6 and
Foundation
TM
Fieldbus with advanced diagnostics that
minimize unplanned plant outages, minimize maintenance
costs and by providing the industrys most reliable
transmitter.
- Provide advanced warning of possible failure events
and avoid costly shutdowns.
- Three levels of failure reporting
- Comprehensive list of on-board diagnostics (Ref. ST
3000 User manual with HART
6, 34-ST-25-17 Rev:
June 09 and Foundation
TM
Fieldbus option manual 34-
ST-25-15 Rev: June 09)
ST 3000 Smart Pressure Transmitter 3
Operating Conditions All Models
Parameter
Reference
Condition (at
zero static)
Rated Condition Operative Limits Transportation and
Storage
C F C F C F C F
Ambient Temperature
251 772 -40 to 85 -40 to 185 -40 to 85 -40 to 185 -55 to 125 -67 to 257
Meter Body Temperature
251 772 -40 to 110
1
-40 to 230 -40 to 125 -40 to 257 -55 to 125 -67 to 257
Humidity %RH 10 to 55 0 to 100 0 to 100 0 to 100
Overpressure
STD904 psi
bar
STG90L psi
bar
0
0
0
0
4,500
310
500
35
4,500
310
500
35
Vacuum Region Minimum
Pressure
mmHg absolute
inH
2
O absolute
Atmospheric
Atmospheric
25
13
2 (short term*)
1 (short term*)
Supply Voltage, Current, and
Load Resistance
Voltage Range: 10.8 to 42.4 Vdc at terminals
Current Range: 3.0 to 21.8 mA
Load Resistance: 0 to 1,440 ohms (as shown in Figure 2)
Maximum Allowable
Working Pressure (MAWP)
(ST 3000 products are rated to
Maximum Allowable Working Pressure.)
STD904 = 4,500 psi, 310 bar
STG90L = 500 psi, 35 bar
Static Pressure Limit = Maximum Allowable Working Pressure (MAWP) for STD904.
STG90L can withstand overpressure of 1.5X MAWP without damage.
*
Short term equals 2 hours at 70C (158F)
Note: A minimum of 250 ohms
of loop resistance is necessary
to support communications.
Loop resistance equals barrier
resistance plus wire resistance
plus receiver resistance.
= Operating Area
0 10.8 16.28 20.63 25 28.3 37.0 42.4
1440
1200
800
650
450
250
Operating Voltage (Vdc)
Loop
Resistance
(ohms)
Note: A minimum of 250 ohms
of loop resistance is necessary
to support communications.
Loop resistance equals barrier
resistance plus wire resistance
plus receiver resistance.
= Operating Area
0 10.8 16.28 20.63 25 28.3 37.0 42.4
1440
1200
800
650
450
250
Operating Voltage (Vdc)
Loop
Resistance
(ohms)
Figure 2 - Supply voltage and loop resistance chart
4 ST 3000 Smart Pressure Transmitter
Performance Under Rated Conditions* - Model STD904
Parameter Description
Upper Range Limit inH
2
O
mbar
400 (39.2F/4C is standard reference temperature for inH2O range.)
1,000
Minimum Span inH
2
O
mbar
4 Note: Recommended minimum span in square root mode is 20 inH2O (50 mbar).
10
Turndown Ratio 100 to 1
Zero Elevation and Suppression 5 to +100% URL.
Accuracy (Reference Includes
combined effects of linearity,
hysteresis, and repeatability)
Accuracy includes residual error
after averaging successive
readings.
For FOUNDATION
TM
Fieldbus use
Digital Mode specifications.
For HART
|
|
.
|
\
|
+
O inH span
O inH 25
0.075 0.075
2
2
or
(
|
.
|
\
|
+
mbar span
mbar 62
0.075 0.075
in % of span
In Digital Mode: 0.125% of calibrated span or upper range value (URV), whichever is
greater, terminal based.
