
o
TEMPERATURE C, oF, oR, K
TC:Thermocouples
B, E, J, K, N, R, S, T (NBS) VOLTAGE mv, v
L, U (DIN) VOLUME gal, l, Gal, m3, bbl, bush, Yd3, ft3, In3
Configurable for 2 wires or differential
LEVEL ft, m, in, cm, mm
mV: Linear Voltage Measurement TIME min, sec, h, dia
-6 - 22 mV
-10 - 100 mV MASS gram, Kg, Ton, lb, Shton, LTon
-20 - 500 mV g/s, g/min, g/h, kg/s, kg/m, kg/h, kg/d,
Configurable for 2 wires or differential Ton/m, Ton/h, Ton/d, lb/s, lb/m, lb/h,
MASS FLOW lb/d, Ton/d
Special: Special Sensor
Is used for special sensors, e.g., load cells or SGU, g/cm3, Kg/m3, g/ml, Kg/l, g/I,
TWARD, BRIX, Baum H, Baum L,
resistive position indicators. It turns the DENSITY API, % So/w, % Solv, Ball
TT301 into a transmitter for mass, volume,
position, etc. MISC. Ohm, Hz, mA, %, pH, )s, cPo

SPECIAL 5 caracters
Special Sensor Configuration
Special Sensor is a function that allows sensors whose
characteristics are not stored in the TT301 memory as TABLE 3.1 - Available Special Sensor Unit
a standard to be used.
> key to see all options.
Use the <
Any sensor may be used, provided that the TT301 can
accept the sensors output. The mV and Ohm limitations TYPE - Sensor Type
can be seen in table 3.2. Ohm - Resistive output
mV - Voltage output
The sensors characteristic can be programmed into the
TT301's EEPROM in form of a 16-point table. Such CONNECTION - Sensor Connection
tables are usually made available by the sensor 2 wires
manufacturer but can also be obtained by testing it. 3 wires
4 wires
The special sensor function can not be used at the Differential
same time as the Setpoint generator.
To change the special sensor configuration, select LRL - Lower Range Limit
special in the sensor menu. The minimum lower value that should be
configurable, in reading value, not sensed
input.
/CONF (TAG) XMTR
[ Special Sensor ] URL - Upper Range Limit
Type =Ohm
The maximum upper value that should be
Connection = 3 wires
configurable, in reading value, not sensed
input.
Programming Using Terminal 3.11

Min - Minimum Span To enter the table, select Table (X, Y).
The minimum Span that should be configura-ble, The display will show:
in reading value, not sensed input.
/CONF (TAG) XMTR
Unit - Engineering Unit that should be associated with [Sp. Sensor Table]
the measured variable.
If one of over 100 standard units is selected, it NEW EDIT EXIT
will automatically get its HART protocol code.
This way all supervisory systems supporting - NEW is used to make a new table.
HART can access the unit. - EDIT is used to look at, and change an existing table.
Should a special unit be necessary, select - EXIT is used to escape.
SPECIAL in the UNIT menu. Select the desired function and the display will show:
Table (x,y) - Linearization Table
Table that relates the measured input to /CONF (TAG) XMTR
reading [Sp. Sensor Table]
X = sensed input in Ohm or mV X1 = -22.00 mV
Y1 = 0.00 kg
Y = desired reading
COLD JUNCTION - This Function is used to enable or Use the cursor keys < > and <> to see all the 16 points.
disable the cold junction To change, press the <EXE> key. When the table is
compesation for special mV completed, select SAVE to download the table to the
sensor. transmitter. It is good practice to enter points in the table
beyond the maximum operation limits (LRL & URL). Chose
EXIT - Exits the special sensor configuration. A one point approximately 10% below LRL and another at a
message will prompt you to turn the special minimum of 10% above URL. Should you want to delete a
sensor ON or not. point, press the <DEL> key.
Special Sensor Special Unit Selection COLD JUNCTION (Only for Thermocouple Sensor)
To configure a special unit, select SPECIAL in the UNIT This function allows to turn the Cold Junction
menu. The display will show: Compensation, then the cold junction in the XMTR must be
disable.
/CONF (TAG) XMTR
[Choose new unit] /CONF (TAG)
Special Unit = undef
XMTR
Change it? Y / N
Disp. = PV% None
Sensor = J NBS
Press <N> to exit or <Y> to change, the display will 2W
show:
Cold Junction is
ON
/CONF (TAG) XMTR
To enable or disable the $Cold Junction# move the cursor
Special Unit = _ to $Cold Junction# and press <EXE>. Confirm <Y> to
move the change or <N> to don t move change.
PID Module (Optional)
Enter desired unit, maximum 5 characters. Then press Here the PID module can be switched on turning the
the <EXE> key. TT301 into a controller, or switched off turning it into a
transmitter.
Special Sensor Table
This is where the desired reading as a function of the
/CONF (TAG) XMTR
sensor output is tabulated. The sensor output is entered Disp. = PV% None
as the x-value. Sensor = Pt100 I 3W
PID Module is OFF
The desired reading is entered as y-value with the
limitations: -19999 < = Y < = +19999. Note the following To change mode, move the cursor to "PID Module"and
limitations for the x-values: press <EXE> key. Confirm <Y> to make the change or
<N> not to change.
CONN. 2, 3 or 4 DIFFERENTIAL The transmitter 4-20 mA output can be configuredas
TYPE WIRE (each input) the output of a PID controller.
Where:
Ohm 0 to 2000 0 to 1000
e = PV-SP (direct) or SP-PV (reverse)
V -20 to 500 -10 to 250 SP = Setpoint
PV = Process Variable (pressure, level, flow, etc.)
Kp = Proportion gain
Table 3.2 - Special Sensor Input Range Tr = Integration time
Td = Derivate time
MV = Manipulated Variable (output)
3.12 TT301 - Operation and Maintenance Instruction Manual

Fig. 3.5 – Terminal Control Tree


Programming Using Terminal 3.13

Note that the branch CNTRL now appears in the main


menu, enabling configuration and tuning of the PID
module. /CNTR (TAG) PID
INDIC. SAF_LIMIT
TUNING OP_MODE
MONIT - Monitoring SP.TABLE EXIT
This function allows simultaneous monitoring of 4 of the
transmitters dynamic variables and output current on
the display of the HT2. To activate it, select MONIT in Operation Mode - OP_MODE
the main menu. The display will show:
The "Op. mode" options:

/MONIT (TAG) PID


OUT 7.722mA /CNTR (TAG) PID
PV 23.260 ºC
TIME 0.000min Out Action REVERSE
SP_Tracking is OFF

> key to see the fourth variable. To change


Use the <
any of the variables to another, select it using the > key, the display will show the other
By pressing the <
cursor keys and then, press <EXE>. options:

The display will show: /CNTR (TAG) PID

Power_ON is MANUAL
/MONIT (TAG) PID SP Generator is OFF
[Dynamic Variable]
Primary = PV
Change it? Y / N Direct - Output increases when PV increases.

Reverse - Output decreases when PV increases.


