Вы находитесь на странице: 1из 537

Tender No: E19/2012

33/11kV SUBSTATION WORKS IN NORTH &


EASTERN AREAS OF NORTHERN EMIRATES




VOLUME III


SCOPE OF WORKS









TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES

Volume III
Scope of Works


Page 1 of 536


SCOPE OF WORKS

Table of Contents

SCHEDULE NO. DESCRIPTION
SCHEDULE
A to E
DEFINITE WORKS
PART - A NORTH AREA ( 1 )
A1 NEW 33/11kV SHEIKH KHALIFA HOSPITAL (SHKH) SUBSTATION
A2 NEW 33/11kV RIFFAH-3 (RIF3) SUBSTATION
A3 NEW 33/11kV ZAITH-3 (ZAT3) SUBSTATION
A4 NEW 33/11kV JAZEERAH INDUSTRIAL (JZIN) SUBSTATION
A5 CAPACITOR BANK INSTALLATION AT 33/11kV KHARAN (KHAR) SUBSTATION
A6 PROTECTION MODIFICATION WORKS AT EXISTING SUBSTATIONS IN
NORTH AREA (1)
PART - B NORTH AREA ( 2 )
B1 NEW 33/11kV RAMS-2 (RMS2) SUBSTATION
B2 NEW 33/11kV SHAMAL (SHML) SUBSTATION
B3 NEW 33/11kV GHALILAH (GHAL) SUBSTATION
B4 NEW 33/11kV SEIH AL BURAIRAT (SEBU) SUBSTATION
B5 NEW 33/11kV WADI SHAM (WDSH) SUBSTATION
B6 EXTENSION OF 132/33/11kV NAKHEEL POWER (NKPS) SUBSTATION
B7 EXTENSION OF 33/11kV MAREED (MARD) SUBSTATION
B8 EXTENSION OF 33/11kV SHARISHA (SHAR) SUBSTATION
B9 PROTECTION MODIFICATION WORKS AT EXISTING SUBSTATIONS IN
NORTH AREA (2)


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 2 of 536



SCHEDULE NO DESCRIPTION
PART - C EAST AREA (A)
C1 NEW 33/11kV NAJAIMAT (NAJM) SUBSTATION
C2 NEW 33/11kV WATER FIELD 2 (WFL2) SUBSTATION
C3 NEW 33/11kV AL HAIL INDUSTRIAL (HAIN) SUBSTATION
C4 EXTENSION OF 33/11kV MIRASHID (MIRA) SUBSTATION
C5 EXTENSION OF 33/11kV HALIFAT (HALI) SUBSTATION
C6 EXTENSION OF 33/11kV QIDFA (QDFA) SUBSTATION
C7 EXTENSION OF 33/11kV AL HAIL (HAIL) SUBSTATION
C8 EXTENSION OF 33/11kV SAFFA (SAFF) SUBSTATION
C9 EXTENSION OF 33/11kV FUJAIRAH TOWER (FUJR) SUBSTATION
C10 EXTENSION OF 33/11kV FUJAIRAH TOWN CENTER (TWNC) SUBSTATION
C11 PROTECTION MODIFICATION WORKS AT EXISTING SUBSTATIONS IN
EAST AREA (A)

PART - D EAST AREA (B)
D1 NEW 33/11kV SEIH DIBBA (SEDI) SUBSTATION
D2 NEW 33/11kV TAWYEEN (TAWY) SUBSTATION
D3 EXTENSION OF 132/33/11kV DIBBA MAIN (DBMN) SUBSTATION
D4 EXTENSION OF 33/11kV AKKAMIA (AKAM) SUBSTATION
D5 EXTENSION OF 33/11kV DIBBA AL HISN (DHSN) SUBSTATION
D6 EXTENSION OF 33/11kV WASSAT (WAST) SUBSTATION
D7 EXTENSION OF 132/33/11kV DADNAH MAIN (DAMN) SUBSTATION
D8 EXTENSION OF 33/11kV BIDIYA (BIDY) SUBSTATION
D9 PROTECTION MODIFICATION WORKS AT EXISTING SUBSTATIONS IN
EAST AREA (B)

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 3 of 536


PART - E COMMON ITEMS
E1 SUPPLY OF SPARE 33/11KV DISTRIBUTION TRANSFORMER
E2 SCADA WORKS AT EXISTING UAQ SYSTEM CONTROL CENTRE
E3 TELECOMMUNICATION EQUIPMENT
SCHEDULE F OPTIONAL SCOPE OF WORKS


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 4 of 536


NUMBERING SYSTEM

The following numbering system has been used in identifying the plant description, site and
different type of work which is also been used in the price schedule for re-relation purposes.

A 1 G 01. 01.1




Sub item (1 to 99)


Sub item (01 to 99)



Item of Work for each discipline (01 to 99)



Discipline G : General
E : Electrical
SC: SCADA
T : Telecom
C : Civil, Structural & Architectural
M : Mechanical



Site (1 to 20) common for all sites (O)


Plant Description. A - E Substation (Definite Work)
F Substation (Optional Work)











TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 5 of 536


SCOPE OF WORKS


TABLE OF CONTENTS

SL. No. Description

1.0 Project Description
2.0 Manufacturer Supervisor
3.0 Testing and Commissioning of Main Relays & Fault Recorder
4.0 Site Establishment and Services
5.0 Power Supply for Installation, Testing & Commissioning Works
6.0 Overall Co-ordination
6.1 Interfacing of Main Protection Relays and Communication System
7.0 Site Testing
8.0 Auxiliary Mandatory Requirements
9.0 33kV & 11kV Cables
10.0 HV Test for Substation Equipment
11.0 Site Work Permits/Security Passes
12.0 General Requirements for Modification Works at Existing Substations
13.0 Tenderers Visit to Sites
14.0 Brief Scope of Works




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 6 of 536


SCOPE OF WORKS

1. Project Description

New 33/11kV substations shall be constructed on turnkey basis (design, supply,
construction, installation, testing and commissioning) at the sites as shown in the
site location drawings. Also, some existing substations shall be extended as
specified below:

Part A North Area (1)

New Substations

A1- New 33/11kV Sheikh Khalifa Hospital (SHKH) Substation
A2- New 33/11kV Riffah-3 (RIF3) Substation
A3- New 33/11kV Zaith-3 (ZAT3) Substation
A4- New 33/11kV Jazeerah Industrial (JZIN) Substation

Extension works at Existing Substations

A5- Capacitor Bank Installation at 33/11kV Kharan (KHAR) Substation
A6- Protection Modification Works at Existing Substations in North Area (1)

Part B North Area (2)

New Substations

B1- New 33/11kV Rams-2 (RMS2) Substation
B2- New 33/11kV Shamal (SHML) Substation
B3- New 33/11kV Ghalilah (GHAL) Substation
B4- New 33/11kV Seih Al Burairat (SEBU) Substation
B5- New 33/11kV Wadi Sham (WDSH) Substation

Extension works at Existing Substations

B6- Extension of 132/33/11kV Nakheel Power (NKPS) Substation
B7- Extension of 33/11kV Mareed (MARD) Substation
B8- Extension of 33/11kV Sharisha (SHAR) Substation
B9- Protection Modification Works at Existing Substations in North Area (2)







TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 7 of 536


Part C East Area (A)

New Substations
C1- New 33/11kV Najaimat (NAJM) Substation
C2- New 33/11kV Water Field-2 (WFL2) Substation
C3- New 33/11kV Al Hail Industrial (HAIN) Substation

Extension works at Existing Substations

C4- Extension of 33/11kV Mirashid (MIRA) Substation
C5- Extension of 33/11kV Halifat (HALI) Substation
C6- Extension of 33/11kV Qidfa (QDFA) Substation
C7- Extension of 33/11kV Al Hail (HAIL) substation
C8- Extension of 33/11kV Saffa (SAFF) substation
C9- Extension of 33/11kV Fujairah Tower (FUJR) substation
C10- Extension of 33/11kV Fujairah Town Center(TWCN) Substation
C11- Protection Modification Works at Existing Substations in East Area (A)

Part D East Area (B)
New Substations
D1- New 33/11kV Seih Dibba (SEDI) Substation
D2- New 33/11kV Tawyeen (TAWY) Substation

Extension works at Existing Substations

D3- Extension of 132/33/11kV Dibba Main (DBMN) Substation
D4- Extension of 33/11kV Akkamia (AKAM) Substation
D5- Extension of 33/11kv Dibba Al Hisn (DHSN) Substation
D6- Extension of 33/11kV Wassat (WAST) Substation
D7- Extension of 132/33/11kV Dadnah Main (DAMN) Substation
D8- Extension of 33/11kV Bidiya (BIDY) Substation
D9- Protection Modification Works at Existing Substations in East Area (B)

Part E Common Items

E1- Supply of Spare 33/11kv Distribution Transformer
E2- Scada Works at Existing UAQ System Control Centre
E3- Telecommunication Equipment

Schedule F- Optional Scope of Works




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 8 of 536


General Requirements

Each new substation shall be indoor load center substation and is intended for
installation of three (3) Nos. of 33/11kV transformers for feeding power to
consumers. 33kV switchgear shall be of GIS type, 11kV switchgear shall be metal
clad air insulated type for indoor installation. Distribution Transformers shall be of oil
filled and foreseen for indoor or outdoor installation. Control, protection, SCADA and
communication equipment shall be located in separate rooms. Auxiliary AC/DC
power supply, illumination, grounding, lightning protection, cabling systems etc.
shall be provided as required for the project.

A conceptual layout of the substation building is enclosed with the tender document.
The contractor shall rearrange the design, as required, based on the approved plot
and final OHL/cable routing without any contractual implication to FEWA. The
clearance shown in the drawing is minimum and contractor shall rearrange the
layout if required to maintain the minimum clearances based on the actual
equipment size selected. The room size shall be increased, if required, to achieve
the minimum clearance as specified, based on the size of equipment finally
approved, without any contractual implication to FEWA.

The substation building shall be provided with space for installation of future
equipment as indicated in the SLD, layout drawing.

The main substation building shall also be provided with store and toilet facilities.

A make-up and fire water pump house along with all other auxiliaries for complete
service water, fire protection system shall be provided in the substation.

Boundary wall shall be constructed along the perimeter of the substation plot.
Access roads from the nearest asphalt municipal road shall be provided upto the
substation main gates.

2.0 Manufacturer Supervisor

The manufacturer supervisor from the factory for installation, testing and
commissioning activities shall be arranged by the contractor within the overall
quoted price for the following equipment. The manufacture specialist shall be
proposed from the works and local Engineers trained or certified by the
manufacturer are not acceptable against the same.

33kV & 11kV Switchgear
20/25 MVA Distribution Transformers
20MVA Distribution Transformers
Main protection relays and BCPU
110V DC System
Capacitor banks
Scada and communication system

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 9 of 536


The manufacturer's specialist being proposed shall be from the works of the
equipment and shall be experienced/specialized in the respective equipment. The
cost of providing manufacturers specialist for the above equipment shall be
included in the quoted price without any contractual implication to FEWA.

2.1 Manufacturer Supervisor for FEWA Free Issued Equipment Extensions

The manufacturer supervisor for installation, testing and commissioning activities
shall be arranged by the Contractor under this Contract. FEWA will not provide any
manufacturer supervisor.

3.0 Testing and Commissioning of Main Relays

3.1 The following main protection relays shall be configured, programmed and tested by
the manufacturer specialist. The contractor shall arrange the manufacturers testing
engineer for the testing of following relays. The contractor in his offer shall include
all cost towards arranging manufacturer specialist including fee for the supervisor.

a) Main Protections for 33kV OHL and Cables.
b) Transformer differential/REF protection for 33/11kV transformers.
c) Automatic voltage regulation
d) Busbar protection for 33kV Switchgear.
e) Check synch relay for 33 kV.
f) End to end testing of Main protections.
g) 11kV Bay control and protection unit.
h) Capacitor bank protection and PFC relays
i) SCADA and telecom system

The complete features/characteristics of all other relays shall be tested by the
contractor. All characteristics/features of numerical relays whether used in
schematic diagram or not, shall be tested by the contractor/manufacturer relay
testing engineers. It is the responsibility of the contractor for overall testing and
commissioning of all protection system.

3.2 The contractor shall also provide necessary tools, testing equipment, manpower
and any other assistance required for successful testing and commissioning of all
relays. All necessary costs towards the same are deemed to be included in the
quoted price.

4.0 Site Establishment & Services

The contractor shall provide all the site facilities and other services for FEWA and
Engineer (Consultant) as specified in special conditions of contract.

5.0 Power Supply for Installation, Testing & Commissioning Works

The contractor shall arrange the AC/DC power supplies required for the entire
construction, installation, testing and commissioning works. Particular attention shall

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 10 of 536


be provided for testing power supply for numerical relays. Dedicated charger with
battery backup shall be employed for the testing purpose in order to reduce the
ripples in the power supply which may adversely affect the performance of
numerical relays.

Power supply arranged by the contractor shall be retained until commissioning and
permanent auxiliary supply is available to the substation from the auxiliary
transformer. Necessary power for HVAC system, lighting and small power system
and fire protection system etc shall be maintained upto energization of all equipment
including LVAC through the auxiliary transformers.

6.0 Overall Coordination

It is the responsibility of the contractor to fully co-ordinate and co-operate with other
contractor including OHL/cabling contractors and other remote end substation
contractors wherever required.

7.0 Site Testing

The contractor shall carryout the site tests for all equipment as per the relevant
standards, manufacturer instruction manuals, manufacturer recommendations and
as required by FEWA, in the presence of Engineer/FEWA.

The costs towards all site testing for new substations, Extension substations, and
remote end substations (wherever protection modification work shall be included in
this tender) are deemed to be included in the quoted price.

The end to end testing of main protection and remote substation feeder testing shall
be included for the following substations :

a) Remote end modification as required in the scope of work.
b) Wherever the remote end substation names are indicated to
match the protection.
c) Wherever the remote end substation names are identified and
the remote end substation is under construction or part of
another contract.

The contractor shall prepare the check list and site test formats for all the substation
equipment including the details of test procedures, equipment/instrument employed,
test diagrams, method statement etc and shall be approved by Engineer/FEWA
before commencing the site testing.

It is mandatory to complete the requirement of approved Check list by the contractor
before commencing the site testing for all substation Equipment and SCADA and
communication equipment.

All testing equipment are subjected to Engineer/FEWAs approval. The valid
calibration certificates of all test instruments/equipment shall be made available at

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 11 of 536


site by the substation contractor before commencing any test. The contractor shall
deploy only qualified and experienced Engineers and approved by Engineer/FEWA,
for site testing of each equipment.

The site testing and commissioning engineers will be interviewed and supervised by
Engineer/FEWA. If the performance of the testing engineers is found not
satisfactory during execution then they shall be replaced with qualified and
experienced engineer without any implication to FEWA at any stage of contract.

8.0 Auxiliary Mandatory Requirements

For each 33/11kV substation (for all new and extension substations), the following
items shall be supplied by the contractor within the quoted price:

a) Proper key boxes with identification tags, master key system, key schedule,
etc.
b) First aid box having all necessary first aid requirements.
c) First aid chart for electrical shocks to be made available in Arabic and English
with clear pictures and neatly framed.
d) Two pairs of safety gloves for MV equipment.
e) Substation single line diagram describing the entire electrical system neatly
framed in each switchgear room and control room.
f) Necessary furnitures to maintain the As built documents and O&M manuals
shall be provided. Also, an operator table with chair shall be provided. The
furnitures type and make shall be subject for Engineer/FEWA approval.
g) Suitable arrangement/boards to keep all operation and maintenance tools of
each equipment separately.
h) Suitable panel and SCADA numbering labels both in English and Arabic for all
equipment including both sides of GIS, Relay/Control Panels, 11kV
switchgear, transformer and all substation equipment as per FEWA
requirements, specification and subject to Engineer/FEWA approval.
i) Suitable danger boards, identification plates etc wherever required.
j) Fire retardant cabinet for keeping the site test reports and the same shall be
provided before starting the installation of electrical equipment.

For existing substations, the existing facilities (if available) shall be suitably modified
and upgraded or new items shall be supplied, if such facilities are not available.

9.0 33kV and 11kV Cables

The following cable sizes are preferred for 33kV and 11kV systems.

33kV - 1C x 500 sq.mm copper XLPE cable.
11kV - 1C x 630 or 1Cx800 sq.mm copper XLPE cable.

The number of cables indicated (for 33kV and 11kV) in this tender is indicative and
for tender propose only. The Contractor shall submit the cable sizing calculation and

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 12 of 536


as per calculation, the required number of cables shall be provided without any
contractual implication to FEWA.

10.0 HV test for Substation Equipment

HV test at site for all equipment as applicable as per relevant IEC standard including
33kV GIS, 11kV switchgear, 33kV cables, 11kV cables etc. shall be conducted at
site. Partial discharge measurement shall be carried out during the HV Test of 33kV
GIS. All necessary equipment for PD measurement shall be arranged and the PD
test criteria as specified in IEC 62271-203 for HV equipment shall be considered as
reference and to be proved at site.

All necessary cost towards arranging HV test equipment, PD measurement,
manufacturers Supervisor etc shall be included in the overall quoted price.

Any site test which is not specifically indicated in the specification but necessary as
per standard engineering practice/IEC/ as required by FEWA shall be conducted at
site without any contractual implication to FEWA.

11.0 Site Work Permits/Security Passes

When undertaking work requiring a permit, the Contractor shall assist and co-
ordinate with FEWA to comply with requirements for safety and operation until the
permit shall be obtained, in strict compliance with FEWA procedure, each morning,
before commencing work in the designated area. Site work permits shall be in
accordance with FEWA safety/security regulations.

Any delay or expenses for securing necessary permission/permits/passes from the
concerned authorities shall not entitle the Contractor to any claim for extension of
completion date or payment.

12.0 General Requirements for Modification Works at Existing Substations

All the modifications as required in the GIS, LV Compartment, C & RP, BZP, RTU,
CCC etc. including but not limited to changing the labels, modifying the schematic
diagrams, GA drawings, layout drawing preparation and revision of all relevant
drawings, SLDs, layouts etc. as required to reflect the circuit changes shall be
carried out by the contractor under scope of this contract within the quoted price. All
such drawings whether specifically mentioned or not shall be modified and
submitted to Authoritys approval by the substation contractor at an early stage of
project execution. All extension and modification works shall be carried out by the
substation contractor with minimum outage only. The substation contractor in his
offer shall state the requirement of shut down in existing substations. The complete
set of as built drawings (wherever changes as required) shall be resubmitted
incorporating the changes.

The Authority reserve the right to ask the substation contractor to retest and
recommission any item or plant disturbed during modification works without any cost

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 13 of 536


and time implication to the Authority and no deviation is acceptable in this regard.
The contractor must visit the site and all necessary existing information, drawings,
documents, etc. required shall be collected without any implications to authority.
Any civil modifications anticipated in the 33kV GIS room, Control & Relay room etc.
shall be carried out by the contractor without any contractual implication to FEWA.

Modification of the existing protection/control/AVR, etc panels shall be carried out by
qualified and experienced manufacturer representatives subject to approval of
FEWA. All the modifications shall be carried out with minimum shutdown
requirements and without any disturbance to existing system. The tenderer shall
make site visit and assess themselves all the required modifications to be carried
out in existing panels and the cost towards all works shall be included within the
quoted price.

All modifications required in existing panels, LV Compartment relay and control
panels, AC/DC system etc shall be included within the quoted price.

The existing substation as built drawings including but not limited to layout of main
equipment, sections, cable route layout, cable tray layout, earthing drawings, control
and protection schematic diagrams of existing bays (bus coupler, common control
panels, adjacent panels etc), substation single line diagrams, associated civil and
electromechanical drawings affected by the modification works etc shall be suitably
modified and submit to Authoritys approval at an early stage. All such drawings
shall also be made as final as built drawings by the substation contractor in
addition to the equipment drawings.

If the existing drawings are not available with FEWA, then the Contractor shall
prepare all such drainage based on the actual existing building and equipment
details and shall prepare as built drawings after completion of the modification
works. All cost towards such works shall be deemed to be included within the
quoted price.

Any relocation of existing equipment required for works shall be deemed to be
included in the quoted price. New control cables/LV power cables, communication
cables, fixing arrangement of relocated equipment etc are also included within the
quoted price. All the relay setting calculations as required by FEWA shall be carried
out by the contractor under scope of this contract and shall be submitted to FEWA
approval.

Any necessary details including but not limited to existing relay setting,
drawings/information, equipment technical data, etc as required shall be collected
from site/equipment by contractor under the scope of this tender. All schematic
diagrams shall be tested and all protection testing including end to end testing shall
be carried out within the quoted price.

The complete end-to-end protection testing shall be carried out for all the feeders
being subject of modification woks, as indicated in the corresponding Tender single

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 14 of 536


line diagram drawing. End-to-end Schematic diagram for Main Protection shall be
prepared and submitted for approval by the Contractor.

13.0 Tenderers Visit to Sites

The Tenderers shall visit the new substation sites and the existing substations in
order to ascertain the actual conditions, verify the scope of works and accordingly
include in their offer all items required for the satisfactory operation of the system.

14.0 Brief Scope of Works

All details specified above item 1.0 to 13.0, schedule of requirements, price
schedule, detailed Technical Specification, General requirement specification,
drawings etc shall be read in conjunction with the detailed scope of work.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 15 of 536


PART A : NORTH AREA (1)

A1 NEW 33/11kV SHEIKH KHALIFA HOSPITAL (SHKH) SUBSTATION

A1E SCOPE OF WORK ELECTRICAL

A1E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified twelve (12) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of six (6)
outgoing cable feeders (3 feeeders on L.H.S and 3 feeders on R.H.S of 33kV
GIS). Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Seven (7) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 16 of 536


01.02.1 Two (2) Bus Sections.

01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Seven (7) cable feeders with fibre optic current differential protection scheme

01.02.4 Four (4) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.5 One (1) common control panel

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 21 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

A1E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 17 of 536


02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Twelve (12 ) 630A outgoing cable feeders with energy metering

02.01.5 Twelve (12 ) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

A1E03 Transformers and Neutral Earthing Resistor

03.01 High Voltage Distribution Transformer (HVDT) and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power
supply to auxiliary system of the substation as per schedule of requirement,
detailed technical specification etc. Auxiliary transformer sizing calculation that
includes motor starting conditions shall be submitted and as per calculation
transformer rating is to be selected.

A1E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control and relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 18 of 536


Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

A1E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required, the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of
11kV NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate the number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 19 of 536


05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control, communication and instrumentation cables for the entire substation.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides

05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 20 of 536


A1E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

A1E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.

A1E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 21 of 536


A1E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

A1E10 Diversion of existing 33kV Cables including FO cables to New Sheikh
Khalifa Hospital substation

At present three (3) circuits of 33kV Cables are already laid from existing
132/33/11kV Riffah II Main substation upto the 33/11kV transformers installed at
Sheikh Khalifa Hospital. Contractor shall disconnect, dismantle these cables and
divert,reroute, terminate to the 33kV GIS which will be installed under this
contract at Sheikh Khalifa Hospital Substation including rerouting and diversion
of existing two(2) nos of Fiber optic cables (32 fibres each). Contractor shall
completely install, test and commission these 33kV Cables and FO cables. Any
additional 33kV cables, FO cables, joints etc as required shall be included in the
scope of work within the quoted price. The scope shall also include supply,
erection, testing and commissioning of 19 inch rail mounted ODF with all
accessories for above FO cables at New Sheikh Khalifa Hospital substation.

A1 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.

















TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 22 of 536



ITEM
NO.

DESCRIPTION

CATEGORY
A1
SC1
SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA
SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.

SCADA
SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 23 of 536


SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:

Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA


A1C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS
General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The
scope of works listed below are only indicative and no additional costs will be
considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

A1C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under this section includes Site clearing/Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 24 of 536


01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation was carried out and the report is provided in these
Tender documents. However, this report is provided for guidance and information
only and this will not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC)
shall be carried out as per the Soil Investigation agencys recommendations and
as per design requirements with Authority/Engineers approval and all required
tests including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also to be considered. Bidder to include his price for Soil improvement
including Piling if required, in item A1C03.02 Sub structure concrete works.

01.04 Authority and Engineers Site Offices and facilities

Provision of Type-B Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

A1C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper
execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered. All design, working drawings and
shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in the Civil General
Schedules Volume V, Section 7.
A1C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings etc. as per the drawings including drainage,
plumbing and other services.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 25 of 536


03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks,
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks,
etc., up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls
etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.

03.06 Floor finishes including Skirting and dado, etc.

Floor finishes as specified in internal finishes in the Particular Technical
Specifications shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores
and Toilets as per specification and standards.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 26 of 536


03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminium channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.

03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including future/
spare ducts and sleeves as per specification and standards.

b) RCC Cable trenches with removable heavy duty RCC covers shall be
constructed inside transformer rooms and all other cable trenches and pull
pits required for the entire substation.

c) RCC trenches for fire main ring with RCC covers.

d) Construction of all manhole chambers required for plumbing, water supply,
telephone cabling etc and valve pits for service water and firefighting
systems are included in this scope of work.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 27 of 536


A1C04 Fire pump room

Construction of R.C.C framed building similar to substation main building, for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc. shall be included.

A1C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

A1C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements,
etc. All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.

A1C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.

07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.

A1C08 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including Cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 28 of 536


The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.

A1C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standards.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements.

A1C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing Municipality asphalt road as per specification and standards.

A1M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local
authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

A1M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.

Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 29 of 536


A1M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return
valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.

1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.

1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 30 of 536


1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.

A1M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.

1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.

1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 31 of 536


A1M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

A1M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 32 of 536


A1M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.

A1M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 33 of 536


1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

A1M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).

A1M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863,
IEC 332 and FM 3971.

A1M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the entire substation including but not
limited to the following:





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 34 of 536


M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of Hermetic
/ Semi-hermetic / Scroll compressors with suction and delivery valves, Condenser
and Evaporator coil with copper fins, Evaporator fan with drive, Drain pan, Filter
chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.

A1M3 : Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.,

A1M4: Service Water Supply System

All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves, shelter,
float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel

The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to transfer
the water from the underground water tank to the portable water storage tank
located at roof level. The inlet to the underground water tank from the water
distribution main line has to be provided with necessary water meter, gate valves,
isolation vales, etc. Necessary water flow & leakage test shall be carried out prior
to the handing over of substation. This shall include all works related to pumps,
pipe routings with protection, pipe supports etc.,




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 35 of 536


M4.02 Roof water storage tank, Booster pumps and piping works:
Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete distribution
of portable water pipes to various rooms such as Battery room, toilet etc., shall be
provided. This shall include all works related to pumps, pipe routings with
protection, pipe supports, etc. Shade provision shall be made for the pump set by
insulated aluminum sandwich panels supported by structural steel members.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 36 of 536


A2 NEW 33/11kV RIFFAH-3 (RIF3) SUBSTATION

A2E SCOPE OF WORK ELECTRICAL

A2E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified twelve (12) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of six (6)
outgoing cable feeders (3 feeeders on L.H.S and 3 feeders on R.H.S of 33kV
GIS). Also the substation Control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Seven (7) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 37 of 536


01.02.1 Two (2) Bus Sections.

01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Five (5) cable feeders with fibre optic current differential protection scheme

01.02.4 Two (2) cable feeders with pilot wire current differential protection scheme

01.02.5 Two (2) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.6 Two (2) nos of Floor standing Pilot wire isolation transformer cubicle suitable for
15 kV scheme (comprising of 15 kV isolation transformers, HV TBs etc).

Note: 15kV Pilot wire cable shall be laid and terminated from the above pilot wire
isolation transformer cubicle upto pilot wire termination cubicle which will be
installed by the cable contractor.

01.02.7 One (1) common control panel

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 21 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

A2E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 38 of 536


equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Twelve (12 ) 630A outgoing cable feeders with energy metering

02.01.5 Twelve (12 ) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

A2E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power
supply to auxiliary system of the substation as per schedule of requirement,
detailed technical specification etc. Auxiliary transformer sizing calculation that
includes motor starting conditions shall be submitted and as per calculation
transformer rating is to be selected.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 39 of 536


A2E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

A2E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of 11kV
NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate the number of cables and size with calculation. If more numbers of

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 40 of 536


cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.

05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the entire substation.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides

05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 41 of 536


05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.

A2E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

A2E07 110 V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 42 of 536


A2E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.

A2E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

A2E10 De-commissioning of Old Reefah substation

All the existing equipment of the Old Reefah 33/11kV Substation shall be
deenergized and decommissioned after energizing the new substation.


A2 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.

ITEM NO. DESCRIPTION CATEGORY
A2 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.
SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 43 of 536


SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.

SCADA
SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:

Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 44 of 536


A2C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the Tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The
scope of works listed below are only indicative and no additional costs will be
considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

A2C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization,etc.

Scope of work under this section includes Site clearing/ Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.

01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation will be carried out and the report will be provided
later. However, that report provided will be for guidance and information only and
this will not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the Soil Investigation agencys recommendations and as per
design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item A2C03.02 Sub structure concrete works.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 45 of 536


01.04 Authority and Engineers Site Offices and facilities

Provision of Type-A Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

A2C02 Design and Drawings

Conceptual layout drawings are provided in this Tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper
execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered . All design, working drawings
and shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.
A2C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings etc. as per the drawings including drainage
plumbing and other services.

03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks,
etc., up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls
etc., as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 46 of 536


03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal finishes in the Particular Technical
Specifications shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores,
and Toilets as per specification and standards.

03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminium channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 47 of 536


03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.

03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including
future/ spare ducts and sleeves as per specification and standards.

b) RCC Cable trenches with removable heavy duty RCC covers shall be
constructed inside transformer rooms and all other cable trenches and
pull pits required for the entire substation.

c) RCC trenches for fire main ring with RCC covers.

d) Construction of all manhole chambers required for plumbing, water
supply, telephone cabling etc and valve pits for service water and
firefighting systems are included in this scope of work.

A2C04 Fire pump room

Construction of R.C.C framed building similar to substation main building, for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc shall be included.

A2C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

A2C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements etc.
All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 48 of 536


A2C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.

07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.

A2C08 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including Cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.

The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.

A2C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standards.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements.

A2C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing Municipality asphalt road as per specification and standards.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 49 of 536


A2M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local
authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

A2M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.
Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

A2M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 50 of 536


valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.

1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.

1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 51 of 536


A2M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.

1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.

1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.

A2M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

A2M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 52 of 536


1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

A2M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 53 of 536


1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.

A2M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

A2M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 54 of 536


1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).

A2M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

A2M2: HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the entire substation including but not
limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of Hermetic
/ Semi-hermetic / Scroll compressors with suction and delivery valves, Condenser
and Evaporator coil with copper fins, Evaporator fan with drive, Drain pan, Filter
chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.







TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 55 of 536


A2M3 : Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.

A2M4: Service Water Supply System
All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves, shelter,
float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel
The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to transfer
the water from the underground water tank to the portable water storage tank
located at roof level. The inlet to the underground water tank from the water
distribution main line has to be provided with necessary water meter, gate valves,
isolation vales, etc. Necessary water flow & leakage test shall be carried out prior
to the handing over of substation. This shall include all works related to pumps,
pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:
Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete distribution
of portable water pipes to various rooms such as Battery room, toilet etc., shall be
provided. This shall include all works related to pumps, pipe routings with
protection, pipe supports, etc. Shade provision shall be made for the pump set by
insulated aluminum sandwich panels supported by structural steel members.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 56 of 536


A3 NEW 33/11kV ZAITH-3 (ZAT3) SUBSTATION

A3E SCOPE OF WORK ELECTRICAL

A3E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified twelve (12) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of six (6)
outgoing cable feeders (3 feeeders on L.H.S and 3 feeders on R.H.S of 33kV
GIS). Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Seven (7) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 57 of 536


01.02.1 Two (2) Bus Sections.

01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Seven (7) cable feeders with fibre optic current differential protection scheme

01.02.4 Four (4) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.5 One (1) common control panel

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 21 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

A3E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 58 of 536


02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Six (6 ) 630A outgoing cable feeders with energy metering

02.01.5 Eighteen (18) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

A3E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power
supply to auxiliary system of the substation as per schedule of requirement,
detailed technical specification etc. Auxiliary transformer sizing calculation that
includes motor starting conditions shall be submitted and as per calculation
transformer rating is to be selected.

A3E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 59 of 536


Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

A3E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of 11kV
NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate the number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 60 of 536


05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the entire substation.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides

05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 61 of 536


A3E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

A3E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.

A3E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 62 of 536


A3E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

A3 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.

ITEM NO. DESCRIPTION CATEGORY
A3 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA
SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.
All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.
SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 63 of 536


SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:

Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA


A3C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the Tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The
scope of works listed below are only indicative and no additional costs will be

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 64 of 536


considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

A3C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization,etc.

Scope of work under this section includes Site clearing/ Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.

01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation was carried out and the report is provided in these
Tender documents. As per the Soil investigation report, Stone columns/pile
foundation is recommended by the Soil investigation agency for main building
structures. Bidder to consider this requirement and include his price for Stone
column/piling works including all required tests in item A3 C03.02- Substructure
concrete works.

However, this report is provided for guidance and information only and this will
not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards to reconfirm the requirements.

01.04 Authority and Engineers Site Offices and facilities

Provision of Type-B Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

A3C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper
execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 65 of 536


elsewhere in the specification shall be adhered . All design, working drawings
and shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

A3C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings etc. as per the drawings including drainage,
plumbing and other services.

03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks, etc.,
up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls
etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 66 of 536


03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in internal finishes in the Particular Technical
Specification shall be considered.
03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores,
and Toilets as per specification and standards.

03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminum channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.

03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including
future/ spare ducts and sleeves as per specification and standards.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 67 of 536


b) RCC Cable trenches with removable heavy duty RCC covers shall be
constructed inside transformer rooms and all other cable trenches and
pull pits required for the entire substation.

c) RCC trenches for fire main ring with RCC covers.

d) Construction of all manhole chambers required for plumbing, water
supply, telephone cabling etc and valve pits for service water and
firefighting systems are included in this scope of work.

A3C04 Fire pump room

Construction of R.C.C framed building similar to substation main building, for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc shall be included.

A3C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

A3C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements etc.
All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.

A3C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.

07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 68 of 536


07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.

A3C08 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including Cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.

The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.

A3C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standard.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements.

A3C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing Municipality asphalt road as per specification and standards.

A3M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local
authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 69 of 536


A3M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.

Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

A3M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return
valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.

1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 70 of 536


1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.

1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.

A3M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.

1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.

1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 71 of 536


1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.

A3M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

A3M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 72 of 536


1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

A3M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment
Rooms, including LVAC, DC, Control and Relay Room, SCADA/Telecom Room,
11kV Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.







TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 73 of 536


1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.

A3M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

A3M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).

A3M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 74 of 536


and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

A3M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the entire substation including but not
limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of Hermetic
/ Semi-hermetic / Scroll compressors with suction and delivery valves, Condenser
and Evaporator coil with copper fins, Evaporator fan with drive, Drain pan, Filter
chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.

A3M3 Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.,

A3M4 Service Water Supply System

All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves, shelter,
float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel

The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to transfer
the water from the underground water tank to the portable water storage tank

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 75 of 536


located at roof level. The inlet to the underground water tank from the water
distribution main line has to be provided with necessary water meter, gate valves,
isolation vales, etc. Necessary water flow & leakage test shall be carried out prior
to the handing over of substation. This shall include all works related to pumps,
pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:

Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete distribution
of portable water pipes to various rooms such as Battery room, toilet etc., shall be
provided. This shall include all works related to pumps, pipe routings with
protection, pipe supports, etc. Shade provision shall be made for the pump set by
insulated aluminum sandwich panels supported by structural steel members.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 76 of 536


A4 NEW 33/11kV JAZEERAH INDUSTRIAL (JZIN) SUBSTATION

A4E SCOPE OF WORK ELECTRICAL

A4E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified sixteen (16) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of eight
(8) outgoing cable feeders (4 feeders on L.H.S and 4 feeders on R.H.S of 33kV
GIS). Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for additional bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Six (6) Cable feeders with Energy Metering.

01.01.4 Five (5) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing and commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 77 of 536


01.02.1 Two (2) Bus Sections.

01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Six (6) cable feeders with Energy Metering & fibre optic current differential
protection scheme

01.02.4 Five (5) cable feeders with fibre optic current differential protection scheme

01.02.5 Nine (9) sets of matching F.O. current differential protection relays, test terminal
blocks, etc (loose supply) for remote ends.

01.02.6 One (1) common control panel

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 33 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

A4E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of six (6)
outgoing cable feeders (3 feeders on L.H.S and 3 feeders on R.H.S of 11kV
switchgear).


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 78 of 536


All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Twelve (12 ) 630A outgoing cable feeders with energy metering

02.01.5 Twelve (12 ) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

A4E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power supply
to auxiliary system of the substation as per schedule of requirement, detailed
technical specification etc. Auxiliary transformer sizing calculation that includes
motor starting conditions shall be submitted and as per calculation transformer
rating is to be selected.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 79 of 536


A4E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

A4E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of 11kV
NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate the number of cables and size with calculation. If more numbers of

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 80 of 536


cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.

05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the entire substation.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides

05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 81 of 536


05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.

A4E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

A4E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 82 of 536


A4E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.

A4E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

A4 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.

ITEM NO. DESCRIPTION CATEGORY
A4 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 83 of 536


SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.

SCADA
SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:

Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 84 of 536


A4C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS
General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the Tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The
scope of works listed below are only indicative and no additional costs will be
considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

A4C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization,etc.

Scope of work under this section includes Site clearing/ Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.

01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation works will be carried out and the report will be
provided later. However, this report is provided for guidance and information only
and this will not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC)
shall be carried out as per the Soil Investigation agencys recommendations and
as per design requirements with Authority / Engineers approval and all required
tests including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item A4C03.02 Sub structure concrete works.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 85 of 536


01.04 Authority and Engineers Site Offices and facilities

Provision of Type-B Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

A4C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper
execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

A4C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings, etc. as per the drawings including drainage,
plumbing and other services.

03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks,
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks,
etc., up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls
etc., as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 86 of 536


03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in internal finishes in the Particular Technical
Specifications shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores,
and Toilets as per specification and standards.

03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminum channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 87 of 536


03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.

03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including
future/ spare ducts and sleeves as per specification and standards.

b) RCC Cable trenches with removable heavy duty RCC covers shall be
constructed inside transformer rooms and all other cable trenches and
pull pits required for the entire substation.

c) RCC trenches for fire main ring with RCC covers.

d) Construction of all manhole chambers required for plumbing, water
supply, telephone cabling etc and valve pits for service water and
firefighting systems are included in this scope of work.
A4C04 Fire pump room

Construction of R.C.C framed building similar to substation main building, for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc. shall be included.

A4C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

A4C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements,
etc. All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 88 of 536


A4C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.

07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.

A4C08 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including Cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.

The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.

A4C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standards.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements

A4C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing Municipality asphalt road as per specification and standards.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 89 of 536


A4M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local
authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

A4M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.

Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

A4M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 90 of 536


1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return
valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.

1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.

1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 91 of 536


A4M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.

1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.

1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.

A4M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

A4M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 92 of 536


1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

A4M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 93 of 536


1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.

A4M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

A4M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 94 of 536


1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).

A4M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

A4M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the entire substation including but not
limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of Hermetic
/ Semi-hermetic / Scroll compressors with suction and delivery valves, Condenser
and Evaporator coil with copper fins, Evaporator fan with drive, Drain pan, Filter
chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.







TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 95 of 536


A4M3 Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.,

A4M4 Service Water Supply System

All works required for complete fully functioning Service water system for the
entire substation including roof water storage tank, pumps, piping, valves, shelter,
float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel

The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to transfer
the water from the underground water tank to the portable water storage tank
located at roof level. The inlet to the underground water tank from the water
distribution main line has to be provided with necessary water meter, gate valves,
isolation vales, etc. Necessary water flow & leakage test shall be carried out prior
to the handing over of substation. This shall include all works related to pumps,
pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:
Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete distribution
of portable water pipes to various rooms such as Battery room, toilet etc., shall be
provided. This shall include all works related to pumps, pipe routings with
protection, pipe supports, etc. Shade provision shall be made for the pump set by
insulated aluminum sandwich panels supported by structural steel members.















TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 96 of 536


A5 CAPACITOR BANK INSTALLATION AT 33/11kV KHARAN
(KHAR) SUBSTATION

A5E SCOPE OF WORK ELECTRICAL

A5E01 11kV System

01.01 11kV Air Insulated Switchgear

01.01.1 Modification of existing 11kV Cable feeder (=K14) to convert as 11kV Capacitor
bank feeder

In the existing 11kV Switchgear (2000A, 31.5kA/3sec, Make: ABB Unigear Type
ZS1), one (1) 11kV Spare Cable Feeder (=K14) shall be modified and used as
11kV Capacitor bank Feeder. All work related to modification of GA, Schematic
diagram, new wiring and CT replacement shall be carried out as per the
protection requirement within the quoted price.

01.01.2 Modification of existing 11kV Cable feeder (=K25) to convert as 11kV Capacitor
bank feeder

In the existing 11kV Switchgear (2000A, 31.5kA/3sec, Make Siemens
Simoprime), one (1) 11kV Spare Cable Feeder (=K25) shall be modified and
used as 11kV Capacitor bank Feeder. All work related to modification of GA,
Schematic diagram, new wiring and CT replacement shall be carried out as per
the protection requirement within the quoted price.

A5E02 Capacitor Banks

02.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

02.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

A5E03 Cabling System

03.01 Cables

03.01.1 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 97 of 536


03.01.1.1 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

03.01.2 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension/modification works in the substation.

03.01.3 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the extension/modification works in the
substation.

03.02 Cable Terminations

03.02.1 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

03.02.1.1 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

03.02.2 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.02.3 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.03 Cable Trays, Conduits and Accessories

03.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension/modification
works in the substation.

A5E04 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 98 of 536


A5E05 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

A5 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.























TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 99 of 536


ITEM NO. DESCRIPTION CATEGORY
A5 SC1 SCOPE OF WORK SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of basic and
extension racks to update the existing ABB RTU 232
to the new version of ABB RTU 560 to accommodate
the new/modified 11kV circuits as per the substation
requirements and SCADA data.

Scope shall also include complete substation
requirements as per tender documents including point
to point test for all affected circuits, end to end testing
of new/upgraded circuits with UAQ SCC, providing
Accessories, cabling etc. as per specification
requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA
SC 1.2 Existing 11kV CCC panel to be upgraded in all
respect to include the new/modified circuits. All works
required to complete the scope including providing all
necessary accessories, DIN Rails, Cable troughs,
cabling, transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope.

All design and engineering of CCC to be included in
the scope as per the specification and approved
before manufacturing.

SCADA
SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

SCADA
SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 100 of 536


A5C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the Tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

A5C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area and demobilization as per
the specification and requirements stated elsewhere in the specification.

Prior to commencement of works for new Capacitor bank building, existing
services at the proposed location for the new Capacitor bank building to be
rerouted and existing structures such as RCC manholes/foundations etc.
demolished and reconstructed on suitable alternate location. The proposed area
shall be backfilled, graded and leveled to match with the existing Substation level
on completion of the works. Tenderer shall include his price for all the above
works

01.02 Soil Investigation

During the execution the Contractor shall employ an agency with Authority /
Engineers approval to carry out the Soil investigation for the Substation as per
specification and standards.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the Soil Investigation agencys recommendations and as per
design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in Item A5 C03.02 Sub structure Concrete Works.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 101 of 536


01.03 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

A5C02 Design and Drawings

Conceptual layout drawings are provided in this Tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered . All design, working drawings and
shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

A5C03 New Capacitor Bank Building with Clean Agent room

Design and Construction of Capacitor bank building for housing Capacitor bank
units and Clean agent room as per the specifications, including drainage, cable
trenches and other services.

03.01 Earth Work

Earth work includes excavation for foundations, trenches, duct banks etc. This
includes necessary planking/ shoring and strutting, backfilling, dewatering, etc.
The excess earth material after backfilling shall be carted away to a designated
location approved by the concerned authority. Extreme care shall be taken to
protect the existing equipment and structures during construction. All required
protection arrangements shall be made prior to excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement, beams, columns, walls, trenches, tunnels, duct
banks, etc. up to ground floor level including ground floor slab. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor slab such as walls,
columns, beams, slabs, arches, corbels, sill beams, lintel beams, tie beams,
parapet walls, etc., as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 102 of 536


03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors

Supply and installation of doors for the new building including ironmongeries as
per specification and standards. Sliding gate and solenoid locks for Capacitor
Bank rooms are also included in this Scope of work.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specification shall be considered.

03.07 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.08 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.09 External Finishes

All external surfaces of the buildings shall be finished as per
specification/finishing schedule and standards. External elevations of the new
rooms shall match with the existing Substation building.

03.10 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.

03.11 Cable Duct Banks, Trenches Manhole chambers and all other civil works

RCC Cable trenches with removable heavy duty RCC covers shall be constructed
for 11kV, LV and control cables between existing 33kV substation basement and
the new Capacitor bank building. Core drilling in existing substation basement
walls is also included.

All other cable trenches and pull pits required for the entire extension works are
also included in this scope of work.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 103 of 536


This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Capacitor bank installation works.

A5C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards to match with the existing system.

A5C05 Internal Roads, Pavements and Site Surfacing

05.01 Internal Roads

All required works for Road interconnection between existing substation road and
new Capacitor bank building as per Specifications and standards including
extension/modification of existing internal roads around the new Capacitor bank
building (type II interlocking tiled road or to match existing internal road type)
and reinstatement of disturbed/damaged existing roads, as per specification and
standards.

05.02 Pavements and Walkways

All works for Pavements/walkways for proposed new Capacitor bank building and
reinstatement of existing walkways as per specification and standards.

05.03 Gravel spreading and filling

Reinstatement of Gravel spreading/filling for open areas not covered by
roads/pavements to match with existing.

A5C06 Modification works in existing Substation Building

All required Civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing of additional openings in the Ground
floor slabs and walls if required as per Electrical scope and designing and
providing the slab support system necessitated due to the modification works.
Also all openings rendered redundant on completion of the works to be
closed/sealed with appropriate means to the approval of Authority/Engineer.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 104 of 536


Part of existing boundary wall to be demolished and Boundary wall, wherever
demolished during construction works, to be reinstated as originally existing if
required.

New Boundary wall to be constructed around new extension of the plot as per
specification and standards to match with the existing Boundary wall.

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.

A5M SCOPE OF WORK MECHANICAL

A5M 1 Fire Protection and Detection System

A5M 1C Clean Agent System

A5M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 105 of 536


1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

A5M 1D Automatic Fire Detection and Alarm System

All work necessary for extension of existing Fire Detection & Alarm System with
all accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Clean Agent Room. On completion of Fire Detection
and Alarm System modification works, existing Fire Alarm Control Panel shall be
tested for correct operation.

1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.
.
1D.02 Photoelectric smoke detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors, as per NFPA recommendations.

A5M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) for new Capacitor Bank rooms.







TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 106 of 536


A5M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

A5M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air
Conditioning and Ventilation plant fully functioning for the new Capacitor room
and clean agent room including but not limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers etc., Bib tap with hose tapping from existing service water
line to be provided near the package units.

M2.02 Extraction fan for clean agent room

M2.03 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.04 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.05 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.06 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.















TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 107 of 536


A6. PROTECTION MODIFICATION WORKS AT EXISTING SUBSTATIONS IN
NORTH AREA (1)

All the modifications as required in the 33 kV GIS, LV Compartment,Control &
Relay Panels , Busbar protection panels etc including but not limited to changing
the labels, modifying the schematic diagrams, GA drawings, layout drawing
preparation and revision of all relevant drawings, SLDs, etc. as required to reflect
the circuit changes shall be carried out by the contractor under scope of this
contract within the quoted price. All such drawings whether specifically
mentioned or not shall be modified and submitted to Engineer/Authoritys
approval by the substation contractor at an early stage of project execution. All
extension and modification works shall be carried out by the substation
contractor with minimum outage only. The substation contractor in his offer shall
state the requirement of shut down in the existing substations.

The complete set of as built drawings (wherever changes as required) shall be
resubmitted incorporating the changes. The Authority reserve the right to ask the
substation contractor to retest and recommission any item or plant disturbed
during modification works without any cost and time implication to the Authority
and no deviation is acceptable in this regard. The contractor must visit the site
and all necessary existing information, drawings, documents, etc. required shall
be collected without any implications to authority. Any minor civil modifications
anticipated in the 33 kV GIS room, Control & Relay room etc. shall be carried out
by the substation contractor.

Modification of the existing protection panels shall be carried out by qualified and
experienced Engineer approved by FEWA. All the modifications shall be carried
out with minimum shutdown requirements and without any disturbance to existing
system. The tenderer shall make site visit and assess themselves all the required
modifications to be carried out in existing panels and the cost towards all works
shall be included within the quoted price.
All modifications required in existing panels, relay and control panels, AC/DC
system etc shall be included within the quoted price.

The existing substation as built drawings including but not limited to layout of
main equipments, sections, cable route layout, cable tray layout, earthing
drawings, control and protection schematic diagrams of existing bays (Bus
section, common control panels, adjacent panels etc), substation single line
diagrams, associated civil and electromechanical drawings affected by the
modification works etc shall be suitably modified and submitted for approval at an
early stage. All such drawings shall also be made as final as built drawings by
the substation contractor in addition to the equipment drawings.

Any relocation of existing equipments required for works shall be deemed to be
included in the quoted price. New control cables/LV power cables, fixing
arrangement of relocated equipments etc are also included within the quoted
price.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 108 of 536


All the relay setting calculations as required by Authority shall be carried out by
the contractor under scope of this contract and shall be submitted to
Engineer/Authority for approval.

Any necessary details including but not limited to existing relay setting and
drawings/ information etc as required shall be collected from site/relays by
contractor under the scope of this tender. All schematic diagrams shall be tested
and all protection testing including end to end testing shall be carried out within
the quoted price.

Providing manufacturer Specialist for testing and commissioning of Main
protection relays for 33 kV OHL/cable feeders shall be under the scope of this
tender. All cost towards testing and commissioning of Main protection relays by
manufacturer specialist shall be included within the quoted price.

The Main protection relays in the new substation shall be matched with existing
relays at respective remote end substation. In case contractor cannot comply
with this requirement then all cost towards modification and replacement of Main
Protection relays at existing respective remote end substations shall be included
within the quoted price of existing substation modification works without any
contractual implication to Authority. However Authority reserves the right to
decide either to supply new relays and modify the existing panel or to match with
existing relays and the same will be decided during engineering stage.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

A6.1 Protection Modification Works at existing Riffah II Main (RIMN2) Substation
for New Sheikh Khalifa Hospital cable feeders Three (3) circuits

The existing 33kV C&R Panels (H202, H203 & H208) presently designated as
Sheikh Khalifa Hospital Circuit-1, 2 & 3 shall be modified as follows:

A6.1.1 Protection modification as required for New Sheikh Khalifa Hospital Cable feeder
(H202) Circuit No.1

A6.1.2 Protection modification as required for New Sheikh Khalifa Hospital Cable feeder
(H203) Circuit No.2

A6.1.3 Protection modification as required for New Sheikh Khalifa Hospital Cable feeder
(H208) Circuit No.3

The existing 33kV C&R Panels (H202, H203 & H208) are equipped with main
protection suitable for fibre optic current differential protection relay type Solkor
N, manufactured by Siemens.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 109 of 536


Bidder shall match the above main protection relay at new Sheikh Khalifa
Hospital Substation. However, if matching is not possible then bidder shall
replace the existing main protection relay matching with new Sheikh Khalifa
Hospital at Riffah II Main Substation within the overall quoted price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new fibre optic
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

A6.2 Protection Modification Works at existing Riffah Main (RIMN) Substation for
New Riffah-3 substation cable feeeders Three (3) circuits

The existing 33kV Cable Feeder Bays (Bays # H201, H202 & H208) C&R Panels
shall be modified as follows.

A6.2.1 Protection modification as required for New Riffah-3 Cable feeder (H201) Circuit
No.1

A6.2.2 Protection modification as required for New Riffah-3 Cable feeder (H202) Circuit
No.2

A6.2.3 Protection modification as required for New Riffah-3 Cable feeder (H208) Circuit
No.3

The existing 33kV Spare C&R Panels (H201, H202 & H208) are equipped with
main protection suitable for fibre optic current differential protection relay type
Solkor N, manufactured by Siemens.

Bidder shall match the above main protection relay at new Riffah 3 Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with new Riffah 3 at existing Riffah Main Substation
within the overall quoted price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new fibre optic
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 110 of 536


to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

A6.3 Protection Modification Works at existing Al Zaith II Substation for New
Riffah-3 cable feeders Two (2) circuits

The existing 33kV Cable Feeder Bays (Bays # H202 & H203) C&R Panels shall
be modified as follows.

A6.3.1 Protection modification as required for New Riffah-3 Cable feeder (H202) Circuit
No.1

A6.3.2 Protection modification as required for New Riffah-3 Cable feeder (H203) Circuit
No.2

The existing 33kV C&R Panels are equipped with main protection suitable for
pilot wire protection type Solkor Rf, Manufactured by Siemens.

Bidder shall match the above main protection relay at new Riffah-3 Substation.

However, if matching is not possible then bidder shall replace the existing pilot
wire protection relay matching with new Riffah -3 at Al Zaith II Substation. The
send or receive ends shall be properly coordinated by the bidder in order to
satisfy the scheme requirement. The compatibility of new relays installed at
Riffah-3 (in case of retaining the pilot wire protection relay at Zaith II) shall be
confirmed by the Relay manufacturer.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new pilot wire
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

CT Calculation shall be submitted and the new relay shall be suitable for the CT
characteristic available at the existing Al Zaith II substation. Bidders shall test the
CTs and note the parameters before making the CT sizing calculation.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 111 of 536


A6.4 Protection Modification Works at existing Riffah II Main (RIMN2) Substation
for New Zaith-3 substation cable feeders Three (3) circuits

The existing 33kV Spare Cable Feeder Bays (Bays # H204, H209 & H211) C&R
Panels shall be modified as follows.

A6.4.1 Protection modification as required for New Zaith-3 Cable feeder (H204) Circuit
No.1

A6.4.2 Protection modification as required for New Zaith-3 Cable feeder (H209) Circuit
No.2

A6.4.3 Protection modification as required for New Zaith-3 Cable feeder (H211) Circuit
No.3

The existing 33kV Spare C&R Panels (H204, H209 & H211) are equipped with
main protection suitable for fibre optic current differential protection relay type
Solkor N, manufactured by Siemens.

Bidder shall match the above main protection relay at new Zaith-3 Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with new Zaith-3 at existing Riffah II Main Substation
within the overall quoted price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new fibre optic
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

A6.5 Protection Modification Works at existing Riffah Main (RIMN) Substation for
New Jazeerah Industrial cable feeders Two (2) circuits

The existing 33kV Spare Cable Feeder Bays (Bays # H207 & H209) C&R Panels
shall be modified as follows.

A6.5.1 Protection modification as required for New Jazeerah Industrial Cable feeder
(H207) Circuit No.1


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 112 of 536


A6.5.2 Protection modification as required for New Jazeerah Industrial Cable feeder
(H209) Circuit No.2

The existing 33kV Spare C&R Panels (H207 & H209) are equipped with main
protection suitable for fibre optic current differential protection relay type Solkor
N, manufactured by Siemens.

Bidder shall match the above main protection relay at new Jazeerah Industrial
Substation. However, if matching is not possible then bidder shall replace the
existing main protection relay matching with new Jazeerah Industrial at existing
Riffah Main Substation within the overall quoted price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new fibre optic
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 113 of 536


PART B : NORTH AREA (2)

B1 NEW 33/11kV RAMS-2 (RMS2) SUBSTATION

B1E SCOPE OF WORK ELECTRICAL

B1E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified twelve (12) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of six (6)
outgoing cable feeders (3 feeeders on L.H.S and 3 feeders on R.H.S of 33kV
GIS). Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Seven (7) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 114 of 536


01.02.1 Two (2) Bus Sections.

01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Seven (7) cable feeders with fibre optic current differential protection scheme

01.02.4 Three (3) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.5 One (1) common control panel

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 21 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

B1E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 115 of 536


02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Six (6 ) 630A outgoing cable feeders with energy metering

02.01.5 Eighteen (18) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

B1E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power
supply to auxiliary system of the substation as per schedule of requirement,
detailed technical specification etc. Auxiliary transformer sizing calculation that
includes motor starting conditions shall be submitted and as per calculation
transformer rating is to be selected.

B1E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 116 of 536


Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

B1E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of 11kV
NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate the number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 117 of 536


05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the entire substation.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides

05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 118 of 536


B1E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

B1E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.

B1E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 119 of 536


B1E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

B1 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.

ITEM NO. DESCRIPTION CATEGORY
B1 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA
SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 120 of 536


SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:

Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA


B1C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the Tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 121 of 536


scope of works listed below are only indicative and no additional costs will be
considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

B1C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under this section includes Site clearing/ Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.

01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation was carried out and the report is provided in these
Tender documents. However, this report is provided for guidance and information
only and this will not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC)
shall be carried out as per the Soil Investigation agencys recommendations and
as per design requirements with Authority/Engineers approval and all required
tests including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item B1C03.02 Sub structure Concrete Works.

01.04 Authority and Engineers Site Offices and facilities

Provision of Type-A Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 122 of 536


B1C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper
execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered . All design, working drawings
and shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in the Civil General
Schedules Volume V, Section 7.

B1C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings, etc. as per the drawings including drainage,
plumbing and other services.

03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks,
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks,
etc., up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls,
etc. as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 123 of 536


03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.

03.06 Floor finishes including Skirting and dado, etc.

Floor finishes as specified in Internal finishes in the Particular Technical
Specifications shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores
and Toilets as per specification and standards.

03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminium channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 124 of 536


03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including
future/ spare ducts and sleeves as per specification and standards.

b) RCC Cable trenches with removable heavy duty RCC covers shall be
constructed inside Transformer rooms and all other cable trenches
and pull pits required for the entire substation.

c) RCC trenches for fire main ring with RCC covers.

d) Construction of all manhole chambers required for plumbing, water
supply, telephone cabling etc and valve pits for service water and
firefighting systems are included in this scope of work.

B1C04 Fire pump room

Construction of R.C.C framed building similar to substation main building, for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc. shall be included.

B1C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

B1C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements,
etc. All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.

B1C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 125 of 536


07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.

B1C08 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including Cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.

The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.

B1C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standards.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements.

B1C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing Municipality asphalt road as per specification and standards.

B1M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 126 of 536


authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

B1M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.

Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

B1M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return
valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 127 of 536


1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.

1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.

B1M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.

1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 128 of 536


1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.

B1M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

B1M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 129 of 536


1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

B1M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 130 of 536


1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.

B1M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

B1M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).

B1M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 131 of 536


and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

B1M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the entire substation including but not
limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of Hermetic
/ Semi-hermetic / Scroll compressors with suction and delivery valves, Condenser
and Evaporator coil with copper fins, Evaporator fan with drive, Drain pan, Filter
chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.

B1M3 Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.

B1M4 Service Water Supply System
All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves, shelter,
float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel
The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to transfer
the water from the underground water tank to the portable water storage tank

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 132 of 536


located at roof level. The inlet to the underground water tank from the water
distribution main line has to be provided with necessary water meter, gate valves,
isolation vales, etc. Necessary water flow & leakage test shall be carried out prior
to the handing over of substation. This shall include all works related to pumps,
pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:
Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete distribution
of portable water pipes to various rooms such as Battery room, toilet etc., shall be
provided. This shall include all works related to pumps, pipe routings with
protection, pipe supports, etc. Shade provision shall be made for the pump set by
insulated aluminum sandwich panels supported by structural steel members.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 133 of 536


B2 NEW 33/11kV SHAMAL (SHML) SUBSTATION

B2E SCOPE OF WORK ELECTRICAL

B2E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified twelve (12) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of six (6)
outgoing cable feeders (3 feeeders on L.H.S and 3 feeders on R.H.S of 33kV
GIS). Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Seven (7) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.

01.02.1 Two (2) Bus Sections.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 134 of 536


01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Seven (7) cable feeders with fibre optic current differential protection scheme

01.02.4 Four (4) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.5 One (1) common control panel

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 21 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

B2E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 135 of 536


02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Six (6 ) 630A outgoing cable feeders with energy metering

02.01.5 Eighteen (18) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

B2E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power supply
to auxiliary system of the substation as per schedule of requirement, detailed
technical specification etc. Auxiliary transformer sizing calculation that includes
motor starting conditions shall be submitted and as per calculation transformer
rating is to be selected.

B2E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 136 of 536


Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

B2E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of 11kV
NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate the number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 137 of 536


05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the entire substation.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides

05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 138 of 536


B2E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

B2E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.

B2E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 139 of 536


B2E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

B2 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.

ITEM NO. DESCRIPTION CATEGORY
B2 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA
SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 140 of 536


SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:

Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 141 of 536


B2C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the Tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The
scope of works listed below are only indicative and no additional costs will be
considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

B2C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under this section includes Site clearing/ Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.

01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation was carried out and the report is provided in these
Tender documents. However, this report is provided for guidance and information
only and this will not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC)
shall be carried out as per the Soil Investigation agencys recommendations and
as per design requirements with Authority/Engineers approval and all required
tests including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item B1C03.02 Sub structure Concrete Works.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 142 of 536


01.04 Authority and Engineers Site Offices and facilities

Provision of Type-B Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

B2C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper
execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

B2C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings, etc. as per the drawings including drainage,
plumbing and other services.

03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks, etc.,
up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls
etc., as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 143 of 536


03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in internal finishes in the Particular Technical
Specifications shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores
and Toilets as per specification and standards.

03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminium channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 144 of 536


03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.

03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including
future/ spare ducts and sleeves as per specification and standards.

b) RCC Cable trenches with removable heavy duty RCC covers shall be
constructed inside transformer rooms and all other cable trenches and
pull pits required for the entire substation.

c) RCC trenches for fire main ring with RCC covers.

d) Construction of all manhole chambers required for plumbing, water
supply, telephone cabling etc and valve pits for service water and
firefighting systems are included in this scope of work.
B2C04 Fire pump room

Construction of R.C.C framed building similar to substation main building, for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc shall be included.

B2C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

B2C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements etc.
All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 145 of 536


B2C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.
07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.

B2C08 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.

The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.

B2C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standard.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements

B2C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing municipality asphalt road as per specification and standards.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 146 of 536


B2M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local
authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

B2M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.

Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

B2M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 147 of 536


valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.

1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.

1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 148 of 536


B2M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.

1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.

1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.

B2M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

B2M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 149 of 536


1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

B2M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 150 of 536


1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.

B2M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

B2M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 151 of 536


1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).

B2M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

B2M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the entire substation including but not
limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of Hermetic
/ Semi-hermetic / Scroll compressors with suction and delivery valves, Condenser
and Evaporator coil with copper fins, Evaporator fan with drive, Drain pan, Filter
chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.







TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 152 of 536


B2M3 Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.,

B2M4 Service Water Supply System

All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves, shelter,
float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel

The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to transfer
the water from the underground water tank to the portable water storage tank
located at roof level. The inlet to the underground water tank from the water
distribution main line has to be provided with necessary water meter, gate valves,
isolation vales, etc. Necessary water flow & leakage test shall be carried out prior
to the handing over of substation. This shall include all works related to pumps,
pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:
Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete distribution
of portable water pipes to various rooms such as Battery room, toilet etc., shall be
provided. This shall include all works related to pumps, pipe routings with
protection, pipe supports, etc. Shade provision shall be made for the pump set by
insulated aluminum sandwich panels supported by structural steel members.














TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 153 of 536


B3 NEW 33/11kV GHALILAH (GHAL) SUBSTATION

B3E SCOPE OF WORK ELECTRICAL

B3E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified twelve (12) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of six (6)
outgoing cable feeders (3 feeeders on L.H.S and 3 feeders on R.H.S of 33kV
GIS). Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Seven (7) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 154 of 536


01.02.1 Two (2) Bus Sections.

01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Two (2) cable feeders with fibre optic current differential protection scheme

01.02.4 Five (5) cable feeders with Pilot wire current differential protection scheme

01.02.5 Five (5) nos of Floor standing Pilot wire isolation transformer cubicles suitable for
15kV scheme (comprising of 15kV isolation transformers, HV TBs etc)

Note: 15kV Pilot wire cable shall be laid and terminated from the above pilot wire
isolation transformer cubicle upto pilot wire termination cubicle which will be
installed by the cable contractor.

01.02.6 One (1) common control panel

Note: Protection of new Ghalilah and new Wadi Sham substation shall be coordinated
and subject to approval.

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 21 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

B3E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 155 of 536


equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Nine (9) 1250A cable feeders with Energy Metering for SWRO Plant

02.01.5 Three (3 ) 630A outgoing cable feeders with energy metering

02.01.6 Twelve (12) 630A outgoing cable feeders

02.01.7 Three (3) Capacitor bank feeders

02.02 11kV Busbar Protection Panels

02.02.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 11kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

B3E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 156 of 536


03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power supply
to auxiliary system of the substation as per schedule of requirement, detailed
technical specification etc. Auxiliary transformer sizing calculation that includes
motor starting conditions shall be submitted and as per calculation transformer
rating is to be selected.

B3E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

B3E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of 11kV
NER circuits.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 157 of 536


05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate the number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.

05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the entire substation.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides

05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 158 of 536


05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.

B3E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

B3E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 159 of 536


07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.

B3E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.

B3E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

B3E10 Diversion of Existing 33kV Cables & Pilot cables to New Ghalilah
substation

The 33kV Cable circuits at existing Ghalilah 132/33/3.3kV Power substation
which includes two (2) nos from existing Sham substation & three (3) nos from
existing Khor Kuwair substation shall be diverted, rerouted and terminated to the
33kV GIS which will be installed under this contract at new Ghalilah substation
including rerouting, diversion and termination of related pilot wire cables to the
new Ghalilah substation. Contractor shall completely install, test and commission
these 33kV Cables and Pilot wire cables. Any additional 33kV cables, Pilot
cables, joints, pilot wire terminations etc as required shall be include in the
scope of work within the quoted price. The scope shall also include supply,
installation, testing and commissioning of Pilot cable termination cubicle (one
pilot wire termination cubicle shall be supplied for each pilot cable and totally
five(5) nos to be supplied) at New Ghalilah substation.

B3 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 160 of 536


ITEM NO. DESCRIPTION CATEGORY
B3 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA
SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.
SCADA
SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 161 of 536


SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:

Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA


B3C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the Tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The
scope of works listed below are only indicative and no additional costs will be
considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

B3C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under this section includes Site clearing/ Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 162 of 536


01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation was carried out and the report is provided in these
Tender documents. However, this report is provided for guidance and information
only and this will not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC)
shall be carried out as per the Soil Investigation agencys recommendations and
as per design requirements with Authority/Engineers approval and all required
tests including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item B3C03.02 Sub structure concrete works.

01.04 Authority and Engineers Site Offices and facilities

Provision of Type-B Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices

B3C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper
execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered. All design, working drawings and
shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in the Civil General
Schedules Volume V, Section 7.

B3C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings, etc. as per the drawings including drainage,
plumbing and other services.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 163 of 536


03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks,
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks,
etc., up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls
etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.
03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal finishes in the Particular Technical
Specifications shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores
and Toilets as per specification and standards.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 164 of 536


03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminum channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.

03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including
future/ spare ducts and sleeves as per specification and standards.

b) RCC Cable trenches with removable heavy duty RCC covers shall be
constructed inside transformer rooms and all other cable trenches and
pull pits required for the entire substation.

c) RCC trenches for fire main ring with RCC covers.

d) Construction of all manhole chambers required for plumbing, water
supply, telephone cabling etc and valve pits for service water and
firefighting systems are included in this scope of work.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 165 of 536


B3C04 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements etc.
All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.

B3C05 Drainage works

05.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.

05.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

05.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.

B3C06 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.

The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 166 of 536


B3C07 Internal Roads, Pavements and Site Surfacing

07.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

07.02 All works for Pavements/ walkway as per specification and standard.

07.03 Gravel spreading / filling for open areas not covered by roads/ pavements

B3C08 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing municipality asphalt road as per specification and standards.

B3M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local
authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

B3M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.

Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

B3M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 167 of 536


1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return
valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.

1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.

1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 168 of 536


instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.

B3M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.

1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.

1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.

B3M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

B3M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 169 of 536


1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

ll work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

B3M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 170 of 536


supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.

B3M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 171 of 536


B3M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).

B3M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

B3M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the entire substation including but not
limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of Hermetic
/ Semi-hermetic / Scroll compressors with suction and delivery valves, Condenser
and Evaporator coil with copper fins, Evaporator fan with drive, Drain pan, Filter
chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 172 of 536


M2.08 Complete HVAC system testing, commissioning and training.

B3M3 Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.,

B3M4 Service Water Supply System

All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves, shelter,
float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel

The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to transfer
the water from the underground water tank to the portable water storage tank
located at roof level. The inlet to the underground water tank from the water
distribution main line has to be provided with necessary water meter, gate valves,
isolation vales, etc. Necessary water flow & leakage test shall be carried out prior
to the handing over of substation. This shall include all works related to pumps,
pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:

Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete distribution
of portable water pipes to various rooms such as Battery room, toilet etc., shall be
provided. This shall include all works related to pumps, pipe routings with
protection, pipe supports, etc. Shade provision shall be made for the pump set by
insulated aluminum sandwich panels supported by structural steel members.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 173 of 536


B4 NEW 33/11kV SEIH AL BURAIRAT (SEBU) SUBSTATION

B4E SCOPE OF WORK ELECTRICAL

B4E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified twelve (12) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of six (6)
outgoing cable feeders (3 feeeders on L.H.S and 3 feeders on R.H.S of 33kV
GIS). Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Seven (7) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 174 of 536


01.02.1 Two (2) Bus Sections.

01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Seven (7) cable feeders with fibre optic current differential protection scheme

01.02.4 Two (2) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.5 One (1) common control panel

Note: 1) Protection of new SEBU and existing Nakheel Old Town substation shall be
coordinated and subject to approval.

2) Protection of new SEBU and existing Qusaidat Main substation shall be
coordinated and subject to approval.

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 21 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

B4E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 175 of 536


All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Six (6 ) 630A outgoing cable feeders with energy metering

02.01.5 Eighteen (18) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

B4E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power supply
to auxiliary system of the substation as per schedule of requirement, detailed
technical specification etc. Auxiliary transformer sizing calculation that includes
motor starting conditions shall be submitted and as per calculation transformer
rating is to be selected.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 176 of 536


B4E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

B4E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of 11kV
NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate the number of cables and size with calculation. If more numbers of

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 177 of 536


cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.

05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the entire substation.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides

05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 178 of 536


05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.

B4E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

B4E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.

B4E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 179 of 536


boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.

B4E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

B4E10 Diversion of Existing 33 kV Cables including FO Cables to New Seih Al
Burairat substation

All existing 33kV Cable circuits at existing 33/11kV Zahra substation which
includes three (3) nos feeders from Old Town Main Substation & two (2) nos
feeders from Qusaidat substation shall be diverted, rerouted and terminated at
the 33kV GIS which will be installed under this contract at Seih Al Burairat
substation including rerouting and diversion of existing three (3) nos of Fiber
optic cables (32 fibres each). Contractor shall completely install, test and
commission these 33kV Cables and FO cables. Any additional 33kV cables, FO
cables, joints, FO terminations etc as required shall be included in the scope of
work within the quoted price. The scope shall also include supply, erection,
testing and commissioning of 19 inch rail mounted ODF with all accessories for
the above FO cables at New Seih Al Burairat substation.

B4E11 Diversion of Existing 11kV Cables to New Seih Al Burairat substation

All existing 11kV Cable circuits at existing 33/11kV Zahra substation (around 10
nos) shall be diverted, rerouted and terminated at the 11kV Switchgear which
will be installed under this contract at Seih Al Burairat substation. Contractor shall
completely install, test and commission these 11kV Cables. Any additional 11kV
cables, joints etc as required shall be included in the scope of work within the
quoted price.

B4E12 De-commissioning of Old Zahra 33/11 kV substation

All the existing equipment of the Old Zahra 33/11kV Substation shall be
deenergized and decommissioned after energization of new 33/11kV Seih Al
Burairat substation.

B4 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 180 of 536


specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.

ITEM NO. DESCRIPTION CATEGORY
B4 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA
SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.

SCADA
SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 181 of 536


SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:
Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA


B4C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the Tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The
scope of works listed below are only indicative and no additional costs will be
considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

B4C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under this section includes Site clearing/Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 182 of 536


01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation will be carried out and the report will be provided
later. However, that report provided will be for guidance and information only and
this will not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC)
shall be carried out as per the Soil Investigation agencys recommendations and
as per design requirements with Authority/Engineers approval and all required
tests including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item B4 C03.02 Sub structure concrete works.

01.04 Authority and Engineers Site Offices and facilities

Provision of Type-B Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

B4C02 Design and Drawings

Conceptual layout drawings are provided in this Tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper
execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered. All design, working drawings and
shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in the Civil General
Schedules Volume V, Section 7.

B4C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings, etc. as per the drawings including drainage,
plumbing and other services.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 183 of 536


03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks,
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks,
etc., up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls
etc. as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in internal finishes in the Particular Technical
Specifications shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores
and Toilets as per specification and standards.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 184 of 536


03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminium channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.


03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including
future/ spare ducts and sleeves as per specification and standards.

b) RCC Cable trenches with removable heavy duty RCC covers shall be
constructed inside transformer rooms and all other cable trenches and
pull pits required for the entire substation.

c) RCC trenches for fire main ring with RCC covers.

d) Construction of all manhole chambers required for plumbing, water
supply, telephone cabling etc and valve pits for service water and
firefighting systems are included in this scope of work.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 185 of 536


B4C04 Fire pump room

Construction of R.C.C framed building similar to substation main building, for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc shall be included.

B4C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

B4C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements,
etc. All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.

B4C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.

07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.

B4C08 Boundary wall extension and Gate

Part of existing boundary wall to be demolished as indicated on the Tender
drawings and Boundary wall, wherever demolished during construction works, to
be reinstated as originally existing, if required.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 186 of 536


New Boundary wall to be constructed around new extension of the plot to match
with the existing Boundary wall.and new gates to be installed, all as per
specification and standards.

B4C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standards.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements.

B4C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing municipality asphalt road as per specification and standards.

B4M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local
authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

B4M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.

Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

B4M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 187 of 536


discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return
valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.

1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.

1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 188 of 536


1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.

B4M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.

1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.
1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.

B4M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

B4M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 189 of 536


wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

B4M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 190 of 536


1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.

B4M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 191 of 536


1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

B4M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).

B4M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

B4M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air
Conditioning and Ventilation plant fully functioning for the entire substation
including but not limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and
return air diffusers, sand trap louvers with filters, expansion Joints and supports.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 192 of 536


M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.

B4M3 Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.,

B4M4 Service Water Supply System

All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves,
shelter, float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel

The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to
transfer the water from the underground water tank to the portable water
storage tank located at roof level. The inlet to the underground water tank from
the water distribution main line has to be provided with necessary water meter,
gate valves, isolation vales, etc. Necessary water flow & leakage test shall be
carried out prior to the handing over of substation. This shall include all works
related to pumps, pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:

Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete
distribution of portable water pipes to various rooms such as Battery room, toilet
etc., shall be provided. This shall include all works related to pumps, pipe
routings with protection, pipe supports, etc. Shade provision shall be made for
the pump set by insulated aluminum sandwich panels supported by structural
steel members.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 193 of 536


B5 NEW 33/11kV WADI SHAM (WDSH) SUBSTATION

B5E SCOPE OF WORK ELECTRICAL

B5E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified twelve (12) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of six (6)
outgoing cable feeders (3 feeeders on L.H.S and 3 feeders on R.H.S of 33kV
GIS). Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Seven (7) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.

01.02.1 Two (2) Bus Sections.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 194 of 536


01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Seven (7) cable feeders with fibre optic current differential protection scheme

01.02.4 Five (5) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.5 One (1) common control panel

Note: 1) Protection of new Wadi Sham and new Ghalilah substation shall be
coordinated and subject to approval.

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 21 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

B5E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 195 of 536


02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Six (6 ) 630A outgoing cable feeders with energy metering

02.01.5 Eighteen (18) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

B5E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power supply
to auxiliary system of the substation as per schedule of requirement, detailed
technical specification etc. Auxiliary transformer sizing calculation that includes
motor starting conditions shall be submitted and as per calculation transformer
rating is to be selected.

B5E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 196 of 536


Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

B5E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of 11kV
NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate the number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 197 of 536


05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the entire substation.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides

05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 198 of 536


B5E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

B5E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.

B5E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 199 of 536


B5E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

B5 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.


ITEM NO. DESCRIPTION CATEGORY
B5 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA
SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 200 of 536


SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:
Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA

B5C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the Tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The
scope of works listed below are only indicative and no additional costs will be

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 201 of 536


considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

B5C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization,etc.

Scope of work under this section includes Site clearing/ Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.

01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation will be carried out and the report will be provided
later. However, that report provided will be for guidance and information only and
this will not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC)
shall be carried out as per the Soil Investigation agencys recommendations and
as per design requirements with Authority/Engineers approval and all required
tests including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item B5C03.02 Sub structure Concrete Works.

01.04 Authority and Engineers Site Offices and facilities

Provision of Type-B Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices

B5C02 Design and Drawings

Conceptual layout drawings are provided in this Tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 202 of 536


execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

B5C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings, etc. as per the drawings including drainage,
plumbing and other services.

03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks,
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks,
etc., up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls,
etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 203 of 536


03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal finishes in the Particular Technical
Specifications shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores
and Toilets as per specification and standards.

03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminum channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 204 of 536


03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including
future/ spare ducts and sleeves as per specification and standards.

b) RCC Cable trenches with removable heavy duty RCC covers shall be
constructed inside transformer rooms and all other cable trenches and
pull pits required for the entire substation.

c) RCC trenches for fire main ring with RCC covers.

d) Construction of all manhole chambers required for plumbing, water
supply, telephone cabling etc and valve pits for service water and
firefighting systems are included in this scope of work.

B5C04 Fire pump room

Construction of R.C.C framed building similar to substation main building, for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc shall be included.

B5C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

B5C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements etc.
All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.

B5C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 205 of 536


07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.

B5C08 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including Cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.

The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.

B5C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standards.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements.

B5C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing Municipality asphalt road as per specification and standards.

B5M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 206 of 536


authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

B5M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.

Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

B5M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return
valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 207 of 536


1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.

1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.

B5M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 208 of 536


1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.

1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.

B5M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

B5M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 209 of 536


1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

B5M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 210 of 536


1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.

B5M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

B5M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 211 of 536


B5M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

B5M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air
Conditioning and Ventilation plant fully functioning for the entire substation
including but not limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers and split type air conditioning units consists of indoor &
outdoor units etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.

B5M3 Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.,





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 212 of 536


B5M4 Service Water Supply System

All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves, shelter,
float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel

The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to transfer
the water from the underground water tank to the portable water storage tank
located at roof level. The inlet to the underground water tank from the water
distribution main line has to be provided with necessary water meter, gate valves,
isolation vales, etc. Necessary water flow & leakage test shall be carried out prior
to the handing over of substation. This shall include all works related to pumps,
pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:

Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete distribution
of portable water pipes to various rooms such as Battery room, toilet etc., shall be
provided. This shall include all works related to pumps, pipe routings with
protection, pipe supports, etc. Shade provision shall be made for the pump set by
insulated aluminum sandwich panels supported by structural steel members.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 213 of 536


B6 EXTENSION OF 132/33/11 kV NAKHEEL POWER
(NKPS) SUBSTATION

B6E SCOPE OF WORK ELECTRICAL

B6E01 33kV System

01.01 33kV Combined Control / Relay Panels

01.01.1 Modification, testing and commissioning of existing HVDT-1, 2 & 3 Feeder
control and relay panels

The existing Spare HVDT-1, 2 & 3 Feeder bays C&R Panels (H301, H304 &
H306) shall be used for new 20MVA HVDT-1, 2 & 3 respectively.

Bidders shall review the existing scheme of C&R panels pertaining to the 20
MVA transformers (H301, H304 & H306). Any modification required to fulfill the
tender protection logic diagram including the testing and commissioning of
existing GIS bays, C&R Panels pertaining to HVDT1,2, &3 shall be included
within the quoted price

B6E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

02.01.2 Three (3) incoming 20 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Nine (9 ) 630A outgoing cable feeders with energy metering

02.01.4 Nine (9) 630A outgoing cable feeders

Note: The 11 kV Switchgear shall be installed in the existing 11kV room. The tenderer
has to study and propose the 11kV switchgear layout in such a way the
Power/control cable openings of the 11kV switchgear does not foul with the floor

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 214 of 536


beams. Necessary dummy panels, if required, shall be included to clear all the
floor beams. Any civil work including core drilling in the floor for 11kV and
LV/Control Cables, steel fixing base for 11kV Switchgear, and other services(if
required) shall be carried out as per civil scope of work.

B6E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20MVA 33/11kV Distribution Transformer

All work related to taking delivery from FEWA Stores, local transportation,
installation, testing and commissioning of three (3) sets of 20 MVA Dyn11
33/11kV, ONAN Distribution transformers with accessories, OLTC, remote
control panel (RTCC) for OLTC, neutral CTs etc. that will be free issued by
FEWA.

Note: The existing transformer rooms shall be extended/modified as per civil scope of
work for installation of new transformers with adequate electrical and mechanical
clearances.

03.01.2 Neutral Earthing Resistor (NER)

All work related to taking delivery from FEWA Stores, local transportation,
installation, testing and commissioning of three (3) NERs of 6.35 ohms, 1000A,
10 seconds for earthing 11kV neutral of above 20 MVA HVDTs which will be free
issued by FEWA.

Note: The existing NER room shall be used for installation of new NERs as per Civil
scope of work with adequate electrical and mechanical clearances.

B6E04 Cabling System

04.01 Cables

04.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required, the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

04.01.1.1 Existing 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 215 of 536


04.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

04.01.2.1 11kV Switchgear to HVDT (2X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

04.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of
11kV NER circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

04.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for extension/modification works of the substation.

04.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for extension/modification works of the
substation.

04.02 Cable Terminations

04.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

04.02.1.1 Existing 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits
at 33kV GIS side

04.02.1.2 Existing 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer
side

04.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

04.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 216 of 536


04.02.2.2 HVDT to NER circuit three (3) circuits at both sides

04.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for extension/modification works of the substation.

04.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for extension/modification works of the substation.

04.03 Cable Trays, Conduits and Accessories

04.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for extension/modification
works of the substation.

B6E05 LVAC System

05.01 Extension of LVAC Auxilairy system

All work related to extension of Existing Low voltage AC Supply system which
includes but not limited to provision of additional Sub Distribution panel,
MCCB/MCBs etc as required for the extension /modification works.

B6E06 110V DC System

06.01 Extension of 110 V DC Auxilairy system

All work related to extension of Existing 110 V DC Supply system which includes
but not limited to provision of additional Sub Distribution panel, MCCB/MCBs etc
as required for the extension /modification works.

B6E07 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the existing transformer and
NER rooms which shall be utilized for installation of new transformers and NERs
as per above extension scope of work in the existing substation.

B6E08 Earthing and Lightning Protection

All work related to equipment earthing as required for the extension /modification
works in the substation. Lightening protection shall be provided for the
transformer and NER room building extension.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 217 of 536


B6E09 Diversion of existing 11kV Cable feeders from old 11kV Switchgear to New
11kV Switchgear

All existing 11kV Cable circuits at existing 11kV switchgear of Nakheel Power
substation (around 06 nos) shall be diverted, rerouted and terminated at the
11kV Switchgear which will be installed under this contract at Nakheel Power
substation. Contractor shall completely install, test and commission these 11kV
Cables. Any additional 11kV cables, joints etc as required shall be included in the
scope of work within the quoted price.