For URV below reference point (25 inH
2
O), accuracy equals:
(
|
|
.
|
\
|
+
O inH span
O inH 25
0.075 0.05
2
2
or
(
|
.
|
\
|
+
mbar span
mbar 62
0.075 0.05
in % of span
Zero Temperature Effect per
28C (50F)
In Analog Mode: 0.325% of span.
For URV below reference point (50 inH
2
O), effect equals:
(
|
|
.
|
\
|
+
O inH span
O inH 50
0.3125 0.0125
2
2
or
(
|
.
|
\
|
+
mbar span
mbar 125
0.3125 0.0125
in % of span
In Digital Mode: 0.3125% of span.
For URV below reference point (50 inH
2
O), effect equals:
|
|
.
|
\
|
O inH span
O inH 50
0.3125
2
2
or
|
|
.
|
\
|
mbar span
mbar 125
0.3125
in % of span
Combined Zero and Span
Temperature Effect per 28C
(50F)
In Analog Mode: 0.6% of span.
For URV below reference point (50 inH
2
O), effect equals:
(
|
|
.
|
\
|
+
O inH span
O inH 50
0.40 0.20
2
2
or
(
|
.
|
\
|
+
mbar span
mbar 125
0.40 0.20
in % of span
In Digital Mode: 0.575% of span.
For URV below reference point (50 inH
2
O), effect equals:
(
|
|
.
|
\
|
+
O inH span
O inH 50
0.40 0.175
2
2
or
(
|
.
|
\
|
+
mbar span
mbar 125
0.40 0.175
in % of span
Zero Static Pressure Effect
per 1000 psi (70 bar)
0.3% of span.
For URV below reference point (50 inH
2
O), effect equals:
(
|
|
.
|
\
|
+
O inH span
O inH 50
0.2875 0.0125
2
2
or
(
|
.
|
\
|
+
mbar span
mbar 125
0.2875 0.0125
in % of span
Combined Zero and Span
Static Pressure Effect per
1000 psi (70 bar)
0.6% of span.
For URV below reference point (50 inH
2
O), effect equals:
(
|
|
.
|
\
|
+
O inH span
O inH 50
0.40 0.20
2
2
or
(
|
.
|
\
|
+
mbar span
mbar 125
0.40 0.20
in % of span
Stability 0.03% of URL per year.
- Performance specifications are based on reference conditions of 25C (77F), zero (0) static pressure, 10 to 55% RH.
ST 3000 Smart Pressure Transmitter 5
Performance Under Rated Conditions* - Model STG90L
Parameter Description
Upper Range Limit psi
bar
500
35
Minimum Span psi
bar
5
0.35
Turndown Ratio 100 to 1
Zero Elevation and
Suppression
No limit except minimum span from absolute 0 (zero) to +100% URL. Specifications
valid over this range.
Accuracy (Reference Includes
combined effects of linearity,
hysteresis, and repeatability)
Accuracy includes residual error
after averaging successive
readings.
For HART
|
|
.
|
\
|
+
psi span
psi 50
0.3125 0.0125
or
(
|
.
|
\
|
+
bar span
bar 3.5
0.3125 0.0125
in % of span
In Digital Mode: 0.3125% of span.
For URV below reference point (50 psi), effect equals:
|
|
.
|
\
|
psi span
psi 50
0.3125
or
|
|
.
|
\
|
bar span
bar 3.5
0.3125
in % of span
Combined Zero and Span
Temperature Effect per 28C
(50F)
In Analog Mode: 0.6% of span.
For URV below reference point (50 psi), effect equals:
(
|
|
.
|
\
|
+
psi span
psi 50
0.40 0.20
or
(
|
.
|
\
|
+
bar span
bar 3.5
0.40 0.20
in % of span
In Digital Mode: 0.575% of span.
