Академический Документы
Профессиональный Документы
Культура Документы
=
=
m
i n
k k
T n d E
2
1
)) ( (
(2)
Where;
n: sample number,
k: subscript for phase a, b, c, or ground g,
d
1k
: the value of d1 of phase k at sample number n.
i: the fault inception sample,
m: last sample in the calculation period, and
T: the sampling period (10 sec here).
The sampling period T is a constant, so it can be omitted from the equation to produce a new index
E
k
that is higher in to magnitude than the energy index E
k
.
T
E
E
k
k
=
'
(3)
After a detailed study on switching operations and all types of faults (with or without high
impedance) using PSCAD/EMTDC, the following facts are observed:
1) Single line to ground faults (Downed conductor or regular low impedance fault)
a) The faulted phase has the highest energy index.
b) The energies of the other two phases are close to each other (the difference is very small, less
than phase).
c) The energy index for the ground is large (more than ground).
2) Double line to ground faults (Downed conductors or regular low impedance fault)
a) The faulted phases have the highest energy index.
b) The energy index for the ground is large (more than ground).
3) Line to line faults
3
a) The faulted phases have the highest energy index and they are nearly equal (the difference is
4
0 2000 4000 6000 8000 10000
-2000
0
2000
T
h
r
e
c
u
r
r
e
n
t
s
,
A
(a)
e
p
h
a
s
e
0 2000 4000 6000 8000 10000
-10
0
10
d
1
(
p
h
a
s
e
a
)
,
(b)
A
0 2000 4000 6000 8000 10000
-10
0
10
d
1
(
p
h
a
s
e
b
)
,
A
(c)
0 2000 4000 6000 8000 10000
-10
0
10
d
1
(
p
h
a
s
e
c
)
,
A
(d)
0 2000 4000 6000 8000 10000
-10
0
10
d
1
(
g
r
o
u
n
d
)
,
A
(e) sample number
0 2000 4000 6000 8000 10000
-2000
0
2000
T
h
r
e
e
p
h
a
s
e
c
u
r
r
e
n
t
s
,
A
(a)
0 2000 4000 6000 8000 10000
-5
0
5
d
1
(
p
h
a
s
e
a
)
,
A
(b)
0 2000 4000 6000 8000 10000
-5
0
5
d
1
(
p
h
a
s
e
b
)
,
A
(c)
0 2000 4000 6000 8000 10000
-5
0
5
d
1
(
p
h
a
s
e
c
)
,
A
(d)
0 2000 4000 6000 8000 10000
-2
0
2
d
1
(
g
r
o
u
n
d
)
,
A
(e) sample number
0 2000 4000 6000 8000 10000
-5000
0
5000
T
h
r
e
e
p
h
a
s
c
u
r
(a)
e
r
e
n
t
s
,
A
0 2000 4000 6000 8000 10000
-2
0
2
d
1
(
p
h
a
s
e
a
)
,
A
(b)
0 2000 4000 6000 8000 10000
-5
0
5
d
1
(
p
h
a
s
e
b
)
,
A
(c)
0 2000 4000 6000 8000 10000
-2
0
2
d
1
(
p
h
a
s
e
c
)
,
A
(d)
0 2000 4000 6000 8000 10000
-2
0
2
d
1
(
g
r
o
u
n
d
)
,
A
(e) sample number
0 2000 4000 6000 8000 10000
-2
0
2
d
1
(
g
r
o
u
n
d
)
,
A
(e) sample number
0 2000 4000 6000 8000 10000
-2000
0
2000
T
h
r
e
e
p
h
a
s
e
c
u
r
r
e
n
t
s
,
A
(a)
0 2000 4000 6000 8000 10000
-5
0
5
d
1
(
p
h
a
s
e
a
)
,
A
(b)
0 2000 4000 6000 8000 10000
-5
0
5
d
1
(
p
h
a
s
e
b
)
,
A
(c)
0 2000 4000 6000 8000 10000
-10
0
10
d
1
(
p
h
a
s
e
c
)
,
A
(d)
less than phase).
b) The energy index for the other phase is very small and nearly zero (the difference is less than
phase).
c) The energy index for the ground is very small, (less than ground).
4) Three phase symmetrical faults
a) The energy indices for the three phases are random.
b) The energy index for the ground is very small, (less than ground).
