Вы находитесь на странице: 1из 8

BA2103

Messko EPT202-IM
DNP3.0 interface description









BA2103/00/01 Page 1 of 8 22/04/2008












Messko EPT202-IM interface
Vendor Name: Messko GmbH
Device Name: EPT202IM
Highest DNP Level Supported:

For Requests: Level 1
For Responses: Level 1

Device Function:

Slave


GENERAL INFORMATION:
Maximum Data Link Frame Size (octets):

Transmitted: 300
Received: (must be 292)
Maximum Application Fragment Size (octets):

Transmitted: 200 (if >2048, must be
configurable)
Received: 2048 (must be > = 249)

Maximum Data Link Re-tries:

Unlimited

Maximum Application Layer Re-tries:

Unlimited
Requires Data Link Layer Confirmation:

Never

Requires Application Layer Confirmation:

When reporting Event Data ( Remote devices only)

Publisher:
Messko GmbH
Gablonzer Str. 25-27
D-61440 Oberursel

BA2103/00/01 Page 2 of 8 22.04.2008

Timeouts while waiting for:

Data Link Confirm None Fixed at________ Variable Configurable*
Complete Appl. Fragment None Fixed at________ Variable Configurable*
Application Confirm None Fixed at 5s
(1
Variable Configurable*
Complete Appl. Response None Fixed at________ Variable Configurable*
Others _____________________________________________________________________
*Attach explanation if Variable or Configurable was checked for any timeout

1)
If it was not possible to resend the message for more than 5s it is discarded

Default Status Object/Variation:

No Status objects reported
Configurable (attach explanation)
Default Static Object ___________
Default Static Variation ___________
Default Event Object ___________
Default Event Variation ___________
Point-by-point list attached

Default Analog Object/Variation:

No Analog objects reported
Configurable (attach explanation)
Default Static Object ______________
Default Static Variation ______________
Default Event Object ______________
Default Event Variation ______________
Point-by-point list attached
Default Counter Object/Variation:

No Counters reported
Configurable (attach explanation)
Default Static Object ___________
Default Static Variation ___________
Default Event Object ___________
Default Event Variation ___________
Point-by-point list attached

Counters Roll Over at:

No Counters Reported
Configurable (attach explanation)
16 Bits
32 Bits
Other Value _____________
Point-by-point list attached
Default Frozen Counter Object/Variation:

No Frozen Counters reported
Configurable (attach explanation)
Default Static Object ___________
Default Static Variation ___________
Default Event Object ___________
Default Event Variation ___________
Point-by-point list attached

Counters frozen by means of:

Remote device time based
Fixed time
Configurable; range _____ to _____
Master Request (see implementation
table for supported function codes)
Both
Analog Deadbands:

Fixed

Configuring Analog Deadbands:

Not Applicable
Are the updated deadband values preserved through a device reset:

NO

The number of multiple objects allowed in a single read request message:

Number of multiple objects allowed: Maximum length of application frame message is the
limit.

Ability to DISABLE/ENABLE DNP database
points:
Not Applicable
IIN 1-6 Device Trouble Bit

Never used


BA2103/00/01 Page 3 of 8 22.04.2008

Time Sync Information:

Time Sync Period:
Never

Sends/Executes Digital Control Operations:

SELECT/OPERATE* Never Always Sometimes Configurable
DIRECT OPERATE* Never Always Sometimes Configurable
DIRECT OPERATE NO ACK* Never Always Sometimes Configurable

Count > 1 Never Always Sometimes Configurable
Pulse On Never Always Sometimes Configurable
Pulse Off Never Always Sometimes Configurable
Latch On Never Always Sometimes Configurable
Latch Off Never Always Sometimes Configurable
Trip/Close Never Always Sometimes Configurable
Raise/Lower Never Always Sometimes Configurable

Queue Never Always Sometimes Configurable
Clear Queue Never Always Sometimes Configurable

Sends/Executes Analog Control Operations:

SELECT/OPERATE* Never Always Sometimes Configurable
DIRECT OPERATE* Never Always Sometimes Configurable
DIRECT OPERATE NO ACK* Never Always Sometimes Configurable

Queue Never Always Sometimes Configurable
Clear Queue Never Always Sometimes Configurable

The maximum number of objects supported in a single control request for objects 12 and
41.