Press <N> to exit, or <Y> to change.
The display will show:
SP tracking - When in MANUAL, the Setpoint follows
the PV. When the controller is switched to AUTO, the
/MONIT (TAG) PID last PV value, before the switching will be assumed as
[Primary Variable] SP.
MV PV Tamb
PV% SP% SP Power ON - When the PID is ON, sets the mode, in
which the controller will return after a power failure:
> key to see all options.
Use the < . Last (mode prior to failure);
. Automatic;
OUT - Shows output in mA. . Manual.
MV - Shows output in %.
PV - Shows Process Variable in the selected SP-Generator - If it is ON, the Setpoint will
engineering unit. automatically change according to a table (recipe)
TAmb - Shows ambient temperature in deg C. programmed in SP.TABLE. If it is OFF, the user has to
PV% - Shows Process Variable in %. configure a Setpoint. The Setpoint generator and
SP% - Shows Setpoint in %. special sensor can not be used at the same time.
SP - Shows Setpoint in the selected engineering
unit.
TIME - Shows the Setpoint generator time in min. INDIC - Indication
ER% - Shows deviation between SP% and PV%. The Setpoint, the Auto/Manual mode and the Output
manual adjustment are achieved by "INDIC" option, that
CNTRL - CONTROL (Optional) stands for indication.
This branch can only be accessed when the PID
module is ON. To activate the PID module see CONF. Press <EXE> when the cursor is blinking under
When the PID module is on, the main menu shows: "INDIC".

/ (TAG) PID
/CNTR (TAG) PID
INFO CONF MONIT
Ti: 1440 SPG: run
CNTRL TRIM MAINT
SP:51.71% PV: 37.82%
ALARM EXIT
MANUAL MV: 20.00%
Select control configuration by moving the cursor to
CNTRL. Note that Ti and SPG are only displayed if the Setpoint
Press <EXE> key, the display will show: Generator is ON.
3.14 TT301 - Operation and Maintenance Instruction Manual

In order to make any change in the SP, MV, Ti or the High Limit - Is the maximum allowable output (in %).
operating status, just move the cursor to the desired
item and press <EXE>. E.g., for MV, the display will SP-TABLE - Setpoint table
show: When the Setpoint generator is on, it will change the
Setpoint automatically according to a table (recipe). To
configure this table select SP-TABLE in the menu. The
display will show:
/CNTR (TAG) PID

Output = 20.00 /CNTR (TAG) PID


Change it ? Y / N [Set Point Table]

NEW EDIT EXIT


Type <Y>, enter the desired new output value
(remember that the control must be in MANUAL) and
press <EXE>.The output will ramp up or down to the - NEW is used to make a new table.
new value. The ramp adjustment is done at "SAF_LIMIT - EDIT is used to look at, and make changes in an
- OUT.CHG/S". existing table.
- EXIT is used to escape.
Note that when the Setpoint is changed, it is only the
current operating Setpoint that is changed. After a Select the desired function and the display will show,
power-off it will be lost unless you , at the prompt e.g.:
"SAVE Y/N", confirm <Y>. This stores the new setpoint
in a non-volatile memory. This is done to reduce the
number of changes operated in a certain memory /CNTR (TAG) PID
[Set Point Table]
position of the EEPROM. The maximum number of
TI1 = 6.00min
changes is somewhere above 10.000. SP1 = 75.00%

TUNING
Select the option TUNING and press <EXE>. The Note that the time is always in minutes and the
display will show: Setpoint in %.

> and <


Use the cursor keys < > to see all 16 points.
/CNTR (TAG) PID To change, press the <EXE> key. When the table is
Kp = 1.00 completed, select SAVE to download the table to the
Tr = 0.10min/rep transmitter.
Td = 0.00sec
TRIM
Move the cursor to the desired parameter and make the The TRIM function is used to make the reading comply
necessary changes. with the user's resistance, voltage or current standards.

The Proportional Action is gain, not proportional band. To proceed with the TRIM adjustment, the Control Loop
Range 0-100. should be in MANUAL to avoid bumps to the
process.
The Integral Action is minutes per repetition. Range 0-
999. When the function TRIM is selected, the display will
show:
The Derivative constant is in seconds. Range 0-999.
The derivative gain is fixed in 0.1.
/TRIM (TAG) XMTR
The integral and derivative actions can be canceled by
CURRENT READING
setting Tr and Td equals to 0. EXIT

SAF. LIMITS - Control Limits There are two options:


This option enables the adjustment of the following
parameters of the controller: Output current and Input reading.

Safety out - Is the output after a power interruption or Current TRIM (4-20 mA Output)
during a failure. When the microprocessor generates a 0% signal, the
Digital to Analog Converter and associated electronics
Out Chg/s - Is the maximum allowable rate-of-change are supposed to deliver a 4 mA output. If the signal is
of the output. 100%, the output should be 20 mA.

Low Limit - Is the minimum allowable output (in %).


Programming Using Terminal 3.15

Fig. 3.6 – Terminal Trim Tree

There may be differences between the factory current


standard and your plant current standard. In this case, /TRIM (TAG) XMTR
[ 4mA Current Trim ]
you may use the current TRIM adjustment as follows:
Enter line current
I (mA) = _
When TRIM is performed, the reference should be
connected direct to terminals 2 and 3 with shortest
possible wires. The transmitter should be configured for Type 4.012 and <EXE>.
2-wire sensor connection.
The display will repeat the question if the current is
 Select the CURRENT option. The display will show: correct or not. Answer it properly until the reading is
4.00 mA. The same procedure shall be applied for the
20 mA.
/TRIM (TAG) XMTR
Reading TRIM (Input)
4mA 20mA EXIT There may be differences between the factory
standards for resistance and mV and your plant
standards. In this case, you may use the READING
 Select which point should be calibrated, for example trim adjustment. The reading trim adjustment is
4 mA). The display will show: composed of ZERO, GAIN and FACTORY options. The
ZERO and GAIN trim should be done at the LOWER
and UPPER RANGE VALUE respectively.
/TRIM (TAG) XMTR
[ 4mA Current Trim ] ZERO - allows matching the value of resistance or mV
Insert multimeter at lower range value. The ZERO trim adjustment
on line / test point doesn t interfere in the GAIN trim. GAIN - allows
matching the value of resistance or mV at upper range
 Make sure the multimeter is properly installed. It value. FACTORY - recovers the ZERO and GAIN
should have an accuracy better than 0.02%. factory trim.
To proceed with zero trim, connect a resistance or mV
After a while:
standard with accuracy better than 0.02%. Select
READING, followed and the display will show:
/TRIM (TAG) XMTR
[ 4mA Current Trim ] /TRIM (TAG) XMTR
Is the line current [Zero Trim]
4.00 mA Y / N Input is 138.48 Ohms
Is it correct Y/N
If the reading is 4.00 mA, answer Yes <Y>.
If the reading is, for example, 4.012 mA, press <N>
(No).
3.16 TT301 - Operation and Maintenance Instruction Manual

Fig. 3.7 – Terminal Maintenance Tree

Suppose the correct input is 138.5 Ohm, then the MAINTENANCE - MAINT
reading is wrong. To change it, press <N> and the This function allows the change of the passwords and
display will show: the reading of the OPERATION COUNTER.