5) Switching operation
a) Switching operation has the same characteristics as the three phase symmetrical fault.
b) The Energy index of the modal signal is lower than that of the three phase symmetrical fault.
Figs. 3 to 5 show the three phase currents and d1 coefficients for the three phases and ground
current of different down conductor faults with different locations and fault impedances. Fig. 6 shows
a bc-g fault with high fault impedance to simulate two downed conductors. Figs. 7 and 8 depict a line-
to-line and symmetrical faults to show the success of the proposed technique to deal with low
impedance faults. Figs. 9 and 10 show a load switching operation at the sending end and a capacitor
switching operation at the receiving end respectively.
Fig. 3. DWT decomposition of phase c downed
conductor at 80 km from end S with 200 ohm fault
impedance (a) three phase currents (b) d1 of phase
a (c) d1 of phase b (d) d1 of phase c (e) d1 of
ground current.
Fig. 4. DWT decomposition of phase a downed
conductor at 195 km from end S with 100 ohm fault
impedance (a) three phase currents (b) d1 of phase
a (c) d1 of phase b (d) d1 of phase c (e) d1 of
ground current.
Fig. 5. DWT decomposition of phase b downed
conductor at 130 km from end S with 120 ohm fault
impedance (a) three phase currents (b) d1 of phase
a (c) d1 of phase b (d) d1 of phase c (e) d1 of
ground current.
Fig. 6. DWT decomposition of bc-g fault at 180 km
from end S with 100 ohm fault impedance (a) three
phase currents (b) d1 of phase a (c) d1 of phase b
(d) d1 of phase c (e) d1 of ground current.
0 2000 4000 6000 8000 10000
-1
0
1
x10
4
T
h
r
e
e
p
h
a
s
e
c
u
r
r
e
n
t
s
,
A
(a)
0 2000 4000 6000 8000 10000
-20
0
20
d
1
(
p
h
a
s
e
a
)
,
A
(b)
0 2000 4000 6000 8000 10000
-5
0
5
d
1
(
p
h
a
s
e
b
)
,
A
(c)
0 2000 4000 6000 8000 10000
-20
0
20
d
1
(
p
h
a
s
e
c
)
,
A
(d)
0 2000 4000 6000 8000 10000
-1
0
1
x10
-3
d
1
(
g
r
o
u
n
d
)
,
A
(e) sample number
0 2000 4000 6000 8000 10000
-1
0
1
x10
4
T
h
r
e
e
p
h
a
s
e
c
u
r
r
e
n
t
s
,
A
(a)
0 2000 4000 6000 8000 10000
-5
0
5
d
1
(
p
h
a
s
e
a
)
,
A
(b)
0 2000 4000 6000 8000 10000
-5
0
5
5
d
1
(
p
h
a
s
e
b
)
,
A
(c)
0 2000 4000 6000 8000 10000
-1
0
1
d
1
(
p
h
a
s
e
c
)
,
A
(d)
0 2000 4000 6000 8000 10000
-0.1
0
0.1
d
1
(
g
r
o
u
n
d
)
,
A
(e) sample number
0 2000 4000 6000 8000 10000
-2000
0
2000
T
h
r
e
e
p
h
a
s
e
c
u
r
r
e
n
t
s
,
A
(a)
0 2000 4000 6000 8000 10000
-1
0
1
d
1
(
p
h
a
s
e
a
)
,
A
(b)
0 2000 4000 6000 8000 10000
-0.2
0
0.2
d
1
(
p
h
a
s
e
b
)
,
A
(c)
0 2000 4000 6000 8000 10000
-1
0
1
d
1
(
p
h
a
s
e
c
)
,
A
(d)
0 2000 4000 6000 8000 10000
-2
0
2
x10
-10
d
1
(
g
r
o
u
n
d
Fig. 7. DWT decomposition of ab fault at 110 km
from end S (a) three phase currents (b) d1 of phase
a (c) d1 of phase b (d) d1 of phase c (e) d1 of
ground current.
Fig. 8. DWT decomposition of abc fault at 90 km
from end S (a) three phase currents (b) d1 of phase
a (c) d1 of phase b (d) d1 of phase c (e) d1 of
ground current.
