Which facilities does SIPROTEC 4 offer ? Which facilities does SIPROTEC 4 offer ?
IEC-Interface
The "VDEW-interface " is international standard IEC 60870-5-103 (without parameterizing)
A di t d ti f VDEW it hi ti ibl According to recommendation of VDEW switching operations are possible
PROFIBUS-Interface
PROFIBUS FMS i t l hi h i l d ll f ti E ll t i j ti ith PROFIBUS FMS is a protocol which includes all functions. Excellent in conjunction with
SICAM
PROFIBUS DP a protocol for simpler applications in conjunction with automatization
s stems for ind strial application systems for industrial application.
Additional interfaces
Modbus Modbus
DNP 3
...........
Energy Sector Energy Automation
Siemens AG 2008
Which features does SIPROTEC 4 offer? Which features does SIPROTEC 4 offer?
variable interfaces
as fibre optics or electrical
exchangeable
refittable
Energy Sector Energy Automation
Siemens AG 2008
Seite 3 27.02.2013
Communication: Setup with IEC 60870-5-103
To load dispatcher
Communication: Setup with IEC 60870 5 103
To load dispatcher
SICAM SCADA
STATION
IEC 60870-5-103 e.g. RS 485
IEC 60870-5-103 z.B, point to point
Energy Sector Energy Automation
Siemens AG 2008
Seite 4 27.02.2013
Select the communication interfaces Select the communication interfaces
Energy Sector Energy Automation
Siemens AG 2008
Seite 5 27.02.2013
Set the IEC address Set the IEC address
Energy Sector Energy Automation
Siemens AG 2008
Seite 6 27.02.2013
IEC Parameter IEC Parameter
Energy Sector Energy Automation
Siemens AG 2008
Seite 7 27.02.2013
Masking with IEC protocol Masking with IEC protocol
X
Energy Sector Energy Automation
Siemens AG 2008
Seite 8 27.02.2013
Communication: Setup with Profibus FMS
To Load dispatcher
Communication: Setup with Profibus FMS
DIGSI 4
To Load dispatcher
SICAM
SUB-STATION
SICAM
Profibus FMS
Energy Sector Energy Automation
Siemens AG 2008
Seite 9 27.02.2013
Setting the communication interface Setting the communication interface
Energy Sector Energy Automation
Siemens AG 2008
Seite 10 27.02.2013
Setting of the Profibus FMS Addresses Setting of the Profibus FMS Addresses
PROFIBUS FMS (SICAM SAS)
PROFIBUS FMS (DIGSI 4 via PC)
Energy Sector Energy Automation
Siemens AG 2008
Seite 11 27.02.2013
FMS Parameters on PC FMS Parameters on PC
Energy Sector Energy Automation
Siemens AG 2008
Seite 12 27.02.2013
FMS Parameters at the device FMS Parameters at the device
Energy Sector Energy Automation
Siemens AG 2008
Seite 13 27.02.2013
Masking with FMS Protocol Masking with FMS Protocol
X
X
Energy Sector Energy Automation
Siemens AG 2008
Seite 14 27.02.2013
Communication: Setup with additional protocols
P fib DP
To load dispatcher
e.g. Profibus DP
To load dispatcher
SIMATIC S7
STATION
SIMATIC S7
e.g Profibus DP
Energy Sector Energy Automation
Siemens AG 2008
Seite 15 27.02.2013
Additional protocols e.g. Profibus DP Additional protocols e.g. Profibus DP
Energy Sector Energy Automation
Siemens AG 2008
Seite 16 27.02.2013
Additional Protocols
S l t th M i fil d Add Select the Mapping-file and Address
Energy Sector Energy Automation
Siemens AG 2008
Seite 17 27.02.2013
Additional Protocols e.g. Profibus DP
7SJ6 St d d i 3 1 bi 3 4 7SJ6-Standardmapping 3-1 bis 3-4
Output 7 7 8 3 Double commands
29 29 24 5 Single commands
Input 7 7 8 3 Double annunciations
146 114 64 26 Single annunciations
25 10 21 8 Measurement values
6 2 6 2 counter values 6 2 6 2 counter values
2 1 1 0 value annunciations
9 9 8 2 Bytes Output
The volume of the data objects which are offered via Profibus DP
100 48 80 28 Bytes Input
The volume of the data-objects which are offered via Profibus-DP
(Number of the Commands, Annunciations, Measuring values, Counter
values in Output- resp. Input direction) is exclusively determined by the
selection of a Standardmapping.
Energy Sector Energy Automation
Siemens AG 2008
Seite 18 27.02.2013
pp g
Marshalling of Informations Marshalling of Informations
Energy Sector Energy Automation
Siemens AG 2008
Seite 19 27.02.2013
Scaling of Measuring Values Scaling of Measuring Values
Energy Sector Energy Automation
Siemens AG 2008
Seite 20 27.02.2013
Communication: Setup via Service Interface C
To Load Dispatcher
Communication: Setup via Service Interface C
To Load Dispatcher
DIGSI 4
Office
c

p
h
o
n
e

c
o
n
n
.
STATION
P
u
b
l
i
c
IEC 870-5
Modem
STATION
Energy Sector Energy Automation
Siemens AG 2008
Seite 21 27.02.2013
DIGSI 4 for Remote communication
i S i I t f via Service Interface
Energy Sector Energy Automation
Siemens AG 2008
Seite 22 27.02.2013
Communication: Setup via Operator Interface
To Load Dispatcher
Communication: Setup via Operator Interface
To Load Dispatcher
STATION
DIGSI 4
IEC 870-5
Energy Sector Energy Automation
Siemens AG 2008
Seite 23 27.02.2013
DIGSI 4 via Operator Interface DIGSI 4 via Operator Interface
Energy Sector Energy Automation
Siemens AG 2008
Seite 24 27.02.2013