For URV below reference point (50 psi), effect equals:
(
|
|
.
|
\
|
+
psi span
psi 50
0.40 0.1750
or
(
|
.
|
\
|
+
bar span
bar 3.5
0.40 0.175
in % of span
Stability 0.03% of URL per year
- Performance specifications are based on reference conditions of 25C (77F), zero (0) static pressure, 10 to 55% RH,
and 316 Stainless Steel barrier diaphragm.
6 ST 3000 Smart Pressure Transmitter
Performance Under Rated Conditions All Models
Parameter Description
Output (two-wire) Analog 4 to 20 mA or DE digital communications mode. Option available for HART protocol.
Supply Voltage Effect 0.005% span per volt.
Damping Time Constant Adjustable from 0 to 32 seconds digital damping.
CE Conformity (Europe) 89/336/EEC, Electromagnetic Compatibility (EMC) Directive.
NAMUR NE 43 Compliance
(Option NE)
Transmitter failure information is generated when the measuring information is invalid or no longer
present. Failure information is transmitted as a current signal but outside the normal 4-20 mA
measurement signal level. Transmitter failure values are: 3.6 mA and 21.0 mA.
The normal signal range is 3.8 mA and 20.5 mA.
SIL 2/3 Compliance SIL certified to IEC 61508 for non-redundant use in SIL 2 related Safety Systems (single use)
and for redundant (multiple) use in SIL 3 Safety Systems through
TV Nord Sys Tec GmbH & Co. KG under the following standards:
IEC61508-1: 1998; IEC 61508-2: 2000; IEC61508-3: 1998.
Lightning Protection Option
(Code LP)
Leakage Current : 10 microamps max. @ 42.4 VDC, 93C
Impulse Rating: 10/20 sec. 5,000 Amps (50 strikes) 10,000 Amps (20 strikes)
(rise/decay) 10/1,000 sec. 250 Amps (1,000 strikes) 500 Amps (400 strikes)
Physical and Approval Bodies
Parameter Description
Barrier Diaphragms Material 316L Stainless Steel
Process Head Material 316L Stainless Steel
Head Gaskets (STD904 only) Glass filled PTFE
Meter Body Bolting (STD904 only)
Carbon Steel (Zinc plated, standard) or A286 SS (NACE) bolts and 304 SS (NACE) nuts for
process heads.
Mounting Bracket
Carbon Steel (Zinc-plated) or Stainless Steel angle bracket or Carbon Steel flat bracket available
(standard options).
Vent/Drain Valves & Plugs
1
316 SS
4
, Hastelloy
C-276
2
, Monel
400
8
(Model STD904 only)
Fill Fluid Silicone DC
200 oil
Electronic Housing
Epoxy-Polyester hybrid paint. Low Copper-Aluminum. Meets NEMA 4X (watertight) and NEMA 7
(explosion proof). Stainless steel optional.
Process Connections STD904
STG90L
-inch NPT; -inch NPT with adapter. (Process heads meet DIN19213.)
-inch NPT
Wiring Accepts up to 16 AWG (1.5 mm diameter).
Mounting
Can be mounted in virtually any position using the standard mounting bracket. Bracket is
designed to mount on 2-inch (50 mm) vertical or horizontal pipe. See Figure 3.
Process Connections -inch NPT; -inch NPT with adapter (standard option, meets DIN requirements)
Dimensions See Figures 4 and 5
Net Weight STD904
STG90L
9 pounds (4.1 Kg)
3.8 pounds (1.7Kg)
Net Weight 9.0 pounds (4.1 Kg).
2
Hastelloy
and Experion
are registered trademarks of Honeywell International Inc.
Teflon
HC
H6
FF r
ME
SM
CI m
ZS s
NE 15
p
LP
CC
15
21
200 Silicone
Barrier Diaphragms Selection
NAMUR Failsafe Software
316L SS
Span
Base STG models no longer include a default communications option. All units now
require the selection of a communication option from Table III (AN, DE, HC, H6 or FF).