FORMAT
/TRIM (TAG) XMTR
[ Zero Trim ]
FORMAT/CODE # shows the "Ordering Code"
according to the specification of the customer.
(Ohms)=-
EXAMPLE:

.
Enter <1>, <3>, <8>, < >, <5> and then, press the
TT301 1 1 - 1 0 - 0
<EXE> key. The transmitter is now calibrated to the
new reference.
TT301 Temperature Transmitter; with Digital Indicator
To proceed with gain trim, connect a resistance or mV (1); with Carbon Steel Bracket (1); with Local Adjust (1);
standard with accuracy better than 0.02%. Select 1/2" NPT Electrical Connection (O); without other
READING followed GAIN and the display will show: Special Features (O).

SERIAL NUMBER
/TRIM (TAG) XMTR Three serial numbers are stored. The first is the Device
[Gain Trim] ID. This number is unique to every circuit and can not
Input is 264,3 Ohms be changed.
Is it correct Y/N
Sensor serial number. The serial number of the sensor
Suppose the correct input is 264,11 Ohm, then the connected to the TT301 or the sensor that it was
reading is wrong.To change it, press <N> and the calibrated for, may be entered here.
display will show: The format item also allows storage of the assembly
serial number in the main board.
/TRIM (TAG) XMTR Note that the assembly serial number is written on the
[Gain Trim]
identification plate. For each transmitter, this number
(Ohms)=-
can be changed, if necessary.

CHANGE COUNTER - OP_COUNT


.
Enter <2>, <6>, <4>, < >, <1>, <1> and then, press Every time a change is made, there is an increment in
the respective change counter.
the <EXE> key. The transmitter is now calibrated to the
new reference. Should you ever want to recall the
The monitored items are:
original factory calibration trim, select FACTORY.
- LRV/URV (Any Change in range).
Programming Using Terminal 3.17

Fig. 3.8 – Terminal Alarm Tree

- FIXED (Any activation of the loop test fixed current). At PASSWORD you can assign passwords to the levels
1, 2 and 3. These password can be changed by anyone
- Trim_4mA (Any trim in 4 mA). that knows password level 3. In order to cancel a
password, type six times SPACE.
- Trim_20mA (Any trim in 20 mA).
Password Level 3 is hierarchically superior to password
- Trim Reading (Any change in location or data). level 2, which is superior to level 1.

- BOUT (Any change UP to DOWN scale or DOWN to


ATTENTION:
UP scale).
In case of loss or forgetfulness of passwords, contact
- SENSOR. Smar Service.

- OP-MODE (Any change XMTR to PID or PID to CONFIGURATION LEVEL


XMTR). This function allows the user to modify the default
- Local Adjustment Protection (Any change in password level for each type of operation. This
WR_PROT).
configuration is stored in the TT301 EEPROM.
- Communication Protection (Any change in
WR-PROT - WRITE PROTECT
WR_PROT).
This command is used to protect the transmitter
configuration. All data except Message, Tag, Descriptor
- Multidrop.
and Date are Write protected.
- PASSWORD (Any change of PASSWORD or
Write protection can be done for the communication
CONF_LEVEL).
and/or the local adjustment.
PASSWORDS ALARM - ALARM
There are three levels of passwords. They are used to This function affects the dual alarm. The actions and
restrict access to certain operations in the trip levels can be configured independently for alarm 1
programming. and 2. It also allows monitoring of alarm status and
acknowledgement of alarms. Alarm 0 indicates non
The branches for which passwords can be configured configurable alarms such as burnout.
for, are:
When the ALARM function is selected, the display will
MONIT
show:
INFO
CONF
CNTRL /ALARM (TAG) XMTR
TRIM AL0: OFF
AL1: OFF
MAINT
AL2: OFF
LOAD
ALARM
To enable, e.g., Alarm 1, make sure the cursor is
At the default condition no passwords are required. blinking under "AL1" and then, press the <EXE> key.
The display will show:
Each operation branch may have a password level
assigned. For example, the default password level is 0
but you can set, for example, INFO with level 1 and /ALARM (TAG) XMTR
MAINT with level 3. These levels can be changed at Ack Action Level
CONFIGURATION LEVEL (see below). Exit
3.18 TT301 - Operation and Maintenance Instruction Manual

Acknowledge - Acknowledges an alarm, this will turn


off the "ACK" on the transmitter /ALARM (TAG) XMTR
display indicating that the alarm has AL0: NO ALARM
AL1: >75.00% ACK
been noted. AL2: NO ALARM
Action - Configures the operation mode of the alarm:
off, low or high. "ACK" indicates that alarm now is acknowledged.
Limits - Configures the level at which the alarm will ON-LINE MULTIDROP OPERATION
trip. Multidrop connection is formed by several transmitters
Configuring Alarms connected a single communication transmission line.
Put the cursor blinking under "Action" and press the Communication between the host and the transmitters
<EXE> key. The display will show: takes place digitally with the transmitters analog output
desactivated (XMTR mode), or with the analog output
activated (PID mode).
/ALARM (TAG) XMTR
The communication with the transmitters and the host
(HT2, DCS, Data Acquisition System or PC) can be
Low High Off
done with a Bell 202 Modem using Hart Protocol. Each
transmitter is identified by a unique address from 1 to
Low - The alarm is activated when PV is below the
15.
trip level - decreasing signal.
The TT301 is factory set to address 0, that means a
High - The alarm is activated when PV is above the
non multidrop operation mode, allowing transmitter to
trip level - increasing signal.
communicate with the Hand-Held Terminal,
Off - The alarm is disabled. superimposing the communication on the 4-20 mA
signal. To operate in multidrop mode, the transmitter
Select the desired option and press <EXE> key. address must be changed to a number from 1 to 15.
To configure the trip level, put cursor under the "Level" This change deactivates the 4-20 mA analog output
option in the menu and press the <EXE> key. The sending it to 4 mA (XMTR mode), or keeps the 4-20
display will show: mA operation when the transmitter is configured for
PID operating mode.
/ALARM (TAG) XMTR When intrinsic safety is a requirement, special attention
must be paid to the entity parameters allowed to that
Enter New Limit (%) area:
0<= Limit =<100%
n

/ALARM (TAG) XMTR Ca ≥ ∑ Cj j + Cc


j =1
Enter New Limit (%)
n
La ≥ ∑ Li j + Lc
AL1: _

e.g., if 75% is desired, key-in <7>, <5> followed by j =1


<EXE> key.
ACKNOWLEDGING ALARMS
If the alarms are enabled and an alarm condition
Voc ≤ min V max j [ ]
appears, the display will show, e.g.:

/ALARM (TAG) XMTR


I sc ≤ min Im ax j[ ]
AL0: NO ALARM
AL1: >75.00% ACK
AL2: NO ALARM
Where:
Indicating that alarm 1 is on, since PV is larger than Ca, La - Allowable Capacitance and Inductance
75%, which in this case is the limit. The "NACK"
indicates that the alarm is not yet acknowledged. To Cij, Lij - Non protected internal Capacitance/Induc-
acknowledge, choose consecutively "AL1" followed by tance of transmitter j (j = up to 15)
"Acknowledge" from the menus and the display will Cc, Lc - Cable capacitance and Inductance
show:
Voc - Barrier open circuit voltage
/ALARM (TAG) XMTR Isc - Barrier short circuit current
Acknowledging AL1 Vmaxj - Maximum allowable voltage to be applied to
the instrument j
Imaxj - Maximum allowable current to be applied to
the instrument j
To operate in multidrop mode, it is necessary to see
Programming Using Terminal 3.19

which transmitters are connected on the same line.


