TRANSFORMER DATASHEET

A BB 1/3

Reference n. 12Q1704200

Rated Power [kVA] 16000 / 20000
Cooling system ONAN /ONAF
Voltage ratio [kV] 33 / 11


Brief description of transformer

Core

Core is three limbs type, manufactured using cold rolled low losses material. Sheets are cutted at 45 and
overlapped. Depending from core dimensions and design, core cooling channels are provided. Thickness of core
sheets can be 0.30, 0.27 or 0.23mm, depending from material used.
Top and bottom jokes are pressed by steel made core clamps. Upper and lower clamps are connected by tie
rods. Core is insulated from core clamping system.

Windings

Windings are concentric type, made by high quality electrolytic copper. According to power, application and
design, windings can be foil, multilayer (single strand or CTC conductor), helical or disc. Oil ducts between
windings and conductors are provided in order to assure a proper cooling.

Tank and conservator

Tank is able to withstand full vacuum. Radiators are attached to the tank with shut off valves.

Transformer cover is bolted. Active part is attached under transformer lid.
Oil thight is assured by synthetic rubber gasket between tank and cover.

Conservator contains two compartments, one for oil in the main tank and the other for the oil of the on load tap
changer. Both compartments are provided with silicagel breather in order to avoid oil moisture contamination. Main
tank is provided with n. 4 lifting hooks and n. 8 jacking lugs.

Surface treatment

Internal tank: painted with oil resistant coating.
External tank: Painting cycle according to ISO 12944-5 C3-M.
Radiators: Painting cycle according to ISO 12944-5 C3-M.
All metallic parts are sandblasted before painting.

Tap Changer

Transformer is equipped with an on load tap changer on HV side.
Tapping range i s 33 (+4;-12x1.25%) in 16 / 17 steps. Step voltage i s 1.25%.
On load tap changer is in tank type with separate compartment for diverter switch. Tap changer is equipped
with separate conservator and protective relay. Tap changer motor drive unit contains circuits for tap changer
control and signals.



S.p.A.
BUDGET OFFER ONLY FOR DISCUSSION
12Q1704200 Issued by RS
20.09.2012 Rev. 00 Checked by PT
TRANSFORMER DATASHEET

A BB 2/3

Main accessories


- Primary side bushings 3x COMEM 52/1250A
- Secondary side bushings 4x COMEM 24/2000A

- Tap changer type On-load
main accessories Tap changer conservator with silicagel
breather
Oil level indicator with n. 2 contacts
Comem type
protective relay

- Buchholz relay with n. 2 contacts
- Pressure Relief Device with n. 1 contact
- Oil level indicator for main tank conservator with n. 2 contacts
- Oil temperature indicator with n. 2 contacts
- Silicagel breather
- Filter valve
- Oil drain valve
- Oil sampling valves
- Rating plate according IEC standard


Supply Voltages

- OLTC Motor 400VAC 50Hz 3ph
- OLTC Control 110VAC 50Hz 1ph
- Fans 400VAC 50Hz 1ph
- Heaters 230VAC 50Hz 1ph


Connecti ons

- Primary side Air filled cable box, top mounted, bottom entry.
- Secondary side Air filled cable box, top mounted, bottom entry.




S.p.A.
BUDGET OFFER ONLY FOR DISCUSSION
12Q1704200 Issued by RS
20.09.2012 Rev. 00 Checked by PT
TRANSFORMER DATASHEET

A BB 3/3

Technical datasheet

Rated data
Rev. index
Rated power [kVA] 16000 / 20000

Cooling system ONAN / ONAF

Voltage ratio [kV] 33 +4;-12 x1.25% / 11

Vector group Dyn11


Frequency [Hz] 50

Type of flux voltage variation CFVV

Insulation fluid
Mineral oil
Nynas Nytro Libra



Environment


Maximum ambient temperature [C] 50

Top oil temperature rise [K] 55

Average windings temperature rise [K] 50

Hot spot temperature rise [K] 68

Altitude [m] <1000

Insulation class A

Transformer location Outdoor


Guaranteed values


No load losses [W] 13000 +IEC tolerance

Load losses at rated power nominal ratio at 20MVA [W] 130000 +IEC tolerance

Short circuit impedance at 20MVA and nom voltage ratio [%] 12.5 IEC tolerance


Insul ation levels

HV HVN LV LVN
Nominal voltage, Um [kV] 36 - 12 12
Lightning impulse, LI [kV] 200 - 110 110
Applied voltage, AC [kV] 70 - 28 28

Bushings

Rated voltage [kV] 52 - 24 24
Rated current [A] 1250 - 2000 2000
Lightning impulse [kV] 250 - 125 125
Applied Voltage [kV] 95 - 50 50

Prel iminary dimensions and weights

Oil [kg] 8000
Untanking mass [kg] 18000
Total weight [kg] 35000

Length [mm] 6500
Width [mm] 4900
Height [mm] 4700

Documentation used to prepare the offer

- No documentation has been considered


Notes/Remarks
- References to documents not listed above have not been considered.
- Only routine tests according to IEC Standard are included in this offer. All other tests will be quoted separately.
- Penalty for transformers will be applied after IEC tolerances for all losses.
- Only accessories specified above are included in this offer.
- Cable glands, NER, CTs, AVR, RTCCP, etc are not included in this offer.
- This is a budget quotation. It is not binding for ABB.