Selection
Wetted Process
Heads
Vent/Drain
Valves
Gage Pressure
I
HART
5.x Protocol Compatible Electronics
No Selection
FOUNDATION
TM
Fieldbus Communications
Communication Options (Must choose a communications option)
TABLE III - OPTIONS
STG90L _ _ _
0-20 to 0-500 psi/0-1.4 to 0-35 bar
Analog only (can be configured using appropriate Honeywell DE tool)
_ _ G
b
Custom Calibration and I.D. in Memory
TC
SL
AN
Transmitter Configuration - (Fieldbus) FC
Transmitter Housing & Electronics Options
HART
6.x
Protocol Compatible Electronics
b
b
b
18 ST 3000 Smart Pressure Transmitter
34-ST-16U-56
Issue 25
Page 2 of 4 Avail.
STG90L
TABLE III - OPTIONS (cont'd)
A1 n
A2
TB
a
a
a
a
MB
MX
SB
SX
FB
UM
F1
F3
F5
22
MT 2
W1
W2
W3
W4
9X
Dust Ignition Proof
b
b
b
b
Int. Safe, Zone 0/1, or
Flameproof, Zone 1
Stainless Steel Customer Wired-On Tag
1/2" NPT to 3/4" NPT 316 SS Conduit Adapter
TG
Certificate of Origin (F0195)
User's Manual Paper Copy (Standard, HC/H6, or FF ships accordingly)
Calibration Test Report and Certificate of Conformance (F3399)
ZD
Flameproof,
Zone 1
Intrinsically Safe,
Zone 0/1
ZA
b
b
b
b
ST 3000 Smart Pressure Transmitter 19
34-ST-16U-56
Issue 25
Page 3 of 4
STG90L
TABLE III - Approvals Options (continued)
23
10
See ATEX installation requirements in the ST 3000 User's Manual
Ex ia IIC
T4 (Ta = 50C to +93C);
T5 (Ta = 50C to +85C);
T6 (Ta = 50C to +70C);
Ui = 30V; Ii = 100mA
Ex tD A20 IP6X
T95C (at Ta = 93C) or
T80C (at Ta = 78C)
3C
Ex d IIC
T5 (Ta = 40C to +93C),
T6 (Ta = 40C to +78C)
Supply 11- 42Vdc
Ex tD A21 IP6X
T95C (at Ta = 93C) or
T80C (at Ta = 78C)
Ex nA, IIC
T5 (Ta = 40C to +93C),
T6 (Ta = 40C to +78C);
Zone 2 Supply < 42Vdc,
23mA
Ex tD A22 IP6X
T95C (at Ta = 93C) or
T80C (at Ta = 78C)
(Honeywell)
b
ATEX
10
(LCIE)
Enclosure IP 66/67
Ex tD A20 IP6X
T95C (at Ta = 93C) or
T80C (at Ta = 78C)
Ex ia IIC
T4 (Ta = 50C to +93C);
T5 (Ta = 50C to +85C);
T6 (Ta = 50C to +70C)
Enclosure IP 66/67
3N
3S
Enclosure IP 66/67
Dust-Ignitionproof,
Zone 0
Multiple Marking
11
Int. Safe, Zone 0/1, or
Flameproof, Zone 1, or
Non-Sparking, Zone 2
Intrinsically Safe,
Zone 1
BR- Ex ia IIC; T4, T5, T6
(See CERTUSP certificate for detailed
temperature codes by Communications
option)
Flameproof,
Zone 1
Non-Sparking,
Zone 2
Ex nA, IIC
T5 (Ta = 40C to +93C),
T6 (Ta = 40C to +78C);
Zone 2 Supply < 42Vdc,
23mA
(Honeywell). Enclosure IP
66/67
33
Enclosure IP 66/67
Ex ia IIC
T4 (Ta = 50C to +93C);
T5 (Ta = 50C to +85C);
T6 (Ta = 50C to +70C)
Enclosure IP 66/67
Intrinsically Safe,
Zone 0
Ex d IIC
T5 (Ta = 40C to +93C),
T6 (Ta = 40C to +78C)
Supply 11- 42Vdc
Ex tD A21 IP6X
T95C (at Ta = 93C) or
T80C (at Ta = 78C)
6D
6S
11
The user must determine the type of protection required for installation of the equipment. The user shall then check the box []
adjacent to the type of protection used on the equipment certification nameplate. Once a type of protection has been checked on
CERTUSP
INMETRO
(Brazil)
Flameproof, Zone 1 BR- Ex d IIC T5, T6
the nameplate, subsequently the equipment shall not be reinstalled using any of the other certification types.