This operation is called polling, and it is done auto-
matically as soon as ON-LINE-MULTIDROP option is MDROP
executed.
AD_0

WARMING:
AD_0, this is the address of the only transmitter on the
The current output will be send to 4 mA as soon as
line. If there were more, they would be listed as well,
the transmitter address is changed (it does not occur
select it by pressing the <EXE> key. The display will
when the transmitter is configured for PID Operation
show:
Mode).

CONFIGURATION THE TT301 FOR MULTI- MDROP

DROP Present Address = 0


First, connect the transmitter that shall be reconfigured Change it Y / N
for multidrop operation to the HT2, only one transmitter
at the time.
If the <N> key is pressed, configuration will continue
as in "ON_LINE_SINGLE_UNIT" and the address will
A few seconds after selecting "TT301" from the menu
remain 0. To change the address, press the <Y> key.
the following menu will be displayed:
The display will show:

SMAR-HT2
ON_LINE_SINGLE_UNIT MDROP
ON_LINE_MULTIDROP Choose New Address
EXIT AD_1 AD_2 AD_3
AD_4 AD_5 AD_6

With the cursor blinking under the "ON_LINE


These are the available "free" addresses, more can be
MULTIDROP" option, press the <EXE> key. The display
viewed using the cursor keys. Select the desired
will show:
address and press the <EXE> key. The transmitter will
now have that address. Configuration continues with a
MDROP new search for transmitters on the line, and you will
note that the transmitters address has been changed.
Polling Address X
Now the transmitter is ready to be connected to a
multidrop line. Note that no other transmitters on the
same line - regardless of make, model and type -
should have the same address.

CONFIGURATION IN MULTIDROP MODE


In order to talk to a specific transmitter in multidrop
mode using the HT2, select "ON_LINE_MULTIDROP".
After the HT2 has identified the transmitters on the line
select the desired transmitter's address from the
menu. When prompted "Present address..." "...Change
it Y/N", press <N>. and <EXE> key to proceed. The
display will briefly show:

>>>> SMAR LD301 <<<<

Pressure XMTR
version 2.XX

After this, the same menu as seen when in the


ON_LINE_SINGLE_UNIT mode is displayed.

Configuration can now be done in the same way as for


a single unit.
Fig. 3.9 – On-Line Multidrop Option

The HT2 now searches all addresses and after a few


seconds, the display will show:
3.20 TT301 - Operation and Maintenance Instruction Manual
Programming Using Local Adjustment 4.1

4 PROGRAMMING USING LOCAL ADJUSTMENT


THE MAGNETIC TOOL Transmitter mode:

Smar's magnetic tool is the second man-machine Z - It is used to select the Lower Range Value.
interface, it compromises the advantage of the powerful S - It is used to select the Upper Range Value.
HT2 and the convenience of the "good-old" screwdriver.
They work exactly as the adjustment with reference of
If the transmitter is fitted with a display, and is the HT2 controller mode for transmitters with digital
configured for complete - local - adjustment (using display.
internal jumper) the magnetic tool is almost as powerful
as the HT2, eliminating the need for a HT2 in most Controller mode:
basic applications.
Z - Moves the options (OPERATION and BATCH).
If the transmitter is not fitted with a display, or is S - Activates the selected function.
configured for simple - local - adjustment (using internal
jumper) the adjustment capability is reduced to If "Complete Local Adjustment" is selected by the
reranging. jumpers position, the switches have the following
functions:
To select the function mode of the magnetic switches
configure the jumpers located at the top of the main Z - Moves the options.
circuit board as indicated below: S - Activates the selected function.

Local Adjustment Disabled


RERANGING USING THE LOCAL ZERO AND SPAN
ADJUSTMENTS IN SIMPLE MODE
Local Adjustment Disabled
It is possible to rerange the transmitter with the local
adjustment switches located on the top of the electronic
Simple Local Adjustment housing. The switches work like the adjustment "with
Enabled reference" for the HT2.

In order to make these adjustment, the instrument must


Complete Local Adjustment be configured as "transmitter" (XMTR).
Enabled
To adjust the zero of the transmitter, proceed as
follows:

 Apply the Lower Value, signal.


 Wait for the process to stabilize.
 Insert the magnetic tool in the ZERO adjustment
hole. (see Fig. 4.2)

Fig. 4.1 – Local Adjustment Switches

The transmitter has, under the identification plate, holes


for two magnetic switches activated by the magnetic
tool.

The holes are marked with Z (Zero) and S (Span). If


"Simple Local Adjustment" is selected by the jumpers
position, the switches have the following functions:
Fig. 4.2 – Local Zero and Span Adjustment
4.2 TT301 - Operation and Maintenance Instruction Manual

Fig. 4.3 - Local Adjustment Programming Tree – Main Menu

 Wait 2s. The transmitter should be reading 4 mA. OPER-(OPERATION) Is the option where the operation
 Remove the tool. related parameters of the
controller are configured: Auto/
As the reranging with reference, the span is maintained. Manual, Setpoint, Manual output.
In case you want to change the span, proceed as
follows: BATCH Is the option where the Setpoint generator
related functions are operated: on/off, Pause,
 Apply the Upper Value, signal. Reset and time adjustment.
 Wait for the process to stabilize.
 Insert the magnetic tool in the SPAN adjustment TUNE-(TUNING) Is the option where the PID-Algorithm
hole. related parameters are configured:
 Remove the tool. Action, Kp, Tr, and Td.

Note that when zero adjustment is done, the URV can CONF-(CONFIGURATION) Is the option where the
not be pushed above the URL. In this case, span is not output and display rela-
maintained. ted parameters are con-
figured: unit, primary and
COMPLETE LOCAL ADJUSTMENT secondary display, Lower
and Upper Value, dam-
LOCAL PROGRAMMING TREE ping, sensor type and
The programming tree is a tree-shaped structure with a operation mode.
menu of all available software resources, as shown in
Figure 4.3. ESC-(ESCAPE) Is the option used to go back to
normal monitoring mode.
The Local Programming mode is entered by activating
switch (Z). In transmitter mode, only the configuration
branch of the tree is applicable, thus the first menu
function will be UNIT.

WARNING:
When programming using local adjustment, the transmitter
will not prompt "Control loop should be in manual!" as it
does when programming using the HT2. Therefore it is a
good idea, prior to configuration, to switch the loop to
manual. And do not forget to return to auto after
configuration is completed
Programming Using Local Adjustment 4.3

OPERATION [OPER]

Fig. 4.4 – Local Adjustment Operation Tree

Z: Moves to the next branch Z: Moves to the ACK function.


(BATCH).
S: Decreases the control output
S: Enters the OPERATION until the magnetic tool is removed
branch, starting with function or the lower output limit is
AUTO/MANUAL. reached.

Auto/Manual (A/M) Acknowledge (ACK)

Z: Moves to the SETPOINT


INCREASE function. Z: Moves the SAVE function.

S: Toggles controller status, S: Acknowledges all alarms.