B6 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.




















TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 218 of 536



ITEM NO.

DESCRIPTION

CATEGORY
B6 SC1 SCADA
SC 1.1 Upgrade with necessary modifications of existing ABB
560 RTU to include new 33kV and 11kV circuits as
per substation SCADA circuit data requirements. The
scope shall include providing panel, extension racks,
modules, cables and other accessories as per the
requirements.

Scope shall also include complete substation
requirements as per tender documents including end
to end testing of new/upgraded circuits with UAQ
SCC, providing Accessories, cabling etc. as per
specification requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA
SC 1.2 New completely equipped CCC panels to be provided
for 11kV circuits.

Existing 33kV CCC panels to be upgraded in all
respect to include the new/replacement transformer
circuits.
All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope.

All design and engineering of CCC to be included in
the scope as per the specification and approved
before manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 219 of 536


SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

All cabling and termination from battery chargers and
LVAC panel to respective equipment.

All control cables and system cables specification for
scada and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 All works required to implement new SCADA
numbering system for entire 132/33/11kV substation
in accordance with the guidelines given in
specification. The works shall include replacement of
existing SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA


B6C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

B6C01 Preliminaries

Scope of work under preliminaries includes Site clearing, temporary fencing
around the work area and re-routing of existing services if any, etc.

Prior to commencement of works for extension of the existing Transformer rooms,
existing services at the proposed location for extension of the existing
Transformer rooms if any, to be rerouted and existing structures such as RCC

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 220 of 536


manholes/foundations etc. if any, to be demolished and reconstructed on suitable
alternate locations. The proposed area shall be backfilled, graded and leveled to
match with the existing Substation level, on completion of the works.

Soil Investigation Report for the existing Substation is included in this Tender
document.

B6C02 Design and Drawings

Conceptual layout drawings are provided in this Tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered. All design, working drawings and
shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

B6C03 Extension of Transformer Rooms

Design and Construction of extension to existing Transformer rooms to
accommodate the new 20 MVA Transformers as per the drawings, including
providing roof truss, drainage and other services. The scope shall include all Civil
modifications required in the Transformer rooms like modifications to the
Transformer plinths, cable trenches, core cutting, additional steel supports if
required for the installation of new equipment including re-instatement of the
structure to its original condition, etc..

03.01 Building works

All required works for the extension of the Transformer rooms shall include the
required Earthworks including shoring and dewatering as required, Substructure
concrete works including waterproofing of concrete structures, Super structure
concrete works, walls,beams,roof and floor/roof finishes, external works, cable
trenches, duct banks, manholes and drainage works all as per standards and
specifications. All other Civil works as may be required for the completion of the
Transformer room extensions.

03.02 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project including trussed roof for the Transformer room
extensions as per specification and standards.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 221 of 536


B6C04 Modification works in existing Substation Building

All required Civil modification works within the existing Substation building to
house new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing additional openings and modification of
existing openings if required in the slabs and walls and designing and providing
the slab support system necessitated due to the modification works. Also all
openings rendered redundant on completion of the works to be closed/sealed
with appropriate means to the approval of Authority/Engineer.

Also included is the demolition of the wall between the 11kV Switchgear room
and LVAC room and reconstruction of the same in a different location including
shifting of the doors.

Removal of metal screens of existing Transformer and NER rooms to enable
installation of Transformers and NERs and reinstatement of the same after the
installation of the Transformers and NERs is included in the scope of works. If the
mesh is damaged during removal/re fixing, it shall be reinstated with new one to
the satisfaction of Authority/Engineer.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.

B6M SCOPE OF WORK MECHANICAL

B6M 1 Fire Protection and Detection System

B6M 1B Fixed Water Spray System for Transformers

1B.01 Removal and reinstallation of deluge system

All work necessary for removal and reinstallation of piping, fittings, flanges,
sprinklers and nozzles of existing deluge system. On completion, pipe work shall
be retested.

B6M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 222 of 536


and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 223 of 536


B7 EXTENSION OF 33/11 kV MAREED (MARD) SUBSTATION

B7E SCOPE OF WORK ELECTRICAL

B7E01 11kV System

01.01 11kV Air Insulated Switchgear

Existing 11kV Air Insulated Switchgear (Make KONCAR, Type BVK12, 2000A,
31.5kA/3s) shall be extended on Bus 1 for one capacitor bank feeder and
replacement of flashover/damaged cable feder.

All work related to design, supply, installation, testing and commissioning of
extension bays with all necessary, bus ducts, risers, adapters, circuit breakers,
earthing switches, CTs, VTs, cable terminations, protection, control and metering
equipment as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

The Tenderer has to study and propose the 11kV switchgear layout in such a
way the Power/control cable openings of the 11kV switchgear does not foul with
the floor beams. Necessary dummy panels, if required, shall be included to clear
all the floor beams. The contractor shall make necessary site visit and ascertain
himself regarding the existing equipment and required modification before
tendering. Any civil work including core drilling in the floor for 11kV and
LV/Control Cables, steel fixing base for 11kV Switchgear, and other services (if
required) shall be included for new 11kV panels within the quoted price. The
scope shall include but not limited to the following circuits

01.01.1 One(1) 630 A Capacitor bank feeder

01.01.2 Replacement of damaged/flashover feeder (K202) with new 630A Cable feeder.

01.01.3 Modification of existing 11kV Cable feeder (=K26) to convert as 11kV Capacitor
bank feeder

In the existing 11kV Switchgear, one (1) Spare Cable Feeder (=K26) shall be
modified and used as 11kV Capacitor bank Feeder. All work related to
modification of GA, Schematic diagram, new wiring and CT replacement if
required shall be carried out as per the protection requirement within the quoted
price.

B7E02 Capacitor Banks

02.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

02.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 224 of 536


accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

B7E03 Cabling System

03.01 Cables

03.01.1 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

03.01.1.1 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

03.01.2 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension/modification works in the substation.

03.01.3 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the extension/modification works in the
substation.

03.02 Cable Terminations

03.02.1 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

03.02.1.1 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

03.02.2 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.02.3 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 225 of 536


03.03 Cable Trays, Conduits and Accessories

03.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension/modification
works in the substation.

B7E04 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.

B7E05 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

B7 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.









TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 226 of 536


ITEM NO. DESCRIPTION CATEGORY
B7 SC1 SCOPE OF WORK SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of basic and
extension racks to update the existing ABB RTU 232
to the new version of ABB RTU 560 to accommodate
the new/upgraded 11kV circuits as per the substation
requirements and SCADA data.

Scope shall also include complete substation
requirements as per tender documents including point
to point test for all affected circuits, end to end testing
of new/upgraded circuits with UAQ SCC, providing
accessories, cabling etc. as per specification
requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA
SC 1.2 Existing 11kV CCC panels to be upgraded in all
respect to include the new/upgraded circuits as per
the substation scope and SCADA circuit data.

All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope.

All design and engineering of CCC to be included in
the scope as per the specification and approved
before manufacturing.

SCADA
SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 227 of 536


SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA


B7C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

B7C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area and demobilization as per
the specification and requirements stated elsewhere in the specification.

Prior to commencement of works for new Capacitor bank building, existing
services at proposed location for new Capacitor bank building to be rerouted and
existing structures such as RCC manholes/foundations etc. demolished and
reconstructed on suitable alternate location. The proposed area shall be
backfilled, graded and leveled to match with the existing Substation level on
completion of the works. Tenderer shall include his price for all the above works

Soil Investigation Report for the existing Substation is included in this Tender
document.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the Soil Investigation agencys recommendations and as per

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 228 of 536


design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required in item B7C03.02 Sub structure concrete works.

01.02 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices

B7C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

B7C03 New Capacitor Bank Building with Clean Agent room

Design and Construction of new building for housing Capacitor bank units and
Clean agent room as per the specifications, including drainage, cable trenches
and other services.

03.01 Earth Work

Earth work includes excavation for foundations, trenches, duct banks, etc. This
includes necessary planking/ shoring and strutting, backfilling, dewatering, etc.
The excess earth material after backfilling shall be carted away to a designated
location approved by the concerned authority. Extreme care shall be taken to
protect the existing equipment and structures during construction. All required
protection arrangements shall be made prior to excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement, beams, columns, walls, trenches, tunnels, duct
banks, etc. up to ground floor including ground floor slab. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 229 of 536


03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor slab such as walls,
columns, beams, slabs, arches, corbels, sill beams, lintel beams, tie beams,
parapet walls etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors

Supply and installation of doors for the new building including ironmongeries as
per specification and standards. Sliding gate and solenoid locks for Capacitor
Bank rooms are also included in this Scope of work.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specifications shall be considered.

03.07 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.08 Internal Painting

Internal painting for the building shall be carried out as per specification and
standards.

03.09 External Finishes

All external surfaces of the buildings shall be finished as per
specification/finishing schedule and standards. External elevations of the new
building shall match with the existing Substation building.

03.10 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 230 of 536


03.11 Cable Duct Banks, Trenches Manhole chambers and all other civil works

RCC Cable trenches with removable heavy duty RCC covers shall be constructed
for 11kV, LV and control cables between existing 33kV substation basement and
the new Capacitor bank building. Core drilling in existing substation basement
walls is also included.

All other cable trenches and pull pits required for the entire extension works are
also included in this scope of work.

This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Capacitor bank installation works

B7C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards to match with existing system.

B7C05 Modification works in existing Substation Building

All required Civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing of additional openings in the Ground
floor slab and walls if required as per Electrical scope and designing and
providing the slab support system necessitated due to the modification works.
Also all openings rendered redundant on completion of the works to be
closed/sealed with appropriate means to the approval of Authority/Engineer.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

Boundary wall, wherever demolished during construction works, to be reinstated
as originally existing.

Internal roads, pavements and gravel areas damaged during construction of the
new Building shall be reinstated and interconnection to the new Building shall be
made.

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 231 of 536


B7M SCOPE OF WORK MECHANICAL

B7M 1 Fire Protection and Detection System

B7M 1C Clean Agent System

B7M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 232 of 536


B7M 1D Automatic Fire Detection and Alarm System

All work necessary for extension of existing Fire Detection & Alarm System with
all accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Clean Agent Room. On completion of Fire Detection
and Alarm System modification works, existing Fire Alarm Control Panel shall be
tested for correct operation.

1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.
.
1D.02 Photoelectric smoke detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors, as per NFPA recommendations.

B7M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) for new Capacitor Bank rooms.

B7M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

B7M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air
Conditioning and Ventilation plant fully functioning for the new Capacitor room
and clean agent room including but not limited to the following:


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 233 of 536


M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers etc., Bib tap with hose tapping from existing service water
line to be provided near the package units.

M2.02 Extraction fan for clean agent room

M2.03 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.04 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.05 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.06 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 234 of 536


B8 EXTENSION OF 33/11kV SHARISHA (SHAR) SUBSTATION

B8E SCOPE OF WORK ELECTRICAL

B8E01 11kV System

01.01 11kV Air Insulated Switchgear

Existing 11kV Air Insulated Switchgear (Make SIEMENS, Type SIMOPRIME,
2000A, 31.5kA/3s) shall be extended for specified number of bays.

All work related to design, supply, installation, testing and commissioning of
extension bays with all necessary, bus ducts, risers, adapters, circuit breakers,
earthing switches, CTs, VTs, cable terminations, protection, control and metering
equipment as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

The Tenderer has to study and propose the 11kV switchgear layout in such a
way the Power/control cable openings of the 11kV switchgear does not foul with
the floor beams. Necessary dummy panels, if required, shall be included to clear
all the floor beams. The contractor shall make necessary site visit and ascertain
himself regarding the existing equipment and required modification before
tendering. Any civil work including core drilling in the floor for 11kV and
LV/Control Cables, steel fixing base for 11kV Switchgear, and other services (if
required) shall be included as per civil scope of work. The scope shall include
but not limited to the following circuits

01.01.1 Two (2) 630 A Capacitor bank feeders

01.01.2 Two (2) 630 A Cable feeders

B8E02 Capacitor Banks

02.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

02.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.









TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 235 of 536


B8E03 Cabling System

03.01 Cables

03.01.1 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

03.01.1.1 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

03.01.2 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension/modification works in the substation.

03.01.3 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the extension/modification works in the
substation.

03.02 Cable Terminations

03.02.1 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

03.02.1.1 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

03.02.2 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.02.3 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.03 Cable Trays, Conduits and Accessories

03.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension/modification
works in the substation.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 236 of 536


B8E04 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.

B8E05 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

B8 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.

















TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 237 of 536




ITEM NO. DESCRIPTION CATEGORY
B8 SC1 SCOPE OF WORK SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of basic and
extension racks to update the existing ABB RTU 232
to the new version of ABB RTU 560 to accommodate
the new/upgraded 11kV circuits as per the substation
requirements and SCADA data.

Scope shall also include complete substation
requirements as per tender documents including point
to point test for all affected circuits, end to end testing
of new/upgraded circuits with UAQ SCC, providing
accessories, cabling etc. as per specification
requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA
SC 1.2 New completely equipped CCC panels to be provided
for 11kV circuits.

All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope.

All design and engineering of CCC to be included in
the scope as per the specification and approved
before manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 238 of 536


SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

All cabling and termination from battery chargers and
LVAC panel to respective equipment.

All control cables and system cables specification for
scada and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA


B8C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

B8C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area and demobilization as per
the specification and requirements stated elsewhere in the specification.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 239 of 536


Prior to commencement of works for new Capacitor bank building, existing
services at proposed location for new Capacitor bank building to be rerouted and
existing structures such as RCC manholes/foundations etc. demolished and
reconstructed on suitable alternate location. The proposed area shall be
backfilled, graded and leveled to match with the existing Substation level on
completion of the works. Tenderer shall include his price for all the above works

01.02 Soil Investigation

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the soil investigation agencys recommendations and as per
design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in Item B8 C03.02 Sub structure Concrete Works.

01.03 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

B8C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

B8C03 New Capacitor Bank Building with Clean Agent room

Design and Construction of new building for housing Capacitor bank units and
Clean agent room as per the specifications, including drainage, cable trenches
and other services.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 240 of 536


03.01 Earth Work

Earth work includes excavation for foundations, trenches, duct banks etc. This
includes necessary planking/ shoring and strutting, backfilling, dewatering, etc.
The excess earth material after backfilling shall be carted away to a designated
location approved by the concerned authority. Extreme care shall be taken to
protect the existing equipment and structures during construction. All required
protection arrangements shall be made prior to excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement, beams, columns, walls, trenches, tunnels, duct
banks, etc. up to ground floor including ground floor slab. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor slab such as walls,
columns, beams, slabs, arches, corbels, sill beams, lintel beams, tie beams,
parapet walls etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors

Supply and installation of doors for the new building including ironmongeries as
per specification and standards. Sliding gate and solenoid locks for Capacitor
Bank rooms are also included in this Scope of work.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specification shall be considered.

03.07 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 241 of 536


03.08 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.09 External Finishes

All external surfaces of the buildings shall be finished as per
specification/finishing schedule and standards. External elevations of the new
Building shall match with the existing Substation building.

03.10 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.

03.11 Cable Duct Banks, Trenches Manhole chambers and all other civil works

RCC Cable trenches with removable heavy duty RCC covers shall be constructed
for 11kV, LV and control cables between existing 33kV substation basement and
the new Capacitor bank building. Core drilling in existing substation basement
walls and reinstatement as required by Authority / Engineer is also included.

All other cable trenches and pull pits required for the entire extension works are
also included in this scope of work.

This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Capacitor bank installation works

B8C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards to match with existing system.

B8C05 Modification works in existing Substation Building

All required Civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing additional openings in the Ground floor
slabs and walls if required as per Electrical scope and designing and providing
the slab support system necessitated due to the modification works. Also all
openings rendered redundant on completion of the works to be closed/sealed
with appropriate means to the approval of Authority/Engineer.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 242 of 536


All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

Boundary wall, wherever demolished during construction works, to be reinstated
as originally existing.

Internal roads, pavements and gravel areas damaged during construction of the
new Building shall be reinstated and interconnection to the new Building shall be
made.

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.

B8M SCOPE OF WORK MECHANICAL

B8M 1 Fire Protection and Detection System

B8M 1C Clean Agent System

B8M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 243 of 536


1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

B8M 1D Automatic Fire Detection and Alarm System

All work necessary for extension of existing Fire Detection & Alarm System with
all accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Clean Agent Room. On completion of Fire Detection
and Alarm System modification works, existing Fire Alarm Control Panel shall be
tested for correct operation.

1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.
.
1D.02 Photoelectric smoke detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors, as per NFPA recommendations.

B8M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) for new Capacitor Bank rooms.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 244 of 536


B8M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

B8M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the new Capacitor room and clean agent
room including but not limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers etc., Bib tap with hose tapping from existing service water
line to be provided near the package units.

M2.02 Extraction fan for clean agent room

M2.03 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.04 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.05 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.06 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 245 of 536


B9. PROTECTION MODIFICATION WORKS AT EXISTING SUBSTATIONS IN
NORTH AREA (2)

All the modifications as required in the 33 kV GIS, LV Compartment,Control &
Relay Panels , Busbar protection panels etc including but not limited to changing
the labels, modifying the schematic diagrams, GA drawings, layout drawing
preparation and revision of all relevant drawings, SLDs, etc. as required to reflect
the circuit changes shall be carried out by the contractor under scope of this
contract within the quoted price. All such drawings whether specifically
mentioned or not shall be modified and submitted to Engineer/Authoritys
approval by the substation contractor at an early stage of project execution. All
extension and modification works shall be carried out by the substation
contractor with minimum outage only. The substation contractor in his offer shall
state the requirement of shut down in the existing substations.

The complete set of as built drawings (wherever changes as required) shall be
resubmitted incorporating the changes. The Authority reserve the right to ask the
substation contractor to retest and recommission any item or plant disturbed
during modification works without any cost and time implication to the Authority
and no deviation is acceptable in this regard. The contractor must visit the site
and all necessary existing information, drawings, documents, etc. required shall
be collected without any implications to authority. Any minor civil modifications
anticipated in the 33 kV GIS room, Control & Relay room etc. shall be carried out
by the substation contractor.

Modification of the existing protection panels shall be carried out by qualified and
experienced Engineer approved by FEWA. All the modifications shall be carried
out with minimum shutdown requirements and without any disturbance to existing
system. The tenderer shall make site visit and assess themselves all the required
modifications to be carried out in existing panels and the cost towards all works
shall be included within the quoted price.

All modifications required in existing panels, relay and control panels, AC/DC
system etc shall be included within the quoted price.

The existing substation as built drawings including but not limited to layout of
main equipments, sections, cable route layout, cable tray layout, earthing
drawings, control and protection schematic diagrams of existing bays (Bus
section, common control panels, adjacent panels etc), substation single line
diagrams, associated civil and electromechanical drawings affected by the
modification works etc shall be suitably modified and submitted for approval at an
early stage. All such drawings shall also be made as final as built drawings by
the substation contractor in addition to the equipment drawings.

Any relocation of existing equipments required for works shall be deemed to be
included in the quoted price. New control cables/LV power cables, fixing
arrangement of relocated equipments etc are also included within the quoted
price.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 246 of 536


All the relay setting calculations as required by Authority shall be carried out by
the contractor under scope of this contract and shall be submitted to
Engineer/Authority for approval.

Any necessary details including but not limited to existing relay setting and
drawings/ information etc as required shall be collected from site/relays by
contractor under the scope of this tender. All schematic diagrams shall be tested
and all protection testing including end to end testing shall be carried out within
the quoted price.

Providing manufacturer Specialist for testing and commissioning of Main
protection relays for 33 kV OHL/cable feeders shall be under the scope of this
tender. All cost towards testing and commissioning of Main protection relays by
manufacturer specialist shall be included within the quoted price.

The Main protection relays in the new substation shall be matched with existing
relays at respective remote end substation. In case contractor cannot comply
with this requirement then all cost towards modification and replacement of Main
Protection relays at existing respective remote end substations shall be included
within the quoted price of existing substation modification works without any
contractual implication to Authority. However Authority reserves the right to
decide either to supply new relays and modify the existing panel or to match with
existing relays and the same will be decided during engineering stage.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

B9.1 Protection Modification Works at existing Rams Substation for New Rams-2
substation cable feeder One (1) circuit

The existing 33kV Spare Cable Feeder Bay (Bay # H204) C&R Panel shall be
modified as follows.

B9.1.1 Protection modification as required for New Rams-2 Cable feeder (H204) Circuit

The existing 33kV Spare C&R Panel (H204) is equipped with main protection
suitable for fibre optic current differential protection relay type Solkor N,
manufactured by Siemens.

Bidder shall match the above main protection relay at new Rams-2 Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with new Rams-2 at existing Rams Substation within
the overall quoted price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new fibre optic

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 247 of 536


current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

B9.2 Protection Modification Works at existing Transco Khor Kuwair (T/KHRK)
Substation for New Rams-2 substation cable feeders Three (3) circuits

The existing 33kV Spare Bays (H11, H20 & H33) C&R Panels at Transco Khor
Kuwair shall be modified as follows:

B9.2.1 Protection modification as required for New Rams-2 Cable feeder (H11) Circuit
No. 1

B9.2.2 Protection modification as required for New Rams-2 Cable feeder (H20) Circuit
No. 2

B9.2.3 Protection modification as required for New Rams-2 Cable feeder (H33) Circuit
No. 3

The existing 33kV Spare Bays (H11, H20 & H33) C&R Panels at Transco Khor
Kuwair are equipped with main protection suitable for fibre optic current
differential protection relay type RED670, manufactured by ABB.

Bidder shall match the above main protection relay at new Rams-2 Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with new Rams-2 at Transco Khor Kuwair substation
within the overall quoted price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new fibre optic
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required to
satisfy the scheme requirement shall be supplied and installed within the quoted
price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 248 of 536


B9.3 Protection Modification Works at existing Nakheel Old Town (OTMN)
Substation for New Shamal substation cable feeeders Three (3) circuits

The existing 33kV Spare Cable Feeder Bays (Bays # H05, H11 & H21) C&R
Panels shall be modified as follows.

B9.3.1 Protection modification as required for New Shamal Cable feeder (H05) Circuit
No. 1

B9.3.2 Protection modification as required for New Shamal Cable feeder (H11) Circuit
No. 2

B9.3.3 Protection modification as required for New Shamal Cable feeder (H21) Circuit
No. 3

The existing 33kV Spare C&R Panels (H05, H11 & H21) are equipped with main
protection suitable for fibre optic current differential protection relay type RED670,
manufactured by ABB.

Bidder shall match the above main protection relay at new Shamal Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with new Shamal at existing Nakheel Old Town
Substation within the overall quoted price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new fibre optic
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required to
satisfy the scheme requirement shall be supplied and installed within the quoted
price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

B9.4 Protection Modification Works at existing Khor Kuwair (KHOR) Substation
for New Ghalilah substation cable feeders Three (3) circuits

The existing 33kV GIS Bays (H203, H204 & H205) C&R Panels presently
designated as Ghalilah PS Circuit 1, 2 & 3 shall be modified as follows:

B9.4.1 Protection modification as required for New Ghalilah Cable feeder (H203) Circuit
No.1


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 249 of 536


B9.4.2 Protection modification as required for New Ghalilah Cable feeder (H204) Circuit
No.2

B9.4.3 Protection modification as required for New Ghalilah Cable feeder (H205) Circuit
No.3

The existing 33kV C&R Panels are equipped with main protection suitable for
pilot wire protection type Solkor Rf, manufactured by Siemens.

Bidder shall match the above main protection relay at new Ghalilah Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with new Ghalilah at the existing Khor Kuwair
Substation. The send or receive ends shall be properly coordinated by the bidder
in order to satisfy the scheme requirement. The compatibility of new relays
installed at Ghalilah (in case of retaining the pilot wire protection relay at Khor
Kuwair) shall be confirmed by the Relay manufacturer.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new pilot wire
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

CT Calculation shall be submitted and the new relay shall be suitable for the CT
characteristic available at the existing Khor Kuwair substation. Bidders shall test
the CTs and note the parameters before making the CT sizing calculation.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

B9.5 Protection Modification Works at existing Sham (SHAM) Substation for New
Ghalilah substation cable feeders Two (2) circuits

The existing 33kV AIS feeders H201 & H202 presently designated as Ghalilah PS
Circuit 1 & 2 shall be modified as follows:

B9.5.1 Protection modification as required for New Ghalilah Cable feeder (H201) Circuit
No.1

B9.5.2 Protection modification as required for New Ghalilah Cable feeder (H202) Circuit
No.2


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 250 of 536


The existing 33kV AIS (make Merlin Gerin) has no separate C&R Panels and
there is no main protection available at the existing Sham Substation. The
existing 33kV Switchgear panels are provided with OC/EF protection only.

Bidder shall supply and install new pilot wire current differential protection relay
for the above two cable feeders at Sham matching with new Ghalilah Substation
in a wall mounted DB/Panel subject to FEWA approval. The wall mounted
DB/Panel shall be provided with door and necessary auxiliary relay, trip relay,
test block, terminal block and any other component as required to satisfy the
scheme requirement shall be supplied and installed with in the quoted price.

B9.5.3 Design, supply, installation, testing and commissioning of two (2) sets of 33kV
Current transformers for pilot wire current differential protection scheme.(one set
per feeder)

Bidder shall supply and install two (2) sets of new 33kV Current transformers in
the existing 33kV Air insulated Switchgear make Merlin Gerin. All necessary
modifications in the existing 33kV Air insulated switchgear for installing the new
33kV current transformers shall be carried out within the quoted price. The CT
sizing calculations as per protection requirement shall be prepared and
submitted for FEWA/Engineer approval.

B9.5.4 Design, supply, installation, testing and commissioning of one (1) Floor standing
Pilot wire isolation transformer cubicle for the above two cable feeders suitable
for 15kV scheme (comprising of 15kV isolation transformers, HV TBs etc)

Note: 15kV Pilot wire cable shall be laid and terminated from the above pilot wire
isolation transformer cubicle upto existing pilot wire termination cubicle by the
substation contractor.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

B9.6 Protection Modification Works at existing Nakheel Main Old Town (OTMN)
Substation for New SEBU substation cable feeders Three (3) circuits

The existing 33kV Cable Feeder Bays (Bays # H07, H20 & H27) C&R Panels
shall be modified as follows.

B9.6.1 Protection modification as required for New SEBU Cable feeder (H07) Circuit
No. 1

B9.6.2 Protection modification as required for New SEBU Cable feeder (H20) Circuit
No. 2




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 251 of 536


B9.6.3 Protection modification as required for New SEBU Cable feeder (H27) Circuit
No. 3

The existing 33kV C&R Panels (H07, H120& H27) are equipped with main
protection suitable for fibre optic current differential protection relay type
RED670, manufactured by ABB.

Bidder shall match the above main protection relay at new SEBU Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with new SEBU at existing Nakheel Old Town
Substation within the overall quoted price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new fibre optic
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

B9.7 Protection Modification Works at existing Qusaidat Main Substation for New
SEBU substation cable feeders Two (2) circuits

The existing 33kV GIS Bays (H204 & H216) C&R Panels shall be modified as
follows:

B9.7.1 Protection modification as required for New SEBU Cable feeder (H204) Circuit
No.1

B9.7.2 Protection modification as required for New SEBU Cable feeder (H216) Circuit
No.2

The existing 33kV GIS Bays (H204 & H216) C&R Panels are equipped with main
protection suitable for fibre optic current differential protection relay type Solkor
N, manufactured by Siemens.

Bidder shall match the above main protection relay at new SEBU Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with new SEBU at existing Qusaidat Main Substation
within the overall quoted price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 252 of 536


relays to FEWA stores (if required). Supply and installation of new fibre optic
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

B9.8 Overall end to end testing & commissioning of new Ghalilah new Wadi
Sham Feeders Two (2) Circuits.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 253 of 536


PART C : EAST AREA (A)

C1 NEW 33/11kV NAJAIMAT (NAJM) SUBSTATION

C1E SCOPE OF WORK ELECTRICAL

C1E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified sixteen (16) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of two (2)
outgoing cable feeders (1 feeeder on L.H.S and 1 feeder on R.H.S of 33kV GIS).
Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Eleven (11) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 254 of 536


01.02.1 Two (2) Bus Sections.

01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Nine (9) cable feeders with fibre optic current differential protection scheme

01.02.4 Two (2) cable feeders with Pilot wire current differential protection scheme

01.02.5 Six (6) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.6 Two (2) nos of Floor standing Pilot wire isolation transformer cubicles suitable for
15 kV scheme (comprising of 15 kV isolation transformers, HV TBs etc)

Note: 15kV Pilot wire cable shall be laid and terminated from the above pilot wire
isolation transformer cubicle upto pilot wire termination cubicle which will be
installed by the cable contractor.

01.02.7 One (1) common control panel

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 24 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

C1E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to Design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 255 of 536


equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Twelve (12 ) 630A outgoing cable feeders with energy metering

02.01.5 Twelve (12) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

C1E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power
supply to auxiliary system of the substation as per schedule of requirement,
detailed technical specification etc. Auxiliary transformer sizing calculation that
includes motor starting conditions shall be submitted and as per calculation
transformer rating is to be selected.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 256 of 536


C1E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

C1E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. If required by cable sizing calculation, the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.1.2 33kV GIS of new Najaimat substation to 33kV GIS of existing 132/33/11kV
Fujairah Main Substation (2X1CX500 sq.mm/phase) cables required for the
three (3) Nos. of cable circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of
11kV NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 257 of 536


05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.

05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control, communication and instrumentation cables for the entire substation.

05.01.5 Fibre Optic Cables

All works related to design, supply, installation, testing and commissioning of 32
fibre , single mode FO cables for protection and communication/Scada purpose.
The quantity of FO cables shall meet the requirement of all 33kV Cable circuits.
However minimum two(2) FO Cables for the following 3 nos of 33kV Cable
circuits :

05.01.5.1 Fiber Optic Cable (32 fibers) from new 33/11kV Najaimat substation to existing
Fujairah Main substation Two(2) cables required for the three (3) Nos. of 33kV
Cable circuits.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.1.3 33kV GIS of new Najaimat substation to 33kV GIS of existing 132/33/11kV
Fujairah Main Substation , plug-in - type termination for three (3) circuits at 33 kV
GIS side ( both ends )




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 258 of 536


05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides

05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.5 Fiber optic Cable Terminations and accessories

ODF and all accessories including joints and terminations for Fiber Optic Cable
(32 fibers). The OTB shall be provided at existing Fujairah Main substation.

05.02.5.1 FO Cable terminations for Two(2) nos of FO cables from new 33/11kV Najaimat
substation to existing Fujairah Main substation at both ends.

Note: The floor standing FO distribution panel at New Najaimat substation is included
as per item no E 3.3 of Telecommunication Equipment scope of work. However
the wall mounted OTB at existing Fujairah Main substation for the above 2 nos of
FO cables (one OTB shall be supplied for each FO cable and totally two(2) nos
to be supplied) shall be included within the quoted price. Also the end to end
testing of the FO cable and the documentation as per requirement shall be
included within the quoted price.

05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 259 of 536


C1E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

C1E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.

C1E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 260 of 536


C1E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

C1E10 Diversion of Existing 33kV Cables and Pilot cables to New Najaimat
substation

Two (2) nos of existing 33 kV Cable circuits from 33/11 kV Al Hail substation at
Fujairah Main 132/33/11kV Substation shall be diverted, rerouted and terminated
to the 33kV GIS which will be installed under this contract at new Najaimat
substation including rerouting, diversion and termination of related pilot wire
cables to the new Najaimat substation. Contractor shall completely install, test
and commission these 33kV Cables and Pilot wire cables. Any additional 33kV
cables, Pilot cables, joints, pilot wire terminations etc as required shall be
include in the scope of work within the quoted price. The scope shall also include
supply, installation, testing and commissioning of Pilot cable termination cubicle
(one pilot wire termination cubicle shall be supplied for each pilot cable and
totally two (2) nos to be supplied) at New Najaimat substation.

C1 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.

















TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 261 of 536


ITEM NO. DESCRIPTION CATEGORY
C1 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA
SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.

SCADA
SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 262 of 536


SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:
Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA

C1C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the Tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority / Engineer. The
scope of works listed below are only indicative and no additional costs will be
considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

C1C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization,etc.

Scope of work under this section includes Site clearing/Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 263 of 536


01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation was carried out and the report is provided in these
Tender documents. However, this report is provided for guidance and information
only and this will not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC)
shall be carried out as per the Soil Investigation agencys recommendations and
as per design requirements with Authority/Engineers approval and all required
tests including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item C1C03.02 Sub structure Concrete Works.

01.04 Authority and Engineers Site Offices and facilities

Provision of Type-A Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

C1C02 Design and Drawings

Conceptual layout drawings are provided in this Tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper
execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

C1C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings etc. as per the drawings including drainage
plumbing and other services.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 264 of 536


03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks, etc.,
up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls
etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal finishes in the Particular Technical
Specifications shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores
and Toilets as per specification and standards.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 265 of 536


03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminium channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.

03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including
future/ spare ducts and sleeves as per specification and standards.

b) RCC Cable trenches with removable heavy duty RCC covers shall be
constructed inside transformer rooms and all other cable trenches and
pull pits required for the entire substation.

c) RCC Cable trenches with removable heavy duty RCC covers shall be
constructed to accommodate the new cables to be laid from the existing
132/33/11kV Fujairah Main Substation to the new 33/11kV Najaimath
Substation

d) RCC trenches for fire main ring with RCC covers.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 266 of 536


e) Construction of all manhole chambers required for plumbing, water
supply, telephone cabling etc and valve pits for service water and
firefighting systems are included in this scope of work.

C1C04 Fire pump room

Construction of R.C.C framed building similar to substation main building, for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc shall be included.

C1C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

C1C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements etc.
All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.

C1C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.

07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 267 of 536


C1C08 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.

The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.

C1C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standard.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements.

C1C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing Municipality asphalt road as per specification and standards.

C1M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local
authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

C1M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 268 of 536


Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

C1M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return
valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.

1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 269 of 536


1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.

C1M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.

1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.

1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 270 of 536


connections, grounding etc. for the system.

C1M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

C1M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 271 of 536


and dry voltage outputs for interlocks.

C1M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 272 of 536


C1M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

C1M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).

C1M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 273 of 536


C1M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the entire substation including but not
limited to the following:


M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of Hermetic
/ Semi-hermetic / Scroll compressors with suction and delivery valves, Condenser
and Evaporator coil with copper fins, Evaporator fan with drive, Drain pan, Filter
chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.

C1M3 Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.,

C1M4 Service Water Supply System

All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves, shelter,
float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel

The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to transfer
the water from the underground water tank to the portable water storage tank
located at roof level. The inlet to the underground water tank from the water
distribution main line has to be provided with necessary water meter, gate valves,

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 274 of 536


isolation vales, etc. Necessary water flow & leakage test shall be carried out prior
to the handing over of substation. This shall include all works related to pumps,
pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:

Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete distribution
of portable water pipes to various rooms such as Battery room, toilet etc., shall be
provided. This shall include all works related to pumps, pipe routings with
protection, pipe supports, etc. Shade provision shall be made for the pump set by
insulated aluminum sandwich panels supported by structural steel members.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 275 of 536


C2 NEW 33/11kV WATER FIELD-2 (WFL2) SUBSTATION

C2E SCOPE OF WORK ELECTRICAL

C2E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified fourteen (14) bays with all necessary circuit breakers,
disconnectors, earthing switches, CTs, VTs, cable termination sockets and plugs,
plug-in termination, dummy plugs, protection, control and metering equipment as
per schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of four (4)
outgoing cable feeders (2 feeeders on L.H.S and 2 feeders on R.H.S of 33kV
GIS). Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Seven (7) Cable feeders.

01.01.4 Two (2) OHL feeders

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 276 of 536


01.02.1 Two (2) Bus Sections.

01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 One (1) cable feeder with fibre optic current differential protection scheme

01.02.4 Six (6) cable feeders with Pilot wire current differential protection scheme

01.02.5 Two (2) OHL feeders with Distance protection scheme

01.02.6 One (1) set of matching F.O. current differential protection relay and test terminal
block etc (loose supply) for remote ends.

01.02.7 Six (6) nos of Floor standing Pilot wire isolation transformer cubicles suitable for
15 kV scheme (comprising of 15kV isolation transformers, HV TBs etc)

Note: 15kV Pilot wire cable shall be laid and terminated from the above pilot wire
isolation transformer cubicle upto pilot wire termination cubicle which will be
installed by the cable contractor.

01.02.8 One (1) common control panel

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 27 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

C2E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 277 of 536


switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Twelve (12) 630A outgoing cable feeders with energy metering

02.01.5 Twelve (12) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

C2E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power supply
to auxiliary system of the substation as per schedule of requirement, detailed
technical specification etc. Auxiliary transformer sizing calculation that includes

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 278 of 536


motor starting conditions shall be submitted and as per calculation transformer
rating is to be selected.

C2E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

C2E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of 11kV
NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 279 of 536


Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate the number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.

05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the entire substation.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides

05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 280 of 536


05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.

C2E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

C2E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 281 of 536


C2E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.

C2E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

C2E10 Diversion of Existing 33kV Cables & Pilot cables to New Water Field-2
substation

All 33 kV Cable circuits at existing Water Field substation which includes two (2)
nos from Fujairah Tower substation, three (3) nos from Fujairah Main substation,
one (1) nos from Town centre substation and two(2) OHL feeders from Munay
Main substation shall be diverted, rerouted and terminated to the 33kV GIS which
will be installed under this contract at new Water Field-2 substation including
rerouting, diversion and termination of related pilot wire cables to the new Water
Field-2 substation. Contractor shall completely install, test and commission these
33kV Cables and pilot wire cables. Any additional 33kV cables, Pilot cables,
joints, pilot wire terminations etc as required shall be include in the scope of
work within the quoted price. The scope shall also include supply, installation,
testing and commissioning of Pilot cable termination cubicle (one pilot wire
termination cubicle shall be supplied for each pilot cable and totally six(6) nos to
be supplied) at New Water Field-2 substation.

C2E11 Diversion of Existing 11kV Cables to New Water Field-2 substation

All existing 11 kV Cable circuits at existing 33/11kV Waterfield substation to be
diverted and to be rerouted and and terminated at the 11kV Switchgear which will
be installed under this contract at New Water Field-2 substation. Contractor shall
completely install, test and commission these 11kV Cables. Any additional 11kV
cables, joints etc as required shall be included in the scope of work within the
quoted price.

C2E12 De-commissioning of Old Water Field 33/11 kV substation

All the existing equipment of the Old Water Field 33/11kV Substation shall be
deenergized and decommissioned after energization of new 33/11kV Water
Field-2 substation.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 282 of 536


C2 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.

ITEM NO. DESCRIPTION CATEGORY
C2 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA
SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 283 of 536


SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:
Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA


C2C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the Tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The
scope of works listed below are only indicative and no additional costs will be

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 284 of 536


considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

C2C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization,etc.

Scope of work under this section includes Site clearing/ Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.

01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation will be carried out and the report will be provided
later. However, that report provided will be for guidance and information only and
this will not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC)
shall be carried out as per the Soil Investigation agencys recommendations and
as per design requirements with Authority/Engineers approval and all required
tests including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item C2 C03.02 Sub structure concrete works.

01.04 Authority and Engineers Site Offices and facilities

Provision of Type-B Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

C2C02 Design and Drawings

Conceptual layout drawings are provided in this Tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 285 of 536


execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

C2C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings, etc. as per the drawings including drainage,
plumbing and other services.

03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks,
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks, etc.,
up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls,
etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 286 of 536


03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal finishes in the Particular Technical
Specifications shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores
and Toilets as per specification and standards.

03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

3.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminium channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 287 of 536


03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including
future/ spare ducts and sleeves as per specification and standards.

b) RCC Cable trenches with removable heavy duty RCC covers shall be
constructed inside transformer rooms and all other cable trenches and
pull pits required for the entire substation.

c) RCC trenches for fire main ring with RCC covers.

d) Construction of all manhole chambers required for plumbing, water
supply, telephone cabling etc and valve pits for service water and
firefighting systems are included in this scope of work.

C2C04 Fire pump room

Construction of R.C.C framed building similar to substation main building, for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc shall be included.

C2C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

C2C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements etc.
All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.

C2C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 288 of 536


07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.

C2C08 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including Cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.

The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.

C2C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standards.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements.

C2C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing Municipality asphalt road as per specification and standards.

C2M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 289 of 536


authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

C2M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.
Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

C2M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return
valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 290 of 536


1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.

1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.

C2M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 291 of 536


1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.

1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.

C2M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

C2M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 292 of 536


1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

C2M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 293 of 536


1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.

C2M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

C2M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 294 of 536


C2M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

C2M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the entire substation including but not
limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of Hermetic
/ Semi-hermetic / Scroll compressors with suction and delivery valves, Condenser
and Evaporator coil with copper fins, Evaporator fan with drive, Drain pan, Filter
chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with DDC
controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.

C2M3 Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.,





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 295 of 536


C2M4 Service Water Supply System

All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves, shelter,
float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel

The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to transfer
the water from the underground water tank to the portable water storage tank
located at roof level. The inlet to the underground water tank from the water
distribution main line has to be provided with necessary water meter, gate valves,
isolation vales, etc. Necessary water flow & leakage test shall be carried out prior
to the handing over of substation. This shall include all works related to pumps,
pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:

Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete distribution
of portable water pipes to various rooms such as Battery room, toilet etc., shall be
provided. This shall include all works related to pumps, pipe routings with
protection, pipe supports, etc. Shade provision shall be made for the pump set by
insulated aluminum sandwich panels supported by structural steel members.




















TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 296 of 536


C3 NEW 33/11kV AL HAIL INDUSTRIAL (HAIN) SUBSTATION

C3E SCOPE OF WORK ELECTRICAL

C3E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified sixteen (16) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of two (2)
outgoing cable feeders (1 feeeder on L.H.S and 1 feeder on R.H.S of 33kV GIS).
Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Eleven (11) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 297 of 536


01.02.1 Two (2) Bus Sections.

01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Eleven (11) cable feeders with fibre optic current differential protection scheme

01.02.4 Eight (8) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.5 One (1) common control panel

Note: Protection of new Al Hail Industrial and new Transco Al Hail Industrial substation
shall be coordinated and subject to approval.

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 24 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

C3E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 298 of 536


02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Twelve (12 ) 630A outgoing cable feeders with energy metering

02.01.5 Twelve (12) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

C3E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power supply
to auxiliary system of the substation as per schedule of requirement, detailed
technical specification etc. Auxiliary transformer sizing calculation that includes
motor starting conditions shall be submitted and as per calculation transformer
rating is to be selected.

C3E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 299 of 536


with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

C3E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. If required by cable sizing calculation, the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.1.2 33kV GIS of new 33/11kV Al Hail Industrial substation to 33 kV GIS of existing
132/33kV Transco Al Hail Industrial Substation (2X1CX500 sq.mm/phase)
cables required for the three (3) Nos. of cable circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of
11kV NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 300 of 536


05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.

05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control, communication and instrumentation cables for the entire substation.

05.01.5 Fibre Optic Cables

All works related to design, supply, installation, testing and commissioning of 32
fibre , single mode FO cables for protection and communication/Scada purpose.
The quantity of FO cables shall meet the requirement of all 33kV Cable circuits.
However minimum two(2) FO Cables for the following 3 nos of 33kV Cable
circuits :

05.01.5.1 Fiber Optic Cable (32 fibers) from new 33/11kV Al Hail Industrial substation to
existing Transco Al Hail Industrial substation Two(2) cables required for the
three (3) Nos. of 33kV Cable circuits.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.1.3 33kV GIS of 33/11kV Al Hail Industrial substation to 33kV GIS of existing
132/33kV Transco Al Hail Industrial Substation, plug-in - type termination for
three (3) circuits at 33 kV GIS side (both ends).

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 301 of 536


05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.5 Fiber optic Cable Terminations and accessories

ODF and all accessories including joints and terminations for Fiber Optic Cable
(32 fibers). The OTB shall be provided at existing Transco Al Hail Industrial
substation.

05.02.5.1 FO Cable terminations for Two(2) nos of FO cables from new 33/11kV Al Hail
Industrial substation to existing Transco Al Hail Industrial substation at both ends.

Note: The floor standing FO distribution panel at new Al Hail Industrial substation is
included as per item no E 3.3 of Telecommunication Equipment scope of work.
However the wall mounted OTB at existing Transco Al Hail Industrial substation
for the above 2 nos of FO cables (one OTB shall be supplied for each FO cable
and totally two(2) nos to be supplied) shall be included within the quoted price.
Also the end to end testing of the FO cable and the documentation as per
requirement shall be included within the quoted price.

05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.

C3E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 302 of 536


06.01.2 One (1) set of Essential Distribution Board.

C3E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.

C3E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.

C3E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 303 of 536


C3 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.

ITEM NO. DESCRIPTION CATEGORY
B4 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA
SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 304 of 536


SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 Temperature and Humidity Acquisition devices.

Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:
Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA


C3C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 305 of 536


scope of works listed below are only indicative and no additional costs will be
considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

C3C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under this section includes Site clearing/Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.

01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation was carried out and the report is provided in these
Tender documents. However, this report is provided for guidance and information
only and this will not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC)
shall be carried out as per the Soil Investigation agencys recommendations and
as per design requirements with Authority/Engineers approval and all required
tests including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required in item C3 03.02 Sub structure concrete works.

01.04 Authority and Engineers Site Offices and facilities

Provision of Type-B Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 306 of 536


C3C02 Design and Drawings

Conceptual layout drawings are provided in this Tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper
execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

C3C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings, etc. as per the drawings including drainage,
plumbing and other services.

03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks,
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks, etc.,
up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls,
etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 307 of 536


03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal finishes in the Particular Technical
Specifications shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores
and Toilets as per specification and standards.

03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminium channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 308 of 536


03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including
future/ spare ducts and sleeves as per specification and standards.

b) RCC Cable trenches with removable heavy duty RCC covers shall
be constructed inside transformer rooms and all other cable
trenches and pull pits required for the entire substation.

c) RCC Cable trenches with removable heavy duty RCC covers shall
be constructed to accommodate the new cables to be laid from the
existing 132/33/11 kV Transco Al Hail Industrial Substation to the
new 33/11 kV Al Hail Industrial Substation.

d) RCC trenches for fire main ring with RCC covers.

e) Construction of all manhole chambers required for plumbing, water
supply, telephone cabling etc and valve pits for service water and
firefighting systems are included in this scope of work.

C3C04 Fire pump room

Construction of R.C.C framed building similar to substation main building for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc. shall be included.

C3C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

C3C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements etc.
All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 309 of 536


C3C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.

07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.

C3C08 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including Cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.

The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.

C3C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standard.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements.

C3C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing Municipality asphalt road as per specification and standards.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 310 of 536


C3M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local
authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

C3M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.

Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

C3M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 311 of 536


1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return
valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.

1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.

1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 312 of 536


C3M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.

1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.

1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.

C3M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

C3M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 313 of 536


1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

C3M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 314 of 536


1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.

C3M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

C3M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 315 of 536


1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).

C3M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

C3M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air
Conditioning and Ventilation plant fully functioning for the entire substation
including but not limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and
return air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.







TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 316 of 536


C3M3 Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.,

C3M4 Service Water Supply System

All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves,
shelter, float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel

The transfer pump with one duty and one standby along with the control
panel, pump cut in / cut off, complete pipes and fittings etc., shall be provided
to transfer the water from the underground water tank to the portable water
storage tank located at roof level. The inlet to the underground water tank
from the water distribution main line has to be provided with necessary water
meter, gate valves, isolation vales, etc. Necessary water flow & leakage test
shall be carried out prior to the handing over of substation. This shall include
all works related to pumps, pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:

Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500
Liters.) capacity and shall be located at the highest roof level and shall be
mounted on R.C.C pedestals. The Booster pump with one duty and one
standby along with the control panel, pump cut in / cut off, pipes and fittings
and complete distribution of portable water pipes to various rooms such as
Battery room, toilet etc., shall be provided. This shall include all works related
to pumps, pipe routings with protection, pipe supports, etc. Shade provision
shall be made for the pump set by insulated aluminum sandwich panels
supported by structural steel members.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 317 of 536


C4 EXTENSION OF 33/11kV MIRASHID (MIRA) SUBSTATION

C4E SCOPE OF WORK ELECTRICAL

C4E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified Ten (10) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 One (1) Bus Section and Bus riser with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Two (2) 20 MVA, 33/11kV, HVDT feeders

01.01.3 Seven (7) Cable feeders.

Notes:
1. The 33 kV GIS shall be installed in the existing 33 kV switchgear room.
The Tenderer has to study and propose the 33 kV GIS room layout in
such a way the Power/control cable openings of the 33 kV GIS does not
foul with the floor beams. The Contractor shall make necessary site visit
and ascertain himself regarding the required modification before
tendering.

2. The replacement of existing 33kV switchgear by new 33kV GIS shall be
carried out including completion of civil works with minimum interruption
of power. All necessary possibilities shall be reviewed and the
replacement shall be completed in minimum outage period.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 318 of 536


01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.

01.02.1 One (1) Bus Section.

01.02.2 Two (2) 20 MVA, 33/11kV, HVDT feeders

01.02.3 Five (5) cable feeders with fibre optic current differential protection scheme

01.02.4 Two (2) cable feeders with pilot wire current differential protection scheme

01.02.5 Three (3) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.6 Two (2) nos of Floor standing Pilot wire isolation transformer cubicles suitable for
15kV scheme (comprising of 15 kV isolation transformers, HV TBs etc)

Note: 15kV Pilot wire cable shall be laid and terminated from the above pilot wire
isolation transformer cubicle upto pilot wire termination cubicle which will be
installed by the cable contractor.

01.02.7 One (1) common control panel

Note: 1) Protection of Mirashid and existing Fujairah Corniche substation shall be
coordinated and subject to approval.

2) Protection of Mirashid and existing Ghurfa Main substation shall be
coordinated and subject to approval.

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 2 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 21 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 319 of 536


01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

C4E02 Cabling System

02.01 Cables

02.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation,if required, the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

02.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for two (2) Nos.
of HVDT circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

02.01.2 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension /modification works in the existing
substation.

02.01.3 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the extension /modification works in the
existing substation.

02.02 Cable Terminations

02.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

02.02.1.1 33kV GIS to HVDT circuits, plug-in - type termination for two (2) circuits at 33kV
GIS side


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 320 of 536


02.02.1.2 33kV GIS to HVDT circuits , termination for two (2) circuits at transformer side

02.02.2 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension /modification works in the existing substation.

02.02.3 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension /modification works in the existing substation.

All the control & instrumentation cables of existing transformers, etc shall be
terminated on the new 33 kV GIS switchgear /relay/control panels as applicable
and required as per the approved scheme.

02.03 Cable Trays, Conduits and Accessories

02.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension /modification
works in the existing substation.

C4E03 110 V DC System

03.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of One
(1) set of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account existing
feeders and the above extension under this scope. Also aging factor of 30% and
design margin of 10% shall be considered The temperature derating factor shall
be considered as per battery manufacturers recommendation.

03.02 110 V Battery Charger & DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110 V Battery Charger and one (1) set of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc. The rating shall take into account the existing load and the
extension load under this scope.

C4E04 Earthing

All work related to equipment earthing as required for the extension /modification
works in the substation.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 321 of 536


C4E05 Dismantling/ Removal of existing 33kV Cables and retermination at the
new 33kV GIS

The existing 33kV Cables and terminations for the following circuits shall be
dismantled/removed from existing 33kV GIS. After installation of new 33kV GIS
these cables shall be reterminated to the new 33kV GIS. HV Test with reduced
voltage for these 33kV Cables shall be included within the quoted price.

05.01 Dismantling/ removal of 33kV Cables and terminations of existing Ghurfa Main
substation circuits and retermination to the new 33kV GIS Two (2) circuits

Notes: In case the retermination is not possible on new 33kV GIS panels due to
shortage of existing cable length then new 33kV cables for the two(2) feeders
shall be laid outside the boundary of the substation.Straight through joints shall
be made outside the boundary fo the substation.

C4E06 Testing and commissioning of existing HVDT 1&2

All works related to testing and commissioning of existing 33/11kV 20 MVA
HVDT 1 & 2 including replacement of complete oil and oil filtration .The testing
and commissioning shall be done as specified for new transformers.

C4E07 Dismantling of Existing Equipments

All works related to decommissioning, dismantling, packing, transportation and
delivery to FEWA stores Sharjah for the existing equipments as mentioned
below. The packing shall be suitable for long term storage.

07.01 One (1) set of 33 kV GIS (Calor Emag make) comprising of 9 nos of panels with
accessories

07.02 Eight (8) nos of 33 kV C&R Panels with accessories

07.03 One (1) set of 110 V Battery system

07.04 One (1) set of 110 V Battery chargers & DCDB

07.05 33kV Cables of existing HVDT 1 &2 feeders.

C4 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 322 of 536


transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.



ITEM NO. DESCRIPTION CATEGORY
C4 SC1 SCOPE OF WORK SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of existing ABB
560 RTU to include new 33kV circuits as per
substation SCADA circuit data requirements.
The scope shall include providing extension racks,
modules, cables and other accessories as per the
requirements.

Scope shall also include complete substation
requirements as per tender documents including end
to end testing of new/upgraded circuits with UAQ
SCC, providing Accessories, cabling etc. as per
specification requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 323 of 536


SC 1.2 All the components installed in the existing 33kV
marshalling kiosk including the panel to be
dismantled, properly packed (considering future
usage) and delivered to FEWA stores. New
completely equipped CCC panels (based on latest
revision of signal list) to be provided for all the newly
replaced 33kV circuits.

All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope.

All design and engineering of CCC to be included in
the scope as per the specification and approved
before manufacturing.

SCADA
SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

All cabling and termination from battery chargers and
LVAC panel to respective equipment.

All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA


C4C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

C4C01 Modification works in existing Substation Building

All required civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope shall be included. Modification
works shall include providing of additional openings in the Ground floor slabs and

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 324 of 536


walls, designing and providing the slab support system necessitated due to the
modification works, closing of redundant openings in the slabs and all other
related works.

All finishes to rooms in which extension and modification works to be carried out
under this scope shall be made to be as good as new viz. Wall paint, false ceiling,
floor coatings, etc. to be reinstated.

This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Substation Extension works.

All extension and modification works shall be carried out as per Method
Statement approved by Authority/Engineer.

C4M SCOPE OF WORK MECHANICAL

C4M 1 Fire Protection and Detection System

C4M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 325 of 536


C5 EXTENSION OF 33/11 kV HALIFAT (HALI) SUBSTATION

C5E SCOPE OF WORK ELECTRICAL

C5E01 33kV System

01.01 33kV GIS

01.01.1 Modification of existing 15MVA HVDT-1 & 2 Feeder Bays (H02 & H07) to
20/25MVA HVDT-1 & 2 Feeder Bays

The existing 15MVA HVDT-1 and HVDT-2 Feeder bays H02 (H301) & +H07
(H302) of 33kV GIS shall be modified and used as 20/25MVA HVDT-1 and
HVDT-2 Feeder bays. All work related to modification of 33kV GIS, LV
compartment, including replacement of CTs as per approved CT sizing
calculation shall be carried out and supply of necessary busbars, insulators etc
as required for modification to be provided. All cost towards the above
modification including supply of necessary material, modifications etc shall be
included within the quoted price. All drawings shall be updated to reflect the
changes.

01.02 33kV combined control/relay panels

01.02.1 Modification, testing and commissioning of existing two (2) nos HVDT Feeder
control and relay panels.

Bidders shall review the existing scheme of C&R panels pertaining to the 15
MVA transformers (H301 & H302). Any modifications required to fulfill the tender
protection logic diagram including supply of necessary relays, test terminal
blocks etc shall be supplied, modified and commissioned with in the quoted price.

C5E02 11kV System

02.01 11kV Air Insulated Switchgear

Existing 11kV Air Insulated Switchgear (Make: ABB, Type: Unigear ZS1, 2000A,
31.5kA/3s) shall be extended as shown in the single line diagram and layout
drawing. All work related to design, supply, installation, testing and
commissioning of extension bays with all necessary, bus ducts, risers, adapters,
circuit breakers, earthing switches, CTs, VTs, cable terminations, protection,
control and metering equipment as per schedule of requirement, single line
diagram and detailed technical schedule and specification, C & P diagram etc.

The tenderer has to study and propose the 11kV switchgear layout in such a way
the Power/control cable openings of the 11kV switchgear does not foul with the
floor beams. Necessary dummy panels, if required, shall be included to clear all
the floor beams. The contractor shall make necessary site visit and ascertain

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 326 of 536


himself regarding the existing equipment and required modification before
tendering. The scope shall include but not limited to the following circuits.

02.01.1 Two (2) 630 A Capacitor bank feeders

Note: Any civil work including core drilling in the floor for 11kV and LV/Control Cables,
steel fixing base for 11kV Switchgear, commissioning of existing bays and other
services (if required) shall be included for new 11kV panels as per civil scope of
work.

02.02 11kV AIS Modification works

02.02.1 The existing 15MVA 11kV HVDT-1 and HVDT-2 Incomer bays +K5 & +K18 shall
be modified and used as 20/25 MVA 11kV HVDT-1 and HVDT-2 Incomer bays.
All work related to modification of GA, Schematic diagram, new wiring, any other
components as required to satisfy the scheme requirement and replacement of
CTs as per approved CT sizing calculations shall be included within the quoted
price.

Also CL. 0.2SFs5 CTs along with Energy meter shall be provided for these
existing 11 kV HVDT 1 & 2 Incomer panels.

C5E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF Distribution transformer
with accessories, OLTC, remote control panel (RTCC) for OLTC, neutral CTs etc.
(Percentage impedance at rated tap and maximum rated MVA = 12.5/15.62%)
as per schedule of requirement, detailed technical specification etc.

Note: 1) All the necessary civil works necessary for installation of new 20/25 MVA
transformers in the existing Transformers rooms shall be done by the Contractor
as specified in the Civil scope of work.

2) The new 20/25MVA transformers size shall be suitable for installation in
existing 15MVA transformer room. The minimum clearance around the
transformer shall be provided as specified in design criteria.

03.01.2 NER Modification works (CT Replacement)

The existing 2 nos of NERs ( Make : Metal Deploy, 6.35 ohms, 1000A, 10 sec)
shall be used for neutral earthing of new 20/25 MVA HVDT-1 & 2 and the
existing CTs shall be replaced based on approved CT sizing calculation.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 327 of 536


C5E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

C5E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. If required by cable sizing calculation, the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for two (2) Nos.
of HVDT circuits.

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for two
(2) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for two (2) Nos. of 11kV NER
circuit.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 328 of 536


05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension /modification works in the existing
substation.

05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control, communication and instrumentation cables for the extension
/modification works in the existing substation.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for new HVDT, two (2)
circuits at 33kV GIS side

05.02.1.2 33kV GIS to HVDT, termination for two (2) circuits at transformer side

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit two (2) circuit at both sides

05.02.2.2 HVDT to NER circuit two (2) circuit at both sides

05.02.2.3 11kV switchgear to Capacitor bank circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension /modification works in the existing substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension /modification works in the existing substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 329 of 536


05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension /modification
works in the existing substation.

C5E06 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.

C5E07 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

C5E08 Dismantling of Existing Equipments

All works related to decommissioning, dismantling, packing, transportation and
delivery to FEWA stores Sharjah for the existing equipments as mentioned
below. The packing shall be suitable for long term storage.

08.01 Two (2) 15 MVA , 33/11kV HVDT transformers (Make:France transfo METZ) with
accessories, OLTC, RTCC etc.

C5 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 330 of 536


ITEM NO. DESCRIPTION CATEGORY
C5 SC1 SCOPE OF WORK SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of basic and
extension racks to update the existing ABB RTU 232
to the new version of ABB RTU 560 to accommodate
the new/modified 11kV & 33kV circuits as per the
substation requirements and SCADA data.

Scope shall also include complete substation
requirements as per tender documents including point
to point test for all affected circuits, end to end testing
of new/upgraded circuits with UAQ SCC, providing
Accessories, cabling etc. as per specification
requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA
SC 1.2 Existing 11kV CCC panels to be upgraded in all
respect to include the new 11kV circuits.

Existing 33kV CCC panels to be upgraded to include
the modification/upgraded circuits.

All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope.

All design and engineering of CCC to be included in
the scope as per the specification and approved
before manufacturing.
SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 331 of 536


SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

All cabling and termination from battery chargers and
LVAC panel to respective equipment.

All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA


C5C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

C5C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area, and demobilization as per
the specification and requirements stated elsewhere in the specification.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 332 of 536


Prior to commencement of works for new Capacitor bank building, existing
services at proposed location for new Capacitor bank building to be rerouted and
existing structures such as RCC manholes/foundations etc. demolished and
reconstructed on suitable alternate location. The proposed area shall be
backfilled, graded and leveled to match existing Substation level on completion of
the works. Tenderer shall include his price of all the above works

01.02 Soil Investigation

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the soil investigation agencys recommendations and as per
design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required in Item C5 C03.02 Sub structure concrete works.

01.03 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices

C5C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

C5C03 New Capacitor Bank Building with Clean Agent room

Design and Construction of new building for housing Capacitor bank units and
Clean agent room as per the specifications, including drainage, cable trenches
and other services.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 333 of 536


03.01 Earth Work

Earth work includes excavation for foundations, trenches, duct banks etc. This
includes necessary planking/ shoring and strutting, backfilling, dewatering, etc.
The excess earth material after backfilling shall be carted away to a designated
location approved by the concerned authority. Extreme care shall be taken to
protect the existing equipment and structures during construction. All required
protection arrangements shall be made prior to excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement, beams, columns, walls, trenches, tunnels, duct
banks, etc. up to ground floor including ground floor slab. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor slab such as walls,
columns, beams, slabs, arches, corbels, sill beams, lintel beams, tie beams,
parapet walls etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.
All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors

Supply and installation of doors for the new building including ironmongeries as
per specification and standards. Sliding gate and solenoid locks for Capacitor
Bank rooms are also included in this Scope of work.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specification shall be considered.

03.07 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 334 of 536


03.08 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.09 External Finishes

All external surfaces of the new building shall be finished as per
specification/finishing schedule and standards. External elevations of the new
building shall match with the existing Substation building.

03.10 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.

03.11 Cable Duct Banks, Trenches Manhole chambers and all other civil works

RCC/Cable trenches with removable heavy duty RCC covers shall be constructed
for 11kV, LV and control cables between existing 33kV substation basement and
the new Capacitor bank building. Core drilling in existing substation basement
walls is also included.

All other cable trenches and pull pits required for the entire extension works are
also included in this scope of work.

This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Capacitor bank installation works

C5C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards to match with existing system.

C5C05 Internal Roads, Pavements and Site Surfacing

05.01 Internal Roads

All required works for Road interconnection between existing substation road and
new Capacitor bank building as per Specifications and standards including
extension/modification of existing internal roads around the new Capacitor bank
building (type II interlocking tiled road or to match existing internal road type)
and reinstatement of disturbed/damaged existing roads, as per specification and
standards.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 335 of 536


05.02 Pavements and Walkways

All works for Pavements/walkways for proposed new Capacitor bank building and
reinstatement of existing walkways as per specification and standards.

05.03 Gravel spreading and filling

Reinstatement of Gravel spreading/filling for open areas not covered by
roads/pavements to match with existing.

C5C06 Modification works in existing Substation Building

All required Civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing additional openings in the Ground floor
slab, walls and designing and providing the slab support system necessitated due
to the modification works. Also modification of the plinths and cable trenches in
the Transformer rooms is included in this scope. Also all openings rendered
redundant on completion of the works to be closed/sealed with appropriate
means to the approval of Authority/Engineer.

Removal of metal screens of Transformer rooms to enable installation of the new
Transformers and reinstatement of the same after Transformer installation is
included in the scope of works. If the mesh is damaged during removal/re fixing, it
shall be reinstated with new mesh to the satisfaction of Authority/Engineer.

Boundary wall, wherever demolished during construction works, to be reinstated
as originally existing.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.

C5M SCOPE OF WORK MECHANICAL

C5M 1 Fire Protection and Detection System

C5M 1C Clean Agent System

C5M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 336 of 536


control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

C5M 1D Automatic Fire Detection and Alarm System

All work necessary for extension of existing Fire Detection & Alarm System with
all accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Clean Agent Room. On completion of Fire Detection
and Alarm System modification works, existing Fire Alarm Control Panel shall be
tested for correct operation.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 337 of 536


1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.
.
1D.02 Photoelectric smoke detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors, as per NFPA recommendations.

C5M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) for new Capacitor Bank rooms.

C5M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

C5M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the new Capacitor room and clean agent
room including but not limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers etc., Bib tap with hose tapping from existing service water
line to be provided near the package units.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 338 of 536


M2.02 Extraction fan for clean agent room

M2.03 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.04 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.05 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.06 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 339 of 536


C6 EXTENSION OF 33/11kV QIDFA (QDFA) SUBSTATION

C6E SCOPE OF WORK ELECTRICAL

C6E01 11kV System

01.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

01.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

01.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

01.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

01.01.4 Nine (9 ) 630A outgoing cable feeders with energy metering

01.01.5 Nine (9 ) 630A outgoing cable feeders

01.01.6 Three (3) Capacitor bank feeders

Note: The new 11kV Switchgear shall be installed in existing 11 kV room of the
substation. The contractor shall make necessary site visit and shall propose the
11kV switchgear layout arrangement in line with the existing floor openings. The
power/control cable openings of the 11kV switchgear should not foul with the floor
beams. Necessary dummy panels, if required, shall be included to clear all the
floor beams. Any civil work including core drilling in the floor for 11kV and
LV/Control Cables, steel fixing base for 11kV Switchgear and other services (if
required) for new 11kV switchgear bays shall be included as per civil scope of
work .








TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 340 of 536


C6E02 Transformers and Neutral Earthing Resistor

02.01 HVDT and NER

02.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF Distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

Note: The new 20/25 MVA Transformers shall be installed in the existing transformer
rooms. All the necessary civil works necessary for installation of new 20/25 MVA
transformers in the existing Transformers rooms shall be done by the Contractor
as specified in the Civil scope of work.

02.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

Note: The new NERs shall be installed in the existing NER room. All the necessary
civil works necessary for installation of new NERs in the existing NER room shall
be done by the Contractor as specified in the Civil scope of work.

C6E03 Cabling System

03.01 Cables

03.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. If required by cable sizing calculation, the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

03.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

03.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 341 of 536


03.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

03.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of
11kV NER circuits.

03.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the three (3) Nos. of 6 MVAr, 11kV capacitor bank circuits.

03.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

03.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension/modification works in the existing
substation.

03.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control, communication and instrumentation cables required for the
extension/modification works in the existing substation.
.
03.02 Cable Terminations

03.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

03.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

03.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

03.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 342 of 536


03.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

03.02.2.2 HVDT to NER circuit three (3) circuits at both sides

03.02.2.3 11kV switchgear to Capacitor Bank circuit three (3) circuits at both sides

03.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

03.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc required for the extension/modification works in the existing
substation.

03.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc required for the extension/modification works in the existing
substation.

03.03 Cable Trays, Conduits and Accessories

03.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories required for the extension/modification
works in the existing substation.

C6E04 Earthing

All work related to equipment earthing as required for the extension /modification
works in the substation.

C6C CIVIL ENGINEERING AND BUILDING WORKS

C6C01 Modification Works

The rooms are already available in the existing Substation building for the
installation of new Electrical equipment as per the Electrical scope of works. The
Contractor shall ensure that the existing rooms are adequate for the installation of
the equipment and modifications if any required shall be carried out within the
quoted price.

However, the scope shall include all Civil modifications required in the substation
like modifications in the Transformer plinths, cable trenches, core cutting,
additional steel supports if required for the installation of new equipment
including re-instatement of the structure to its original condition, finishing the
rooms where modification works are carried out, etc. Removal of metal screens
of Transformer rooms to enable installation of the new Transformers and
reinstatement of the same after Transformer installation is included in the scope

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 343 of 536


of works. If the mesh is damaged during removal / re fixing, it shall be reinstated
with the new to the satisfaction of Authority/Engineer.

Modification works shall also include providing additional openings in the Ground
floor slabs and walls, designing and providing the slab support system
necessitated due to the modification works, closing of redundant openings in the
slabs and all other related works.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

The bidder shall visit the site and study the requirements thoroughly before
submitting the offer.

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.

C6M SCOPE OF WORK MECHANICAL

C6M 1 Fire Protection and Detection System

C6M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 344 of 536


C7 EXTENSION OF 33/11kV AL HAIL (HAIL) SUBSTATION

C7E SCOPE OF WORK ELECTRICAL

C7E01 11kV System

01.01 11kV Air Insulated Switchgear

Existing 11kV Air Insulated Switchgear (Make SIEMENS, Turkey, 2000A,
31.5kA/3s) shall be extended by specified number of bays.

All work related to design, supply, installation, testing and commissioning of
extension bays with all necessary, bus ducts, risers, adapters, circuit breakers,
earthing switches, CTs, VTs, cable terminations, protection, control and metering
equipment as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

The Tenderer has to study and propose the 11kV switchgear layout in such a
way the Power/control cable openings of the 11kV switchgear does not foul with
the floor beams. Necessary dummy panels, if required, shall be included to clear
all the floor beams. The contractor shall make necessary site visit and ascertain
himself regarding the existing equipment and required modification before
tendering. Any civil work including core drilling in the floor for 11kV and
LV/Control Cables, steel fixing base for 11kV Switchgear, and other services (if
required) shall be included as per civil scope of work.

The scope shall include but not limited to the following circuits

01.01.1 One (1) 630 A, Capacitor bank feeder

01.01.2 Modification of existing 11kV Cable feeder (=K19) to convert as 11kV Capacitor
bank feeder

In the existing 11kV Switchgear (2000A, 31.5kA/3sec, Make: Siemens, Turkey)
one (1) Spare Cable Feeder (=K19) shall be modified and used as 11kV
Capacitor bank Feeder. All work related to modification of GA, Schematic
diagram, new wiring and any other component as required to satisfy the scheme
requirement shall be included within the quoted price.

C7E02 Capacitor Banks

02.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

02.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 345 of 536


C7E03 Cabling System

03.01 Cables

03.01.1 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

03.01.1.1 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

03.01.2 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension/modification works in the substation.

03.01.3 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the extension/modification works in the
substation.

03.02 Cable Terminations

03.02.1 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

03.02.1.1 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

03.02.2 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.02.3 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.03 Cable Trays, Conduits and Accessories

03.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension/modification
works in the substation.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 346 of 536


C7E04 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.

C7E05 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

C7 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.















TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 347 of 536


C7 SC1 SCOPE OF WORK SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of existing
Microsol RTU to modify new/existing 11kV circuits as
per substation requirements and SCADA data. The
scope shall include providing extension racks,
modules, cables and other accessories as per the
requirements.

Scope shall also include complete substation
requirements as per tender documents including end
to end testing of new/upgraded circuits with UAQ
SCC, providing Accessories, cabling etc. as per
specification requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA
SC 1.2 Upgrade of existing 11kV CCC panel for
new/upgraded 11kV circuits.

All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope.

All design and engineering of CCC to be included in
the scope as per the specification and approved
before manufacturing.

SCADA
SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

SCADA
SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 348 of 536


C7C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

C7C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area and demobilization as per
the specification and requirements stated elsewhere in the specification.

Prior to commencement of works for new Capacitor bank building, existing
services at proposed location for new Capacitor bank building to be rerouted and
existing structures such as RCC manholes/foundations etc. demolished and
reconstructed on suitable alternate location. The proposed area shall be
backfilled, graded and leveled to match existing Substation level on completion of
the works. Tenderer shall include his price of all the above works

01.02 Soil Investigation

During the execution the Contractor shall employ an agency with Authority /
Engineers approval to carry out the Soil investigation for the substation as per
specification and standards.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the soil investigation agencys recommendations and as per
design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required in Item C7 C03.02 Sub structure concrete works.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 349 of 536


01.03 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

C7C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

C7C03 New Capacitor Bank Building with Clean Agent room

Design and Construction of new building for housing Capacitor bank units and
Clean agent room as per the specifications, including drainage, cable trenches
and other services.

03.01 Earth Work

Earth work includes excavation for foundations, trenches, duct banks etc. This
includes necessary planking/ shoring and strutting, backfilling, dewatering, etc.
The excess earth material after backfilling shall be carted away to a designated
location approved by the concerned authority. Extreme care shall be taken to
protect the existing equipment and structures during construction. All required
protection arrangements shall be made prior to excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement, beams, columns, walls, trenches, tunnels, duct
banks, etc. up to ground floor including ground floor slab. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor slab such as walls,
columns, beams, slabs, arches, corbels, sill beams, lintel beams, tie beams,
parapet walls, etc., as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 350 of 536


03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors

Supply and installation of doors for the new building including ironmongeries as
per specification and standards. Sliding gate and solenoid locks for Capacitor
Bank rooms are also included in this Scope of work.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specifications shall be considered.

03.07 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.08 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.09 External Finishes

All external surfaces of the buildings shall be finished as per
specification/finishing schedule and standards. External elevations of the new
rooms shall match with the existing Substation building.

03.10 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.

03.11 Cable Duct Banks, Trenches Manhole chambers and all other civil works

RCC Cable trenches with removable heavy duty RCC covers shall be constructed
for 11kV, LV and control cables between existing 33kV substation basement and
the new Capacitor bank building. Core drilling in existing substation basement
walls is also included.

All other cable trenches and pull pits required for the entire extension works are
also included in this scope of work.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 351 of 536


This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Capacitor bank installation works

C7C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards to match with existing system.

C7C05 Modification works in existing Substation Building

All required Civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing of additional openings in the Ground
floor slabs and walls, designing and providing the slab support system
necessitated due to the modification works. Also all openings rendered redundant
on completion of the works to be closed/sealed with appropriate means to the
approval of Authority/Engineer.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

Internal roads, pavements and gravel areas damaged during construction of the
new Building shall be reinstated and interconnection to the new Building shall be
made.

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.

C7M SCOPE OF WORK MECHANICAL

C7M 1 Fire Protection and Detection System

C7M 1C Clean Agent System

C7M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 352 of 536


1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

C7M 1D Automatic Fire Detection and Alarm System

All work necessary for extension of existing Fire Detection & Alarm System with
all accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Clean Agent Room. On completion of Fire Detection
and Alarm System modification works, existing Fire Alarm Control Panel shall be
tested for correct operation.

1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 353 of 536


1D.02 Photoelectric smoke detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors, as per NFPA recommendations.

C7M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) for new Capacitor Bank rooms.

C7M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

C7M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the new Capacitor room and clean agent
room including but not limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers etc., Bib tap with hose tapping from existing service water
line to be provided near the package units.

M2.02 Extraction fan for clean agent room

M2.03 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.04 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 354 of 536


M2.05 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.06 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 355 of 536


C8 EXTENSION OF 33/11kV SAFFA (SAFF) SUBSTATION

C8E SCOPE OF WORK ELECTRICAL

C8E01 11kV System

01.01 11kV Air Insulated Switchgear

Existing 11kV Air Insulated Switchgear (Make ABB Unigear type ZS1, 2000A,
31.5kA/3s) shall be extended by specified number of bays.

All work related to design, supply, installation, testing and commissioning of
extension bays with all necessary, bus ducts, risers, adapters, circuit breakers,
earthing switches, CTs, VTs, cable terminations, protection, control and metering
equipment as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

The Tenderer has to study and propose the 11kV switchgear layout in such a
way the Power/control cable openings of the 11kV switchgear does not foul with
the floor beams. Necessary dummy panels, if required, shall be included to clear
all the floor beams. The contractor shall make necessary site visit and ascertain
himself regarding the existing equipment and required modification before
tendering. Any civil work including core drilling in the floor for 11kV and
LV/Control Cables, steel fixing base for 11kV Switchgear, and other services (if
required) shall be included for new 11kV bays as per civil scope of work..
The scope shall include but not limited to the following circuits

01.01.1 One (1) 630 A , Capacitor bank feeder

01.01.2 One (1) 630 A , Cable feeder

01.01.3 Modification of existing 11kV Cable feeder(=K01) to convert as 11kV Capacitor
bank feeder

In the existing 11kV Switchgear (2000A, 31.5kA/3sec, Make: ABB,Unigear Type
ZS1) one (1) Cable Feeder (=K01) shall be modified and used as 11kV
Capacitor bank Feeder. All work related to modification of GA, Schematic
diagram, new wiring and CT replacement shall be carried out as per the
protection requirement within the quoted price.

C8E02 Capacitor Banks

02.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

02.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 356 of 536


accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

C8E03 Cabling System

03.01 Cables

03.01.1 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

03.01.1.1 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

03.01.2 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension/modification works in the substation.

03.01.3 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the extension/modification works in the
substation.

03.02 Cable Terminations

03.02.1 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

03.02.1.1 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

03.02.2 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.02.3 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 357 of 536


03.03 Cable Trays, Conduits and Accessories

03.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension/modification
works in the substation.

C8E04 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.

C8E05 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

C8 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be completed
in all respect to meet the substation modification requirements and hence any
items not specifically listed but are essential to satisfactorily complete the works
shall be included in the scope. Therefore, bidder is required to conduct a detailed
site survey before quoting so as to see the availability of existing resources
(Panels, Power supply etc.). Other available resources viz. spare transducers,
Relays, Spare DI/DO modules, Spare circuits etc. already installed at existing
substation can be utilized to meet the scope requirements but the same quantity
shall be compensated to FEWA either by handing over to FEWA as spare or by
installing the same in the panel (in case of space availability/possibility of further
future extension). FEWA/EPE will not be responsible for any lack of information
and it will be bidders responsibility to acquire all information that is required for
quoting the prices and completing the works in accordance with tender
documents.









TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 358 of 536


C8 SC1 SCOPE OF WORK SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of existing ABB
560 RTU to include new/modified 11kV circuits as per
substation requirements and SCADA data. The scope
shall include providing extension racks, modules,
cables and other accessories as per the requirements.
Scope shall also include complete substation
requirements as per tender documents including end
to end testing of new/upgraded circuits with UAQ
SCC, providing Accessories, cabling etc. as per
specification requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA
SC 1.2 New completely equipped CCC panel to be provided
for new 11kV circuits and existing 11kV CCC panels
to be modified in all respect to meet the upgraded
11kV circuits as per substation requirements.

All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope.

All design and engineering of CCC to be included in
the scope as per the specification and approved
before manufacturing.

SCADA
SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

All cabling and termination from battery chargers and
LVAC panel to respective equipment.

All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.
SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 359 of 536


SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA


C8C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

C8C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area, and demobilization as per
the specification and requirements stated elsewhere in the specification.

Prior to commencement of works for new Capacitor bank building, existing
services at proposed location for new Capacitor bank building to be rerouted and
existing structures such as RCC manholes/foundations etc. demolished and
reconstructed on suitable alternate location. The proposed area shall be
backfilled, graded and leveled to match with the existing Substation level on
completion of the works. Tenderer shall include his price for all the above works.

01.02 Soil Investigation

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 360 of 536


Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the soil investigation agencys recommendations and as per
design requirements with Authority / Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required in Item C8 C03.02 Sub structure Concrete Works.

01.03 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices

C8C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

C8C03 New Capacitor Bank Building with Clean Agent room

Design and Construction of new building for housing Capacitor bank units and
Clean agent room as per the specifications, including drainage, cable trenches
and other services.

03.01 Earth Work

Earth work includes excavation for foundations, trenches, duct banks etc. This
includes necessary planking/ shoring and strutting, backfilling, dewatering, etc.
The excess earth material after backfilling shall be carted away to a designated
location approved by the concerned authority. Extreme care shall be taken to
protect the existing equipment and structures during construction. All required
protection arrangements shall be made prior to excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement, beams, columns, walls, trenches, tunnels, duct
banks, etc. up to ground floor including ground floor slab. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 361 of 536


03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor slab such as walls,
columns, beams, slabs, arches, corbels, sill beams, lintel beams, tie beams,
parapet walls, etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.
All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors

Supply and installation of doors for the new building including ironmongeries as
per specification and standards. Sliding gate and solenoid locks for Capacitor
Bank rooms are also included in this Scope of work.

03.06 Floor finishes including Skirting and dado, etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specifications shall be considered.

03.07 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.08 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.09 External Finishes

All external surfaces of the buildings shall be finished as per
specification/finishing schedule and standards. External elevations of the new
rooms shall match with the existing Substation building.

03.10 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 362 of 536


03.11 Cable Duct Banks, Trenches Manhole chambers and all other civil works

RCC Cable trenches with removable heavy duty RCC covers shall be constructed
for 11kV, LV and control cables between existing 33kV substation basement and
the new Capacitor bank building. Core drilling in existing substation basement
walls is also included.

All other cable trenches and pull pits required for the entire extension works are
also included in this scope of work.

This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Capacitor bank installation works

C8C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards/to match with existing system.

C8C05 Modification works in existing Substation Building

All required Civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing of additional openings in the Ground
floor slab,walls and designing and providing the slab support system necessitated
due to the modification works. Also all openings rendered redundant on
completion of the works to be closed/sealed with appropriate means to the
approval of Authority/Engineer.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

Boundary wall, wherever demolished during construction works, to be reinstated
as originally existing and existing gate to be relocated.

Internal roads, pavements and gravel areas damaged during construction of the
new Building shall be reinstated and interconnection to the new Building shall be
made.

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 363 of 536


C8M SCOPE OF WORK MECHANICAL

C8M 1 Fire Protection and Detection System

C8M 1C Clean Agent System

C8M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 364 of 536


C8M 1D Automatic Fire Detection and Alarm System

All work necessary for extension of existing Fire Detection & Alarm System with
all accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Clean Agent Room. On completion of Fire Detection
and Alarm System modification works, existing Fire Alarm Control Panel shall be
tested for correct operation.

1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.

1D.02 Photoelectric smoke detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors, as per NFPA recommendations.

C8M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) for new Capacitor Bank rooms.

C8M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

C8M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the new Capacitor room and clean agent
room including but not limited to the following:


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 365 of 536


M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers etc., Bib tap with hose tapping from existing service water
line to be provided near the package units.

M2.02 Extraction fan for clean agent room

M2.03 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.04 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.05 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.06 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 366 of 536


C9 EXTENSION OF 33/11kV FUJAIRAH TOWER (FUJR) SUBSTATION

C9E SCOPE OF WORK ELECTRICAL

C9E01 11kV System

01.01 11kV Air Insulated Switchgear

Existing 11kV Air Insulated Switchgear (Make TAMCO, UAE, 2000A, 20kA/3s)
shall be extended by 4 nos of panels. These panels shall be free issued by
FEWA from 33/11kV Akkamia (AKAM) substation after it is being dismantled as
per scope item D4.

All work related to taking delivery from Akkamia substation, transportation,
installation, testing and commissioning of the extension bays with all necessary,
bus ducts, risers, adapters, circuit breakers, earthing switches, CTs, VTs, cable
terminations, protection, control and metering equipment as per schedule of
requirement, single line diagram and detailed technical schedule and
specification, C & P diagram etc.