Number of objects allowed for object 12: actually no objects of type 41 are implemented
Number of objects allowed for object 41: actually no objects of type 41 are implemented

Control Points per address:

1 control point per address
Do all indices support the same control codes:

YES

Maximum Select/Execute Delay Time:

Fixed at 15 seconds
Ability for REMOTE/LOCAL control mode:

Global

Sends Unsolicited Responses:

Sometimes (after Link Reset)
Sends Static Data in Unsolicited
Responses:

When Status Flags Change
No other options permitted.


BA2103/00/01 Page 4 of 8 22.04.2008

ENABLE/DISABLE Unsolicited

Function codes 20,21 supported
Minimum number of events and/or minimum
time before transmission of an unsolicited
message.

# of events:1
min. amount of time(msec) : 100

Assign Class Function code supported:
NO
Is the Event Buffer size configurable:
NO
Configurable Per Class buffer:
NO

Are the updated ENABLE/DISABLE
unsolicited settings saved through a
device reset:

NO

Are the updated Assign Class settings saved
through a device reset:

NO
Supports Collision Avoidance:
Never

Source Address Filtering:
Not Supported

Supports Multi-drop communications: Yes No
One master and multiple slaves on the line are supported because the unit ignores messages with other
addresses than its own.
Sends Multi-Fragment Responses: Yes No




Supported Application Layer Function Codes
- Direction Primary Secondary
o Confirm (0x00)
o Read (0x01)
o Write (0x02)
o Enable Unsolicited Respones (0x14)
o Disable Unsolicited Responses (0x15)
o Delay Measurement (0x17)
- Direction Secondary Primary
o Response (0x81)
o Unsolicited Response (0x82)

BA2103/00/01 Page 5 of 8 22.04.2008

Supported Objects

OBJECT

REQUEST
(slave must parse)

RESPONSE
(master must parse)

Obj

Var

Description

Func
Codes
(dec)

Qual Codes
(hex)

Func Codes
(dec)

Qual Codes
(hex)
1 0 Binary Input - All Variations
1
(Read)
06
(No Range)

1 1 Binary Input
1
(Read)
06
(No Range)
129
(Response)
130
(Unsol Resp)
00
(Start-Stop)
30 0 Analog Input - All Variations
1
(Read)
06
(No Range)

30 2 16-Bit Analog Input
1
(Read)
06
(No Range)
129
(Response)
130
(Unsol Resp)
00
(Start-Stop)
50 0 Time and Date - All Variations
50 1 Time and Date
1
(Read)
07
(Count of
Points where
Range = 1)
129
(Response)
07
(Count of
Points where
Range = 1)
50 1 Time and Date
2
(Write)
07
(Count of
Points where
Range = 1)

52 2 Time Delay Fine
129
(Response)
07
(Count of
Points where
Range = 1)
60 0
60 1 Class 0 Data
1
(Read)
06
(No Range)

60 2 Class 1 Data
1
(Read)
06
(No Range)

60 3 Class 2 Data
1
(Read)
06
(No Range)

80 1 Internal Indications
1
(Read)
00, 01
129
(Response)

80 1 Internal Indications
2
(Write)
00
(index=7)
129
(Response)