Automatic to Manual or Manual to
Automatic. A and M indicates
status.
Save (SAVE)

Setpoint Adjustment (SP) Z: Moves to ESCAPE of the


operation menu.
Z: Moves to the SETPOINT
DECREASE function. S: Saves the setpoint and manual
output values in the transmitter
S: Increases the setpoint until the EEPROM, for use after power-on.
magnetic tool is removed or
100% is reached.
Escape (ESC)

Z: Moves to the MANIPULATED Z: Moves to the AUTO/ MANUAL


VARIABLE ADJUSTMENT func- function.
tion.
S: Escapes to the MAIN menu.
S: Decreases the setpoint until
the magnetic tool is removed or
0% is reached.

Manipulated Variable Adjustment (MV)

Z: Moves to the MANIPULATED


VARIABLE DECREASE func-
tion.

S: Increases the control output


until the magnetic tool is removed
or the upper output limit is
reached.
4.4 TT301 - Operation and Maintenance Instruction Manual

BATCH [BATCH]

Fig. 4.5 – Local Adjustment Batch Tree

Z: Moves to the TUNING branch. Time (TIME)

S: Enters the BATCH branch, Z: Moves to the time decrease


starting with function SPGEN function.
on/off.
S: Increases the time register for
the setpoint generator until the
magnetic tool is removed or
Setpoint Generator On/Off (SPGEN) 19999 min. is reached.

Z: Moves to the SPGEN Pause/


Run function. Z: Selects ESCAPE of the
BATCH menu.
S: Toggles setpoint generator.
On to Off or Off to On. S: Decreases the time register for
the setpoint generator until the
magnetic tool is removed or the
time-base register is zero.
Setpoint Generator Pause/Run (SPGEN)
Escape (ESC)
Z: Moves to the RESET function.
Z: Moves to the SPGEN on/off
S: Toggles setpoint generator function.
mode, pause to run or run to
pause. S: Escapes to the MAIN menu.

Reset (RESET)

Z: Moves to the TIME INCREASE


function.

S: Resets the time register of the


setpoint generator to 0.
Programming Using Local Adjustment 4.5

TUNING [TUNE]

Fig. 4.6 – Local Adjustment Tuning Tree

Z: Moves to the CONFIGURA- Td - Adjust (TD)


TION branch.
Z: Moves to the derivative time
S: Enters the TUNING branch, decrease function.
starting with function KP-
ADJUSTMENT. S: Increases the derivative time
until the magnetic tool is removed
or 999 seconds are reached.
Kp - Adjust (KP)

Z: Moves to the proportional gain Z: Moves to the ACTION function.


decrease function.
S: Decreases the derivative time
S: Increases the proportional gain until the magnetic tool is removed
until the magnetic tool is removed or 0 second is reached.
or 100 is reached.

Action (ACT)
Z: Moves to the TR_ADJUST-
MENT function. Z: Moves to the SAVE function.

S: Decreases the proportional S: Toggles the action direct to


gain until the magnetic tool is reverse or reverse to direct.
removed or 0.0 is reached. The far-right character of the
unit/function-field indicates the
present mode:
Tr - Adjust (TR) D = direct action
R = reverse action
Z: Moves to the integral time
decrease function. Save (SAVE)

S: Increases the integral time Z: Moves to the ESCAPE to


until the magnetic tool is removed TUNING menu.
or 999 minutes are reached.
S: Saves the KP, TR and TD
constants in the transmitter
Z: Moves to the TD_ADJUST EEPROM.
function.
Escape (ESC)
S: Decreases the integral time
until the magnetic tool is removed Z: Moves to the KP-ADJUST-
or 0 minute is reached. MENT function.

S: Escapes to the MAIN menu.


4.6 TT301 - Operation and Maintenance Instruction Manual

Fig. 4.7 – Local Adjustment Configuration Tree


Programming Using Local Adjustment 4.7

CONFIGURATION [CONF]
DISPLAY
Z: Selects ESCAPE of the DESCRIPTION
d1-
monitoring mode. SP% Setpoint (%)
PV% Process Variable (%)
S: Enters the CONFIGURATION
branch, starting with function MV% Output (%)
UNIT. ER% Error (%)
 Nothing
TI SP generator time
Unit (UNIT)
CU Output (mA)
Z: Moves to the DISPLAY-1 PV Process Variable (eng. unit)
function. SP Setpoint (eng. unit)
ESC -escape-
S: Starts selection of engineering
unit for process variable and
setpoint indication. After The desired variable is activated using (A). Escape
activating (S), you can move leaves primary variable unchanged.
around the options available in
the table below by activating (Z). NOTE
In TRANSMITTER mode, only PV%, CU, PV and "none" are
DISPLAY DESCRIPTION selectable.
C Degree Celsius
F Degree Fahrenheit
Display 2 (LCD_2)
R Degree Rankine Z: Moves to the ZERO ADJUST
K Kelvin function.
mV millivolt
Ohm Ohm
S: Starts selection of variable to
be indicated as secondary
SPEC Special Unit display.
NO No Unit
ESC -escape- The procedure for selection is the
same as for DISPLAY_1, above.
The desired unit is activated by using (S). Escape
leaves unit unchanged. Lower Range Value Adjustment without Reference
(LRV)

NOTE Z: Moves to the LRV decrease


See special sensor in Section 3 for more information on function.
“special-unit”
S: Increases the Lower Value
until the magnetic tool is removed
Display 1 (LCD_1)
or the maximum for the Lower
Value is reached.
Z: Moves to the DISPLAY-2
function.
Z: Moves to the URV ADJUST-
S: Starts selection of variable to MENT function.
be indicated as primary display.
After activating (S), you can move S: Decreases the Lower Value
around the options available in
until the magnetic tool is removed
the following table by activating
or the minimum for the Lower
(Z).
Value is reached.
4.8 TT301 - Operation and Maintenance Instruction Manual

Upper Range Value Adjust without Reference (URV)


Z: Moves to the SENSOR
Z: Moves to the URV decrease function.
function.
S: Increases the Upper Value
S: Increases the Upper Value (Decreases output) until the
until the magnetic tool is removed magnetic tool is removed or the
or the maximum for the Upper maximum for the Upper Value is
Value is reached. reached.