The Tenderer has to study and propose the 11kV switchgear layout in such a
way the Power/control cable openings of the 11kV switchgear does not foul with
the floor beams. Necessary dummy panels, if required, shall be included to clear
all the floor beams. The contractor shall make necessary site visit and ascertain
himself regarding the existing equipment and required modification before
tendering. Any civil work including core drilling in the floor for 11kV and
LV/Control Cables, steel fixing base for 11kV Switchgear, and other services (if
required) shall be included for these 11kV panels as per civil scope of work.
The scope of shall include but not limited to the following circuits

01.01.1 Two (2) 630 A , Cable feeders (Free issued from Akkamia substation)

01.01.2 Installation and modification of 2 nos of 11kV Cable feeders (Free issued from
Akkamia substation) and convert as 11kV Capacitor bank feeders

The two (2) nos of 11kV Switchgear panels (2000A, 20kA/3sec, Make: TAMCO
UAE) free issued from Akkamia substation shall be modified after installation and
used as 11kV Capacitor bank Feeder. All work related to modification of GA,
Schematic diagram, new wiring and CT replacement shall be carried out as per
the protection requirement within the quoted price.

C9E02 Capacitor Banks

02.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

02.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 367 of 536


accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

C9E03 Cabling System

03.01 Cables

03.01.1 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

03.01.1.1 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

03.01.2 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension/modification works in the substation.

03.01.3 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the extension/modification works in the
substation.

03.02 Cable Terminations

03.02.1 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

03.02.1.1 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

03.02.2 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.02.3 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 368 of 536


03.03 Cable Trays, Conduits and Accessories

03.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension/modification
works in the substation.

C9E04 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.

C9E05 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

C9 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.











TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 369 of 536


C9 SC1 SCOPE OF WORK SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of existing ABB
560 RTU to include new/modified 11kV circuits as per
substation requirements and SCADA data. The scope
shall include providing extension racks, modules,
cables and other accessories as per the requirements.
Scope shall also include complete substation
requirements as per tender documents including end
to end testing of new/upgraded circuits with UAQ
SCC, providing Accessories, cabling etc. as per
specification requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA
SC 1.2 New completely equipped CCC panel to be provided
for new 11kV circuits and existing 11kV CCC panels
to be modified in all respect to meet the upgraded
11kV circuits as per substation requirements.

All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope.

All design and engineering of CCC to be included in
the scope as per the specification and approved
before manufacturing.

SCADA
SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

All cabling and termination from battery chargers and
LVAC panel to respective equipment.

All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 370 of 536


SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA


C9C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

C9C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area and demobilization as per
the specification and requirements stated elsewhere in the specification.

Prior to commencement of works for new Capacitor bank building, existing
services at proposed location for new Capacitor bank building to be rerouted and
existing structures such as RCC manholes/foundations etc. demolished and
reconstructed on suitable alternate location. The proposed area shall be
backfilled, graded and leveled to match existing Substation level on completion of
the works. Tenderer shall include his price of all the above works

01.02 Soil Investigation

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 371 of 536


Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the Soil Investigation agencys recommendations and as per
design requirements with Authority / Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in Item C9 C03.02 Sub structure Concrete Works.

01.03 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

C9C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

C9C03 New Capacitor Bank Building with Clean Agent room

Design and Construction of new building for housing Capacitor bank units and
Clean agent room as per the specifications, including drainage, cable trenches
and other services.

03.01 Earth Work

Earth work includes excavation for foundations, trenches, duct banks etc. This
includes necessary planking/ shoring and strutting, backfilling, dewatering, etc.
The excess earth material after backfilling shall be carted away to a designated
location approved by the concerned authority. Extreme care shall be taken to
protect the existing equipment and structures during construction. All required
protection arrangements shall be made prior to excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement, beams, columns, walls, trenches, tunnels, duct
banks, etc. up to ground floor including ground floor slab. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 372 of 536


03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor slab such as walls,
columns, beams, slabs, arches, corbels, sill beams, lintel beams, tie beams,
parapet walls, etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors

Supply and installation of doors for the new building including ironmongeries as
per specification and standards. Sliding gate and solenoid locks for Capacitor
Bank rooms are also included in this Scope of work.

03.06 Floor finishes including Skirting and dado, etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specifications shall be considered.

03.07 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.08 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.09 External Finishes

All external surfaces of the buildings shall be finished as per
specification/finishing schedule and standards. External elevations of the new
rooms shall match with the existing Substation building.

03.10 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 373 of 536


03.11 Cable Duct Banks, Trenches Manhole chambers and all other civil works

RCC Cable trenches with removable heavy duty RCC covers shall be constructed
for 11kV, LV and control cables between existing 33kV substation basement and
the new Capacitor bank building. Core drilling in existing substation basement
walls is also included.

ll other cable trenches and pull pits required for the entire extension works are
also included in this scope of work.

This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Capacitor bank installation works

C9C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards to match with the existing system.

C9C05 Modification works in existing Substation Building

All required Civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing of additional openings in the Ground
floor slab and walls, designing and providing the slab support system
necessitated due to the modification works. Also all openings rendered redundant
on completion of the works to be closed/sealed with appropriate means to the
approval of Authority/Engineer.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

Boundary wall, wherever demolished during construction works, to be reinstated
as originally existing.

Internal roads, pavements and gravel areas damaged during construction of the
new Building shall be reinstated and interconnection to the new Building shall be
made.

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 374 of 536


C9M SCOPE OF WORK MECHANICAL

C9M 1 Fire Protection and Detection System

C9M 1C Clean Agent System

C9M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 375 of 536



C9M 1D Automatic Fire Detection and Alarm System

All work necessary for extension of existing Fire Detection & Alarm System with
all accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Clean Agent Room. On completion of Fire Detection
and Alarm System modification works, existing Fire Alarm Control Panel shall be
tested for correct operation.

1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.

1D.02 Photoelectric smoke detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors, as per NFPA recommendations.

C9M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) for new Capacitor Bank rooms.

C9M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

C9M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the new Capacitor room and clean agent
room including but not limited to the following:


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 376 of 536


M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers etc., Bib tap with hose tapping from existing service water
line to be provided near the package units.

M2.02 Extraction fan for clean agent room

M2.03 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.04 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.05 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.06 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 377 of 536


C10 EXTENSION OF 33/11kV FUJAIRAH TOWN CENTER
(TWCN) SUBSTATION

C10E SCOPE OF WORK ELECTRICAL

C10E01 11kV System

01.01 11kV Air Insulated Switchgear

Existing 11kV Air Insulated Switchgear (Make Siemens, Turkey, 2000A,
31.5kA/3s) shall be extended by specified number of bays.

All work related to design, supply, installation, testing and commissioning of
extension bays with all necessary, bus ducts, risers, adapters, circuit breakers,
earthing switches, CTs, VTs, cable terminations, protection, control and metering
equipment as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

The Tenderer has to study and propose the 11kV switchgear layout in such a
way the Power/control cable openings of the 11kV switchgear does not foul with
the floor beams. Necessary dummy panels, if required, shall be included to clear
all the floor beams. The contractor shall make necessary site visit and ascertain
himself regarding the existing equipment and required modification before
tendering. Any civil work including core drilling in the floor for 11kV and
LV/Control Cables, steel fixing base for 11kV Switchgear, and other services (if
required) shall be included for new 11kV panels as per civil scope of work.
The scope shall include but not limited to the following circuits

01.01.1 Two (2) 630 A , Capacitor bank feeders

C10E02 Capacitor Banks

02.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

02.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

C10E03 Cabling System

03.01 Cables

03.01.1 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 378 of 536


03.01.1.1 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

03.01.2 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension/modification works in the substation.

03.01.3 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the extension/modification works in the
substation.

03.02 Cable Terminations

03.02.1 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

03.02.1.1 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

03.02.2 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.02.3 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.03 Cable Trays, Conduits and Accessories

03.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension/modification
works in the substation.

C10E04 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 379 of 536


C10E05 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

C10 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be completed
in all respect to meet the substation modification requirements and hence any
items not specifically listed but are essential to satisfactorily complete the works
shall be included in the scope. Therefore, bidder is required to conduct a detailed
site survey before quoting so as to see the availability of existing resources
(Panels, Power supply etc.). Other available resources viz. spare transducers,
Relays, Spare DI/DO modules, Spare circuits etc. already installed at existing
substation can be utilized to meet the scope requirements but the same quantity
shall be compensated to FEWA either by handing over to FEWA as spare or by
installing the same in the panel (in case of space availability/possibility of further
future extension). FEWA/EPE will not be responsible for any lack of information
and it will be bidders responsibility to acquire all information that is required for
quoting the prices and completing the works in accordance with tender
documents.


C10 SC1 SCOPE OF WORK SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of basic and
extension racks to update the existing ABB RTU 232
to the new version of ABB RTU 560 to accommodate
the new/modified 11kV circuits as per the substation
requirements and SCADA data.

Scope shall also include complete substation
requirements as per tender documents including point
to point test for all affected circuits, end to end testing
of new/upgraded circuits with UAQ SCC, providing
Accessories, cabling etc. as per specification
requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 380 of 536


SC 1.2 Existing 11kV CCC panels to be modified in all
respect to meet the New/ upgraded 11kV circuits as
per substation requirements.

All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope.

All design and engineering of CCC to be included in
the scope as per the specification and approved
before manufacturing.

SCADA
SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

SCADA
SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA


C10C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 381 of 536


C10C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area and demobilization as per
the specification and requirements stated elsewhere in the specification.

Prior to commencement of works for new Capacitor bank building, existing
services at proposed location for new Capacitor bank building to be rerouted and
existing structures such as RCC manholes/foundations, etc. to be demolished
and reconstructed on suitable alternate location. Also the portion of the existing
Boundary wall between the existing Substation and the extension to the plot is to
be demolished. The proposed area shall be backfilled, graded and leveled to
match existing Substation level on completion of the works.

Tenderer shall include his price for all the above works.

Soil Investigation Report for the existing Substation is included in this Tender
document.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the Soil Investigation agencys recommendations and as per
design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item C10 C03.02 Sub structure concrete works.

01.02 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices

C10C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 382 of 536


C10C03 New Capacitor Bank Building with Clean Agent room

Design and Construction of new building for housing Capacitor bank units and
Clean agent room as per the specifications, including drainage, cable trenches
and other services.

03.01 Earth Work

Earth work includes excavation for foundations, trenches, duct banks etc. This
includes necessary planking/ shoring and strutting, backfilling, dewatering, etc.
The excess earth material after backfilling shall be carted away to a designated
location approved by the concerned authority. Extreme care shall be taken to
protect the existing equipment and structures during construction. All required
protection arrangements shall be made prior to excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement, beams, columns, walls, trenches, tunnels, duct
banks, etc. up to ground floor including ground floor slab. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor slab such as walls,
columns, beams, slabs, arches, corbels, sill beams, lintel beams, tie beams,
parapet walls, etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors

Supply and installation of doors for the entire Capacitor bank building including
ironmongeries as per specification and standards. Sliding gate and solenoid locks
for Capacitor Bank rooms are also included in this Scope of work.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specifications shall be considered.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 383 of 536


03.07 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.08 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.09 External Finishes

All external surfaces of the buildings shall be finished as per
specification/finishing schedule and standards. External elevations of the new
rooms shall match with the existing Substation building.

03.10 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.

03.11 Cable Duct Banks, Trenches Manhole chambers and all other civil works

RCC Cable trenches with removable heavy duty RCC covers shall be constructed
for 11kV, LV and control cables between existing 33kV substation basement and
the new Capacitor bank building. Core drilling in existing substation basement
walls is also included.

All other cable trenches and pull pits required for the entire extension works are
also included in this scope of work.

This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Capacitor bank installation works

C10C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards/to match with existing system.

C10C05 Internal Roads, Pavements and Site Surfacing

05.01 Internal Roads

All required works for Road interconnection between existing substation road and
new Capacitor bank building as per Specifications and standards including

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 384 of 536


extension/modification of existing internal roads around the new Capacitor bank
building (type II interlocking tiled road or to match existing internal road type)
and reinstatement of disturbed/damaged existing roads, as per specification and
standards.

05.02 Pavements and Walkways

All works for Pavements / walkways for proposed new Capacitor bank building
and reinstatement of existing walkways as per specification and standard.

05.03 Gravel spreading and filling

Reinstatement of Gravel spreading/filling for open areas not covered by
roads/pavements to match with existing.

C10C06 Boundary wall extension

Existing boundary wall to be demolished as indicated on the Tender drawings and
new Boundary wall to be constructed around new extension of the plot as per
specification and standards

C10C07 Modification works in existing Substation Building

All required Civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing of additional openings in the Ground
floor slab and walls and designing and providing the slab support system
necessitated due to the modification works. Also all openings rendered redundant
on completion of the works to be closed/sealed with appropriate means to the
approval of Authority/Engineer.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.












TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 385 of 536


C10M SCOPE OF WORK MECHANICAL

C10M 1 Fire Protection and Detection System

C10M 1C Clean Agent System

C10M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 386 of 536


C10M 1D Automatic Fire Detection and Alarm System

All work necessary for extension of existing Fire Detection & Alarm System with
all accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Clean Agent Room. On completion of Fire Detection
and Alarm System modification works, existing Fire Alarm Control Panel shall be
tested for correct operation.

1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.

1D.02 Photoelectric smoke detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors, as per NFPA recommendations.

C10M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) for new Capacitor Bank rooms.

C10M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

C10M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the new Capacitor room and clean agent
room including but not limited to the following:


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 387 of 536


M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers etc., Bib tap with hose tapping from existing service water
line to be provided near the package units.

M2.02 Extraction fan for clean agent room

M2.03 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.04 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.05 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.06 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 388 of 536


C11. PROTECTION MODIFICATION WORKS AT EXISTING SUBSTATIONS IN
EAST AREA (A)

All the modifications as required in the 33 kV GIS, LV Compartment,Control &
Relay Panels , Busbar protection panels etc including but not limited to changing
the labels, modifying the schematic diagrams, GA drawings, layout drawing
preparation and revision of all relevant drawings, SLDs, etc. as required to reflect
the circuit changes shall be carried out by the contractor under scope of this
contract within the quoted price. All such drawings whether specifically
mentioned or not shall be modified and submitted to Engineer/Authoritys
approval by the substation contractor at an early stage of project execution. All
extension and modification works shall be carried out by the substation
contractor with minimum outage only. The substation contractor in his offer shall
state the requirement of shut down in the existing substations.

The complete set of as built drawings (wherever changes as required) shall be
resubmitted incorporating the changes. The Authority reserve the right to ask the
substation contractor to retest and recommission any item or plant disturbed
during modification works without any cost and time implication to the Authority
and no deviation is acceptable in this regard. The contractor must visit the site
and all necessary existing information, drawings, documents, etc. required shall
be collected without any implications to authority. Any minor civil modifications
anticipated in the 33 kV GIS room, Control & Relay room etc. shall be carried out
by the substation contractor.

Modification of the existing protection panels shall be carried out by qualified and
experienced Engineer approved by FEWA. All the modifications shall be carried
out with minimum shutdown requirements and without any disturbance to existing
system. The tenderer shall make site visit and assess themselves all the required
modifications to be carried out in existing panels and the cost towards all works
shall be included within the quoted price.
All modifications required in existing panels, relay and control panels, AC/DC
system etc shall be included within the quoted price.

The existing substation as built drawings including but not limited to layout of
main equipments, sections, cable route layout, cable tray layout, earthing
drawings, control and protection schematic diagrams of existing bays (Bus
section, common control panels, adjacent panels etc), substation single line
diagrams, associated civil and electromechanical drawings affected by the
modification works etc shall be suitably modified and submitted for approval at an
early stage. All such drawings shall also be made as final as built drawings by
the substation contractor in addition to the equipment drawings.

Any relocation of existing equipments required for works shall be deemed to be
included in the quoted price. New control cables/LV power cables, fixing
arrangement of relocated equipments etc are also included within the quoted
price.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 389 of 536


All the relay setting calculations as required by Authority shall be carried out by
the contractor under scope of this contract and shall be submitted to
Engineer/Authority for approval.

Any necessary details including but not limited to existing relay setting and
drawings/ information etc as required shall be collected from site/relays by
contractor under the scope of this tender. All schematic diagrams shall be tested
and all protection testing including end to end testing shall be carried out within
the quoted price.

Providing manufacturer Specialist for testing and commissioning of Main
protection relays for 33 kV OHL/cable feeders shall be under the scope of this
tender. All cost towards testing and commissioning of Main protection relays by
manufacturer specialist shall be included within the quoted price.

The Main protection relays in the new substation shall be matched with existing
relays at respective remote end substation. In case contractor cannot comply
with this requirement then all cost towards modification and replacement of Main
Protection relays at existing respective remote end substations shall be included
within the quoted price of existing substation modification works without any
contractual implication to Authority. However Authority reserves the right to
decide either to supply new relays and modify the existing panel or to match with
existing relays and the same will be decided during engineering stage.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

C11.1 Protection Modification Works at existing Fujairah Main Substation for New
Najaimat substation cable feeders Three (3) circuits

The existing 33kV GIS Spare Bays (C205 & C315) C&R Panels and existing
33kV GIS bay (C115) C&R Panel presently designated as Al Hail circuit-1 shall
be modified as follows:

C11.1.1 Protection modification as required for New Najaimat Cable feeder (C115) Circuit
No.1

C11.1.2 Protection modification as required for New Najaimat Cable feeder (C205) Circuit
No.2

C11.1.3 Protection modification as required for New Najaimat Cable feeder (C315) Circuit
No.3

The existing 33kV C&R Panels (C115, C205 & C315) are equipped with main
protection suitable for pilot wire protection relay type Solkor Rf, manufactured by
Siemens. These relays shall be removed, new relay suitable for direct fibre optic

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 390 of 536


communication matching with the new Najaimat shall be supplied, installed and
commissioned.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed main protection
relays and auxiliaries to FEWA stores. Supply and installation of new fibre optic
current differential protection relay, modification as required in the control & relay
panels including new wiring and modifications. Any other component such as
auxiliary relay, test terminal block, test plug etc as required to satisfy the scheme
requirement shall be supplied and installed within the quoted price.

CT Calculation shall be submitted and the new relay shall be suitable for the CT
characteristic available at the existing Fujairah Main substation. Bidders shall test
the CTs and note the parameters before making the CT sizing calculation.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

C11.2 Protection Modification Works at existing Al Hail Substation for New
Najaimat substation cable feeders Two (2) circuits

The existing 33kV C&R Panels (H201 & H202) presently designated as Fujairah
Main Circuit -1 & 2 shall be modified and used for new Najaimat substation cable
feeders.

C11.2.1 Protection modification as required for New Najaimat Cable feeder (H201) Circuit
No.1

C11.2.2 Protection modification as required for New Najaimat Cable feeder (H202) Circuit
No.2

The existing 33kV C&R Panels (H201 & H202) are equipped with main protection
suitable for pilot wire protection relay type Solkor Rf, manufactured by Siemens..

Bidder shall match the above main protection relay at new Najaimat Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with new Najaimat at the existing Al Hail Substation.
The send or receive ends shall be properly coordinated by the bidder in order to
satisfy the scheme requirement. The compatibility of new relays installed at
Najaimat (in case of retaining the pilot wire protection relay at Al Hail) shall be
confirmed by the Relay manufacturer.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed main protection
relays to FEWA stores (if required). Supply and installation of new pilot wire
current differential protection relay (if required), modification as required in the

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 391 of 536


control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

C11.3 Protection Modification Works at existing Fujairah Main Substation for New
Water Field-2 substation cable feeders Three (3) circuits

The existing 33kV C&R Panels (H225, H235 & H305) presently designated as
Water Field Circuit -1, 2 & 3 shall be modified as follows:

C11.3.1 Protection modification as required for New Water Field-2 Cable feeder (H225)
Circuit No.1

C11.3.2 Protection modification as required for New Water Field-2 Cable feeder (H235)
Circuit No.2

C11.3.3 Protection modification as required for New Water Field-2 Cable feeder (H305)
Circuit No.3

The existing 33kV C&R Panels (H225, H235 & H305) are equipped with main
protection suitable for pilot wire protection relay type Solkor Rf, manufactured by
Siemens..

Bidder shall match the above main protection relay at new Water Field-2
Substation. However, if matching is not possible then bidder shall replace the
existing main protection relay matching with new Water Field-2 at the existing
Fujairah Main Substation. The send or receive ends shall be properly
coordinated by the bidder in order to satisfy the scheme requirement. The
compatibility of new relays installed at new Water Field-2 (in case of retaining the
pilot wire protection relay at Fujairah Main) shall be confirmed by the Relay
manufacturer.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed main protection
relays to FEWA stores (if required). Supply and installation of new pilot wire
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 392 of 536


The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

C11.4 Protection Modification Works at existing Fujairah Town Center Substation
for New Water Field-2 substation cable feeder One (1) circuit

The existing 33kV C&R Panel (H210) presently designated as Water Field Circuit
shall be modified as follows:

C11.4.1 Protection modification as required for New Water Field-2 Cable feeder (H210)
Circuit

The existing 33kV C&R Panel (H210) is equipped with main protection suitable
for pilot wire protection relay type Solkor Rf, manufactured by Siemens..

Bidder shall match the above main protection relay at new Water Field-2
Substation. However, if matching is not possible then bidder shall replace the
existing main protection relay matching with new Water Field-2 at the existing
Fujairah Town Centre Substation. The send or receive ends shall be properly
coordinated by the bidder in order to satisfy the scheme requirement. The
compatibility of new relays installed at new Water Field-2 (in case of retaining the
pilot wire protection relay at Fujairah Town Centre) shall be confirmed by the
Relay manufacturer.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed main protection
relays to FEWA stores (if required). Supply and installation of new pilot wire
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

C11.5 Protection Modification Works at existing Fujairah Tower Substation for
New Water Field-2 substation cable feeders Two (2) circuits

The existing 33kV GIS Bays (H201 & H204) and related C&R Panels presently
designated as Water Field Circuit -1 & 2 shall be modified as follows:

C11.5.1 Protection modification as required for New Water Field-2 Cable feeder (H201)
Circuit No.1


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 393 of 536


C11.5.2 Protection modification as required for New Water Field-2 Cable feeder (H204)
Circuit No.2

The existing 33kV C&R Panels (H201 & H204) are equipped with main protection
suitable for pilot wire protection relay type 7SD6001, manufactured by Siemens.

Bidder shall match the above main protection relay at new Water Field-2
Substation. However, if matching is not possible then bidder shall replace the
existing main protection relay matching with new Water Field-2 at the existing
Fujairah Tower Substation. The send or receive ends shall be properly
coordinated by the bidder in order to satisfy the scheme requirement. The
compatibility of new relays installed at new Water Field-2 (in case of retaining the
pilot wire protection relay at Fujairah Tower) shall be confirmed by the Relay
manufacturer.

Replacement of existing main protection CTs Class 5P20, 800-600/1A with Class
PX, 800-600/1A CTs at Fujairah Tower to match with the new Water Field-2
Cable feeder protection.

The above work shall include replacement of existing main protection CTs,
modification of GA & Schematic diagram, dismantling, packing and handing over
the existing installed main protection relays to FEWA stores (if required). Supply
and installation of new pilot wire current differential protection relay (if required),
modification as required in the control & relay panels including new wiring and
modifications. Any other component such as auxiliary relay, test terminal block,
test plug etc as required to satisfy the scheme requirement shall be supplied and
installed within the quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

C11.6 Protection Modification Works at existing Transco Al Hail Industrial
Substation for New Al Hail Industrial substation cable feeders Three (3)
circuits

Transco Al Hail Industrial substation is under construction, bay numbers will be
adviced to the successful bidder later.

The existing 33kV Spare Cable Feeder Bays C&R Panels at Transco Al Hail
Industrial substation shall be modified as follows:

C11.6.1 Protection modification as required for New Al Hail Industrial Cable feeder Circuit
No. 1

C11.6.2 Protection modification as required for New Al Hail Industrial Cable feeder Circuit
No. 2


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 394 of 536


C11.6.3 Protection modification as required for New Al Hail Industrial Cable feeder Circuit
No. 3

Bidder shall match the main protection relay at new Al Hail Industrial Substation
with Transco Al Hail Industrial substation. However, if matching is not possible
then bidder shall replace the existing main protection relay matching with new Al
Hail Industrial at Transco Al Hail Industrial substation within the overall quoted
price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new fibre optic
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required to
satisfy the scheme requirement shall be supplied and installed within the quoted
price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

C11.7 Protection Modification Works at existing Gurfa Main Substation for
Mirashid substation cable feeders Two (2) circuits

The existing 33kV GIS Bays (H209 & H214) C&R Panels presently designated as
Mirashid Circuit -1 & 2 shall be modified as follows:

C11.7.1 Protection modification as required for Mirashid Cable feeder (H209) Circuit No.1

C11.7.2 Protection modification as required for Mirashid Cable feeder (H214) Circuit No.2

The existing 33kV C&R Panels (H209 & H214) are equipped with main protection
suitable for pilot wire protection relay type Solkor Rf, manufactured by Siemens..

Bidder shall match the above main protection relay at Mirashid Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with Mirashid at the existing Gurfa Substation. The
send or receive ends shall be properly coordinated by the bidder in order to
satisfy the scheme requirement. The compatibility of new relays installed at
Mirashid (in case of retaining the pilot wire protection relay at Gurfa Main) shall
be confirmed by the Relay manufacturer.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new pilot wire
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 395 of 536


component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

C11.8 Protection Modification Works at existing Fujairah Corniche Substation for
Mirashid substation cable feeders Two (2) circuits

The existing 33kV GIS Bays (H204 & H210) C&R Panels presently designated as
Mirashid Circuit -1 & 2 shall be modified as follows:

C11.8.1 Protection modification as required for Mirashid Cable feeder (H204) Circuit No.1

C11.8.2 Protection modification as required for Mirashid Cable feeder (H210) Circuit No.2

The existing 33kV C&R Panels (H204 & H210) are equipped with main protection
suitable for fibre optic current differential protection relay type Solkor N,
manufactured by Siemens.

Bidder shall match the above main protection relay at Mirashid Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with Mirashid at existing Fujairah Corniche Substation
within the overall quoted price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new fibre optic
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 396 of 536


PART D : EAST AREA (B)

D1 NEW 33/11kV SEIH DIBBA (SEDI) SUBSTATION

D1E SCOPE OF WORK ELECTRICAL

D1E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified twelve (12) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of six (6)
outgoing cable feeders (3 feeeders on L.H.S and 3 feeders on R.H.S of 33kV
GIS). Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Seven (7) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 397 of 536


01.02.1 Two (2) Bus Sections.

01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Seven (7) cable feeders with fibre optic current differential protection scheme

01.02.4 Four (4) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.5 One (1) common control panel

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 21 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

D1E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 398 of 536


02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Six (6 ) 630A outgoing cable feeders with energy metering

02.01.5 Eighteen (18) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

D1E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power supply
to auxiliary system of the substation as per schedule of requirement, detailed
technical specification etc. Auxiliary transformer sizing calculation that includes
motor starting conditions shall be submitted and as per calculation transformer
rating is to be selected.

D1E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 399 of 536


Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

D1E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of
11kV NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate the number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 400 of 536


05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the entire substation.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides

05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 401 of 536


D1E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

D1E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.

D1E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 402 of 536


D1E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

D1 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.



ITEM NO.

DESCRIPTION

CATEGORY
D1 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA
SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 403 of 536


SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:
Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA


D1C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the Tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The
scope of works listed below are only indicative and no additional costs will be

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 404 of 536


considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
Tender documents.

D1C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization,etc.

Scope of work under this section includes Site clearing/Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.

01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation was carried out and the report is provided in these
Tender documents. However, this report is provided for guidance and information
only and this will not relieve the Contractor from his contractual obligations.

During the execution the Contractor shall employ an agency with Authority /
Engineers approval to carry out the Soil investigation for the substation as per
specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC)
shall be carried out as per the Soil Investigation agencys recommendations and
as per design requirements with Authority/Engineers approval and all required
tests including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item D1C03.02 Sub structure Concrete Works.

01.04 Authority and Engineers Site Offices and facilities

Provision of Type-A Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 405 of 536


D1C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper
execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

D1C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings, etc. as per the drawings including drainage,
plumbing and other services.

03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks, etc.,
up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls
etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 406 of 536


03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal finishes in the Particular Technical
Specification shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores
and Toilets as per specification and standards.

03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminum channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 407 of 536


03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks including
future/ spare ducts and sleeves as per specification and standards.

b) RCC Cable trenches with removable heavy duty RCC covers shall
be constructed inside transformer rooms and all other cable
trenches and pull pits required for the entire substation.

c) RCC trenches for fire main ring with RCC covers.

d) Construction of all manhole chambers required for plumbing, water
supply, telephone cabling etc and valve pits for service water and
firefighting systems are included in this scope of work.

D1 C04 Fire pump room

Construction of R.C.C framed building similar to substation main building, for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc shall be included.

D1C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

D1C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements,
etc. All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.

D1C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 408 of 536


07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.

D1C08 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.

The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.

D1C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standards.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements.

D1C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing Municipality asphalt road as per specification and standards.

D1M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 409 of 536


authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

D1M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.
Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

D1M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return
valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 410 of 536


1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.

1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.

D1M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.

1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 411 of 536


1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.

D1M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

D1M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 412 of 536


1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

D1M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 413 of 536


1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.

D1M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

D1M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers
All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).

D1M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 414 of 536


and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

D1M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the entire substation including but not
limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of Hermetic
/ Semi-hermetic / Scroll compressors with suction and delivery valves, Condenser
and Evaporator coil with copper fins, Evaporator fan with drive, Drain pan, Filter
chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.

D1M3 Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.,

D1M4 Service Water Supply System

All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves, shelter,
float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel

The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to transfer
the water from the underground water tank to the portable water storage tank

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 415 of 536


located at roof level. The inlet to the underground water tank from the water
distribution main line has to be provided with necessary water meter, gate valves,
isolation vales, etc. Necessary water flow & leakage test shall be carried out prior
to the handing over of substation. This shall include all works related to pumps,
pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:

Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete distribution
of portable water pipes to various rooms such as Battery room, toilet etc., shall be
provided. This shall include all works related to pumps, pipe routings with
protection, pipe supports, etc. Shade provision shall be made for the pump set by
insulated aluminum sandwich panels supported by structural steel members.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 416 of 536


D2 NEW 33/11kV TAWYEEN (TAWY) SUBSTATION

D2E SCOPE OF WORK ELECTRICAL

D2E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified sixteen (16) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

The civil and services works must cater for future envisaged extension of two (2)
outgoing cable feeders (1 feeeder on L.H.S and 1 feeder on R.H.S of 33kV GIS).
Also the substation control room shall be such that it is possible to add the
relevant control and protection equipment and any other auxiliary equipment
required for future bays.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20/25 MVA, 33/11kV, HVDT feeders

01.01.3 Eleven (11) Cable feeders.

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.

01.02.1 Two (2) Bus Sections.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 417 of 536


01.02.2 Three (3) 33/11kV, 20/25 MVA, HVDT feeders

01.02.3 Eleven (11) cable feeders with fibre optic current differential protection scheme

01.02.4 Eight (8) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.5 One (1) common control panel

Note: 1) Protection of new Tawyeen and existing Transco Tawyeen substation shall be
coordinated and subject to approval.

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 24 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).

01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

D2E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 418 of 536


02.01.2 Three (3) incoming 20/25 MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Twelve (12 ) 630A outgoing cable feeders with energy metering

02.01.5 Twelve (12) 630A outgoing cable feeders

02.01.6 Three (3) Capacitor bank feeders

D2E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of
three (3) sets of 20/25 MVA Dyn11 33/11kV, ONAN/ONAF distribution
transformer with accessories, OLTC, remote control panel (RTCC) for OLTC,
neutral CTs etc. (Percentage impedance at rated tap and maximum rated MVA
= 12.5/15.62%) as per schedule of requirement, detailed technical specification
etc.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of three
(3) NERs of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20/25 MVA HVDTs as per schedule of requirement, detailed technical
specification etc including isolators.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433kV, auxiliary transformer with all accessories for power
supply to auxiliary system of the substation as per schedule of requirement,
detailed technical specification etc. Auxiliary transformer sizing calculation that
includes motor starting conditions shall be submitted and as per calculation
transformer rating is to be selected.

D2E04 Capacitor Banks

04.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

04.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control & relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 419 of 536


Note: Civil works and services shall include provision for total number of three (3)
capacitor bank rooms as the additional one (1) capacitor bank set will be installed
in future.

D2E05 Cabling System

05.01 Cables

05.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. If required by cable sizing calculation, the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

05.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for the three (3)
Nos. of HVDT circuits

05.01.1.2 33kV GIS of new 33/11kV Tawyeen substation to 33 kV GIS of existing
132/33kV Transco Tawyeen Substation (2X1CX500 sq.mm/phase) cables
required for the three (3) Nos. of cable circuits

05.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

05.01.2.1 11kV Switchgear to HVDT (3X1CX630 sq.mm/phase) cables required for the
three (3) Nos. of HVDT circuits.

05.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for the three (3) Nos. of
11kV NER circuits.

05.01.2.3 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos. of 6 MVAr, 11kV capacitor bank circuits.

05.01.2.4 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 420 of 536


05.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the entire substation.

05.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control, communication and instrumentation cables for the entire substation.

05.01.5 Fibre Optic Cables

All works related to design, supply, installation, testing and commissioning of 32
fibre , single mode FO cables for protection and communication/Scada purpose.
The quantity of FO cables shall meet the requirement of all 33kV Cable circuits.
However minimum two(2) FO Cables for the following 3 nos of 33kV Cable
circuits :

05.01.5.1 Fiber Optic Cable (32 fibers) from new 33/11kV Tawyeen substation to existing
Transco Tawyeen substation Two(2) cables required for the three (3) Nos. of
33kV Cable circuits.

05.02 Cable Terminations

05.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

05.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for three (3) circuits at 33kV
GIS side

05.02.1.2 33kV GIS to HVDT circuit, termination for three (3) circuits at transformer side

05.02.1.3 33kV GIS of 33/11kV Tawyeen substation to 33kV GIS of existing 132/33kV
Transco Tawyeen substation, plug-in - type termination for three (3) circuits at 33
kV GIS side ( both ends )

05.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

05.02.2.1 11kV switchgear to HVDT circuit three (3) circuits at both sides

05.02.2.2 HVDT to NER circuit three (3) circuits at both sides


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 421 of 536


05.02.2.3 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

05.02.2.4 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

05.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the entire substation.

05.02.5 Fiber optic Cable Terminations and accessories

ODF and all accessories including joints and terminations and OTB (at existing
Transco Tawyeen substation) for Fiber Optic Cable (32 fibers)

05.02.5.1 FO Cable terminations for Two(2) nos of FO cables from new 33/11kV Tawyeen
substation to existing Transco Tawyeen substation at both ends.

Note: The floor standing FO distribution panel at new Tawyeen substation is included
as per item no E 3.3 of Telecommunication Equipment scope of work. However
the wall mounted OTB at existing Transco Tawyeen substation for the above 2
nos of FO cables (one OTB shall be supplied for each FO cable and totally
two(2) nos to be supplied) shall be included within the quoted price. Also the end
to end testing of the FO cable and the documentation as per requirement shall be
included within the quoted price.

05.03 Cable Trays, Conduits and Accessories

05.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the entire substation.

D2E06 LVAC System

06.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

06.01.1 One (1) set of LVAC Distribution Board.

06.01.2 One (1) set of Essential Distribution Board.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 422 of 536


D2E07 110V DC System

07.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account future
feeders. Also aging factor of 30% and design margin of 10% shall be considered
The temperature derating factor shall be considered as per battery
manufacturers recommendation.

07.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc.

07.03 Inverter Panel

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V DC/220V AC, 4 KVA inverters including all accessories as per
schedule requirement, detailed technical specification etc.

D2E08 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
lighting and small power system including lighting panels, fixtures, junction
boxes, conduit and accessories, wires, power outlets, lighting poles etc. for the
entire substation as per schedule of requirement, detailed technical specification
etc.

D2E09 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system of entire substation equipment including station ground
network, equipment earthing and lightning protection etc. as required for the
complete substation as per schedule of requirement, detailed technical
specification etc.

D2 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the works required in SCADA equipments and
major items are clearly listed. However, the SCADA works shall be completed in
all respect to meet the substation requirements and hence any items not
specifically listed but are essential to satisfactorily complete the works shall be
included in the scope.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 423 of 536




ITEM NO.

DESCRIPTION

CATEGORY
D2 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Supply, Installation, testing and commissioning of IEC
60870-5-101/104 Remote Terminal Unit equipped with
Modems. The works shall also include all necessary
system cabling, extension of supply from DC source
and LVAC.

All design and engineering of RTU to be included in
scope and approved before manufacturing. Scope
shall also include complete substation requirements
as per tender documents, End to end testing of all the
signals with UAQ SCC as well as all other works
required to complete the works as per FEWA
specifications.

SCADA
SC 1.2 Supply, Installation, testing and commissioning of
CCC panels separate for 33kV and 11kV circuits as
per the guidelines given in specification and as per
SCADA circuit data.

All design and engineering of CCC to be included in
scope as per specification and approved before
manufacturing.

SCADA
SC 1.3 All the works related to Supply, installation, glanding,
termination, cabling and testing of Control cables,
System cables. Testing between RTU - CCC and
between Plant - CCC as per SCADA circuit data as
well as for future and spare circuits as per the
specification.

All works related to cabling, termination, SCADA
labeling etc. from Battery Chargers, field equipments
and LVAC panels to respective equipments as per the
specification requirements to be included in the scope.
All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 424 of 536


SC 1.4 Temperature and Humidity Acquisition devices
Installation, testing and commissioning of temperature
and humidity acquisition devices and interfacing them
to SCADA so as to send the room temperature /
humidity information for all major rooms (Control
room, SCADA/Telecom room, etc.) to SCADA. The
devices shall have built in voltage free contacts / 4 to
20 mA transducers and equipped with front panel LCD
display. The same shall be subject to approval during
engineering stage.

SCADA
SC 1.5 Power Supply for Communication / SCADA
Equipment:
Design, supply, installation, testing and
commissioning of 48V DC system comprising of One
(01) set of 48V battery bank, two (02) sets of Battery
chargers in separate enclosures and one (01) DCDB
along with all the accessories in a separate enclosure
as per the requirements specified in specifications.
SCADA


D2C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works. The Tenderer must cover all requirements of
the Tender documents and any other items not specifically mentioned but which
are required for the satisfactory design, construction, operation and
maintenance of all equipment to the satisfaction of Authority/Engineer. The
scope of works listed below are only indicative and no additional costs will be
considered for the items which have been overlooked but are essential for the
proper completion of the project in every respect. This scope of work shall be
read in conjunction with General & Particular Technical Specifications and other
tender documents.

D2C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization,etc.

Scope of work under this section includes Site clearing/ Site grading, Site
mobilization including providing temporary Electricity and Water, temporary
fencing around the plot, Project sign board, temporary access road and
demobilization as per the specification and requirements stated elsewhere in the
specification.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 425 of 536


01.02 Topographical surveying

Contractor shall carry out the Topographical survey for the Substation plot and
the report/drawings to be submitted to Authority / Engineer.

01.03 Soil Investigation

Preliminary Soil Investigation was carried out and the report is provided in these
Tender documents. However, this report is provided for guidance and information
only and this will not relieve the Contractor from his contractual obligations

During the execution the Contractor shall employ an agency with Authority /
Engineers approval to carry out the Soil investigation for the substation as per
specification and standards to reconfirm the requirements.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC)
shall be carried out as per the Soil Investigation agencys recommendations and
as per design requirements with Authority/Engineers approval and all required
tests including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item D2 C03.02 Sub structure concrete works.

01.04 Authority and Engineers Site Offices and facilities

Provision of Type-A Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices.

D2C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by Authority /
Engineer. Preparation of final design and drawings required for the proper
execution and completion of the entire project is covered under this scope and
the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority / Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

D2C03 Substation Building

Design and Construction of complete Basement + Ground floor substation
building for housing equipment required for the substation, toilet, corridor, store
room, stairs, auxiliary buildings etc. as per the drawings including drainage
plumbing and other services.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 426 of 536


03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks,
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks, etc.,
up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls,
etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors and Windows

Supply and installation of doors and windows for the entire substation including
Ironmongeries as per specification and standards. Sliding gates with solenoid
locks for capacitor rooms are also included in this scope.

03.06 Floor finishes including Skirting and dado, etc.

Floor finishes as specified in Internal finishes in the Particular Technical
Specifications shall be considered.

03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for all equipment rooms, corridors, stores
and Toilets as per specification and standards.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 427 of 536


03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Toilet & Battery Room Fittings

Supply and installation of Toilet and Battery room fittings as per specification and
standards.

03.10 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.11 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards.

All works related to GRC coping on the parapet wall, GRC screen panels and
powder coated aluminum channels on the external walls for architectural
elevation purpose as per specification and requirements is also included in this
scope.

03.12 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.

03.13 Cable Duct Banks & Trenches, Manhole chambers and valve pits

a) All works required for the construction of Cable duct banks
including future/ spare ducts and sleeves as per specification
and standards.

b) RCC Cable trenches with removable heavy duty RCC covers
shall be constructed inside transformer rooms and all other cable
trenches and pull pits required for the entire substation.

c) RCC Cable trenches with removable heavy duty RCC covers
shall be constructed to accommodate the new cables to be laid
from the existing 132/33/11kV Transco Tawyeen Substation to
the new 33/11kVTawyeen Substation

d) RCC trenches for fire main ring with RCC covers.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 428 of 536


e) Construction of all manhole chambers required for plumbing,
water supply, telephone cabling etc and valve pits for service
water and firefighting systems are included in this scope of work.

D2C04 Fire pump room

Construction of R.C.C framed building similar to substation main building, for
housing fire water pumps, pumps for service water system and related
equipment. All necessary equipment/ pump foundations, etc shall be included.

D2C05 Fire water tank

Construction of RCC underground fire water tank as per specifications and
standards shall be included.

D2C06 External Foundations and all other civil works

This shall include all works related to the construction of external foundations
such as roof water tank foundations, Street light foundations, Fire hose cabinet
foundations, foundations for the external equipment if any, thrust block, pipe
supports etc., including earthwork, embedment, protection and encasements etc.
All attendant Civil engineering works, particularly excavation, sleeves, ducts,
concrete encasement and backfill for electro-mechanical activities shall also be
covered under this item.