2000
)
,
A
(e) sample number
0 2000 4000 6000 8000 10000
-2000
0
T
h
r
e
e
p
h
a
s
e
c
u
r
r
e
n
t
s
,
A
(a)
2
0 2000 4000 6000 8000 10000
-2
0
d
1
(
p
h
a
s
e
a
)
,
A
(b)
5
0 2000 4000 6000 8000 10000
-5
0
d
1
(
p
h
a
s
e
b
)
,
A
(c)
5
0 2000 4000 6000 8000 10000
-5
0
d
1
(
p
h
a
s
e
c
)
,
A
(d)
0 2000 4000 6000 8000 10000
-0.5
0
0.5
x10
-10
d
1
(
g
r
o
u
n
d
)
,
A
(e) sample number
Fig. 9. DWT decomposition of load switching
operation end S (a) three phase currents (b) d1 of
phase a (c) d1 of phase b (d) d1 of phase c (e) d1 of
ground current.
Fig. 10. DWT decomposition of capacitor bank
switching operation at end R (a) three phase
currents (b) d1 of phase a (c) d1 of phase b (d) d1
of phase c (e) d1 of ground current.
Table I shows the energy indices (E
k
) for the cases in Figs. 3 to 10. The detection criterion
presented is able to detect all disturbances. The first four cases, which represent downed conductor
cases, are detected and classified correctly using the detection and classification algorithm. The two
low impedance faults in Figs. 7 and 8 are detected and classified correctly. The two switching
operations shown in Figs. 9 and 10 generate phase energy indices similar to the symmetrical faults;
however, they are correctly classified using the modal signal energy index. It was found based on
simulation that the switching operations generate modal signal energy index less that 500 while the
energy index for the symmetrical fault is higher than this threshold.
3.3 Fault Location
Accurate fault location is very imperative for post fault maintenance. To locate the downed
conductor, traveling wave theory is exploited. The fault generates wide band of high frequency
transients travels both directions. The traveling waves will reach the transmission line ends at different
Table I: Energy index for the three phases and ground during disturbance
Fault type
Fault
distance
from end
S (km)
Fault
impedance
()
E'
a
E'
b
E'
c
E'
g
E'
modal
Algorithm
Classification
c-g 80 200 60.87 60.87 187.62 87.57 Not needed c-g
a-g 195 100 61.81 24.76 24.77 7.91 Not needed a-g
b-g 130 120 9.39 23.99 9.39 11.54 Not needed b-g
bc-g 180 100 21.94 38.49 76.55 11.77 Not needed bc-g
ab 110 0.1 10.67 10.67 0 0 Not needed ab
abc 90 0.1 608.86 3.76 707.71 0 1049.3 abc
LS at end S* 0 -- 5.12 23.76 6.82 0 297.05 switching
CS at end R* 200 -- 0.73 0.051 1.16 0 3.0797 switching
*LS and CS mean load switching and capacitor switching
times depending on the distance between the transmission line end and fault point. For example, for
faults near the sending end, the traveling waves will reach the sending end before the receiving end.
Using synchronized clocks at both of the transmission line ends, the time at which the traveling waves
reach both ends can be recorded and used to locate the fault point [10]. Assume a fault occurred at F1
as shown in Fig. 11. The traveling wave will arrive at the sending end and the receiving end at time
(t
1
) and (t
2
) respectively. The distance between the fault point and the sending end (relay point) is
calculated using (5) [10].
2
) (
1 2
t t v L
d
= (5)
where,
d: the fault distance from the sending end,
L: the transmission line length, and
v: the propagation speed of the traveling wave.
The arrival times of the traveling waves are recorded using d1 of the DWT decomposition of the
modal signals at the sending and receiving ends. The modal signal should be calculated for
both the receiving and the sending ends as shown in Fig. 12. The detection criterion used to detect the
fault is used here to record the arrival time of the traveling waves at both ends (t
1
and t
2
). Table II
shows the actual and calculated distances from end S for the cases shown in figs. 3-8. From Table II, it
is clear that the fault location method gives reliable results with relatively low error.