Reranging using the ZERO and SPAN items in the


Z: Moves to the ZERO AD- menu is equivalent to the applied rerange on the HT2.
JUSTMENT function. The range values are adjusted relative to the applied
input. The value in the display is the applied
S: Decreases the Upper Value temperature in percentage of the range. Changing the
until the magnetic tool is removed lower value shifts the upper value too, maintaining the
or the minimum for the Upper span. Changing the upper value does not affect the
Value is reached. lower value. For example, if you want 4 mA (0%) for the
applied input, adjust until the display reads 0%.
Reranging using the LRV and URV items in the menu Likewise, if you want 20% (7.2 mA), adjust until the
is the same as the keyboard rerange on the HT2. No display shows 20%.
input has to be applied, the range is set independent of
applied input. Adjust the value indicated on the display Sensor (SENS)
to the desired range value. Changing one does not
affect the other. Z: Moves to the OPERATION
MODE function.
Zero Adjust with Reference (ZERO)
S: This function is protected by a
Z: Moves to the ZERO decrease "password", when prompted
function. PSWD activate (S) 2 times to
proceed with sensor selection.
S: Decreases the Lower Value
(Increases output) until the After activating (S), you can move around the options
magnetic tool is removed or the available in the following table by activating (Z).
minimum for the Lower Value is
reached. SENSOR SELECTION TABLE
Z: Moves to the SPAN ADJUST DISPLAY DESCRIPTION
function. mV-1 -6 to 22 mV
mV-2 -10 to 100 mV
S: Increases the Lower Value
(Decreases Output) until the mV-3 -20 to 500 mV
magnetic tool is removed or the Ohm-1 0 to 100 Ohm
maximum for the Lower Value is Ohm-2 0 to 400 Ohm
reached.
Ohm-3 0 to 2000 Ohm
Span Adjust with Reference (SPAN) RTD RTD
TC Thermocouple
Z: Moves to the SPAN decrease SPEC Special Sensor
function.
ESC - escape -
S: Decreases the Upper Value
(Increases Output) until the
magnetic tool is removed or the
minimum for the Upper Value is
reached.
Programming Using Local Adjustment 4.9

For all sensors, further selections must be done to Operation Mode (MODE)
determine the specific type and connection. Move
around the available options - listed in the tables below Z: Moves to the SAVE function.
- using (Z).
S: This function is protected by a
RTD SELECTION TABLE "password", when prompted
PSWD activate (S) 2 times to
DISPLAY DESCRIPTION proceed.
Cu-10 Cu10
After entering the "password", you can move around the
Ni 120 Ni 120 options listed in the table below using (Z). In order to
select the desired option, activate (S).
IE50 IEC Pt50

IE100 IEC Pt100 OPERATION MODE


JI 50 JIS Pt50 DISPLAY DESCRIPTION
JI 100 JIS Pt100 XMTR Transmitter

IE500 IEC Pt500 CNTRL Controller (Optional)

ESC - escape - Save (SAVE)

Z: Selects ESCAPE to
OHMS & RTD CONNECTION CONFIGURATION mode.
DISPLAY DESCRIPTION S: Saves lower value and upper
2 WIRE 2 - wire value.
3 WIRE 3 – wire
4 WIRE 4 – wire
DIFF Differential Escape (ESC)
ESC - escape -
Z: Moves to the UNIT function.

S: Escapes to the MAIN menu.


THERMOCOUPLE - TYPE
DISPLAY DESCRIPTION
B_NBS NBS type B
E_NBS NBS type E
J_NBS NBS type J ESCAPE [ESC]
K_NBS NBS type K
N_NBS NBS type N
Z: Selects OPERATION branch.
R_NBS NBS type R
S_NBS NBS type S S: Escapes to MONITOR mode.
T_NBS NBS type T
L_DIN DIN type L
U_DIN DIN type U
ESC - escape -
4.10 TT301 - Operation and Maintenance Instruction Manual
Maintenance Procedures 5.1

5 MAINTENANCE PROCEDURES
GENERAL Section 1, Figures 1.4, 1.5 and 1.8.

SMAR TT301 intelligent temperature transmitters are ERROR MESSAGES


extensively tested and inspected before delivery to the
end user. Nevertheless, during their design and When communicating using the HT2 the user will be
development, consideration was given to the possibility informed about any problem found by the transmitters
of repairs by the end user, if necessary. self diagnostics.
In general, it is recommended that the end user do not
try to repair printed circuit boards. Instead he should As an example, the HT2 display may show:
have spare circuit boards, which may be ordered from
SMAR whenever necessary.
> OUTPUT SATURATED <
DIAGNOSIS WITH SMAR HAND-HELD TERMINAL

Should any problem be noticed related to the


transmitter's output, investigation may be carried out by
the HT2, as long as power is supplied and The messages are always alternated with the
communication and the processing unit are operating information on the top line. The table below lists the
normally. error messages. Refer to trouble shooting for more
details on corrective action.
The programmer should be connected to the transmitter
in accordance with the wiring diagram shown on

DIAGNOSTICS WITH THE HT2

DIAGNOSTIC MESSAGES POTENTIAL SOURCE OF PROBLEM


PARITY ERROR • Excessive noise or ripple.
OVERRUN ERROR • Excessive noise or ripple.
CHECK SUM ERROR • Excessive noise or ripple.
FRAMING ERROR • Excessive noise or ripple.
• The line resistance is not in accordance with load curve.
• Transmitter not powered.
• Interface not connected.
• Transmitter configured in Multidrop mode being accessed by ON
NO RESPONSE
LINE SINGLE UNIT.
• Transmitter reversely powered (polarity is reversed).
• Interface damaged.
• Power supply or battery voltage of the HT2 lower than 9 V.
LINE BUSY & Other device using the line.
• Software version not compatible between HT2 and transmitter.
CMD NOT IMPLEMENTED • HT2 is trying to carry out a TT301 specific command in a
transmitter from another manufacturer.
• Transmitter carrying out on important task. e.g., Local
TRANSMITTER BUSY
Adjustment.
COLD START • Start-up or Reset due to power supply failure.
• Output in Constant Mode.
OUTPUT FIXED
• Transmitter in Multi-drop mode.
• Primary variable out of calibrated Span (Output current in 3.90 or
OUTPUT SATURATED
21.00 mA, XMTR mode only).
• Temperature out of operating limits.
SV OUT OF LIMITS
• Temperature sensor damaged.
• Input signal out of operating limits.
• Sensor damaged.
PV OUT OF LIMITS
• Transmitter with false configuration.
• PV out of range limits (see table).
5.2 TT301 - Operation and Maintenance Instruction Manual

TROUBLESHOOTING WITH TRANSMITTER Probable Source of Trouble:

 Symptom : NO LINE CURRENT  Transmitter Connection

Probable Source of Trouble: & Check if the sensor is correctly connected to the
TT301 terminal block.
 Transmitter Connections & Check if the sensor signal is reaching the TT301
terminal block by measuring it with a multimeter at
& Check wiring polarity and continuity. the transmitter-end. For mV and thermocouples test
& Check for shorts or ground loops. can be done with connected and disconnected to the
transmitter.
 Power Supply  Sensor
& Check power supply output. The voltage at the TT301 & Check the sensor operation; it shall be within its
terminals must be between 12 and 45 Vdc, and the characteristics.
ripple less than 0.4V. & Check sensor type; it shall be the type and standard
that the TT301 has been configured to.
 Electronic Circuit Failure & Check if process is within the range of the sensor and
the TT301.
& Check the main board for defect by replacing it with
a spare one. NOTE:

Symptom : NO COMMUNICATION A 21.0 or 3.9 mA current in XMTR mode indicates burnout.