All foundations and exposed concrete surfaces shall be coated with polyurethane
paint. This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the substation.

D2C07 Drainage works

07.01 Storm water drainage works

All works required for Storm water drainage as per specification and standards.

07.02 Sanitary Waste Water Drainage & HVAC drainage works

All works related to sanitary waste water drainage and HVAC drainage works as
per specification and standards.

07.03 Oil water Drainage works

All works related to oil water drainage including construction of underground Oil/
water separator tank as per specification and standards.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 429 of 536


D2C08 Boundary wall, Gates and Embankment

All works for the construction of boundary wall including cast Aluminum gates
and PVC coated barbed wire fencing above the boundary wall as per
specification and standards.

The height of the boundary wall shall be 2.5 m (minimum) from finished ground
level with cast in situ RCC frame and reinforced pre-cast concrete wall panels as
per specification and standards. Cast in-situ RCC retaining wall shall be
constructed for the entire plot limit from strip footing up to plinth level.

3 m wide embankment shall be formed all around the boundary wall (externally)
as per specification and standards.

D2C09 Internal Roads, Pavements and Site Surfacing

09.01 All works for internal roads (type II interlocking tiled road) within the boundary
limit around substation building as per specification and standards.

09.02 All works for Pavements/ walkway as per specification and standards.

09.03 Gravel spreading / filling for open areas not covered by roads/ pavements.

D2C10 External Access Road

All works for external access road (type-I asphalt road) from substation gates to
the nearest existing Municipality asphalt road as per specification and standards.

D2M SCOPE OF WORK MECHANICAL

General

The scope of work as mentioned below is in general for design, manufacture,
testing in works, supply, delivery, handling and storing at site, erection, testing,
painting, completion, commissioning, operation and maintenance during the
warranty period and handing over of the Mechanical Systems. However, if any
items specifically not mentioned but the same is essential to complete the project
in all respect and obtain all the necessary permits, approvals from local
authorities having jurisdiction including Civil Defense the same shall be included
in the scope of work without any contractual implications to FEWA.

D2M 1 Fire Protection and Detection System

The tendered shall design the complete fire protection system as per the
recommendations of NFPA and obtain all necessary permits, approvals, and
certificates from authorities having jurisdiction, including Civil Defense approval
on conceptual fire protection system design.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 430 of 536


Fire Water Tank capacity shall be for minimum one hour fire pump run at water
demand as per approved hydraulic calculations, or as required by Civil Defense
Authority, whichever is greater, but should not be less than 284 Cu.M.

D2M 1A Fire Hydrant System

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising Vertical Shaft Turbine Type Pump, electric drive motor,
discharge isolation valves, discharge non-return valve, piping, fittings, supports,
pressure gauges/transmitters with root valves, etc. Motor Driven Fire Pump
nominal capacity should be as per hydraulic calculations, but not less than 1250
GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising Vertical Shaft Turbine Type Pump, diesel engine, fuel oil
storage tank, batteries, batteries chargers, reduction gear unit, discharge
isolation valves, discharge non return valve, pressure gauges/ transmitters with
root valves, piping, fittings, supports, etc. Diesel Engine Fire Pump nominal
capacity should be as per hydraulic calculations, but not less than 1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
pump, electric drive motor, discharge isolation valves, discharge non return
valve, piping, fittings, supports, pressure gauges/ transmitters with root valves,
etc.

1A.04 Hydrants

All work for requisite number of industrial fire hydrants along with valve, coupling,
hydrant, and hydrant cap.

1A.05 Yard Mains

All work for fire main pipe line, underground inside trench, seamless carbon steel
hot dip galvanized pipe, painted in red, minimum PN 16 bar.

1A.06 Hose Boxes

All work for Hose Boxes for each hydrant comprising Hose Box, hose coupling,
spanner, wrench, hose, and discharge nozzle.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 431 of 536


1A.07 Piping

All work the system piping, comprising pipes, supports, fittings, valves, etc,
including underground firewater storage tank accessories with all necessary
nozzles, valves and ladders.

1A.08 Electrical works

All electrical work required for distribution/control panels, control switches,
instruments, annunciation system, cabling, wiring, conducting, AC/DC power
supply distribution, connections, grounding etc. for the system.

1A.09 Automatic Sprinkler System

All work necessary for installation of Automatic Sprinkler System, including
sprinkler alarm valve complete with accessories, control switches and
instruments, test and drain valves, piping, sprinkler heads, etc. for the Fire Pump
Room, Corridor, Store/Workshop and Toilet rooms.

1A.10 Wet Riser System

All work necessary for installation of Wet Riser System, including 2 inch hose
connections complete with drain, relief and isolation valves, hoses with
accessories and cabinets and all necessary piping, for the Cable Basement,
Ground Floor and Roof Floor.

D2M 1B Fixed Water Spray System for Transformers and Basements

1B.01 Deluge Valves

All work for deluge valves comprising strainer of deluge valve, deluge valve with
accessories, strainer for water gong, check/isolation/drain valves, water gong,
manual operation station, etc.

1B.02 Piping, valves, and fittings

All work necessary for piping, valves, fittings, flanges and nozzles for the system.
1B.03 Releasing Devices

All work for releasing devices comprising quartzoid bulb type, for both Cable
Basements and Transformers.

1B.04 Electrical work

All electrical work for control panels, control switches, instruments, annunciation
system, cabling, wiring, conducting, AC/DC power supply distribution,
connections, grounding etc. for the system.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 432 of 536


D2M 1C Clean Agent System

All work necessary for Automatic Clean Agent Extinguishing System, including
one Clean Agent Extinguishing System for Capacitor Bank Rooms and local
Clean Agent Extinguishing Systems for Electrical Equipment Rooms.

D2M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 433 of 536


D2M 1C2 Clean Agent System for Electrical Equipment Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage cylinders, actuating and discharge pipe work and nozzles,
control switches and instruments, cabling, wiring, conducting, AC/DC power
supply distribution, extinguishing control panel expansion modules, detectors,
annunciation system, required interlocks etc. for the Electrical Equipment Rooms,
including LVAC, DC, Control and Relay Room, SCADA/Telecom Room, 11kV
Switchgear Room, Battery Room, NER Room and 33kV GIS room.

1C2.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders, manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C2.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of storage
cylinders pipe work, pneumatic pilot operated valves, brass chrome discharge
nozzles, properly sized pipe work with rigid supports.

1C2.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C2.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C2.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of addressable
Extinguishing Control Panel expansion modules, audible and visual notification
appliances, supervisory inputs, supervised outputs and dry voltage outputs for
interlocks.







TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 434 of 536


D2M 1D Automatic Fire Detection and Alarm System

All work necessary for Automatic Fire Detection & Alarm System with all
accessories comprising Heat detector, photoelectric type smoke detectors, etc.

1D.01 Electrical work

All electrical work required for control panels, control switches, instruments,
annunciation system, cabling, wiring, conducting, AC/DC power supply
distribution, connections, grounding etc. for the system.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply and installation of Photoelectric Smoke detectors
and Heat detectors, as per NFPA recommendations.

1D.03 Linear Heat Detectors

All work necessary for basement cables, circuit wise, Linear Heat Detectors as
per NFPA recommendations.

D2M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg), CO2 extinguishers (12kg) and AFFF extinguisher
(125 ltr).

D2M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 435 of 536


D2M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the entire substation including but not
limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of Hermetic
/ Semi-hermetic / Scroll compressors with suction and delivery valves, Condenser
and Evaporator coil with copper fins, Evaporator fan with drive, Drain pan, Filter
chambers etc.,

M2.02 Split type air conditioning units consists of indoor & outdoor units

M2.03 Supply and Extraction fans

M2.04 Smoke extraction System

M2.05 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.06 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.07 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.08 Complete HVAC system testing, commissioning and training.

D2M3 Electric Monorail Hoists

M3.01 Monorail Hoists

All work required for three (3) tons Monorail Hoists along with Drive Motors,
runway beam and all other accessories, etc.,

D2M4 Service Water Supply System

All works required for complete fully functioning Service water system for the
entire substation including roof storage water tank, pumps, piping, valves, shelter,
float switches, cables, instruments, distribution and control panel, etc.

M4.01 Transfer pumps, piping works and control panel

The transfer pump with one duty and one standby along with the control panel,
pump cut in / cut off, complete pipes and fittings etc., shall be provided to transfer
the water from the underground water tank to the portable water storage tank
located at roof level. The inlet to the underground water tank from the water
distribution main line has to be provided with necessary water meter, gate valves,
isolation vales, etc. Necessary water flow & leakage test shall be carried out prior

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 436 of 536


to the handing over of substation. This shall include all works related to pumps,
pipe routings with protection, pipe supports etc.,

M4.02 Roof water storage tank, Booster pumps and piping works:

Overhead tank shall be of insulated G.R.P panel type of 2.5Cu.M (2,500 Liters.)
capacity and shall be located at the highest roof level and shall be mounted on
R.C.C pedestals. The Booster pump with one duty and one standby along with
the control panel, pump cut in / cut off, pipes and fittings and complete distribution
of portable water pipes to various rooms such as Battery room, toilet etc., shall be
provided. This shall include all works related to pumps, pipe routings with
protection, pipe supports, etc. Shade provision shall be made for the pump set by
insulated aluminum sandwich panels supported by structural steel members.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 437 of 536


D3 EXTENSION OF 132/33/11 kV DIBBA MAIN (DBMN) SUBSTATION

D3E SCOPE OF WORK ELECTRICAL

D3E01 33kV System

01.01 33kV GIS

Existing 33kV Switchgear (Make Siemens Germany, 2500A, 40kA/3sec) shall be
extended for two (2) 33kV Switchgear bays as specified below. All work related
for above extension, such as but not limited to design, supply, installation, testing
and commissioning of Busbars, adapters, dummy panels, circuit breakers,
disconnectors, earthing switches, CTs, VTs, cable termination sockets and plugs,
plug-in termination, dummy plugs, protection, control and metering equipment as
per schedule of requirement, single line diagram and detailed technical schedule
and specification, C & P diagram etc.

Bidder shall check that the existing operating tools, special tools, and tackles,
plugs and connecting leads for HVAC test of GIS/HV test of cables, set of plugs
and connecting lead for CT primary injection, set of special tools to dismantle
plug in type termination from GIS, dummy plugs for line VTs etc. can be used for
the maintenance of the new bays and where not to include the necessary special
tools and equipment in the overall quoted price of GIS bay as common item. SF
6

gas required for topping up at site shall also be supplied within the quoted price.
If line VTs are separately connected then connecting cable, terminations etc.
shall also to be supplied by the GIS manufacturer within the quoted price.

33kV GIS manufacturers supervisors from the factory shall be provided for
installation, testing and commissioning within the quoted price.

The 33kV GIS and Control/Relay panels shall be similar to the existing 33kV GIS
and Control/Relay panels

01.01.1 Two (2) Cable feeders

01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing and commissioning
one (1) complete set of 33kV combined control/relay panels for bays as specified
with all accessories as per schedule of requirement, detailed technical
specification, tender drawings etc.

01.02.1 Two (2) Cable feeders with fibre optic current differential protection scheme

01.02.2 Modification of the existing HVDT-3 control & relay panel (=WR24)




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 438 of 536


Existing Spare HVDT-3 C&R panel +WR24 shall be used for new HVDT-3.
Transformer differential protection relay and inter-trip receive relay are not
available in the existing C&R Panel. Bidders shall review the existing scheme of
C&R panel pertaining to the 20MVA transformer. All modifications required to
fulfill the tender protection logic diagram including supply of necessary relays,
test terminal blocks etc shall be supplied, modified and commissioned within the
quoted price.

Note: 1) Protection of Dibba Main and new Seih Dibba substation shall be coordinated
and subject to approval.

2) The existing synchronizing scheme shall be suitably modified to include the
above feeders of 33 kV GIS.

01.03 33kV Busbar protection panels.

01.03.1 All work related to supply and installation of trip relays for connecting two (2) new
33kV GIS bays with the existing busbar protection and complete wiring
modification in the existing busbar protection panels. The new relay setting
calculation, subject to FEWA approval, shall be prepared and submitted by the
substation contractor.
.
01.04 33kV plug in type terminations.

01.04.1 Supply of 6 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing feeders.

01.04.2 Supply of dummy plugs (for outgoing feeders under this scope)

D3E02 11kV System

02.01 11kV Air Insulated Switchgear

Existing 11kV Air Insulated Switchgear (Make ABB, Type EJF, 2000A,
31.5kA/3s) shall be modified and extended by busduct connection for 3
rd

Switchgear section consisting of specified bays. All work related to design,
supply, installation, testing and commissioning of extensions bays with all
necessary, bus ducts, risers, adapters, circuit breakers, earthing switches, CTs,
VTs, cable terminations, protection, control and metering equipment as per
schedule of requirement, single line diagram and detailed technical schedule and
specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price (if
offered switchgear is different make).


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 439 of 536


The Bidder has to study and propose the 11kV switchgear layout in such a way
the Power/control cable openings of the 11kV switchgear does not foul with the
floor beams. Necessary dummy panels, if required, shall be included to clear all
the floor beams. The contractor shall make necessary site visit and ascertain
himself regarding the existing equipment and required modification before
tendering. The scope shall include but not limited to the following circuits.

02.01.1 One (1) Bus section and bus riser with 3 phase busbar voltage transformers and
busbar earth switches as per single line diagram.

02.01.2 One (1) incoming 20 MVA, 33/11kV HVDT bay with energy metering

02.01.3 Four (4 ) 630A outgoing cable feeders with energy metering

02.01.4 Five (5 ) 630A outgoing cable feeders

Note: Any civil work including core drilling in the floor for 11kV and LV/Control Cables,
steel fixing base for 11kV Switchgear, commissioning of existing bays and other
services (if required) shall be included for new 11kV panels as per civil scope of
work.

D3E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20MVA, 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of one
(1) set of 20 MVA Dyn11 33/11kV, ONAN Distribution transformer with
accessories, OLTC, neutral CTs etc. Transformer shall be capable of parallel
operation with the two existing HVDTs and shall have MVA Rating, Ratio,
percentage impedance, no of taps and range, etc matching with the existing
transformers in the substation and as per detailed technical specification etc.
Transformer shall be of outdoor type. Bidders shall include the required civil
works in their quoted price as elaborated in civil scope.

Supply and installation shall include new AVR panel for 3
rd
transformer, scheme
modification for parallel operation of three HVDT Transformers and all material
and equipment for existing AVR panels modification shall be included in the offer.
Bidders shall familiarize themselves with existing equipment and conduct site
survey prior to bidding. New AVR panel shall be installed adjacent to existing two
AVR Panels in the existing control room located in the 11kV Switchgear room
building and shall be fully compatible by technical characteristics and physical
appearance (dimensions, colour) to the existing ones.

Note: The existing 33/11kV 20MVA transformers are outdoor type (Make-KONCAR).



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 440 of 536


03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of one
(1) NER of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20MVA HVDT as per schedule of requirement, detailed technical specification
etc including isolators. NER shall be of outdoor type.

The new NER shall be installed in the existing NER room .Bidders shall include
the required civil works as per civil scope of work.

D3E04 Cabling System

04.01 Cables

04.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required, the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

04.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for one (1) Nos.
of HVDT circuit.

04.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

04.01.2.1 11kV Switchgear to HVDT (2X1CX630 sq.mm/phase) cables required for one
(1) Nos. of HVDT circuit.

04.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for one (1) Nos. of 11kV
NER circuit.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

04.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension /modification works in the existing
substation.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 441 of 536


04.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control, communication and instrumentation cables for the extension
/modification works in the existing substation.

04.02 Cable Terminations

04.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

04.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for one (1) circuit at 33kV
GIS side

04.02.1.2 33kV GIS to HVDT circuit, termination for one (1) circuit at transformer side

04.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

04.02.2.1 11kV switchgear to HVDT circuit one (1) circuit at both sides

04.02.2.2 HVDT to NER circuit one (1) circuit at both sides

04.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension /modification works in the existing substation.

04.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension /modification works in the existing substation.

04.03 Cable Trays, Conduits and Accessories

04.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension /modification
works in the existing substation.

D3E05 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 442 of 536


accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.

D3E06 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

D3 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.

D3 SC1 SCOPE OF WORK SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade of Remote Terminal Unit (Type GE Harris) to
include all newly added/upgraded 33 & 11kV circuits.

Scope shall also include complete substation
requirements as per tender documents including end
to end testing of new/upgraded circuits with UAQ
SCC, providing Accessories, cabling etc. as per
specification requirements.

All design and engineering of RTU including providing
hardware and software requirements to complete the
works as per tender requirements to be included in
the scope and approved before
manufacturing/material ordering.
SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 443 of 536


SC 1.2 New completely equipped CCC panel to be provided
for the new 33kV circuits.

New completely equipped CCC panels to be provided
for new 11kV circuits.

All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope. All design and engineering of
CCC to be included in the scope as per the
specification and approved before manufacturing.

SCADA
SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

All cabling and termination from battery chargers and
LVAC panel to respective equipment.

All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 All works required to implement new SCADA
numbering system for entire132/ 33/11kV substation
in accordance with the guidelines given in
specification. The works shall include replacement of
existing SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA


D3C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 444 of 536


been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

D3C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area and demobilization as per
the specification and requirements stated elsewhere in the specification.

Prior to commencement of works for the new Transformer room, existing services
at proposed location for new Transformer room if any to be rerouted and existing
structures such as RCC manholes/foundations etc., if any to be demolished and
reconstructed on suitable alternate location. The proposed area shall be
backfilled, graded and leveled to match existing with the existing Substation level
on completion of the works. Tenderer shall include his price of all the above
works.

Soil Investigation Report for the existing Substation is included in this Tender
document.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the Soil Investigation agencys recommendations and as per
design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required in item D3C03.02 Sub structure concrete works.

01.02 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices

D3C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority/Engineers approval.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 445 of 536


Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

D3C03 New Transformer Room

Design and Construction of new Transformer room next to existing Substation
Building adjacent to existing 33/11kV HVDT Transformer for housing one new 20
MVA (33/11KV) Power Transformer with Roof truss as per the specifications,
including drainage, cable trenches from the new room to the existing Substation
and other services.

03.01 Earth Work

Earth work includes excavation for foundations, trenches, duct banks etc. This
includes necessary planking/ shoring and strutting, backfilling, dewatering, etc.
The excess earth material after backfilling shall be carted away to a designated
location approved by the concerned authority. Extreme care shall be taken to
protect the existing equipment and structures during construction. All required
protection arrangements shall be made prior to excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement, beams, columns, walls, trenches, tunnels, duct
banks, etc. up to plinth level including the Transformer plinth. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above plinth level such as walls, columns,
beams, slabs, arches, corbels, sill beams, lintel beams, tie beams, parapet walls,
etc., as per specification and standards.

03.04 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specifications shall be considered.

03.05 Internal and External Finishes

All internal and external surfaces of the buildings shall be finished as per
specification/finishing schedule and standards. External elevations of the new
room shall match with the existing Transformer rooms.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 446 of 536


03.06 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.

03.07 Cable Duct Banks, Trenches Manhole chambers and all other civil works

Modification works if any required, in the existing Cable trench for
accommodating the new cables

All works required for the construction of cable duct banks including future/spare
ducts and sleeves for the newly installed 11kV Switchgear as per specifications
and standards.

Core drilling in existing substation basement walls is also included. All other cable
trenches and pull pits required for the entire extension works are included in
scope of work.

This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Substation Extension works

D3C04 Drainage Works

04.01 Storm water drainage Works

All works required for Storm water drainage as per specification and standards to
match with existing system.

04.02 Oil water Drainage works

All works related to oil water drainage for the new Transformer room including
connecting to the existing system as per specification and standards.

D3C05 Modification works in existing Substation Building

All required civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope of work shall be included.

Modification works shall include providing additional openings in the Ground floor
slab and walls within the existing Substation building to install newElectrical
equipment asper Electrical scope and designing and providing the slab support
system necessitated due to the modification works. Also all openings rendered
redundant on completion of the works to be closed/sealed with appropriate
means to the approval of Authority/Engineer.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 447 of 536


All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

All existing facilities including roads and pavements disturbed during the
construction of the new Transformer room and other construction activity shall be
reinstated.

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.

D3M SCOPE OF WORK MECHANICAL

D3M 1 Fire Protection and Detection System

D3M 1D Automatic Fire Detection and Alarm System

All work necessary for existing Fire Detection & Alarm System extension with all
accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Transformer Room. On completion of Fire Detection
and Alarm System modification works, existing Fire Alarm Control Panel shall be
tested for correct operation.

1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.
.
1D.02 Heat detectors

All work necessary for supply, installation and commissioning of Heat Detectors.

D3M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg).





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 448 of 536


D3M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 449 of 536


D4 EXTENSION OF 33/11kV AKKAMIA (AKAM) SUBSTATION

D4E SCOPE OF WORK ELECTRICAL

D4E01 33kV System

01.01 33kV GIS

All work related to design, supply, installation, testing & commissioning of one
(1) set of 33kV gas insulated switchgear with single busbar system, current rated
2500A, short circuit current 40kA, 3 Sec. (as per IEC rating of 40
0
C) comprising
the specified twelve (12) bays with all necessary circuit breakers, disconnectors,
earthing switches, CTs, VTs, cable termination sockets and plugs, plug-in
termination, dummy plugs, protection, control and metering equipment as per
schedule of requirement, single line diagram, detailed technical schedule and
specification, C & P diagram etc.

All operating tools, special tools, and tackles, one set of plugs and connecting
leads for HVAC test of GIS/HV test of cables, one set of plugs and connecting
lead for CT primary injection, one set of special tools to dismantle plug in type
termination from GIS, 3 dummy plugs for line VTs etc. shall be supplied within
the overall quoted price of GIS as common items. SF
6
gas required for topping
up at site shall also be supplied within the quoted price. If line VTs are separately
connected then connecting cable, terminations etc. shall also to be supplied by
the GIS manufacturer within the quoted price.

01.01.1 Two (2) Bus Sections and Bus risers with busbar earth switches and 3 phase
busbar voltage transformers for each bus as per SLD.

01.01.2 Three (3) 20 MVA, 33/11kV, HVDT feeders

01.01.3 Seven (7) Cable feeders.

Notes:
1. The 33 kV GIS shall be installed in the existing 33 kV switchgear room. The
Tenderer has to study and propose the 33 kV GIS room layout in such a way the
Power/control cable openings of the 33 kV GIS does not foul with the floor
beams. The Contractor shall make necessary site visit and ascertain himself
regarding the required modification before tendering.

2. The replacement of existing 33kV switchgear by new 33kV GIS shall be carried
out including completion of civil works with minimum interruption of power. All
necessary possibilities shall be reviewed and the replacement shall be
completed in minimum outage period.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 450 of 536


01.02 33kV combined control/relay panels

All work related to the design, supply, installation, testing & commissioning of
one (1) complete set of 33kV combined control/ relay panels with all accessories
as per schedule of requirement, detailed technical specification, tender drawings
etc. for the following circuits.

01.02.1 Two (2) Bus Sections.

01.02.2 Three (3) 33/11kV, 20MVA, HVDT feeders

01.02.3 Four (4) cable feeders with fibre optic current differential protection scheme

01.02.4 Three (3) cable feeders with pilot wire current differential protection scheme

01.02.5 Four (4) sets of matching F.O. current differential protection relays and test
terminal blocks etc (loose supply) for remote ends.

01.02.6 Three (3) nos of Floor standing Pilot wire isolation transformer cubicles for above
three cable feeders suitable for 15kV scheme (comprising of 15kV isolation
transformers, HV TBs etc)

Note: 15kV Pilot wire cable shall be laid and terminated from the above pilot wire
isolation transformer cubicle upto pilot wire termination cubicle which will be
installed by the cable contractor.

01.02.7 One (1) common control panel

Note: 1) Protection of new Akkamia and existing Dibba Main substation shall be
coordinated and subject to approval.

2) Protection of new Akkamia and existing Wassat substation shall be
coordinated and subject to approval.

01.03 33kV Busbar protection panels.

01.03.1 All work related to design, supply, installation, testing and commissioning of one
(1) set of 33kV busbar protection panels segregated between disc-zones and
check zones. (Minimum 3 panels).

01.04 33kV plug in type terminations.

01.04.1 Supply of 21 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders).



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 451 of 536


01.05 Gas Handling Plant

01.05.1 One (1) set of SF6 gas filling and evacuation plant for 33kV GIS with SF6 gas for
site top up. The equipment shall be suitable for the type of switchgear offered. All
accessories shall be supplied.

D4E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2500A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 Two (2) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.

02.01.2 Three (3) incoming 20MVA, 33/11kV HVDT bays with energy metering

02.01.3 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.4 Eight (8 ) 630A outgoing cable feeders with energy metering

02.01.5 Nine (9) 630A outgoing cable feeders

Notes :
1. The 11kV Switchgear shall be installed in the existing 11 kV room. The
Tenderer has to study and propose the 11kV switchgear layout in such
a way the Power /control cable openings of the 11kV switchgear does
not foul with the floor beams. Necessary dummy panels, if required,
shall be included to clear all the floor beams. The contractor shall
make necessary site visit and ascertain himself regarding the required
modification before tendering.

2. The replacement of existing 11kV switchgear by new 11kV switchgear
shall be carried out including completion of civil works with minimum
interruption of power. All necessary possibilities shall be reviewed and
the replacement shall be completed in minimum outage period




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 452 of 536


D4E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of one
(1) set of 20 MVA Dyn11 33/11kV, ONAN Distribution transformer with
accessories, OLTC, neutral CTs etc. Transformer shall be capable of parallel
operation with the two existing HVDTs and shall have MVA Rating, Ratio,
percentage impedance, no of taps and range, etc matching with the existing
transformers in the substation and as per detailed technical specification etc.
Transformer shall be of outdoor type. The bidders shall include the required civil
works in their quoted price as elaborated in civil scope of work.

Supply and installation shall include new AVR panel for 3
rd
transformer, scheme
modification for parallel operation of three HVDT Transformers and all material
and equipment for existing AVR panels modification shall be included in the offer.
Bidders shall familiarize themselves with existing equipment and conduct site
survey prior to bidding. New AVR panel shall be installed adjacent to existing two
AVR Panels in the existing control room and shall be fully compatible by
technical characteristics and physical appearance (dimensions, colour) to the
existing ones.

Note: The existing 33/11kV 20MVA transformers are KONCAR Croatia make.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of one
(1) NER of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
power HVDT 20MVA transformer as per schedule of requirement, detailed
technical specification etc including isolators. NER shall be of outdoor type.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433 kV, 500 kVA auxiliary transformer with all accessories for
power supply to auxiliary system of the substation as per schedule of
requirement, detailed technical specification etc.

Note : The new auxiliary transformers shall be installed in the existing auxiliary
transformers rooms. Bidders shall include the required civil works in their quoted
price as elaborated per civil scope of work.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 453 of 536


D4E04 Cabling System

04.01 Cables

04.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation,if required, the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

04.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for three (3)
Nos. of HVDT circuits.

04.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

04.01.2.1 11kV Switchgear to HVDT (2X1CX630 sq.mm/phase) cables required for three
(3) Nos. of HVDT circuits.

04.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for one (1) Nos. of 11kV
NER circuit.

04.01.2.3 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

04.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension /modification works in the existing
substation.

04.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control, communication and instrumentation cables for the extension
/modification works in the existing substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 454 of 536


04.02 Cable Terminations

04.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

04.02.1.1 33kV GIS to HVDT circuits, plug-in - type termination for three (3) circuits at 33kV
GIS side

04.02.1.2 33kV GIS to HVDT circuits , termination for three (3) circuits at transformer side

04.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

04.02.2.1 11kV switchgear to HVDT circuits three (3) circuits at both sides

04.02.2.2 HVDT to NER circuit one (1) circuit at both sides

04.02.2.3 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

04.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension /modification works in the existing substation.

04.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension /modification works in the existing substation.

All the control & instrumentation cables of existing transformers, etc shall be
terminated on the new 33 kV GIS switchgear /relay/control panels as applicable
and required as per the approved scheme.

04.03 Cable Trays, Conduits and Accessories

04.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension /modification
works in the existing substation.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 455 of 536


D4E05 LVAC System

05.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

05.01.1 One (1) set of LVAC Distribution Board.

05.01.2 One (1) set of Essential Distribution Board.

D4E06 110V DC System

06.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account existing
feeders and the above extension under this scope. Also aging factor of 30% and
design margin of 10% shall be considered The temperature derating factor shall
be considered as per battery manufacturers recommendation.

Note: The new sets of batteries shall be installed in the existing battery room. The
Tenderer has to study and propose the Battery room layout The contractor shall
make necessary site visit and ascertain himself regarding the required
modification before tendering.

06.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc. The rating shall take into account the existing load and the
extension load under this scope

D4E07 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 456 of 536


D4E08 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

D4E09 Dismantling /Removal of existing 33kV Cables and retermination at the
new 33kV GIS

The existing 33kV Cables and terminations for the following circuits shall be
dismantled/removed from existing 33kV GIS. After installation of new 33kV GIS
these cables shall be reterminated to the new 33kV GIS. HV Test with reduced
voltage for these 33kV Cables shall be included within the quoted price.

09.01 Dismantling/ removal of 33kV Cables and terminations of existing Dibba Main
cable circuits and retermination to the new 33kV GIS Two (2) circuits

09.02 Dismantling/ removal of 33kV Cables and terminations of existing Wassat cable
circuit and retermination to the new 33kV GIS One (1) circuit

Notes: In case the retermination is not possible on new 33kV GIS panels due to
shortage of existing cable length then new 33kV cables for the above three(3)
feeders shall be laid outside the boundary of the substation.Straight through
joints shall be made outside the boundary fo the substation.

D4E10 Dismantling/ Removal of existing 11kV Cables and retermination at the new
11kV Switchgear

The existing 11kV Cables and terminations for the following circuits shall be
dismantled/removed from existing 11kV switchgear. After installation of new
11kV switchgear these cables shall be reterminated to the new 11kV switchgear.
HV Test with reduced voltage for these 11kV Cables shall be included within the
quoted price.

10.01 Dismantling/ removal of 11kV Cables and terminations of existing outgoing cable
circuits and retermination to the new 11kV AIS Ten (10) circuits

Notes: In case the retermination is not possible on new 11kV AIS panels due to
shortage of existing cable length then new 11kV cables for the 11kV feeders
shall be laid outside the boundary of the substation.Straight through joints shall
be made outside the boundary fo the substation.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 457 of 536


D4E11 Testing and commissioning of existing HVDT 1&2

All works related to testing and commissioning of existing 33/11kV 20 MVA
HVDT 1 & 2 including replacement of complete oil and oil filtration .The testing
and commissioning shall be done as specified for new transformers.

D4E12 Dismantling of Existing Equipments

All works related to decommissioning, dismantling, packing, transportation and
delivery to FEWA stores Sharjah for the existing equipments as mentioned
below. The packing shall be suitable for long term storage.

12.01 One (1) set of 33 kV GIS (Alstommake) comprising of 9 nos of panels with
accessories

12.02 Eight (8) nos of 33 kV C&R Panels with accessories

12.03 Two (2) nos of 33 kV Busbar Protection Panels with accessories

12.04 One (1) set of 11kV Switchgear (TAMCO UAE make) comprising of 12nos of
panels with accessories

12.05 Two (2) sets of 11/0.433 kV 250 kVA Auxilairy Transformers with fittings

12.06 One (1) no of 433 V LVAC Distribution panel

12.07 Two (2) sets of 110 V Battery system

12.08 One (1) set of 110 V Battery chargers & DCDB

12.09 33kV Cables of existing HVDT1 & 2 feeders

12.10 11kV Cables of existing HVDT1 & 2 feeders

D4 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 458 of 536


availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.

D4 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of existing ABB
560 RTU to include all newly replaced 33kV and 11kV
circuits as per substation SCADA circuit data
requirements. The scope shall include providing
extension racks, modules, cables and other
accessories as per the requirements.

Scope shall also include complete substation
requirements as per tender documents including end
to end testing of new/upgraded circuits with UAQ
SCC, providing Accessories, cabling etc. as per
specification requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA
SC 1.2 All the components installed in the existing 33kV
marshalling kiosk including the panel to be
dismantled, properly packed (considering future
usage) and delivered to FEWA stores. New
completely equipped CCC panels to be provided for
all the newly replaced 33kV circuits.

The existing 11kV CCC panels to be relocated and
utilized by upgrading the same in all respect to include
the newly replaced 11kV circuits. Additionally new
completely equipped CCC panels to be provided to
meet the 11kV Switchgear replacement requirements.

All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope. All design and engineering of
CCC to be included in the scope as per the
specification and approved before manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 459 of 536


SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

All cabling and termination from battery chargers and
LVAC panel to respective equipment.

All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA
SC 1.4 All works required to implement new SCADA
numbering system for entire33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA


D4C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

D4C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area and demobilization as per
the specification and requirements stated elsewhere in the specification.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 460 of 536


Prior to commencement of works for the new rooms to be constructed under this
Tender, existing services if any at proposed location for new rooms to be rerouted
and existing structures such as RCC manholes/foundations etc. demolished and
reconstructed on suitable alternate locations. The proposed area shall be
backfilled, graded and leveled to match existing Substation level, on completion
of the works.

Tenderer shall include his price for all the above works

01.02 Soil Investigation

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the soil investigation agencys recommendations and as per
design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required in Item D4 C03.02 Sub structure concrete works.

01.03 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices

D4C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

D4C03 New Transformer Room, NER Room, AC/DC room

Design and Construction of new Transformer room in the vicinity of existing
Substation Building for housing of one new 20 MVA (33/11KV) Power
Transformer with Roof truss, new NER room and new AC/DC Room to house
equipment as per the Electrical scope and specifications, including drainage,

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 461 of 536


cable trenches within and from new Building to existing Substation and other
services.

03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority. Extreme care shall
be taken to protect the existing equipment and structures during construction. All
required protection arrangements shall be made prior to excavation.

03.02 Sub-structure Concrete Work

All RCC works for substructures such as foundations including piling and pile
caps, basement, beams, columns, staircases, trenches, tunnels, duct banks, etc.,
up to ground floor level including ground floor slabs. Waterproofing and
protection for all underground structures as per specification and standards is
also covered under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and above ground
floor slab such as walls, columns, beams, slabs, staircases, arches, corbels,
loading/ off loading platform, sill beams, lintel beams, tie beams, parapet walls
etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors and Windows

Supply and installation of doors and windows for the new Building including
Ironmongeries as per specification and standards.

03.06 Floor finishes including Skirting and dado, etc.

Floor finishes as specified in internal finishes in the Particular Technical
Specifications shall be considered.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 462 of 536


03.07 False Ceiling

Fire rated decorative type perforated Aluminum false ceiling with metal
suspension system shall be provided for the new Control/AC/DC room as per
specification and standards.

03.08 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.09 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.10 External finishes

All external surfaces of the buildings shall be finished as per specification/
finishing schedule and standards. External elevations of the new Building shall
match with the existing Substation Building elevations.

03.11 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project shall be as per specification and standards.

Galvanized Iron gratings shall be provided for the new Transformer room area as
there is no oil/water drainage system available for 33/11kV Transformer. The void
area below the gratings shall be adequate for oil/water storage for the new
Transformer

03.12 Cable Duct Banks & Trenches, Manhole chambers and all other Civil works

All works required for the construction of Cable duct banks including future/
spare ducts and sleeves as per specification and standards.

RCC Cable trenches with removable heavy duty RCC covers shall be
constructed inside Transformer rooms and all other cable trenches and pull pits
required for the entire substation and RCC trenches for fire main ring with RCC
covers are included.

Providing new outdoor cable trench between Control/Relay room and Telecom
room within the existing Substation for new accommodating new cables

This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Substation Extension works

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 463 of 536


D4C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards to match with the existing system.

D4C05 Internal Roads, Pavements and Site Surfacing

05.01 Internal Roads

All required works for Road interconnection between existing substation road and
new Building as per Specifications and standards including extension/modification
of existing internal roads around the new Building (type II interlocking tiled road
or to match existing internal road type) and reinstatement of disturbed/damaged
existing roads, as per specification and standards.

05.02 Pavements and Walkways

All works for Pavements/walkways for proposed new Building and reinstatement
of existing walkways as per specification and standards.

05.03 Gravel spreading and filling

All works for Gravel spreading/filling on open areas not covered by
roads/pavements for proposed new building areas, including reinstatement of
existing gravel spreading/filling to match with existing, as per specification and
standards.

D4C06 Boundary wall extension

Part of existing boundary wall to be demolished as indicated on the Tender
drawings and Boundary wall, wherever demolished during construction works, to
be reinstated as originally existing if required.

New Boundary wall to be constructed around new extension of the plot as per
specification and standards to match with the existing Boundary wall.

D4C07 Modification works in existing Substation Building

All required Civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall comprise the following:

Providing additional openings in the Ground floor slab within the existing
Substation building and designing and providing the slab support system
necessitated due to the modification works, Also all openings rendered redundant

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 464 of 536


on completion of the works to be closed/sealed with appropriate means to the
approval of Authority/Engineer.

Modification in SCADA/Telecom and Battery rooms slab on grade for
providing new cable trenches

Existing Auxiliary Transformer rooms to be made good to accommodate
the new Auxiliary Transformers

Removal of metal screens of existing Auxiliary Transformer rooms to
enable installation of Auxiliary Transformer and reinstatement of the same
after the installation of the Auxiliary Transformers is included in the scope
of works. If the mesh is damaged during removal/re fixing, it shall be
reinstated with new to the satisfaction of Authority/Engineer.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.
.
All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.

D4M SCOPE OF WORK MECHANICAL

D4M 1 Fire Protection and Detection System

D4M 1D Automatic Fire Detection and Alarm System

All work necessary for existing Fire Detection & Alarm System extension with all
accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Transformer and Electrical Rooms. On completion of
Fire Detection and Alarm System modification works, existing Fire Alarm Control
Panel shall be tested for correct operation.

1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.
.
1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors and Heat Detectors.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 465 of 536


D4M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) and CO2 extinguishers (12kg).

D4M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

D4M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air
Conditioning and Ventilation plant fully functioning for the new NER room and
AC/DC room including but not limited to the following:

M2.01 Hi wall mounted split units Air conditioning units comprises of indoor and outdoor
units with interconnecting refrigerant pipes with accessories, drain pipe connection.
Bib tap with hose tapping from existing service water line to be provided near the
package units.

M2.02 Smoke extraction system with fire dampers.

M2.03 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.04 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.








TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 466 of 536


D5 EXTENSION OF 33/11kV DIBBA AL HISN (DHSN) SUBSTATION

D5E SCOPE OF WORK ELECTRICAL

D5E01 33kV System

01.01 33kV GIS

Existing 33kV Switchgear (Make Siemens Germany, 2500A, 40kA/3sec) shall be
extended for five (5) 33kV Switchgear bays as specified below. All work related
for above extension, such as but not limited to design, supply, installation, testing
and commissioning of Busbars, adapters, dummy panels, circuit breakers,
disconnectors, earthing switches, CTs, VTs, cable termination sockets and plugs,
plug-in termination, dummy plugs, protection, control and metering equipment as
per schedule of requirement, single line diagram and detailed technical schedule
and specification, C & P diagram etc.

Bidder shall check that the existing operating tools, special tools, and tackles,
plugs and connecting leads for HVAC test of GIS/HV test of cables, set of plugs
and connecting lead for CT primary injection, set of special tools to dismantle
plug in type termination from GIS, dummy plugs for line VTs etc. can be used for
the maintenance of the new bays and where not to include the necessary special
tools and equipment in the overall quoted price of GIS bay as common item. SF
6

gas required for topping up at site shall also be supplied within the quoted price.
If line VTs are separately connected then connecting cable, terminations etc.
shall also to be supplied by the GIS manufacturer within the quoted price.

33kV GIS manufacturers supervisors from the factory shall be provided for
installation, testing and commissioning within the quoted price.

The 33kV GIS and Control/Relay panels shall be similar to the existing 33kV GIS
and Control/Relay panels.

01.01.1 One (1) Bus section and Bus riser with busbar earth switches and 3 phase
busbar voltage transformers as per Single line diagram

01.01.2 One (1) 20MVA, 33/11kV HVDT Feeder

01.01.3 Three (3) Cable feeders

01.02 33kV combined control/relay panels

All work related to design, supply, installation, testing and commissioning one (1)
complete set of 33kV combined control/relay panels for bays as specified with all
accessories as per schedule of requirement, detailed technical specification,
tender drawings etc.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 467 of 536


01.02.1 One (1) Bus section

01.02.2 One (1) 20 MVA, 33/11 kV HVDT Feeder

01.02.3 Three (3) Cable feeders with fibre optic current differential protection scheme

01.02.4 Three (3) sets of matching F.O. current differential protection relays, test terminal
blocks, test plugs etc (loose supply) for remote ends.

Note: The existing synchronizing scheme shall be suitably modified to include the
above extension of 33 kV GIS.

01.03 33kV Busbar protection panels

01.03.1 All work related to supply, installation, testing and commissioning of new busbar
protection relays (one check zone & one discriminating zone relay) for 3
rd
section
of 33kV GIS (minimum one panel shall be supplied and integrated with the
existing 33kV busbar protection panel). All necessary modification in the existing
busbar protection panel for the integration of 3
rd
busbar protection panel (for the
third busbar discriminating zone and check zone protection) shall be carried out
in order to commission the 3
rd
section of 33 kV GIS busbar to the satisfaction of
FEWA.

01.04 33kV plug in type terminations.

01.04.1 Supply of 9 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders under this scope).

D5E02 11kV System

02.01 11kV Air Insulated Switchgear

Existing 11kV Air Insulated Switchgear (Make: ABB, Type: Unigear ZS1, 2000A,
31.5kA/3s) shall be extended as shown in the single line diagram and layout
drawing. All work related to design, supply, installation, testing and
commissioning of extension bays with all necessary, bus ducts, risers, adapters,
circuit breakers, earthing switches, CTs, VTs, cable terminations, protection,
control and metering equipment as per schedule of requirement, single line
diagram and detailed technical schedule and specification, C & P diagram etc.