Intrinsically Safe, Zone 0/1
Approval
Body
Approval Type Location or Classification Selection
20 ST 3000 Smart Pressure Transmitter
34-ST-16U-56
Issue 25
Page 4 of 4
STG90L
XXXX
Table Table
b
m
n
p
r
s
2
15
21
22
23
HART
or PTFE.
0 0 0 0 0 _ _, _ _, _ _
II III (Optional)
STD904 _ _ _
I
Process Head
Configuration
Selection
DC
200 Silicone
1/4 NPT
Vent/Drain
Valves
1
and Plugs
Selection
Materials of Const.
Ordering Example: STD904-E1A-00000-HC,1C+XXXX
316 SS 316L SS 316 SS
Fill Fluid
1/2 NPT with Adapter (on 1/4 NPT Head)
Body Rating: 4,500 psi (310 bar)
Process Wetted
Heads
Span
0-4" to 0-400" H
2
O / 0-10 to 0-1,000 mbar
Base STD models no longer include a default communications option. All units now require the
selection of a communication option from Table III (AN, DE, HC, H6 or FF).
Barrier Diaphragms
Avail.
STD904
_ _ A
_ _ H
0 0 0 0 0
t
No Selection
22 ST 3000 Smart Pressure Transmitter
34-ST-16U-55
Issue 29
Page 2 of 5
STD904
TABLE III - OPTIONS Selection
e
m
15
P
15
21
c
c
c
MX
SB
SX
22
o
o
2
Supplied as 316 SS or as Grade CF8M, the casting equivalent of 316 SS.
1/2 NPT Male to M20 Female 316 SS Certified Conduit Adapter (ATEX, CSA & IECEx) A1
Stainless Steel Customer Wired-On Tag (blank)
Analog only (can be configured using appropriate Honeywell DE tool)
Transmitter Configuration - (non-Fieldbus)
Transmitter Configuration - (Fieldbus)
DE Protocol communications
HART
5.x Protocol Compatible Electronics
HART
Intrinsically Safe,
Zone 1
b
24
3S
3N
33
24
Flameproof and
Dust-tight Enclosure,
Zone 1
Ex d IIC
T5 (Ta = 40C to +93C),
T6 (Ta = 40C to +78C)
Supply 11- 42Vdc
Ex tD A21 IP6X
T95C (at Ta = 93C) or
T80C (at Ta = 78C)
Enclosure IP 66/67
Dust-tight Enclosure,
Zone 0
Ex ia IIC
T4 (Ta = 50C to +93C);
T5 (Ta = 50C to +85C);
T6 (Ta = 50C to +70C)
Enclosure IP 66/67
Non-Sparking,
Zone 2
Ex nA, IIC
T5 (Ta = 40C to +93C),
T6 (Ta = 40C to +78C);
Zone 2 Supply < 42Vdc, 23mA
Ex tD A22 IP6X
T95C (at Ta = 93C) or
T80C (at Ta = 78C) (Honeywell)
Enclosure IP 66/67
Ex tD A20 IP6X
T95C (at Ta = 93C) or
T80C (at Ta = 78C)
Enclosure IP 66/67
ATEX
10
(LCIE)
No hazardous location approvals
Ex nA, IIC
T5 (Ta = 40C to +93C),
T6 (Ta = 40C to +78C);
Zone 2 Supply < 42Vdc, 23mA
Ex tD A22 IP6X
T95C (at Ta = 93C) or
T80C (at Ta = 78C) (Honeywell).