Symptom : INCORRECT OUTPUT


Probable Source of Trouble:
Probable Source of Trouble:
 Terminal Connections
 Transmitter Connections
& Check terminal interface connections. & Check power supply voltage. The voltage at the
& Check if the interface is connected to the points TT301 terminals must be between 12 and 45V, and
[COMM] and [-] or in the line between the transmitter ripple less than 0.4V.
and the load resistor. & Check for intermittent short circuits, open circuits
& Check if the interface is model IF2 (for HART and grounding problems.
Protocol).
 Noise, Oscillation
 Transmitter Connections & Adjust damping
& Check grounding of the transmitters housing, extra
& Check if connections are as per wiring diagram. important for mV and thermocouple input.
& Check line resistance; it must be equal to or greater & Check the terminal block for moisture.
than 250 Ohm, between the transmitter and the & Check that the shielding of the wires between
power supply. sensor/transmitter and transmitter/panel is grounded
only in one end.
 Power Supply
 Sensor
& Check output of power supply. The voltage at the
& Check the sensor operation; it shall be within its
TT301 terminals must be between 12 and 45V, and
characteristics.
ripple less than 0.4V.
& Check sensor type; it shall be the type and standard
 Electronic Circuit Failure
that the TT301 has been configured to.
& Locate the failure by alternately replacing the  Electronic Circuit Failure
transmitter circuit and the interface with spare parts.
& Check the integrity of circuit replacing it with a spare
 Transmitter Address one.
 Calibration
& In On Line Multidrop item check if the address is "0".
& Check calibration of transmitter.
Symptom : CURRENT OF 21.0 mA OR 3.9 mA
Maintenance Procedures 5.3

DISASSEMBLY PROCEDURE REASSEMBLY PROCEDURE


Refer to Fig. 5.1 - "TT301 Exploded View". Make sure & Put input board (7) into housing (8).
to disconnect power supply before disassembling the & Anchor input board with its screws (6).
transmitter. & Put main board (5) into the housing, ensuring all inter
connecting pins are connected.
Sensor & Put display (4) into the housing, observing the four
If the sensor is mounted on the transmitter, first mounting positions (see Fig. 5.2) "SMAR" should
disconnect the wires in order to prevent the wires from
point in the direction desired as UP.
breaking. To access the terminal block, first loose the
& Anchor main board and display with their screws (3).
cover locking screw on the side marked "Field
& Fit the cover (1) and lock it using the locking screw
Terminals", then unscrew the cover. (13).
Electronic Circuits INTERCHANGEABILITY
The main board (5) and input board (7) are matched
Calibration data is stored in the EEPROM of the main
pairs and must be changed together and not mixed with
board, hence READING TRIM must be done if main-
others.
board or input board has been changed.
To remove the circuit boards (5 and 7) and display (4),
RETURNING MATERIALS
first loose the cover locking (14) on the side not
marked "Field Terminals" then unscrew the cover (1). Should it become necessary to return the transmitter
and/or Hand-Held Terminal to SMAR, simply contact
WARNING: your local agent or SMAR office, informing the defective
instrument's serial number, and return it to our factory.
The board has CMOS components which may be damaged by
electrostatic discharges. Observe correct procedures for In order to expedite analysis and solution of the
handling CMOS components. It is also recommended to store problem, the defective item should be returned with a
the circuit boards in electrostatic-proof cases.
description of the failure observed, with as much details
as possible. Other information concerning to the
Loosen the two screws (3) that anchors the display and
instrument operation, such as service and process
the main circuit board. Gently pull out the display, and
conditions, is also helpful.
then the main board (5). To remove the input board (7),
first unscrew the two screws (6) that anchors it to the
housing (8), gently pull out the board.

Fig. 5.1 – Exploded View


5.4 TT301 - Operation and Maintenance Instruction Manual

SPARE PARTS LIST FOR TRANSMITTER

DESCRIPTION OF PARTS POSITION CODE


HOUSING, Aluminum (NOTE 1)
. 1/2 - 14 NPT 8 214-0200
. M20 x 1.5 8 214-0201
. PG 13.5 DIN 8 214-0202
HOUSING, 316 SS (NOTE 1)
. 1/2 - 14 NPT 8 214-0203
. M20 x 1.5 8 214-0204
. PG 13.5 DIN 8 214-0205
COVER
. Aluminum 1 and 13 204-0102
. 316 SS 1 and 13 204-0105
COVER WITH WINDOW FOR INDICATION
. Aluminum 1 204-0103
. 316 SS 1 204-0106
COVER LOCKING SCREW 14 204-0120
EXTERNAL GROUND SCREW 11 204-0124
IDENTIFICATION PLATE FIXING SCREW 15 204-0116
DIGITAL INDICATOR 4 214-0108
TERMINAL HOLDER INSULATOR 10 214-0220
MAIN AND INPUT CIRCUIT BOARD ASSEMBLY 5&7 214-0221
0-RINGS (NOTE 2) Cover, BUNA-N 2 204-0122
TERMINAL HOLDING SCREW 12 204-0119
MAIN BOARD SCREW
. For units with indicator 3 204-0118
. For units without indicator 3 204-0117
INPUT BOARD SCREW 6 214-0125
MOUNTING BRACKET FOR 2" PIPE MOUNTING (NOTE 3)
. Carbon Steel 18 214-0801
. Stainless Steel 316 18 214-0802
. Carbon Steel bolts, nuts, washers and U-clamp in Stainless Steel 18 214-0803
LOCAL ADJUSTMENT PROTECTION CAP 9 204-0114

NOTE: 1) It includes terminal holder insulator, bolts (cover lock, grounding and terminal holder insulator) and
identification plate without certification.
2) 0-Rings are packaged in packs of 12 units.
3) Including U-clamp, nuts, bolts and washers.
Maintenance Procedures 5.5

ACESSORIES

ORDERING CODE DESCRIPTION


SD_1 Magnetic tool for local adjustment
HT2 Hand-Held Terminal - 80 characters
IF3 HART Protocol Interface
DP03 General Purpose 32K RAM PACK
DP12 TT301 - Version 1.xx, English Language Datapack
BE1 Battery eliminator - 9V (110/220 VAC)

Fig. 5.2 – Four Possible Positions of the Display


Technical Data 6.1

6 TECHNICAL DATA
Functional Specifications Damping
Adjustable 0-32 seconds.
Inputs
Options see table. Configuration
This is done by an external Hand-Held Terminal, that
Output Signal communicates with the transmitter remote or locally
Two-wire,4-20 mA with superimposed digital communi- using Hart Protocol. Locally the magnetic tool can be
cation (HART Protocol Version 5.1/Transmitter/Poll- used as well. The magnetic tool can configure the
Response mode/Common 4-20 mA). majority of the items provided the transmitter is fitted
with a display.
Power Supply
12 to 45 Vdc HHT Main Features
RAM memory: 64 Kbytes
Load Limitation EPROM memory: 128 Kbytes, Datapack
Display: 80 characters, 4 lines
Power Supply: 9 Vdc
Dimensions: Length 142 mm (5.59"), Width 78 mm
(3,07"), Depth 29.3 mm (1.15")

Performance Specifications

Accuracy
See the following tables.

Ambient Temperature Effect


For a 10( C variation:

mV (-6...22 mV), TC (NBS: B, R, S, T): 0.03% of the


input milivoltage or 0.002 mV whichever is greater.
Indication
Optional 4 digit LCD indicator. mV (-10...100 mV), TC (NBS: E, J, K, N; DIN: (L, U):
0.03% of the input milivoltage or 0.01 mV whichever
Hazardous Location Certification is greater.
Explosion proof, weather proof and intrinsically safe
CENELEC and FM standards (Pending). mV (-50...500 mV): 0.03% of the input milivoltage or
0.05 mV whichever is greater.
Zero and Span Adjustment
Noninteractive, by Hand-Held Terminal or local adjust- Ohms (0...100 Ω), RTD (GE: Cu10) : 0.03% of the
ment. input resistence or 0.01 Ω whichever is greater.