The tenderer has to study and propose the 11kV switchgear layout in such a way
the Power/control cable openings of the 11kV switchgear does not foul with the
floor beams. Necessary dummy panels, if required, shall be included to clear all
the floor beams. The contractor shall make necessary site visit and ascertain
himself regarding the existing equipment and required modification before
tendering. The scope shall include but not limited to the following circuits.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 468 of 536


02.01.1 One (1) 2000A Bus interconnector panel with 3 phase Busbar Voltage
transformers and Busbar earth switch as per single line diagram.(shall be
installed on L.H.S of busbar-3 )

02.01.2 Three (3) 2000A Bus interconnector panels (one panel shall be installed on
L.H.S of busbar-1, second on R.H.S of busbar-2 and third on R.H.S of busbar-3
respectively)

02.01.3 One (1) Incoming 20MVA, 33/11kV HVDT Feeder with energy metering

02.01.4 Four (4) 630 A Cable feeders with energy metering

02.01.5 Four (4) 630 A Cable feeders

Note: Any civil work including core drilling in the floor for 11kV and LV/Control Cables,
steel fixing base for 11kV Switchgear, commissioning of existing bays and other
services (if required) shall be done as per civil scope of work.

D5E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of one
(1) set of 20 MVA Dyn11 33/11kV, ONAN Distribution transformer with
accessories, OLTC, neutral CTs etc. Transformer shall be capable of parallel
operation with the two existing HVDTs and shall have MVA Rating, Ratio,
percentage impedance, no of taps and range, etc matching with the existing
transformers in the substation and as per detailed technical specification etc.
Transformer shall be of outdoor type. The bidders shall include the required civil
works in their quoted price as elaborated in civil scope of work.

Supply and installation shall include new AVR panel for 3
rd
transformer, scheme
modification for parallel operation of three HVDT Transformers and all material
and equipment for existing AVR panels modification shall be included in the offer.
Bidders shall familiarize themselves with existing equipment and conduct site
survey prior to bidding. New AVR panel shall be installed adjacent to existing two
AVR Panels in the existing control room and shall be fully compatible by
technical characteristics and physical appearance (dimensions, colour) to the
existing ones.

Note: The existing 33/11kV 20MVA transformers are KONCAR Croatia make.

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of one
(1) NER of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 469 of 536


power HVDT 20MVA transformer as per schedule of requirement, detailed
technical specification etc including isolators. NER shall be of outdoor type.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433 kV, 500 kVA auxiliary transformer with all accessories for
power supply to auxiliary system of the substation as per schedule of
requirement, detailed technical specification etc.

Note : The new auxiliary transformers shall be installed in the existing auxiliary
transformers rooms.

D5E04 Cabling System

04.01 Cables

04.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, if required, the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

04.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for one (1) Nos.
of HVDT circuit.

04.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

04.01.2.1 11kV Switchgear to HVDT (2X1CX630 sq.mm/phase) cables required for one
(1) Nos. of HVDT circuit.

04.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for one (1) Nos. of 11kV
NER circuit.

04.01.2.3 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 470 of 536


04.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension /modification works in the existing
substation.

04.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control, communication and instrumentation cables for the extension
/modification works in the existing substation.

04.02 Cable Terminations

04.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

04.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for new HVDT, one (1)
circuit at 33kV GIS side

04.02.1.2 33kV GIS to new HVDT, termination for one (1) circuit at transformer side

04.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

04.02.2.1 11kV switchgear to HVDT circuit one (1) circuit at both sides

04.02.2.2 HVDT to NER circuit one (1) circuit at both sides

04.02.2.3 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

04.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension /modification works in the existing substation.

04.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension /modification works in the existing substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 471 of 536


04.03 Cable Trays, Conduits and Accessories

04.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension /modification
works in the existing substation.

D5E05 LVAC System

05.01 Extension of LVAC Auxilairy system

All work related to extension of Existing Low voltage AC Supply system which
includes but not limited to provision of any additional Sub Distribution panel,
MCCB/MCBs etc as required for the substation extension /modification works.

D5E06 110V DC System

06.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account existing
feeders and the above extension under this scope. Also aging factor of 30% and
design margin of 10% shall be considered The temperature derating factor shall
be considered as per battery manufacturers recommendation.

Note: The new sets of batteries shall be installed in the existing battery room. The
Tenderer has to study and propose the Battery room layout The contractor shall
make necessary site visit and ascertain himself regarding the required
modification before tendering.

06.02 110 V Battery Charger & DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110 V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc. The rating shall take into account the existing load and the
extension load under this scope

D5E07 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 472 of 536


D5E08 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

D5E09 Dismantling of Existing Equipments

All works related to decommissioning, dismantling, packing, transportation and
delivery to FEWA stores Sharjah for the existing equipments as mentioned
below. The packing shall be suitable for long term storage.

09.01 Two (2) sets of 11/0.433 kV 250 kVA Auxilairy Transformers with fittings

09.02 One (1) sets of 110 V Battery system

09.03 One (1) set of 110 V Battery chargers & DCDB

D5 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.










TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 473 of 536


D5 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of basic and
extension racks to update the existing ABB RTU 232
to the new version of ABB RTU 560 to accommodate
the new/upgraded 33kV & 11kV circuits as per the
substation requirements and SCADA data.

Scope shall also include complete substation
requirements as per tender documents including point
to point test for all affected circuits, end to end testing
of new/upgraded circuits with UAQ SCC, providing
Accessories, cabling etc. as per specification
requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA
SC 1.2 New completely equipped CCC panels to be provided
for new 33kV circuits and 11kV circuits.

All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope.

All design and engineering of CCC to be included in
the scope as per the specification and approved
before manufacturing.

SCADA
SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

All cabling and termination from battery chargers and
LVAC panel to respective equipment.

All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.
SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 474 of 536


SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA


D5C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

D5C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area and demobilization as per
the specification and requirements stated elsewhere in the specification.

Prior to commencement of works for the new rooms to be constructed under this
Tender, existing services if any at proposed location for new rooms to be rerouted
and existing structures such as RCC manholes/foundations etc. demolished and
reconstructed on suitable alternate locations. The proposed area shall be
backfilled, graded and leveled to match existing Substation level, on completion
of the works.

Tenderer shall include his price for all the above works

Soil Investigation Report for the existing Substation is included in this Tender
document


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 475 of 536


Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the soil investigation agencys recommendations and as per
design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in Item D5 C03.02 Sub structure concrete works.

01.02 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices

D5C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

D5C03 New Transformer room, new 11kV Switchgear room for 3
rd
Section of 11 kv
Switchgear and New Control/Relay/AC/DC room

Design and Construction of new Transformer room in the vicinity of existing
Substation Building for housing of one new 20 MVA (33/11KV) Power
Transformer with Roof truss including drainage, cable trenches and other
services.

Also included is the Design and construction of new 11kV Switchgear room and
new Control/Relay room to house new Electrical equipment as per the Electrical
scope of this Tender. Design and construction of new rooms shall be with new
access platform complete with basement including drainage, cable trenches and
other services.

03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority. Extreme care shall
be taken to protect the existing equipment and structures during construction. All

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 476 of 536


required protection arrangements shall be made prior to commencement of
excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement beams, columns, walls, trenches, tunnels duct
banks, etc. up to ground floor level including ground floor slab. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and ground floor slab
such as walls, columns, beams, slabs, arches, corbels, sill beams, lintel beams,
tie beams, parapet walls, loading/off loading platforms, etc., as per specification
and standards

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors and Windows

Supply and installation of doors and windows for the new rooms including
ironmongeries as per specification and standards.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specification shall be considered for the new Buildings.

03.07 False Ceiling

Fire rated decorative type Aluminum false ceiling with metal suspension system
shall be provided for all the new Equipment rooms as per specification and
standards.

03.08 Roof Treatment and Finishes

All works required for Roof waterproofing and insulation, including finishes as per
specifications and standards.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 477 of 536


03.09 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.10 External Finishes

All external surfaces of the buildings shall be finished as per
specification/finishing schedule and standards. External elevations of the new
Building shall match with the existing Substation Building elevations.

Type of finish for the new rooms shall match with the existing Substation Building.

03.11 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.

Galvanized Iron gratings shall be provided for the new Transformer room area as
there is no oil/water drainage system available for 33/11kV Transformer. The void
area below the gratings shall be adequate for oil/water storage for the new
Transformer

03.12 Cable Duct Banks, Trenches, Manhole chambers and all other Civil works

All works required for the construction of Cable duct banks including future/ spare
ducts and sleeves as per specification and standards.

RCC Cable trenches with removable heavy duty RCC covers shall be constructed
inside transformer rooms and cable trenches or duct banks between existing
substation basement and the new building. Core drilling in existing substation
basement walls is also included. All other cable trenches and pull pits required for
the entire extension works are included in scope of work.

This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Substation Extension works.

D5C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards to match with the existing system.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 478 of 536


D5C05 Boundary wall extension

Part of existing boundary wall to be demolished as indicated on the Tender
drawings and Boundary wall, wherever demolished during construction works, to
be reinstated as originally existing if required.

New Boundary wall to be constructed around new extension of the plot as per
specification and standards to match with the existing Boundary wall.

D5C06 Modification works in existing Substation Building

All required Civil modification works within the existing Substation building to
house new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing additional openings in the Ground floor
slab and walls and designing and providing the slab support system necessitated
due to the modification works. Also all openings rendered redundant on
completion of the works to be closed/sealed with appropriate means to the
approval of Authority/Engineer. Existing Auxiliary Transformer rooms to be made
good to accommodate the new Auxiliary Transformers.

Removal of metal screens of existing Auxiliary Transformer rooms to enable
installation of Auxiliary Transformer and reinstatement of the same after Auxiliary
Transformer installation is included in the scope of works. If the mesh is damaged
during removal/re fixing, it shall be reinstated with new to the satisfaction of
Authority/Engineer.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

Internal roads, pavements and gravel areas damaged during construction of the
new Building shall be reinstated and interconnection to the new Building shall be
made

All extension and modification works shall be carried out as per Method
Statement approved by Authority/Engineer.













TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 479 of 536


D5M SCOPE OF WORK MECHANICAL

D5M 1 Fire Protection and Detection System

D5M 1D Automatic Fire Detection and Alarm System

All work necessary for existing Fire Detection & Alarm System extension with all
accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Transformer, Electrical rooms and Cable Basement. On
completion of Fire Detection and Alarm System modification works, existing Fire
Alarm Control Panel shall be tested for correct operation.

1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.
.
1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors and Heat Detectors.

D5M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) and CO2 extinguishers (12kg).

1E.03 Automatic fire extinguishers

All work necessary for supply and installation of ceiling mounted Automatic Dry
Powder Units (4.5kg), inside new Cable Basement.

D5M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 480 of 536


and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

D5M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the new 11kV Switchgear room and control
& relay room including but not limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of Hermetic
/ Semi-hermetic / Scroll compressors with suction and delivery valves, Condenser
and Evaporator coil with copper fins, Evaporator fan with drive, Drain pan, Filter
chambers etc., Bib tap with hose tapping from existing service water line to be
provided near the package units.

M2.02 Supply and Extraction fans

M2.03 Smoke extraction System

M2.04 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.05 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.06 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.07 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 481 of 536


D6 EXTENSION OF 33/11 kV WASSAT (WAST) SUBSTATION

D6E SCOPE OF WORK ELECTRICAL

D6E01 33kV System

01.01 33kV GIS

Existing 33kV Switchgear (Make Siemens Germany, 2500A, 40kA/3sec) shall be
extended for six (6) 33kV Switchgear bays as specified below. All work related
for above extension, such as but not limited to design, supply, installation, testing
and commissioning of Busbars, adapters, dummy panels, circuit breakers,
disconnectors, earthing switches, CTs, VTs, cable termination sockets and plugs,
plug-in termination, dummy plugs, protection, control and metering equipment as
per schedule of requirement, single line diagram and detailed technical schedule
and specification, C & P diagram etc.

Bidder shall check that the existing operating tools, special tools, and tackles,
plugs and connecting leads for HVAC test of GIS/HV test of cables, set of plugs
and connecting lead for CT primary injection, set of special tools to dismantle
plug in type termination from GIS, dummy plugs for line VTs etc. can be used for
the maintenance of the new bays and where not to include the necessary special
tools and equipment in the overall quoted price of GIS bay as common item. SF
6

gas required for topping up at site shall also be supplied within the quoted price.
If line VTs are separately connected then connecting cable, terminations etc.
shall also to be supplied by the GIS manufacturer within the quoted price.

33kV GIS manufacturers supervisors from the factory shall be provided for
installation, testing and commissioning within the quoted price.

The 33kV GIS and Control/Relay panels shall be similar to the existing 33kV GIS
and Control/Relay panels.

01.01.1 One (1) Bus section and Bus riser with busbar earth switches and 3 phase
busbar voltage transformers as per Single line diagram

01.01.2 One (1) 20MVA, 33/11 kV HVDT Feeder

01.01.3 Four (4) Cable feeders

01.02 33kV combined control/relay panels

All work related to design, supply, installation, testing and commissioning one (1)
complete set of 33kV combined control/relay panels for bays as specified with all
accessories as per schedule of requirement, detailed technical specification,
tender drawings etc.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 482 of 536


01.02.1 One (1) Bus section

01.02.2 One (1) 20 MVA, 33/11 kV HVDT Feeder

01.02.3 Four (4) Cable feeders with fibre optic current differential protection scheme

01.02.4 Four (4) sets of matching F.O. current differential protection relays, test terminal
blocks, test plugs etc (loose supply) for remote ends.

Note: The existing synchronizing scheme shall be suitably modified to include the
above extension of 33 kV GIS.

01.03 33kV Busbar protection panels.

01.03.1 All work related to supply, installation, testing and commissioning of new busbar
protection relays (one check zone & one discriminating zone relay) for 3
rd
section
of 33kV GIS (minimum one panel shall be supplied and integrated with the
existing 33kV busbar protection panel). All necessary modification in the existing
busbar protection panel for the integration of 3
rd
busbar protection panel (for the
third busbar discriminating zone and check zone protection) shall be carried out
in order to commission the 3
rd
section of 33 kV GIS busbar to the satisfaction of
FEWA.

01.04 33kV plug in type terminations.

01.04.1 Supply of 12 Nos. of 33kV plug-in type cable terminations, suitable for 33kV,
1Cx500 sq.mm Cu, XLPE cables for outgoing cable feeders.

01.04.2 Supply of dummy plugs (for all outgoing feeders under this scope).

D6E02 11kV System

02.01 11kV Air Insulated Switchgear

All work related to Design, supply, installation, testing and commissioning one (1)
set of 11kV air insulated switchgear rated at 2000A, 31.5kA, 3 Sec. (site rating)
comprising the following bays with all necessary circuit breakers, earthing
switches, CTs, VTs, cable terminations, protection, control and metering
equipment etc as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

All operating tools, special tools, and tackles (2 sets), one set of test leads/test
probes for HVAC test of 11kV switchgear/cables, one set of test leads/test
probes for CT primary injection etc. shall be supplied within the quoted price.

02.01.1 One (1) Bus sections and bus risers with 3 phase busbar voltage transformers
and busbar earth switches as per single line diagram.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 483 of 536


02.01.2 One (1) 2000A Bus interconnector panel with 3 phase Busbar Voltage
transformers and Busbar earth switch as per single line diagram.(shall be
installed on L.H.S of busbar-3 )

02.01.3 Three (3) 2000A Bus interconnector panels (one panel shall be installed on
L.H.S of busbar-1, second on R.H.S of busbar-2 and third on R.H.S of busbar-3
respectively)

02.01.4 Three (3) Incoming 20MVA, 33/11kV HVDT Feeder with energy metering

02.01.5 Two (2) 11/0.433kV auxiliary transformer bays with energy metering

02.01.6 Ten (10) 630 A Cable feeders with energy metering

02.01.7 Eleven (11) 630 A Cable feeders

Note: 1) The existing 11kV Switchgear room shall be used for installation of new 11kV
switchgear panels of Bus1 & Bus2 and the 11kV Panels of Bus3 shall be
installed in the new 11kV room as per layout. The Tenderer has to study and
propose the 11kV switchgear layout in such a way the Power/control cable
openings of the 11kV switchgear does not foul with the floor beams. Necessary
dummy panels, if required, shall be included to clear all the floor beams. The
contractor shall make necessary site visit and ascertain himself regarding the
existing equipment and required modification before tendering. Any civil work
including core drilling in the floor for 11kV and LV/Control Cables, steel fixing
base for 11kV Switchgear, commissioning of existing bays and other services (if
required) shall be done as per civil scope of work.

2) The replacement of existing 11kV switchgear by new 11kV switchgear shall
be carried out including completion of civil works with minimum interruption of
power. All necessary possibilities shall be reviewed and the replacement shall be
completed in minimum outage period.

D6E03 Transformers and Neutral Earthing Resistor

03.01 HVDT and NER

03.01.1 20MVA 33/11kV Distribution Transformer

All work related to design, supply, installation, testing and commissioning of one
(1) set of 20 MVA Dyn11 33/11kV, ONAN Distribution transformer with
accessories, OLTC, neutral CTs etc. Transformer shall be capable of parallel
operation with the two existing HVDTs and shall have MVA Rating, Ratio,
percentage impedance, no of taps and range, etc matching with the existing
transformers in the substation and as per detailed technical specification etc.
Transformer shall be of outdoor type. The bidders shall include the required civil
works in their quoted price as elaborated in civil scope of work.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 484 of 536


Supply and installation shall include new AVR panel for 3
rd
transformer, scheme
modification for parallel operation of three HVDT Transformers and all material
and equipment for existing AVR panels modification shall be included in the offer.
Bidders shall familiarize themselves with existing equipment and conduct site
survey prior to bidding. New AVR panel shall be installed adjacent to existing two
AVR Panels in the existing control room and shall be fully compatible by
technical characteristics and physical appearance (dimensions, colour) to the
existing ones.

Note: The existing 33/11kV 20MVA transformers are outdoor type (Make-Emirates
Transformers, UAE).

03.01.2 Neutral Earthing Resistor (NER)

All work related to design, supply, installation, testing and commissioning of one
(1) NER of 6.35 ohms, 1000A, 10 seconds for earthing 11kV neutral of above
20MVA HVDT as per schedule of requirement, detailed technical specification
etc including isolators. NER shall be of outdoor type.

Note: The new NER shall be installed in the existing NER room.

03.02 Auxiliary Transformer

03.02.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 11/0.433 kV, 500 kVA auxiliary transformer with all accessories for
power supply to auxiliary system of the substation as per schedule of
requirement, detailed technical specification etc.

D6E04 Cabling System

04.01 Cables

04.01.1 33 kV Power Cables

All works related to design, supply, installation, testing and commissioning of
33kV power cables required for the below circuits. Cable numbers and sizes are
indicative for tender purpose only. As per cable sizing calculation, If required, the
Contractor shall increase the cross section or number of cables within the quoted
price in order to satisfy the circuit requirements.

04.01.1.1 33kV GIS to HVDT (1X1CX500 sq.mm/phase) cables required for one (1) Nos.
of HVDT circuit.

04.01.2 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 485 of 536


04.01.2.1 11kV Switchgear to HVDT (2X1CX630 sq.mm/phase) cables required for three
(3) Nos. of HVDT circuits.

04.01.2.2 HVDT to NER- (1X1CX630 sq.mm) cables required for one (1) Nos. of 11kV
NER circuit.

04.01.2.3 11kV Switchgear to auxiliary transformers - (1X1CX630 sq.mm/phase) cables
required for the two (2) Nos. of 11/0.433 auxiliary transformer circuits.

Note: The numbers of cables indicated above are only tentative. Tenderer shall
substantiate number of cables and size with calculation. If more numbers of
cables or higher size of cables are required then tenderer shall provide the same
as per requirement without any contractual implication to FEWA.

04.01.3 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension /modification works in the existing
substation.

04.01.4 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control, communication and instrumentation cables for the extension
/modification works in the existing substation.

04.02 Cable Terminations

04.02.1 33kV Power Cable Terminations

Design, supply and installation of the 33kV cable terminations suitable for
1Cx500sqmm, XLPE cables for the following circuits:

04.02.1.1 33kV GIS to HVDT circuit, plug-in - type termination for new HVDT, one (1)
circuit at 33kV GIS side

04.02.1.2 33kV GIS to new HVDT, termination for one (1) circuit at transformer side

04.02.2 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

04.02.2.1 11kV switchgear to HVDT circuit three (3) circuit at both sides

04.02.2.2 HVDT to NER circuit one (1) circuit at both sides


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 486 of 536


04.02.2.3 11kV switchgear to Auxiliary Transformer circuit two (2) circuits at both sides

04.02.3 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension /modification works in the existing substation.

04.02.4 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension /modification works in the existing substation.

04.03 Cable Trays, Conduits and Accessories

04.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension /modification
works in the existing substation.

D6E05 LVAC System

05.01 LVAC Boards

Auxiliary power supply is derived from 2 Nos 100% redundant 11/0.433kV LT
auxiliary transformers and LVAC distribution boards. All works related to design,
supply, installation, testing and commissioning of the following boards with all
accessories and materials as required as per schedule of requirement, detailed
technical specification etc.

05.01.1 One (1) set of LVAC Distribution Board.

05.01.2 One (1) set of Essential Distribution Board.

D6E06 110V DC System

06.01 110V Batteries

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V batteries including all accessories as per schedule of
requirement, detailed technical specification etc. Battery size shall be subject to
approval of sizing calculation. Sizing calculation shall take into account existing
feeders and the above extension under this scope. Also aging factor of 30% and
design margin of 10% shall be considered The temperature derating factor shall
be considered as per battery manufacturers recommendation.

Note: The new sets of batteries shall be installed in the existing battery room. The
Tenderer has to study and propose the Battery room layout The contractor shall
make necessary site visit and ascertain himself regarding the required
modification before tendering.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 487 of 536


06.02 110 V Battery Charger and DCDB

All work related to design, supply, installation, testing and commissioning of two
(2) sets of 110V Battery Charger and two (2) sets of 110V DC distribution board
including all accessories as per schedule of requirement, detailed technical
specification etc. The rating shall take into account the existing load and the
extension load under this scope

D6E07 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.

D6E08 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

D6E09 Dismantling/ Removal of existing 11kV Cables and retermination at the new
11kV Switchgear

The existing 11kV Cables and terminations for the following circuits shall be
dismantled/removed from existing 11kV switchgear. After installation of new
11kV switchgear these cables shall be reterminated to the new 11kV switchgear.
HV Test with reduced voltage for these 11kV Cables shall be included within the
quoted price.

09.01 Dismantling/ removal of 11kV Cables and terminations of existing outgoing cable
circuits and retermination to the new 11kV AIS Twelve (12) circuits

In case the retermination is not possible on new 11kV AIS panels due to
shortage of existing cable length then new 11kV cables for the 11kV feeders
shall be laid outside the boundary of the substation.Straight through joints shall
be made outside the boundary fo the substation.

D6E10 Dismantling of Existing Equipments

All works related to decommissioning, dismantling, packing, transportation and
delivery to FEWA stores Sharjah for the existing equipments as mentioned
below. The packing shall be suitable for long term storage.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 488 of 536


10.01 One (1) set of 11kV Switchgear (AEG Pakistan make) comprising of 16 nos of
panels with accessories

10.02 Two (2) sets of 11/0.433 kV 250 kVA Auxiliary Transformers with fittings

10.03 One (1) no of 433 V LVAC Distribution panel

10.04 Two (2) sets of 110 V Battery system

10.05 One (1) set of 110 V Battery chargers & DCDB

10.06 11kV Cables of existing HVDT 1 &2 feeders.


D6 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.
















TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 489 of 536


D6 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of existing ABB
560 RTU to include new 33kV and newly replaced
11kV circuits as per substation SCADA circuit data
requirements. The scope shall include providing
extension racks, modules, cables and other
accessories as per the requirements.

Scope shall also include complete substation
requirements as per tender documents including end
to end testing of new/upgraded circuits with UAQ
SCC, providing Accessories, cabling etc. as per
specification requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.
SCADA
SC 1.2 New completely equipped CCC panel to be provided
for new 33kV circuits.

New completely equipped CCC panels to be provided
for all the newly replaced 11kV circuits.

All works required to complete the scope including
providing all necessary accessories, cabling,
transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope.

All design and engineering of CCC to be included in
the scope as per the specification and approved
before manufacturing.

SCADA
SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

All cabling and termination from battery chargers and
LVAC panel to respective equipment.

All control cables and system cables specification for
SCADA and communication shall be submitted to
FEWA/Engineer for review and approval before
manufacturing.

SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 490 of 536


SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA

D6C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

D6C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area, and demobilization as per
the specification and requirements stated elsewhere in the specification.

Prior to commencement of works for the new rooms to be constructed under this
Tender, existing services if any at proposed location for new rooms to be rerouted
and existing structures such as RCC manholes/foundations etc. demolished and
reconstructed on suitable alternate locations. The proposed area shall be
backfilled, graded and leveled to match existing Substation level, on completion
of the works.
Tenderer shall include his price for all the above works

01.02 Soil Investigation

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 491 of 536


Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the soil investigation agencys recommendations and as per
design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required in Item D6 C03.02 Sub structure concrete works.

01.03 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices

D6C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

D6C03 New Transformer room, new 11kV Switchgear room for 3
rd
Section of 11kV
Switchgear, 2 nos. new Auxiliary Transformer rooms and New
Control/Relay/AC/DC room

Design and Construction of new Transformer room in the vicinity of existing
Substation Building for housing of one new 20 MVA (33/11KV) Power
Transformer and new Auxiliary Transformer rooms with Roof truss including
drainage, cable trenches and other services.

Also included is the design and construction of new 11kV Switchgear room and
new Control/Relay/AC/DC room to house new Electrical equipment as per the
Electrical scope of this Tender. Design and construction of new rooms shall be
with new access platform complete with basement including drainage, cable
trenches and other services.

03.01 Earth Work

Earth work includes excavation for foundations, basement, trenches, duct banks
etc. This includes necessary planking/ shoring and strutting, backfilling,
dewatering, etc. The excess earth material after backfilling shall be carted away
to a designated location approved by the concerned authority. Extreme care shall
be taken to protect the existing equipment and structures during construction. All

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 492 of 536


required protection arrangements shall be made prior to commencement of
excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement beams, columns, walls, trenches, tunnels duct
banks, etc. up to ground floor level including ground floor slab. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor level and ground floor slab
such as walls, columns, beams, slabs, arches, corbels, sill beams, lintel beams,
tie beams, parapet walls, loading/off loading platforms, etc., as per specification
and standards

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors and Windows

Supply and installation of doors and windows for the new rooms including
ironmongeries as per specification and standards.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specification shall be considered for the new Buildings.

03.07 False Ceiling

Fire rated decorative type Aluminum false ceiling with metal suspension system
shall be provided for all the new Equipment rooms as per specification and
standards.

03.08 Roof Treatment and Finishes

All works required for Roof waterproofing and insulation, including finishes as per
specifications and standards.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 493 of 536


03.09 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.10 External Finishes

All external surfaces of the buildings shall be finished as per
specification/finishing schedule and standards. External elevations of the new
Building shall match with the existing Substation Building elevations.

Type of finish for the new rooms shall match with the existing Substation Building.

03.11 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.

Galvanized Iron gratings shall be provided for the new Transformer room area as
there is no oil/water drainage system available for 33/11kV Transformer. The void
area below the gratings shall be adequate for oil/water storage for the new
Transformer

03.12 Cable Duct Banks, Trenches, Manhole chambers and all other Civil works

All works required for the construction of Cable duct banks including future/ spare
ducts and sleeves as per specification and standards

RCC Cable trenches with removable heavy duty RCC covers shall be constructed
inside Transformer room and cable trenches or duct banks between existing
substation basement and the new building. Core drilling in existing substation
basement walls is also included. All other cable trenches and pull pits required for
the entire extension works are included in scope of work.

This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Substation Extension works.

D6C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards/to match with existing system.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 494 of 536


D6C05 Modification works in existing Substation Building

All required Civil modification within the existing Substation building to house new
Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing of additional openings in the Ground
floor slab and walls and designing and providing the slab support system
necessitated due to the modification works. Also all openings rendered redundant
on completion of the works to be closed/sealed with appropriate means to the
approval of Authority/Engineer.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

Internal roads, pavements and gravel areas damaged during construction of the
new Building shall be reinstated and interconnection to the new Building shall be
made

All extension and modification works shall be carried out as per Method
Statement approved by Authority/Engineer.

D6M SCOPE OF WORK MECHANICAL

D6M 1 Fire Protection and Detection System

D6M 1D Automatic Fire Detection and Alarm System

All work necessary for existing Fire Detection & Alarm System extension with all
accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Transformers, Electrical rooms and Cable Basement.
On completion of Fire Detection and Alarm System modification works, existing
Fire Alarm Control Panel shall be tested for correct operation.

1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.

1D.02 Photoelectric Detectors and Heat detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors and Heat Detectors.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 495 of 536


D6M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) and CO2 extinguishers (12kg).

1E.03 Automatic fire extinguishers

All work necessary for supply and installation of ceiling mounted Automatic Dry
Powder Units (4.5kg), inside new Cable Basement.

D6M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

D6M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the new 11kV Switchgear room and 33kV
R/C room including but not limited to the following:

M2.01 Hi wall mounted split units Air conditioning units comprises of indoor and outdoor
units with interconnecting refrigerant pipes with accessories, drain pipe connection.
Bib tap with hose tapping from existing service water line to be provided near the
package units.

M2.02 Smoke extraction system with fire dampers.

M2.03 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.04 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 496 of 536


D7 CAPACITOR BANK INSTALLATION AT 132/33/11 kV
DADNAH (DAMN) SUBSTATION

D7E SCOPE OF WORK ELECTRICAL

D7E01 11kV System

01.01 11kV Air Insulated Switchgear

Existing 11kV Air Insulated Switchgear (Make KONCAR Kroatia, 2000A,
31.5kA/3s) shall be extended by adding 4 nos of 11kV Switchgear bays as
mentioned below.

All work related to design, supply, installation, testing and commissioning of
extension bays with all necessary, bus ducts, risers, adapters, circuit breakers,
earthing switches, CTs, VTs, cable terminations, protection, control and metering
equipment as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

The Tenderer has to study and propose the 11kV switchgear layout in such a
way the Power/control cable openings of the 11kV switchgear does not foul with
the floor beams. Necessary dummy panels, if required, shall be included to clear
all the floor beams. The contractor shall make necessary site visit and ascertain
himself regarding the existing equipment and required modification before
tendering. The scope shall include but not limited to the following circuits.

01.01.1 Three (3) 630 A, Cable feeders.

01.01.2 One (1) 630 A , Capacitor bank feeder.

01.01.3 Modification of existing 11kV Cable feeder (=K07) to convert as 11kV Capacitor
bank feeder

In the existing 11kV Switchgear, one (1) 11kV Cable Feeder (=K07) shall be
modified and used as 11kV Capacitor bank Feeder. All work related to
modification of GA, Schematic diagram, new wiring and CT replacement shall be
carried out as per the protection requirement within the quoted price.

Note: Any civil work including core drilling in the floor for 11kV and LV/Control Cables,
steel fixing base for 11kV Switchgear,and other services (if required) shall be
included for new 11kV panels as per civil scope of work








TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 497 of 536


D7E02 Capacitor Banks

02.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

02.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control and relay panels, all fittings and
accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

D7E03 Cabling System

03.01 Cables

03.01.1 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

03.01.1.1 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos of 6 MVAr, 11kV capacitor bank circuits.

03.01.2 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension/modification works in the substation.

03.01.3 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the extension/modification works in the
substation.

03.02 Cable Terminations

03.02.1 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

03.02.1.1 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

03.02.2 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 498 of 536


03.02.3 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.03 Cable Trays, Conduits and Accessories

03.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension/modification
works in the substation.

D7E04 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.

D7E05 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

D7 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 499 of 536



D7 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of existing ABB
560 RTU to include new/upgraded 11kV circuits as
per substation SCADA circuit data requirements. The
scope shall include providing extension racks,
modules, cables and other accessories as per the
requirements.

Scope shall also include complete substation
requirements as per tender documents including end
to end testing of new/upgraded circuits with UAQ
SCC, providing Accessories, cabling etc. as per
specification requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA
SC 1.2 Existing 11kV CCC panel to be upgraded in all
respect to include the new/upgraded circuits. All works
required to complete the scope including providing all
necessary accessories, DIN Rails, Cable troughs,
cabling, transducers, etc. according to Substation
requirements and SCADA circuit data shall be
included in the scope. All design and engineering of
CCC to be included in the scope as per the
specification and approved before manufacturing.

SCADA
SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

SCADA
SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 500 of 536


D7C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

D7C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area and demobilization as per
the specification and requirements stated elsewhere in the specification.

Prior to commencement of works for new Capacitor bank building, existing
services at proposed location for new Capacitor bank building to be rerouted and
existing structures such as RCC manholes/foundations etc. demolished and
reconstructed on suitable alternate location. The proposed area shall be
backfilled, graded and leveled to match with the existing Substation level on
completion of the works. Tenderer shall include his price for all the above works

01.02 Soil Investigation

During the execution the Contractor shall employ an agency with
Authority/Engineers approval to carry out the Soil investigation for the substation
as per specification and standards.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the soil investigation agencys recommendations and as per
design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,
shall also be considered. Bidder to include his price for Soil improvement
including Piling if required in Item D7C03.02 Sub structure Concrete works.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 501 of 536


01.03 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices

D7C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

D7C03 New Capacitor Bank Building with Clean Agent room

Design and Construction of new building for housing Capacitor bank units and
Clean agent room as per the specifications, including drainage, cable trenches
and other services.

03.01 Earth Work

Earth work includes excavation for foundations, trenches, duct banks etc. This
includes necessary planking/ shoring and strutting, backfilling, dewatering, etc.
The excess earth material after backfilling shall be carted away to a designated
location approved by the concerned authority. Extreme care shall be taken to
protect the existing equipment and structures during construction. All required
protection arrangements shall be made prior to excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement, beams, columns, walls, trenches, tunnels, duct
banks, etc. up to ground floor level including ground floor slab. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope.

03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor slab such as walls,
columns, beams, slabs, arches, corbels, sill beams, lintel beams, tie beams,
parapet walls, etc., as per specification and standards.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 502 of 536


03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors

Supply and installation of doors for the new building including ironmongeries as
per specification and standards. Sliding gate and solenoid locks for Capacitor
Bank rooms are also included in this Scope of work.

03.06 Floor finishes including Skirting and dado, etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specifications shall be considered.

03.07 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.08 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.09 External Finishes

All external surfaces of the buildings shall be finished as per
specification/finishing schedule and standards. External elevations of the new
rooms shall match with the existing Substation building.

03.10 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.

03.11 Cable Duct Banks, Trenches Manhole chambers and all other civil works

RCC Cable trenches with removable heavy duty RCC covers shall be constructed
for 11kV, LV and control cables between existing 33kV substation basement and
the new Capacitor bank building. Core drilling in existing substation basement
walls is also included.

All other cable trenches and pull pits required for the entire extension works are
also included in this scope of work.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 503 of 536


This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Capacitor bank installation works

D7C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards to match with existing system.

D7C05 Modification works in existing Substation Building

All required Civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing of additional openings in the Ground
floor slab and walls and designing and providing the slab support system
necessitated due to the modification works. Also all openings rendered redundant
on completion of the works to be closed/sealed with appropriate means to the
approval of Authority/Engineer.

Boundary wall, wherever demolished during construction works, to be reinstated
as originally existing.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

Internal roads, pavements and gravel areas damaged during construction of the
new Building shall be reinstated and interconnection to the new Building shall be
made.

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.

D7M SCOPE OF WORK MECHANICAL

D7M 1 Fire Protection and Detection System

D7M 1C Clean Agent System

D7M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 504 of 536


control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.

1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.

D7M 1D Automatic Fire Detection and Alarm System

All work necessary for extension of existing Fire Detection & Alarm System with
all accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Clean Agent Room. On completion of Fire Detection
and Alarm System modification works, existing Fire Alarm Control Panel shall be
tested for correct operation.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 505 of 536


1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.

1D.02 Photoelectric smoke detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors, as per NFPA recommendations.

D7M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) for new Capacitor Bank rooms.

D7M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

D7M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the new Capacitor room and clean agent
room including but not limited to the following:

M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers etc., Bib tap with hose tapping from existing service water
line to be provided near the package units.

M2.02 Extraction fan for clean agent room


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 506 of 536


M2.03 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.04 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.05 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.06 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 507 of 536


D8 EXTENSION OF33/11kV BIDIYA (BIDY) SUBSTATION

D8E SCOPE OF WORK ELECTRICAL

D8E01 11kV System

01.01 11kV Air Insulated Switchgear

Existing 11kV Air Insulated Switchgear (Make NATUS Germany, 2000A,
31.5kA/3s) shall be extended by adding 3 nos of 11kV Switchgear bays as
mentioned below.

All work related to design, supply, installation, testing and commissioning of
extension bays with all necessary, bus ducts, risers, adapters, circuit breakers,
earthing switches, CTs, VTs, cable terminations, protection, control and metering
equipment as per schedule of requirement, single line diagram and detailed
technical schedule and specification, C & P diagram etc.

The Tenderer has to study and propose the 11kV switchgear layout in such a
way the Power/control cable openings of the 11kV switchgear does not foul with
the floor beams. Necessary dummy panels, if required, shall be included to clear
all the floor beams. The contractor shall make necessary site visit and ascertain
himself regarding the existing equipment and required modification before
tendering. The scope shall include but not limited to the following circuits.

01.01.1 Two (2) 630 A , Cable feeders.

01.01.2 One (1) 630 A , Capacitor bank feeder.

01.01.3 Modification of existing 11kV Cable feeder (=K01) to convert as 11kV Capacitor
bank feeder

In the existing 11kV Switchgear, one (1) 11kV Cable Feeder (=K01) shall be
modified and used as 11kV Capacitor bank Feeder. All work related to
modification of GA, Schematic diagram, new wiring and CT replacement shall be
carried out as per the protection requirement within the quoted price.

Note: Any civil work including core drilling in the floor for 11kV and LV/Control Cables,
steel fixing base for 11kV Switchgear,and other services (if required) shall be
included for new 11kV panels as per civil scope of work

D8E02 Capacitor Banks

02.01 3 Phase, 11kV, 6 MVAr Capacitor Bank

02.01.1 All work related to design, supply, installation, testing and commissioning of two
(2) sets of 3 Phase, 11kV, 6 MVAr capacitor banks (3 stages of 2 MVAR each)
with automatic control complete with control and relay panels, all fittings and

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 508 of 536


accessories, fully in compliance with the detailed technical specification. The
capacitor shall be designed to operate for an ambient temperature of 50
0
C.

D8E03 Cabling System

03.01 Cables

03.01.1 11kV Power Cables

All works related to design, supply, installation, testing and commissioning of
11kV power cables required for the following circuits:

03.01.1.1 11kV Switchgear to capacitor bank - (1X1CX630 sq.mm/phase) cables required
for the two (2) Nos of 6 MVAr, 11kV capacitor bank circuits.

03.01.2 LV Power Cables

All work related to design, supply, installation, testing and commissioning of all
LV Power Cable required for the extension/modification works in the substation.

03.01.3 Control, Communication and Instrumentation Cables

All work related to design, supply, installation, testing and commissioning of all
control and instrumentation cables for the extension/modification works in the
substation.

03.02 Cable Terminations

03.02.1 11kV Power Cable Terminations

Design, supply and installation of the power cable terminations including all lugs,
glands and end termination kit etc. required for termination of all 11kV power
cables for the following circuits:

03.02.1.1 11kV switchgear to Capacitor Bank circuit two (2) circuits at both sides

03.02.2 LV Power Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.

03.02.3 Control, Communication and Instrumentation Cable Terminations

Terminations shall include supply and installation of all lugs, glands, ferrules and
terminations etc for the extension/modification works in the substation.




TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 509 of 536


03.03 Cable Trays, Conduits and Accessories

03.03.1 All work related to design, supply, installation, testing and commissioning of
cable trays, conduits and accessories as required for the extension/modification
works in the substation.

D8E04 Lighting & Small Power System

All work related to design, supply, installation ,testing and commissioning of the
Lighting & Small Power system including fixtures, junction boxes, conduit and
accessories, wires, power outlets etc.as required for the extension /modification
works in the substation.

D8E05 Earthing & Lightning Protection

All work related to design, supply, installation ,testing and commissioning of
grounding system including ground network, equipment earthing and lightning
protection etc. as required for the extension /modification works in the substation.
The new building earthing grid shall be tested independently before connecting
with existing substation earth grid.

D8E06 Dismantling of Existing Equipments

All works related to dismantling, packing, transportation and delivery to FEWA
stores Sharjah for the existing equipments as mentioned below. The packing
shall be suitable for long term storage.

06.01 Outdoor switchyard equipments and structures.

D8 SC SCOPE OF WORK SCADA & COMMUNICATION

This section in general covers the modification required in SCADA equipments
and major items are clearly listed. However, the SCADA works shall be
completed in all respect to meet the substation modification requirements and
hence any items not specifically listed but are essential to satisfactorily complete
the works shall be included in the scope. Therefore, bidder is required to conduct
a detailed site survey before quoting so as to see the availability of existing
resources (Panels, Power supply etc.). Other available resources viz. spare
transducers, Relays, Spare DI/DO modules, Spare circuits etc. already installed
at existing substation can be utilized to meet the scope requirements but the
same quantity shall be compensated to FEWA either by handing over to FEWA
as spare or by installing the same in the panel (in case of space
availability/possibility of further future extension). FEWA/EPE will not be
responsible for any lack of information and it will be bidders responsibility to
acquire all information that is required for quoting the prices and completing the
works in accordance with tender documents.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 510 of 536



D8 SC1 SCADA & COMMUNICATION SCADA
SC 1.1 Upgrade with necessary modifications of existing ABB
560 RTU to include new/upgraded 11kV circuits as
per substation SCADA circuit data requirements. The
scope shall include providing extension racks,
modules, cables and other accessories as per the
requirements.