BA2103/00/01 Page 6 of 8 22.04.2008

Data items
Description Index Default Static Variation
Obj Var Desc Unit Scale Range Point Name
Analog Input 0 30 2 16bit with
Status
C 10 -5002500 Oil Temperature
Analog Input 1 30 2 16bit with
Status
C 10 -5002500 Winding 1 Temperature
Analog Input 2 30 2 16bit with
Status
C 10 -5002500 Winding 2 Temperature
Analog Input 3 30 2 16bit with
Status
C 10 -5002500 Winding 3 Temperature
Analog Input 4 30 2 16bit with
Status
A 0 032767 Load Current 1
Analog Input 5 30 2 16bit with
Status
A 0 032767 Load Current 2
Analog Input 6 30 2 16bit with
Status
A 0 032767 Load Current 3
Analog Input 7 30 2 16bit with
Status
% 0 0100 Oil Level 1
Analog Input 8 30 2 16bit with
Status
% 0 0100 Oil Level 2
Analog Input 9 30 2 16bit with
Status
C 10 -5002500 Ambient Temperature
Analog Input 10 30 2 16bit with
Status
% 10 01000 Life Consumption
Analog Input 11 30 2 16bit with
Status
% 10 01000 Analog Input 1
Analog Input 12 30 2 16bit with
Status
% 10 01000 Analog Input 2
Binary Input 0 1 1 No Status OL-Module On
Binary Input 1 1 1 No Status CT-Module On
Binary Input 2 1 1 No Status Winding On
Binary Input 3 1 1 No Status Set Time
Binary Input 4 1 1 No Status S5 active
Binary Input 5 1 1 No Status S6 active
Binary Input 6 1 1 No Status Lock active
Binary Input 7 1 1 No Status Error active
Binary Input 8 1 1 No Status Ambient Temperature On
Binary Input 9 1 1 No Status S1 active
Binary Input 10 1 1 No Status S2 active

BA2103/00/01 Page 7 of 8 22.04.2008

Description Index Default Static Variation
Obj Var Desc Unit Scale Range Point Name
Binary Input 11 1 1 No Status S3 active
Binary Input 12 1 1 No Status S4 active
Binary Input 13 1 1 No Status Temperature Test Mode active
Binary Input 15 1 1 No Status PC-Test Mode active
Binary Input 17 1 1 No Status Winding 1 On
Binary Input 18 1 1 No Status Winding 2 On
Binary Input 19 1 1 No Status Winding 3 On
Binary Input 21 1 1 No Status OL1 On
Binary Input 22 1 1 No Status OL2 On
Binary Input 24 1 1 No Status OL1 Max active
Binary Input 25 1 1 No Status OL2 Min active
Binary Input 26 1 1 No Status OL2 Max active
Binary Input 27 1 1 No Status OL1 Min active
Binary Input 28 1 1 No Status IM Module On
Binary Input 29 1 1 No Status S8 active
Binary Input 30 1 1 No Status S7 active
Binary Input 31 1 1 No Status Oil Level Test active
Binary Input 32 1 1 No Status Datalogger defect
Binary Input 33 1 1 No Status Error Analog Output Oil Temp
Binary Input 34 1 1 No Status Error Oil Temp Sensor
Binary Input 35 1 1 No Status Error Supply Voltage
Binary Input 36 1 1 No Status Error Analog Output Wind Temp
Binary Input 37 1 1 No Status Error Ambient Temp Sensor
Binary Input 40 1 1 No Status Error OL1 Sensor
Binary Input 41 1 1 No Status Error Analog Output OL1
Binary Input 42 1 1 No Status Error OL2 Sensor
Binary Input 43 1 1 No Status Error Analog Output OL2
Binary Input 44 1 1 No Status Error Analog Output WT2
Binary Input 45 1 1 No Status Error Analog Output WT3
Binary Input 46 1 1 No Status Error IM1 Sensor
Binary Input 47 1 1 No Status Error IM2 Sensor
Binary Input 49 1 1 No Status Input 1 active
Binary Input 50 1 1 No Status Input 2 active

BA2103/00/01 Page 8 of 8 22.04.2008

Description Index Default Static Variation
Obj Var Desc Unit Sca
le
Range Point Name
Binary Input 51 1 1 No Status Input 3 active
Binary Input 52 1 1 No Status Input 4 active
Binary Input 57 1 1 No Status Error Sensor Analog Input 1
Binary Input 58 1 1 No Status Error Sensor Analog Input 2