Temperature Limits Ohms (0...400 Ω), RTD (DIN: Ni: 120; IEC: Pt50, Pt100;
Operation: -40 to 85 ºC (-40 to 185 ºF) JIS: Pt50, Pt100): 0.03% of the input resistence or
Storage: -40 to 120 ºC (-40 to 250 ºF) 0.04 Ω whichever is greater.
Digital Display: -10 to 60 ºC (-14 to 140 ºF) operation
-40 to 85 ºC (-40 to 185 ºF) Ohms (0...2000 Ω), RTD (IEC: Pt500): 0.03% of the
without damage
input resistence or 0.2 Ω whichever is greater
Loss of Input (Burnout)/Failure Alarm
TC: Cold-junction compensation rejection 60:1
In case of sensor burnout or circuit failure, the self
Reference: 25,0  0,3( C
diagnostics drives the output to 3.9 or to 21.0 mA,
according to the user's choice.
Power Supply Effect
0.005% of calibrated span per volt.
Humidity Limits
10 to 100% RH
Vibration Effect
Meets SAMA PMC 31.1
Turn-on Time
Approximately 10 seconds.
Electro-Magnetic Interference Effect
Designed to comply with IEC 801
Update Time
Approximately 0.5 second.
6.2 TT301 - Operation and Maintenance Instruction Manual

Physical Specifications Control Characteristics (Optional)

Electrical Connection PID


Proportional Gain: 0 to 100
1/2-14 NPT, Pg 13.5 or M20 x 1.5.
Integral Time: 0.01 to 999 min/rep
Derivative Time: 0 to 999 s
Material of Construction
Direct/Reverse Action
Injected low copper aluminum with polyester painting or
Lower and Upper output limits: -0.6 to +106.25%
316 Stainless Steel housing, with Buna N 0-rings on
Output rate-of-change limit: 0.02 to 600 %/s
cover (NEMA 4X, IP67).
Power-on safety output: -0.6 to +106.25%
Antireset windup
Mounting
Bumpless Auto/Manual transfer
Can be attached directly to the sensor. With an op- Setpoint Generator up to 16 points, up to 19999
tional bracket can be installed on a 2" pipe or fixed on minutes
a wall or panel.
Alarm
Weight
Dual, trip levels adjustable over entire range.
Without display and mounting bracket: 0.80 kg High or Low action.
Add for digital display: 0.13 kg Acknowledge, messaging
Add for mounting bracket: 0.60 kg

2, 3 OR 4 WIRES DIFERENTIAL
MINIMUN ºC DIGITAL MINIMUN ºC DIGITAL
SENSOR TYPE RANGE ºC RANGE ºF RANGE ºC RANGE ºF
SPAN ºC ACCURACY* SPAN ºC ACCURACY*

Cu10 GE -20 to 250 -4 to 482 50 ±1.0 -270 to 270 -486 to 486 50 ±2.0

Ni 120 DIN -50 to 270 -58 to 518 5 ±0.1 -320 to 320 -576 to 576 5 ±0.5

Pt50 IEC -200 to 850 -328 to 1562 10 ±0.2 -1050 to 1050 -1890 to 1890 10 ±1.0

RTD Pt100 IEC -200 to 850 -328 to 1562 10 ±0.2 -1050 to 1050 -1890 to 1890 10 ±1.0

Pt500 IEC -200 to 450 -328 to 842 10 ±0.2 NA NA NA NA

Pt50 JIS -200 to 600 -328 to 1112 10 ±0.25 -800 to 800 -1440 to 1440 10 ±1.0

Pt100 JIS -200 to 600 -328 to 1112 10 ±0.25 -800 to 800 -1440 to 1440 10 ±1.5

B NBS +100 to 1800 212 to 3272 50 ±0.5** -1700 to 1700 -3060 to 3060 60 ±1.0**

E NBS -100 to 1000 -148 to 1832 20 ±0.2 -1100 to 1100 -1980 to 1980 20 ±1.0

J NBS -150 to 750 -238 to 1382 30 ±0.3 -900 to 900 -1620 to 1620 30 ±0.6

K NBS -200 to 1350 -328 to 2462 60 ±0.6 -1550 to 1550 -2790 to 2790 60 ±1.2

THERMO- N NBS -100 to 1300 -148 to 2372 50 ±0.5 -1400 to 1400 -2520 to 2520 50 ±1.0
COUPLE R NBS 0 to 1750 32 to 3182 40 ±0.4 -1750 to 1750 -3150 to 3150 40 ±2.0

S NBS 0 to 1750 32 to 3182 40 ±0.4 -1750 to 1750 -3150 to 3150 40 ±2.0

T NBS -200 to 400 -328 to 752 15 ±0.15 -600 to 600 -1080 to 1080 15 ±0.8

L DIN -200 to 900 -328 to 1652 35 ±0.35 -1100 to 1100 -1980 to 1980 35 ±0.7

U DIN -200 to 600 -328 to 1112 50 ±0.5 -800 to 800 -1440 to 1440 50 ±2.5

* Accuracy of value read on display and accessed by communication using HHT. The 4-20 mA accuracy is the
digital accuracy ±0.03%.
** Not applicable for the first 20% of the range (up to 440 ºC).
NA Not applicable.
Technical Data 6.3

RANGE MINIMUN DIGITAL * RANGE MINIMUN DIGITAL *


SENSOR SENSOR
mV SPAN mV ACCURACY % OHM SPAN mV ACCURACY %
-6 to 22 0.40 ±0.02% or ±2 µV 0 to 100 1 ±0.02% or ±0.01 Ohm

mV -10 to 100 2.00 ±0.02% or ±10 µV OHM 0 to 400 4 ±0.02% or ±0.04 Ohm

-50 to 500 10.00 ±0.02% or ±50 µV 0 to 2000 20 ±0.02% or ±0.20 Ohm

-28 to 28 0.40 ±0.1% or ±10 µV -100 to 100 1 ±0.08% or ±0.04 Ohm


mV DIF. OHM DIF.
-110 to 110 2.0 ±0.1% or ±50 µV -400 to 400 4 ±0.1% or ±0.2 Ohm

ORDERING CODE
MODEL
TEMPERATURE TRANSMITTER
TT301
CODE Local Indicator
0 Without Indicator
1 With Digital Indicator
CODE Mounting Bracket
0 Without Bracket
1 Carbon Steel Bracket
2 316 SS Bracket
7 Carbon Steel Bracket With 316 SST Fasteners
CODE Zero and Span Adjustment
1 With Local Adjustment
CODE Electrical Connections
0 ½ - 14 NPT
A M20 x 1.5
B Pg 13.5 DIN
Z Outers – Specify
CODE Optional Items*
H1 316 SST Housing
Z With Special Features – Specify

TT301 - 0 2 - 1 B / *

* LEAVE IT BLANK FOR NO OPTIONAL ITEMS.

Вам также может понравиться