Scope shall also include complete substation
requirements as per tender documents including end
to end testing of new/upgraded circuits with UAQ
SCC, providing Accessories, cabling etc. as per
specification requirements.

All design and engineering of RTU to be included in
scope and approved before equipment/material
ordering.

SCADA
SC 1.2 Existing 11kV CCC panel to be upgraded in all
respect to include the new/modified circuits. All works
required to complete the scope including providing all
necessary accessories, cabling, transducers, etc.
according to Substation requirements and SCADA
circuit data shall be included in the scope. All design
and engineering of CCC to be included in the scope
as per the specification and approved before
manufacturing.

SCADA
SC 1.3 Supply and cabling works, termination and testing
between RTU-CCC and between Plant-CCC as per
SCADA circuit.

SCADA
SC 1.4 All works required to implement new SCADA
numbering system for entire 33/11kV substation in
accordance with the guidelines given in specification.
The works shall include replacement of existing
SCADA labels from entire substation with new
SCADA labels, modifications in documentation,
verification and witnessing of new labels with control
centre etc. as per directions given in specification.
SCADA






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 511 of 536


D8C SCOPE OF WORK CIVIL ENGINEERING & BUILDING WORKS

General

The Contractor will be responsible for the design and construction of all Civil
Engineering and building works including the modification works in the existing
Substation. The Tenderer must cover all requirements of the tender documents
and any other items not specifically mentioned but which are required for the
satisfactory design, construction, operation and maintenance of all equipment to
the satisfaction of Authority/Engineer. The scope of works listed below are only
indicative and no additional costs will be considered for the items which have
been overlooked but are essential for the proper completion of the project in
every respect. The Tenderer shall visit the site and study thoroughly the
requirements before submitting the Offer. This scope of work shall be read in
conjunction with General & Particular Technical Specifications and other Tender
documents.

D8C01 Preliminaries

01.01 Site clearing, Site grading, Site mobilization, Site demobilization, etc.

Scope of work under preliminaries includes Site clearing/ site grading, site
mobilization, temporary fencing around the works area and demobilization as per
the specification and requirements stated elsewhere in the specification.

Prior to commencement of works for new Capacitor bank building, existing
services at proposed location for new Capacitor bank building to be rerouted and
existing structures such as RCC manholes/foundations etc. demolished and
reconstructed on suitable alternate location. The proposed area shall be
backfilled, graded and leveled to match with the existing Substation level on
completion of the works. Tenderer shall include his price for all the above works.

Prior to the commencement of works for new Capacitor bank building, existing old
outdoor switchyard within existing substation compound to be
removed/demolished. Removed switchyard materials to be transported and
handed over to FEWA store in Fujairah. Debris to be transported and deposited
on the area approved by the Municipality for that purpose. Existing internal road,
pavements and gravel areas wherever disturbed during demolition works, to be re
instated as originally existing.

Soil Investigation Report for the existing Substation is included in this Tender
document.

Necessary Soil improvement to attain required Safe Bearing Capacity (SBC) shall
be carried out as per the Soil Investigation agencys recommendations and as per
design requirements with Authority/Engineers approval and all required tests
including Plate load tests, zone load tests, SPTs, etc. shall be carried out at
required locations to ensure that the required SBC is achieved. Piling, if required,

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 512 of 536


shall also be considered. Bidder to include his price for Soil improvement
including Piling if required, in item D8 C03.02 Sub structure concrete works.

01.02 Authority and Engineers Site Offices and facilities

Provision of Type-C Authority and Engineers Offices and facilities at site as
specified under the Special Conditions of Contract including all temporary power
supply and water supply for Site offices

D8C02 Design and Drawings

Conceptual layout drawings are provided in this tender document by
Authority/Engineer. Preparation of final design and drawings required for the
proper execution and completion of the entire project is covered under this scope
and the Contractor is solely responsible for the design. All requirements stated
elsewhere in the specification shall be adhered to. All design, working drawings
and shop drawings are subjected to Authority/Engineers approval.

Minimum drawings required to be submitted are listed in Civil General Schedules
Volume V, Section 7.

D8C03 New Capacitor Bank Building with Clean Agent room

Design and Construction of new building for housing Capacitor bank units and
Clean agent room as per the specifications, including drainage, cable trenches
and other services.

03.01 Earth Work

Earth work includes excavation for foundations, trenches, duct banks etc. This
includes necessary planking/ shoring and strutting, backfilling, dewatering, etc.
The excess earth material after backfilling shall be carted away to a designated
location approved by the concerned authority. Extreme care shall be taken to
protect the existing equipment and structures during construction. All required
protection arrangements shall be made prior to excavation.

03.02 Sub-structure Concrete Works

All RCC works for substructures such as foundations including piling and pile
caps if necessary, basement, beams, columns, walls, trenches, tunnels, duct
banks, etc. up to ground floor level including ground floor slab. Waterproofing and
protection for all underground structures as per specification and standards is
included under this scope.






TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 513 of 536


03.03 Super-structure Concrete Works

All RCC works for Superstructures above ground floor slab such as walls,
columns, beams, slabs, arches, corbels, sill beams, lintel beams, tie beams,
parapet walls etc., as per specification and standards.

03.04 External and Internal block walls including plastering

All works related to the External & Internal block walls including RCC stiffeners,
lintels and plastering as per specification and standards.

All exposed concrete surfaces shall also be plastered before painting.

03.05 Doors

Supply and installation of doors for the new building including ironmongeries as
per specification and standards. Sliding gate and solenoid locks for Capacitor
Bank rooms are also included in this Scope of work.

03.06 Floor finishes including Skirting and dado etc.

Floor finishes as specified in Internal Finishes in the Particular Technical
Specifications shall be considered.

03.07 Roof Treatment and Finishes

All works required for roof waterproofing and insulation including finishes as per
specification and standards.

03.08 Internal Painting

Internal painting for the buildings shall be carried out as per specification and
standards.

03.09 External Finishes

All external surfaces of the buildings shall be finished as per
specification/finishing schedule and standards. External elevations of the new
rooms shall match with the existing Substation building.

03.10 Metal Works

All works for design, supply and installation of metallic structures/ elements
required for the entire project as per specification and standards.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 514 of 536


03.11 Cable Duct Banks, Trenches Manhole chambers and all other civil works

RCC Cable trenches with removable heavy duty RCC covers shall be constructed
for 11kV, LV and control cables between existing 33kV substation basement and
the new Capacitor bank building. Core drilling in existing substation basement
walls is also included.

All other cable trenches and pull pits required for the entire extension works are
also included in this scope of work.

This shall also include all other Civil Engineering and Building works not
specifically mentioned in the scope of works but are reasonably required for the
successful completion of the Capacitor bank installation works

D8C04 Drainage Works

04.01 Storm water drainage and HVAC drainage Works

All works required for Storm water drainage and HVAC drainage as per
specification and standards to match with existing system.

D8C05 Modification works in existing Substation Building

All required Civil modification works in the existing Substation building to house
new Electrical equipment as per Electrical scope of work shall be included.
Modification works shall include providing additional openings in the Ground floor
slab and walls and designing and providing the slab support system necessitated
due to the modification works. Also all openings rendered redundant on
completion of the works to be closed/sealed with appropriate means to the
approval of Authority/Engineer.

All finishes to rooms in which modification works to be carried out under this
scope shall be made to be as good as new viz. Wall paint, false ceiling, floor
coatings, etc. to be reinstated.

Internal roads, pavements and gravel areas damaged during construction of the
new Building shall be reinstated and interconnection to the new Building shall be
made

All modification works shall be carried out as per Method Statement approved by
Authority/Engineer.








TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 515 of 536


D8M SCOPE OF WORK MECHANICAL

D8M 1 Fire Protection and Detection System

D8M 1C Clean Agent System

D8M 1C1 Clean Agent System for Capacitor Bank Rooms

All work necessary for Automatic Clean Agent Extinguishing System, including
clean agent storage main and reserve cylinder bank, manifold piping, actuating
and discharge pipe work and nozzles, control switches and instruments, cabling,
wiring, conducting, AC/DC power supply distribution, addressable extinguishing
control panel complete with reserve battery supply, detectors, annunciation
system, required interlocks etc. for the Capacitor Bank Rooms.

1C1.01 Clean Agent Storage

All work necessary for supply, installation and commissioning of portable steel
cylinders constructed of high strength steel alloy, with clean agent stored under
pressure of 25/42 bars, of reputed make and design. All work necessary for
supply, installation and commissioning of storage cylinders manifolds with
common discharge headers, check valves, cylinder valves, discharge flexible
tubing, pressure gauge, and other relevant accessories.

1C1.02 Clean Agent Piping and Appurtenances

All work necessary for supply, installation and commissioning of pneumatic pilot
operated selector valves, brass chrome discharge nozzles, properly sized pipe
work with rigid supports.
1C1.03 Actuation

All work necessary for supply, installation and commissioning of manual release
stations mounted adjacent to the exits from the protected area, manual release
located at the cylinder storage area and DC solenoids.

1C1.04 Detection

All work necessary for supply, installation and commissioning of addressable
photoelectric type smoke detectors.

1C1.05 Instrumentation and Control

All work necessary for supply, installation and commissioning of one common
addressable Extinguishing Control Panel with power supply and battery set,
audible and visual notification appliances, supervisory inputs, supervised outputs
and dry voltage outputs for interlocks.



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 516 of 536


D8M 1D Automatic Fire Detection and Alarm System

All work necessary for extension of existing Fire Detection & Alarm System with
all accessories comprising detectors, cabling, conducting, wiring, control panel
modification, etc. for new Clean Agent Room. On completion of Fire Detection
and Alarm System modification works, existing Fire Alarm Control Panel shall be
tested for correct operation.

1D.01 Electrical work

All electrical work required for cabling, wiring, conducting connections, grounding
etc. for the system extension. Supply and installation of manual call points and
sounder/strobes.

1D.02 Photoelectric smoke detectors:

All work necessary for supply, installation and commissioning of Photoelectric
Smoke Detectors, as per NFPA recommendations.

D8M 1E Portable Fire Extinguishers

1E.01 Standard portable fire extinguishers

All work necessary for supply and installation of Standard Portable fire
Extinguishers CO2 (5 Kg) and DCP (4.5 Kg).

1E.02 Mobile fire extinguishers

All work necessary for supply and installation of Standard Mobile, trolley type
DCP fire Extinguishers (25kg) for new Capacitor Bank rooms.

D8M 1F Fire stopping

1F.01 Fire stopping for cable entries, wall and floor openings

All work necessary for supply and application of non-intumescent (ablative type)
two hours rated fire sealant on cables, cable trays and other openings. All work
necessary for supply and installation of sealing boards with fire sealant on wall
and floor openings. Fire sealant characteristics shall be as per ASTM D2863, IEC
332 and FM 3971.

D8M2 HVAC System

Design, supply, installation, testing and commissioning of complete Air Conditioning
and Ventilation plant fully functioning for the new Capacitor room and clean agent
room including but not limited to the following:



TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 517 of 536


M2.01 Roof mounted Package Air cooled Air conditioning units shall comprises of
Hermetic / Semi-hermetic / Scroll compressors with suction and delivery valves,
Condenser and Evaporator coil with copper fins, Evaporator fan with drive, Drain
pan, Filter chambers etc., Bib tap with hose tapping from existing service water
line to be provided near the package units.

M2.02 Extraction fan for clean agent room

M2.03 GI ducts with thermal and acoustic insulation, aluminum cladding, supply and return
air diffusers, sand trap louvers with filters, expansion Joints and supports.

M2.04 Electrical works including distribution and HVAC Power cum control panels with
DDC controller.

M2.05 Motorized fire dampers for ducts wherever crossing Walls/Floors/Slabs.

M2.06 Complete HVAC system testing, commissioning, training and interfacing with the
existing HVAC control panel.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 518 of 536


D9. PROTECTION MODIFICATION WORKS AT EXISTING SUBSTATIONS IN
EAST AREA (B)

All the modifications as required in the 33 kV GIS, LV Compartment,Control &
Relay Panels , Busbar protection panels etc including but not limited to changing
the labels, modifying the schematic diagrams, GA drawings, layout drawing
preparation and revision of all relevant drawings, SLDs, etc. as required to reflect
the circuit changes shall be carried out by the contractor under scope of this
contract within the quoted price. All such drawings whether specifically
mentioned or not shall be modified and submitted to Engineer/Authoritys
approval by the substation contractor at an early stage of project execution. All
extension and modification works shall be carried out by the substation
contractor with minimum outage only. The substation contractor in his offer shall
state the requirement of shut down in the existing substations.

The complete set of as built drawings (wherever changes as required) shall be
resubmitted incorporating the changes. The Authority reserve the right to ask the
substation contractor to retest and recommission any item or plant disturbed
during modification works without any cost and time implication to the Authority
and no deviation is acceptable in this regard. The contractor must visit the site
and all necessary existing information, drawings, documents, etc. required shall
be collected without any implications to authority. Any minor civil modifications
anticipated in the 33 kV GIS room, Control & Relay room etc. shall be carried out
by the substation contractor.

Modification of the existing protection panels shall be carried out by qualified and
experienced Engineer approved by FEWA. All the modifications shall be carried
out with minimum shutdown requirements and without any disturbance to existing
system. The tenderer shall make site visit and assess themselves all the required
modifications to be carried out in existing panels and the cost towards all works
shall be included within the quoted price.
All modifications required in existing panels, relay and control panels, AC/DC
system etc shall be included within the quoted price.

The existing substation as built drawings including but not limited to layout of
main equipments, sections, cable route layout, cable tray layout, earthing
drawings, control and protection schematic diagrams of existing bays (Bus
section, common control panels, adjacent panels etc), substation single line
diagrams, associated civil and electromechanical drawings affected by the
modification works etc shall be suitably modified and submitted for approval at an
early stage. All such drawings shall also be made as final as built drawings by
the substation contractor in addition to the equipment drawings.

Any relocation of existing equipments required for works shall be deemed to be
included in the quoted price. New control cables/LV power cables, fixing
arrangement of relocated equipments etc are also included within the quoted
price.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 519 of 536


All the relay setting calculations as required by Authority shall be carried out by
the contractor under scope of this contract and shall be submitted to
Engineer/Authority for approval.

Any necessary details including but not limited to existing relay setting and
drawings/ information etc as required shall be collected from site/relays by
contractor under the scope of this tender. All schematic diagrams shall be tested
and all protection testing including end to end testing shall be carried out within
the quoted price.

Providing manufacturer Specialist for testing and commissioning of Main
protection relays for 33 kV OHL/cable feeders shall be under the scope of this
tender. All cost towards testing and commissioning of Main protection relays by
manufacturer specialist shall be included within the quoted price.

The Main protection relays in the new substation shall be matched with existing
relays at respective remote end substation. In case contractor cannot comply
with this requirement then all cost towards modification and replacement of Main
Protection relays at existing respective remote end substations shall be included
within the quoted price of existing substation modification works without any
contractual implication to Authority. However Authority reserves the right to
decide either to supply new relays and modify the existing panel or to match with
existing relays and the same will be decided during engineering stage.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

D9.1 Protection Modification Works at existing Al GHOB Substation for New Seih
Dibba substation cable feeder One (1) circuit

The existing 33kV GIS Spare Bay (H204) C&R Panel shall be modified as follows:

D9.1.1 Protection modification as required for New Seih Dibba Cable feeder (H204)
Circuit

The existing 33kV C&R Panel (H204) at AL GHOB is equipped with main
protection suitable for fibre optic current differential protection relay type Solkor
N, manufactured by Siemens.

Bidder shall match the above main protection relay at new Seih Dibba
Substation. However, if matching is not possible then bidder shall replace the
existing main protection relay matching with new Seih Dibba at existing AL
GHOB Substation within the overall quoted price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new fibre optic

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 520 of 536


current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

D9.2 Protection Modification Works at Transco Tawyeen Substation for New
Tawyeen substation cable feeders Three (3) circuits

Transco Tawyeen Substation is under construction, bay numbers will be adviced
to the successful bidder later.

The existing 33kV main protection relay is MiCOM P543 relay.

D9.2.1 Protection modification as required for New Tawyeen Cable feeder Circuit No. 1

D9.2.2 Protection modification as required for New Tawyeen Cable feeder Circuit No. 2

D9.2.3 Protection modification as required for New Tawyeen Cable feeder Circuit No. 3

Bidder shall match the main protection relay at new Tawyeen substation with
Transco Tawyeen. However, if matching is not possible then bidder shall replace
the existing main protection relay matching with new Tawyeen at Transco
Tawyeen substation within the overall quoted price.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new fibre optic
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required to
satisfy the scheme requirement shall be supplied and installed within the quoted
price.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.








TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 521 of 536


D9.3 Overall end to end testing & commissioning of new Seih Dibba Dibba
Main Feeders Two (2) Circuits.

D9.4 Protection Modification Works at existing Dibba Main Substation for
Akkamia substation cable feeders Two (2) circuits

The existing 33kV GIS Bays (H205 & H208) C&R Panels presently designated as
Akkamia Circuit -1 & 2 shall be modified as follows:

D9.4.1 Protection modification as required for Akkamia Cable feeder (H205) Circuit No.1

D9.4.2 Protection modification as required for Akkamia Cable feeder (H208) Circuit No.2

The existing 33kV C&R Panels (H205 & H208) are equipped with main protection
suitable for pilot wire protection relay type MBCI, manufactured by GEC Alstom.

Bidder shall match the above main protection relay at Akkamia Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with Akkamia at the existing Dibba Main Substation.
The send or receive ends shall be properly coordinated by the bidder in order to
satisfy the scheme requirement. The compatibility of new relays installed at
Akkamia (in case of retaining the pilot wire protection relay at Dibba Main) shall
be confirmed by the Relay manufacturer.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new pilot wire
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

CT Calculation shall be submitted and the new relay shall be suitable for the CT
characteristic available at the existing Dibba Main substation. Bidders shall test
the CTs and note the parameters before making the CT sizing calculation.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.

D9.5 Protection Modification Works at existing Wassat Substation for Akkamia
substation cable feeder One (1) circuit

The existing 33kV C&R Panel (H205) presently designated as Akamiya Circuit
shall be modified as follows:


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 522 of 536


D9.5.1 Protection modification as required for Akkamia Cable feeder (H205) Circuit

The existing 33kV C&R Panel (H205) is equipped with main protection suitable
for pilot wire protection relay type MBCI, manufactured by GEC Alstom.

Bidder shall match the above main protection relay at Akkamia Substation.
However, if matching is not possible then bidder shall replace the existing main
protection relay matching with Akkamia at the existing Wassat Substation. The
send or receive ends shall be properly coordinated by the bidder in order to
satisfy the scheme requirement. The compatibility of new relays installed at
Akkamia (in case of retaining the pilot wire protection relay at Wasat) shall be
confirmed by the Relay manufacturer.

The above work shall include modification of GA & Schematic diagram,
dismantling, packing and handing over the existing installed Main protection
relays to FEWA stores (if required). Supply and installation of new pilot wire
current differential protection relay (if required), modification as required in the
control & relay panels including new wiring and modifications. Any other
component such as auxiliary relay, test terminal block, test plug etc as required
to satisfy the scheme requirement shall be supplied and installed within the
quoted price.

CT Calculation shall be submitted and the new relay shall be suitable for the CT
characteristic available at the existing Wassat substation. Bidders shall test the
CTs and note the parameters before making the CT sizing calculation.

The overall end to end testing including main protection, component testing,
scheme checking, final setting and commissioning shall be carried out within the
quoted price.


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 523 of 536


PART E : COMMON ITEMS

E1 SUPPLY OF SPARE 33/11kV DISTRIBUTION TRANSFORMER

E1E SCOPE OF WORK ELECTRICAL

E1E01 Transformers and Neutral Earthing Resistor

01.01 HVDT and NER

01.01.1 20/25MVA 33/11kV Distribution Transformer

All work related to design and supply of one (1) set of 20/25 MVA Dyn11
33/11kV, ONAN/ONAF distribution transformer with accessories, OLTC, remote
control panel (RTCC) for OLTC, neutral CTs etc. (Percentage impedance at
rated tap and maximum rated MVA = 12.5/15.62%) as per schedule of
requirement, detailed technical specification etc.

01.01.2 Neutral Earthing Resistor (NER)

All work related to design and supply of one (1) NER of 6.35 ohms, 1000A, 10
seconds for earthing 11kV neutral of 20/25 MVA HVDT as per schedule of
requirement, detailed technical specification etc including isolators.
























TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 524 of 536


E2 SCADA WORKS AT EXISTING U.A.Q. SYSTEM CONTROL CENTRE


E2 SC 1

SCADA works
Area : SCC U.A.Q


SC1.1

All works related to installation of modems at FEB
Locations, Upgrade of MUX (if required), terminations
and cabling between Front End Communication servers
and to the SDH equipment in order to include new 33kV
S/S in FEWA SCADA transmission network.

SCADA
COMMS

SC 1.2

All data engineering works and testing at UAQ System
Control Center for new substations as specified in
tender.

SCADA

SC 1.3

All data engineering works and testing at UAQ System
Control Center for existing substations extension as
specified in tender.

SCADA

SC1.4

Supply of test instruments and configuration tools for
both hard ware and software in order to utilize the all
functions of the supplied equipment. Tenderer to submit
the list of test instruments and configuration tools for all
SCADA and communication equipment as per tender
specifications to FEWA for review and approval before
the manufacturing/ purchase.

SCADA
COMMS


E3 TELECOMMUNICATION EQUIPMENT

General

This Article covers the design, manufacture supply, transport, installation, cable
laying, wiring, testing, commissioning and handing over in satisfactory operating
condition of the telecommunication system(s) including all auxiliary equipment,
accessories and work for:

SDH Nodes (OLTE and Multiplex Equipment)
Remote Subscriber Telephone system
RTU Data Transmission on IEC 60870-5-101 and IEC 60870-5-104
protocol
Fiber Optic Distribution Panel
for the various respective sites as indicated i.e.
New 33/11kV Shiekh Khalifa Hospital Substation,

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 525 of 536


New 33/11kV Riffah-3 Substation,
New 33/11kV Zaith-3 Substation,
New 33/11kV Jazeerah Industrial Substation,
New 33/11kV RAMS-2 Substation,
New 33/11kV Shamal Substation,
New 33/11kV Ghalilah Power Substation,
New 33/11kV Seih Al Burairat 33/11kV Substation,
New 33/11kV Wadi Sham Substation
New 33/11kV Najaimat Substation,
New 33/11kV Water Field-2 Substation ,
New 33/11kV Al Hail Industrial Substation
New 33/11kV Seih Dibba Substation,
New 33/11kV Tawyeen Substation.

General reference is made to FEWA Specifications for the technical description
of the equipment and other general requirements, drawings provided in the
tender documents etc.

The works shall be complete on a turnkey basis including all terminations,
cabling etc. and not limited to the requirement of this scope in order to ensure
the overall functionality of the system to the satisfaction of FEWA. It is also
essential that the Contractor has adequate understanding and experience and
shall properly estimate and execute the works in compliance with relevant
Industry Quality Standards.

Spare capacity of the existing communication infrastructure shall not be
considered by the Contractor for the communication links unless explicitly
agreed upon by the FEWA's SCADA Maintenance Department.

The new equipment shall be housed in new cubicle racks, regardless of the
availability of empty space in cubicles of existing stations, unless otherwise
specified or proven that no space is available in existing substations. The
Contractor shall carry out the survey of the above sites in order to familiarize
himself and to propose the new Telecommunication Equipment during design
stage.

Minimum One Number or 25% (whichever is more) of each type of module
installed in the equipment should be provided to FEWA as spare after
commissioning.

Supply and installation including termination of all necessary cables/material/
accessories etc to complete the job in all respects, is deemed to be included in
the scope of supply/works.

The contractor shall co-ordinate his activities with the respective contractor e.g.
for OHL or Power Cable.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 526 of 536


Any minor civil work requirements related to the telecommunication system are
deemed to be included under the scope of the contractor supplying the
telecommunication equipment at the new substations and the corresponding
remote ends or the other sites to establish the link connectivity as specified in
tender drawings related to telecommunication.

All Substation works related to Fibre Optic connectivity and wiring to all FODP
panels pertaining to SCADA and Communication system to be carried out to the
satisfaction of FEWA.

Works shall also include Restoration of existing services if interrupted due to
power cable reconfiguration, patching of FO cables, pilot cables etc. at all
intermediate stations in order to successfully route the services to their
respective destinations.

All the hardware accessories (e.g. test cables/leads/connectors/adapters etc.)
necessary for the troubleshooting, fault finding etc. of the complete
telecommunication equipments shall be included in the scope of work and
provided to FEWA. Additionally, one maintenance laptop completely equipped
with all software tools, licenses required for programming of telecommunication
equipments (OLTE/MUX/PABX etc.) should also be provided. The configuration
of Laptop is subject to FEWA approval during engineering stage.

All the signal transmission between the substations and SCC Umm Al Quwain
along the respective routes, if interrupted due to the OHL/Power Cable
reconfiguration, shall be resumed including rewiring (if any) and re-
commissioning of the respective links to the satisfaction of FEWA/Engineer,
under the scope of this specification.

All relevant design documents shall be approved by FEWA/Engineer before
commencement of any works. All relevant existing telecommunication system
documents as well as telecom substation documents where modifications or
integration works need to be carried out, at any existing stations shall be
revised/updated and new/revised as-built Telecom System & station documents
shall be submitted in consolidated form as final "As Built" by the
Bidder/Contractor. Further, approval at any stage does not relieve the contractor
from his obligations in the contract to ensure conformance to specification.

Within the frame of 33/11kV network upgrade, new telecommunication
equipment shall be installed at new 33/11kV substations. Additionally, new
multiplexers shall also be provided and existing multiplexers shall be upgraded
at existing stations as per the directions given in scope and tender drawings.If
the new substation is not connected directly to 132/33 kV substation with access
to FEWAs fiber optic network then data transmission shall be implemented from
RTU via Modem connection to next substation equipped with OLTE/MUX. This
means that for such new substations with pilot cables/telephone cables
connection to FEWAs fiber optic network, new industrial modems shall be
provided along with isolation transformers. Further wherever possible, direct

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 527 of 536


RS232 connection from RTU to MUX shall be preferred over modem
connections.

All works required at existing substations related to modifications for providing
MCBs to new equipments from existing Battery chargers shall be included in the
scope.The scope of supply for all major items is clearly listed in this tender
document. However, any items that are not specifically listed but are essential to
satisfactorily complete the works and which forms the part of interface between
different equipments should be included by the contractor in the price. Deviations
if any, shall be clearly highlighted else it will be assumed that contractor
understands the requirements specified under this tender and confirm complete
compliance to technical requirements and FEWA practice.

E3.1 SDH Node (OLTE/MUX) at 33/11kV Substations

SDH nodes (OLTE +MUX) shall be supplied, installed and commissioned each at
the followings sites:

New 33/11kV Shiekh Khalifa Hospital Substation,
New 33/11kV Zaith-3 Substation,
New 33/11kV Riffah-3 Substation,
New 33/11kV Jazeerah Industrial Substation,
New 33/11kV RAMS-2 Substation,
New 33/11kV Shamal Substation,
New 33/11kV Seih Al Burairat 33/11kV Substation,
New 33/11kV Najaimat Substation,
New 33/11kV Seih Dibba Substation,
New 33/11kV Tawyeen Substation
New 33/11kV Al Hail Industrial Substation
Existing Remote End Substations including Existing 33/11kV RAMS
S/S,
Upgrade of SDH network in Existing substations to achieve the desired
connectivity.

Further reference to this scope shall be made to tender documents including
Overall Conceptual Telecommunication drawings (FEWA/E1912/T/002).The
offered telecom equipment with min. STM-1 capacity shall be equipped with
range of access interfaces for telephony, data and LAN FE/GE required for
routing of various services mentioned in this section. In general, besides the
requirements specified for RTU data, remote subscribers, all nodes shall have
as a minimum requirement of 2 TCP/IP based Ethernet ports, 2 E1 ports
(G.703 balanced).

All OLTE/MUX equipments shall be delivered with an equipped spare capacity
of at least 50 % after completing the scope of works. Additionally, 02 Nos. of
Patch cords per node (of length suitable enough between Telecom Equipment

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 528 of 536


& FODP) as recommended from SDH manufacturer should be supplied to
FEWA as spare after commissioning.

The required SDH equipment is to provide optical communication links over the
OPGW/FOC of the respective OHL/Power Cable circuits among these
substations. The equipment shall be configured to form the respective optical
links (Preferred in ring configuration but point to point is also acceptable in case
of media limitations) such as in any configuration redundant links shall be
achieved between each substation and its remote ends. The current
telecommunication configuration shall be considered only for conceptual
purpose and the final telecom configuration shall be subject to FEWA approval
during engineering stage.

The existing multiplexers at the remote ends shall be upgraded in all respect to
meet the desired connectivity and to integrate the new nodes/equipments in all
respect.

The integration of the various signals of the new Telecommunication Equipments
with the existing Telecommunication Equipments of above make can be realized
through 2 Mbit level in order to integrate the same at control site. However,
wherever feasible the integration shall be at minimum STM-1 level.The Contractor
shall propose the suitable methodology to achieve redundant path for the various
signals and the final configuration shall be decided during the detail
design/engineering stage and are subject to final approval by Authority/ Engineer.

The scope shall also include all the works required to integrate the new telecom
systems in the existing FEWA Network management system as well as all works
required for establishing successful end to end connectivity for all the services
connected with telecommunication equipments. The system offered shall have min
99.9% availability and the same shall be proven in due course by carrying out the
stability test of the complete system successfully. The duration and procedure of
test shall be subject to approval of FEWA/Engineer.Appropriate modems , FO
converters, attenuators, amplifiers etc. required to achieve end to end data
connectivity to complete the works shall be considered in scope.

In addition to above, SDH equipment terminal configuration software of latest
version along with latest configuration backups shall be provided.

E3.2 PABX Extension/Telephone System at New 33/11 kV substations

Supply install and commissioning of minimum 6 numbers of remote subscribers at
each of the new 33/11kV Substations as mentioned below. The new telephone
system shall be integrated with FEWA existing Telephone network in all respect
(i.e. covering all hardware and software aspects).

New 33/11kV Shiekh Khalifa Hospital Substation,
New 33/11kV Riffah-3 Substation,
New 33/11kV Zaith-3 Substation,

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 529 of 536


New 33/11kV Jazeerah Industrial Substation,
New 33/11kV RAMS-2 Substation,
New 33/11kV Shamal Substation,
New 33/11kV Ghalilah Power Substation,
New 33/11kV Seih Al Burairat,
New 33/11kV Wadi Sham Substation
New 33/11kV Najaimat Substation,
New 33/11kV Water Field-2 Substation ,
New 33/11kV Al Hail Industrial Substation
New 33/11kV Seih Dibba Substation,
New 33/11kV Tawyeen Substation.
Upgradation of existing FEWA PABX Network to meet above
mentioned extensions.

All required wiring, hardware, configuration required at PABX at existing stations to
successfully integrate the telephone system at new 33/11kV S/S into FEWA
network shall be included in the scope.

The scope shall also include supply of any new hardware including modules,
programming/configuration in existing PABX systems to achieve the required
extensions at new 33/11kV S/S.

The extension of PABX shall be as per approval from FEWA/Engineer during
engineering stage. The current FEWA PABX network diagram with conceptual
extensions for new 33/11kV Substations is attached with the tender document
(Please refer drawing number FEWA/E1912/T/007).All telephone cables, wiring,
protection devices/surge arrestors, programming, testing and commissioning to the
satisfaction of the FEWA shall be part of the scope. The telephones shall be
distributed to all the major rooms inside the substation by means of telephone
sockets, properly protected telephone cables and through centrally located Junction
box. The typical minimum distribution of Telephones in the substation should be as
specified below. However, exact locations of the subscribers and final distribution
inside the new substation shall be decided during the detail engineering/approval
stage.

Typical Minimum Telephone distribution in new 33/11kV Substation









T
T
Room
No.
ROOM NAME
NO. OF EXTENSION TYPE OF SET
1. Control and Relay Room 01 Desk Type
2. SCADA/Telecom Room 01 Wall Mounted
3. 33kV GIS Room 01 for each room Wall Mounted
4 11kV Room 01 for each room Wall Mounted
5 Store/Office Room 01 Wall Mounted
6 LVAC Room 01 Wall Mounted
TOTAL 6

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 530 of 536


The above distribution is tentative and minimum. The final distribution shall be as per
the approved layout and shall be subject to approval during engineering.

The telephone sets shall have all necessary standard facilities/features compatible
with the existing PABX/ telephone system. The telephone cables should be armored
type or shall be laid in protective conduits. Telephone cables as well as sets are
subject to approval during design stage.

E3.3 Fiber Optic Distribution Panel

Design, manufacture, installation, wiring and commissioning of FODP panels at each
new Substation as per the guidelines specified in the specification. The panels shall
be of standard size as other panels in telecom room with 19 rails for mounting
Optical distribution frames and equipped with all standard accessories viz. Heater,
hygrostat, door limit switch, lamps, sockets etc. The make, manufacturer as well as
design of panels are subject to FEWA approval during engineering stage.

E3.3.1 Thirteen nos. (13) floor standing panels (FDP) shall be supplied, installed and
commissioned at new substations (one panel at each substation) equipped with F.O
network.

Note: Floor mounted Fibre Distribution Panels shall be manufactured by the
FEWA approved control and relay panel manufacturer on


























TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 531 of 536


SCHEDULE F : OPTIONAL SCOPE OF WORKS

F1 Mandatory Spares

F1.1 For equipment as detailed in Volume V, Section 3

F2. Recommended Spares

F2.1 The tenderer shall specify spares recommended in addition to the above for
operation and maintenance for three (3) years.

F3. Relay Test Equipment

F3.1 Test equipment as specified below:

Relay testing system, Computer aided, suitable for manual/automatic operation
shall be supplied for Secondary injection tests of all types of numerical/static
protection relays e.g.

- Distance protection equipment.
- Directional relays.
- Voltage relays.
- Current relays.
- Frequency relays.
- Fibre optic current differential protection relays.
- Differential relays.
- Synchro-check relays. Etc.

The system shall have, but not limited, the following features:

a) Single unit, compact design & easy to transport with hard case.

b) Voltage outputs with adequate range:

- 3-phase/single phase
- DC voltage output
- Resolution: 6.5 10mV
- Accuracy: 0.01% of range.

c) Current outputs with adequate range:

- 3-phase AC
- 1-phase AC
- DC
- Resolution: 0.65 1 mA
- Accuracy : 0.01%


TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 532 of 536


d) Phase angle - Range: 0 360, Resolution: 0.1

e) Time: 0 - 100 seconds

- Resolution: 0.1 ms
- Accuracy : 0.01%

f) Voltage supply, single phase 240V, 50Hz.

g) Test leads, multi-core cables (as required)

h) Calibration box.

i) Necessary software and key.

j) Remote control with adequate cable.

k) Service temperature +50C.

l) Storage temperature +70C.

m) Sufficient Nos. of Binary inputs/outputs.

F4. Manufacturers Specialist for Site Testing of Numerical Relays

F4.1 Specialist from manufacturer works and subject to FEWA Approval shall conduct
the following, but not limited to, protection tests, for 33kV numerical relays:

- Reconfiguration of relays.
- Application of calculated settings.
- Secondary injection for all functions
- End to end tests/stability.
- On-load check.
- Scheme check(trips, alarms, scada)
- Any further checks during Guaranteed period.
- Relay communication checks.
- Synchro check schemes

All equipment for testing shall be provided by specialist, however FEWA/ erection
contractor will provide manpower for assistance/handling. The quoted price for
above works shall be entered as 'OPTIONAL valid for 3 years after delivery of
Relay & Control panels.

F5. SCADA Training at Manufacturers Works

F5.1 Training at manufacturer works for two (02) engineers on SCADA equipment for
min. 15 working days as per the requirements highlighted in Specification.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 533 of 536


(Tenderer to provide details of Training proposed as well as other details
specified in specification).

F6. Communication Training at Manufacturers Works

F6.1 Training at Manufacturer works for two (02) engineers on Telecommunication
equipment (MUX/SDH/PABX) for min. 15 working days. Training shall include all
the aspects required to make the Engineers expert in configuration, testing,
maintenance and troubleshooting of telecommunication equipment. Training
course details shall be submitted for approval and step by step procedure for
various training course shall be submitted prior to start of testing. Hard and soft
copy of training course and materials should be provided to the engineers.

F7. Supply of test instruments and configuration tools

F7.1 (Tenderer to propose the list of tools for approval of FEWA) for SCADA
equipment

F8. Training for 2 (two) Engineers for Scada and Communication equipment at
SCC, UAQ

F8.1 The training course shall be designed to make FEWA engineers expert in
configuration, maintenance and troubleshooting of links/SCADA system
(Tenderer to provide details of Training proposed as well as other details
specified in specification).

F9. Telecommunication Spare Parts and Tools

F9.1 All tools and measuring equipment required for erection, assembly and
disassembly, service, test and maintenance shall be offered and listed in detail.
The same shall comprise of scope and types as used by the Contractors
personnel during installation, commissioning and tests to allow all normal and
routine maintenance, fault diagnoses, fault location, fault remedy and repair to be
undertaken. The measuring equipment shall be offered as deemed necessary by
the Bidder for the whole offered equipment. Unit prices shall be quoted for all
proposed items.

All test equipment shall be supplied with all necessary cabling, clips, probes, all
type of cables and adapters necessary for connection to all equipment to be
tested.

Test equipment kits shall be provided for all telecommunications and associated
hardware including computers and peripherals.

The bidder/contractor shall provide the price for the following equipment as a
minimum.

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 534 of 536



Equipment Quantity
Digital Communication Analyzer for Signal
analysis from 64kbps to 1Gbps
1 No.
E1 Tester 1 No.
RS232 Meter 1 No.
G.703/64Kbps tester 1 No.
Selective Level Meter/Generator 1 No.
Optical Power Meter/Laser Source 1 No.
Optical Attenuator 1 No.
dB Level Meter 1 No.
Any other Test Equipment recommended by
manufacturer.
1 No.

The specifications of above instruments shall be subject to approval by FEWA.

All test equipment shall be accompanied by the suppliers handbooks and data
sheets and shall include instructions for use with the supplied equipment. Test
equipment kits shall be supplied with all type of probes, cables, connectors and
complete with suitable carrying cases with provision for holding all necessary
cables, instruction manuals, etc.

Should the successful Bidder make use of the spare parts and tools during
erection time, he is bound to replace them immediately in case of damage.

All spare parts and tools shall be handed over to FEWA during the
commissioning phase.

The availability of all spare parts, tools and measuring equipment for a period of
at least 15 years after award of Contract must be guaranteed by the Bidder.

F10 FIRE WATER TANK AND HORIZONTAL FIRE PUMP SET

F10.1 ALUMINUM FIRE WATER TANKS CAPACITY ONE HOUR

F10.1 All work for two (2) cylindrical powder coated marine grade alloy of Aluminum,
membrane lined firewater storage tank with minimum capacity for one hour fire
pump run at water demand as per approved hydraulic calculations, or as
required by Civil Defense Authority, whichever is greater, but should not be less
than 142 Cu.M per each tank with all necessary nozzles, platforms, ladders,
high/low level switches, level gauges, etc., including all the required civil works,
excavation, concrete foundations, etc.

F10.2 ALUMINUM FIRE WATER TANKS CAPACITY TWO HOURS

All work for two (2) cylindrical powder coated marine grade alloy of Aluminum,
membrane lined firewater storage tank with minimum capacity for two hours fire

TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 535 of 536


pump run at water demand as per approved hydraulic calculations, or as
required by Civil Defense Authority, whichever is greater, but should not be less
than 284 Cu.M per each tank with all necessary nozzles, platforms, ladders,
high/low level switches, level gauges, etc., including all the required civil works,
excavation, concrete foundations, etc.

F10.3 HORIZONTAL FIRE PUMPS SET

1A.01 Motor Driven Fire Water Pump

All work required for one (1) Motor Driven NFPA Fire Water Pump with all
accessories comprising horizontal, split casing, centrifugal pump, electric drive
motor, suction/discharge isolation valves, discharge non-return valve, piping,
fittings, supports, pressure gauges/transmitters with root valves, etc. Motor
Driven Fire Pump nominal capacity should be as per hydraulic calculations, but
not less than 1250 GPM.

1A.02 Diesel Engine Driven Fire Water Pump

All work required for one (1) diesel engine driven NFPA Fire water pump with all
accessories comprising horizontal, split casing, centrifugal pump, diesel engine,
fuel oil storage tank, batteries, batteries chargers, reduction gear unit, suction/
discharge isolation valves, discharge non return valve, pressure gauges/
transmitters with root valves, piping, fittings, supports, etc. Diesel Engine Fire
Pump nominal capacity should be as per hydraulic calculations, but not less than
1250 GPM.

1A.03 Jockey Pump

All work required for one (1) NFPA jockey pump with all accessories comprising
vertical centrifugal pump, electric drive motor, suction/discharge isolation valves,
discharge non return valve, piping, fittings, supports, pressure gauges/
transmitters with root valves, etc.

F11. Service Water Tank

E11.1 All works related to the one number of GRP panel insulated service water tank
capacity of 15 m
3
with all nozzles, drain, overflow, RCC foundation, level
switches and instrumentation etc.

F12 RCC Underground Fire water tank-2 hrs. capacity

F12.1 Construction of RCC underground fire water tank as per specifications and
standards for capacity of 2 hours pump run to be included.





TENDER NO. E19/2012

33/11kV SUBSTATION WORKS IN NORTH &
EAST AREAS OF NORTHERN EMIRATES


Volume III
Scope of Works


Page 536 of 536


F13 Wall mounted Split type Air-conditioner

F13.1 All works related to one number of 2.5 tons de-rated capacity of wall mounted
split type air-conditioner with isolator, cables, supports, foundation and all
accessories.