Enclosure IP 66/67
Ex ia IIC
T4 (Ta = 50C to +93C);
T5 (Ta = 50C to +85C);
T6 (Ta = 50C to +70C)
Enclosure IP 66/67
TABLE III - OPTIONS (continued)
Selection Location or Classification
Approval
Body
Approval Type
24 ST 3000 Smart Pressure Transmitter
34-ST-16U-55
Issue 29
Page 4 of 5
STD904
10
See ATEX installation requirements in the ST 3000 User's Manual
11
The user must determine the type of protection required for installation of the equipment. The user shall then check
the box [] adjacent to the type of protection used on the equipment certification nameplate. Once a type of protection
has been checked on the nameplate, subsequently the equipment shall not be reinstalled using any of the other
certification types.
X X X X
RESTRICTIONS
Table Table
b
c _ _ H
e
m
o
p
r
t
2
15
21
22
24 III
This approval code requires the
selection of a certified conduit plug:
A5, A6 or A7
IECEx
Ex d IIC;
T5 (Ta = -40 to +93C),
T6 (Ta = -40 to +78C)
Intrinsically Safe
Non-Incendive
Flameproof,
Zone 1
III SL
III FF
24
III SM
I
6D
CA
Approval
Body
Selection
SAEx
(South
Africa)
2J
Intrinsically Safe
Class I, II, III, Div. 1, Groups
A,B,C,D,E,F,G
Dust-Ignitionproof
24
Class II, III, Div. 1, Groups E,F,G
Class I, II, III, Div. 1, Groups
TABLE III - Approvals Options (continued)
Ex ia IIC; T3, T4, T5 , T6 (See
IECEx certificate for detailed temperature codes by
Communications option)
Canadian
Standards
Association
(CSA)
Intrinsically Safe,
Zone 0/1
A,B,C,D,E,F,G
Flameproof, Zone 1
Intr. Safe, Zone 0/1, or
Flameproof, Zone 1
b
Z2
Multiple Marking
11
Intrinsically Safe,
Zone 0/1
Explosion Proof
Approval Type
Class I, Div. 1, Groups A,B,C,D
Class I, Div. 1, Groups B,C,D
Location or Classification
Select only one option from this group
Ex d IIC T5, T6 Enclosure IP 66/67 ZD
Ex ia IIC T4, T5, T6
Ex d IIC T5, T6 Enclosure IP 66/67
ZA
Selection Selection
BR- Ex ia IIC; T4, T5, T6 (See CERTUSP
certificate for detailed temperature codes by Communications
option)
BR- Ex d IIC; T5, T6
Ex ia IIC T4, T5, T6
Available Only With Not Available With
Factory Identification
6S
Intrinsically Safe,
Zone 0/1
Restriction
Letter
CERTUSP
INMETRO
(Brazil)
Flameproof, Zone 1
FF
III HC or H6 and WP
III Select from Table III S2 or S3
III
Explosion Proof
1C
FF
ME III
FM
Approvals
SM
Class II, III Div. 1, Groups E,F,G
Class I, Div. 2, Groups A,B,C,D
III MX, SX
TC, ME or FISCO/FNICO compliance
not available with 3C, 3N, 33, 3S, 2J,
CA, Z2, ZD, ZA, 6D & 6S
FB, MB, SB
III CR, S4
III
III
TABLE IV
III
FISCO/FNICO compliance available only
with 1C
III
Dust-Ignitionproof
ST 3000 Smart Pressure Transmitter 25
34-ST-16U-55
Issue 29
Page 5 of 5
Teflon