4. CONCLUSION
A protection algorithm for protection of Downed conductors in series-compensated transmission
lines is proposed in this paper. The algorithm uses the DWT to detect and classify the fault while using
the DWT together with the traveling waves to locate the fault. In this paper, the fault can be detected
and classified in 1 ms. The algorithm is tested for different types and conditions of faults. The
algorithm succeeded in all types of faults. This algorithm is reliable in detecting the downed
conductor location using double-ended traveling waves algorithm with the aid of DWT. The faults are
located with relatively low error (1 % maximum error for 200 km line). The algorithm is robust and
can discriminate between faults and switching operations.
6
0 2000 4000 6000 8000 10000
-5000
0
5000
m
o
d
a
l
s
i
g
n
a
l
(
s
e
n
d
i
n
g
e
n
d
)
,
A
(a)
0 2000 4000 6000 8000 10000
-1
0
1
x10
4
m
o
d
a
l
s
i
g
n
a
l
(
r
e
c
e
i
v
i
n
g
e
n
d
)
,
A
(b)
0 2000 4000 6000 8000 10000
-5
0
5
d
1
(
s
e
n
d
i
n
g
e
n
d
)
,
A
(c)
0 2000 4000 6000 8000 10000
-20
0
20
d
1
(
r
e
c
e
i
v
i
n
g
e
n
d
)
,
A
(d) sample number
G1 G2
F1
1
t
2
t
S R
MOV
fault
inception time
Fig. 11 Fault generated traveling waves.
Fig. 12. An a-g fault 130 km from end S (a)
sending end modal signal (b) receiving end modal
signal (c) d1 of DWT decomposition of sending
end modal signal (d) d1 of DWT decomposition of
receiving end modal signal.
Table II: Fault distance Calculation
Fault type
Fault distance from
end S (km)
Fault
impedance
()
t1-t2 (sec)
Calculated distance
from end S (km)
Percentage
Error
c-g 80 200 0.00013 85.5 0.625
a-g 195 100 -0.00064 196 0.513
b-g 130 120 -0.0002 130 0
bc-g 180 100 -0.00053 197.5 0.2778
ab 110 0.1 -0.00007 110.5 0.4545
abc 95 0.1 0.00004 94 1.05
BIBLIOGRAPHY
[1] J. D. Glover and M. Sarma, Power System Analysis and Design. Boston: PWS Publishing Company, 1994.
[2] H. Saadat, Power System Analysis. New York: McGrew-Hill, 1999.
[3] E. C. Senger, W. Kaiser, J. C. Santos, P. M. S. Burt, and C. V. S. Malagodi, "Broken conductors protection
system using carrier communication," IEEE Trans. Power Del., vol. 15, no. 2, pp. 525-530, 2000.
[4] B. D. Russell, K. Mehta, and R. P. Chinchali, "An arcing fault detection technique using low frequency
current components-performance evaluation using recorded field data," IEEE Trans. Power Del., vol. 3, no.
4, pp. 1493-1500, 1988.
[5] A. F. Sultan, G. W. Swift, and D. J. Fedirchuk, "Detecting arcing downed-wires using fault current flicker
and half-cycle asymmetry," IEEE Trans. Power Del., vol. 9,no.1, pp. 461-470, 1994.
[6] A. A. Girgis, W. Chang, and E. B. Makram, "Analysis of high-impedance fault generated signals using a
Kalman filtering approach," IEEE Trans. Power Del., vol. 5,no. 4, pp. 1714-1724, 1990.
[7] A. E. B. Abu-Elanien and M. M. A. Salama, "A Wavelet-ANN Technique for Locating Switched Capacitors
in Distribution Systems," IEEE Trans. Power Del. vol. 24, no.1, pp. 400-409, 2009.
[8] A. I. Megahed, A. M. Moussa, and A. E. Bayoumy, "Usage of wavelet transform in the protection of series-
compensated transmission lines," IEEE Trans. Power Del., vol. 21,no. 3, pp. 1213-1221, 2006.
[9] D. W. P. Thomas and C. Christopoulos, "Ultra-high speed protection of series compensated lines," IEEE
Trans. Power Del., vol. 7, no.1, pp. 139-145, 1992.
[10] H. Lee and A. M. Mousa, "GPS travelling wave fault locator systems: investigation into the anomalous
measurements related to lightning strikes," IEEE Trans. Power Del., vol. 11,no. 3, pp. 1214-1223, 1996.
7