Cooling-Tower Design Tips
By KEITH RINALDI, CEM; Dome-Tech Field Engineering Services; Edison,
N.J. | HPAC Engineering
A cooling tower is only as good as the details of its design and the specification of its
supporting components. Details such as pump net positive suction head (NPSH),
strainers, and pipe size can have a major impact on performance and energy bills. Make
sure the impact is positive by keeping the following in mind.
RELATED RELATED RELATED RELATED
A STRAINER AT THE TOWER INLET CAN PREVENT HEADACHES AFTER START-UP
When cooling towers are replaced, the system and piping often are not. When the system
is filled and started, water flows from the tower, through the pump, through the chiller,
and to the tower spray nozzles. Eventually, pump-discharge pressure increases and flow
decreases, indicating a problem. Building personnel blow down or pull and clean/replace
the pump inlet strainers, which are loaded with dirt/scale. When the system is started
again, pump-discharge pressure still is high, and low flow persists.
What is the problem?
The problem is that the pump inlet strainers catch only dirt and debris between the tower
outlet and the pump inlet. They do nothing to remove dirt and scale originating between
the pump outlet/chiller and the tower. There is a good chance that some, if not all, of the
tower nozzles will be partially blocked. Removing and cleaning each nozzle will be
expensive and time-consuming. Making matters worse is that the nozzles likely will plug
again as soon as the system is restarted.
For this reason, in systems with questionable water-treatment practices and systems that
have been drained or dormant, consider installing a new strainer, block valves, and inlet-
and outlet-pressure gauges on the common header just prior to the tower inlet. Utilize a
strainer that can be opened, cleaned, and placed back into service quickly. In some
systems, this new tower strainer will have to be cleaned several times a day for the first
week or two of service to remove all of the dirt and scale in the system. However, cleaning
a strainer like this usually can be done quickly with in-house personnel.
DO NOT UNDERSIZE THE EQUALIZING LINE
Water drains out of a cooling tower's cold-water basin via gravity. Typically, between the
cold-water basin and the point of connection for the common return header is only a few
Advertisement
Blogs & Blogs & Blogs & Blogs & Opinions Opinions Opinions Opinions
The Customer Isnt Always Right
by Lawrence (Larry) Clark, CEA,
GGP, LEED AP O+M
Posted 1 week ago
in Clark's Remarks
HVAC and Cloud Computing: More
Similar Than You Think
by Lawrence (Larry) Clark, CEA,
GGP, LEED AP O+M
Posted 3 weeks ago
in Clark's Remarks
Getting What You Pay For
by Lawrence (Larry) Clark, CEA,
GGP, LEED AP O+M
Posted 5 weeks ago
in Clark's Remarks
HOME HOME HOME HOME > > > > AIR AIR AIR AIR CONDITIONING CONDITIONING CONDITIONING CONDITIONING > COOLING > COOLING > COOLING > COOLING- -- -TOWER DESIGN TIPS TOWER DESIGN TIPS TOWER DESIGN TIPS TOWER DESIGN TIPS
0 Recommend
Finer Points of Specifying Cooling Towers
Blogs Columns
ComfortechShow
Subscribe Contact Us Newsletters Advertise With Us About Us Info-Dex RSS
Air Conditioning Building Controls Fire / Smoke Heating Humidity Control IAQ & Ventilation Motors / Drives Piping / Pumping Resources
Welcome, andrewmwwong!
My Account | Sign Out
Page 1 of 3 Cooling-Tower Design Tips | Air Conditioning content from HPAC Engineering
4/17/2014 http://hpac.com/air-conditioning/cooling-tower-design-tips
Tweet
feet of vertical drop. As a result, the pressure differential between the tower and the
common header may be only a few feet (or even inches) of water column.
History has shown that even minor differences in piping geometry between cell outlets
and the point of common connection on return headers can have a profound effect on
how water drains from tower cells. In some instances, differences in cell-outlet pipe
length of only 5 to 10 ft have resulted in one cell basin running nearly empty while the
other overflows. A common field fix is to balance water flow between the two cells.
Tower performance will be affected, however, as one cell will be receiving extra water,
while the other will be receiving less and not performing at its rated conditions. This
situation easily can be avoided by paying attention to the design and sizing of the
equalizing line. Follow the tower manufacturer's recommended guidelines, and make the
tower-outlet piping from each cell identical. If it is not identical, slightly oversize it from
the cells to the header.
WATCH THE PUMP NPSH
When an existing roof structure will not support the weight of a new cooling tower as is
the case in many retrofit situations the cooling tower may be installed on a different
support platform, perhaps one adjacent to the building. Rarely does the support platform
reach the height of the building's roof. Often, the tower cold-water basin is located only 10
to 12 ft above ground.
If pumps are to be installed on a foundation and base, only a few feet below a tower basin,
it is imperative that low-NPSH-required (NPSHR) pumps be utilized and that there be a
safety factor in the NPSH available (NPSHA)/NPSHR. A pump selected at NPSHA is a
problem waiting to happen. No one wants to tell an owner that the reason his or her
brand-new pumps sound as if they are pumping marbles is that they were selected
improperly and are going to have to be replaced.
In situations in which a tower is located on an elevated structure, but only 5 or 10 ft above
grade, avoid up and down runs of tower-discharge piping, especially to a level higher than
that of the cold-water basin. Though unusual, this has been witnessed by the author on
two occasions, causing the following problems:
LOCATE THE COOLING TOWER AWAY FROM ACTIVE AREAS
Cooling towers launch water vapor and a small amount of liquid into the air, a
phenomenon known as drift loss. Depending on the amount of drift loss and the weather,
a mist may be felt in the area surrounding the cooling tower. Normally, this is not a
problem. But if a cooling tower is located on a roof directly above or adjacent to a
pedestrian thoroughfare or parking lot, mist detectable by pedestrians quickly can turn
into an air-quality issue. Is the water safe? What chemicals are used? What
microorganisms are in the water? Mist landing and then drying on parked cars also can
pose problems. Try explaining to the CEO that the mist is no big deal and that he simply
needs to get his car washed every other day.
The installation of extra or high-efficiency drift eliminators may solve the problem of drift
loss. However, it will not stop water vapor in the air from condensing and then blowing
into a parking lot. In short, do yourself a favor, and locate cooling towers as far from
active areas as possible.
Keith Rinaldi, CEM, is vice president of Dome-Tech Field Engineering Services.
E-MAIL:
andrewmwwong@yahoo.com
COUNTRY:

Getting everything in a building to work to the


designers intent and in accordance with the
owners project... fb.me/2wTGeneO3
HPAC Engineering
HPACEng @
Forrest Fencl discusses the role of UV-C lighting
in maintaining building # performance:
conditioni - hpac.com/air HVAC #
facilitymanagement #
Scott Arnold
ScottArnoldHPAC @
21h
21h
Tweets
Follow
Tweet to @HPACEng
Newsletter Signup
Sign-up to receive our free newsletters
UNITED STATES
By clicking below, I acknowledge and agree to Penton's
Terms of Service and to Penton's use of my contact
information to communicate with me about Penton's or
its third-party partners' products, services, events and
research opportunities. Penton's use of the information I
provide will be consistent with Penton's Privacy Policy.
SUBSCRIBE
Follow Us
When pumps were shut off, water in upward-sloped pipe ran backward into the tower,
causing it to overflow.
Elevated discharge pipe acted as an air trap. Eventually, air filled the pipe and
slugged through the system, damaging the pumps and causing the chillers to trip off
line because of lost flow. Because the suction piping often ran at a vacuum condition,
the air could not be vented by conventional means.
0 Recommend
Page 2 of 3 Cooling-Tower Design Tips | Air Conditioning content from HPAC Engineering
4/17/2014 http://hpac.com/air-conditioning/cooling-tower-design-tips
Site Features Site Features Site Features Site Features
Media Center
RSS
Sitemap
Site Archive
Newsletters
View Mobile Site
HPAC Engineering Corporate HPAC Engineering Corporate HPAC Engineering Corporate HPAC Engineering Corporate
Privacy Policy
Terms of Service
Contact
Follow Follow Follow Follow Us Us Us Us
Search Search Search Search HPAC.com HPAC.com HPAC.com HPAC.com
Contracting Business Contractor HVAC-Talk Comfortech 2013 Show HVACR Distribution Business Radiant Living
Fire Protection Engineering
HPAC.com HPAC.com HPAC.com HPAC.com
Air Conditioning Building Controls Fire / Smoke Heating Humidity Control IAQ & Ventilation Motors / Drives Piping / Pumping
Mechanical Systems Sites Mechanical Systems Sites Mechanical Systems Sites Mechanical Systems Sites
Copyright 2014 Penton
POSTING AS:
(Sign Out)
YOUR COMMENT: *

E-MAIL:
COUNTRY:
Discuss this Article 0
andrewmwwong
SUBMIT COMMENT
Newsletter Newsletter Newsletter Newsletter Signup Signup Signup Signup
Sign-up to receive our free newsletters
UNITED STATES
By clicking below, I acknowledge and agree to Penton's Terms of Service and to Penton's use of my contact information to
communicate with me about Penton's or its third-party partners' products, services, events and research opportunities.
Penton's use of the information I provide will be consistent with Penton's Privacy Policy.
SUBSCRIBE
Related Related Related Related Articles Articles Articles Articles
Cooling-Tower Design for Critical Applications
Maximizing Cooling-Tower Water Efficiency
UVC Helps Institute Keep Indoor Air, Cooling-Tower Makeup Water Clean
Cooling-Tower Design for Critical Applications
Relocated Plastic Cooling Tower Handles Weather Extremes
Page 3 of 3 Cooling-Tower Design Tips | Air Conditioning content from HPAC Engineering
4/17/2014 http://hpac.com/air-conditioning/cooling-tower-design-tips

Вам также может понравиться