) ( 5 . 0 cot ln 60
1
H
R
tg g Z
t
(1.2)
The wave propagation velocity is taken that oI the light C3x10 m/s or 3x10 Km /s.
According to the above calculations the tower top has a characteristic impedance ZT1214.04 O
which mean that the tower top structure has linear resistance according to the (1.3) Iormula and
the speciIied section has a total resistance according to the (1.4) Iorm.
) / (
ln 2
3 2 1
1
1
m
l l l
Z
r
T
O
+ +
=
(1.3)
) ( , ) ( , ) (
3 1 3 2 1 2 1 1 1
O = O = O = l r R l r R l r R (1.4)
The tower model is divided into sections according to her structure, in which except wave
impedance are placed the RL sections representing the overvoltage traveling wave attenuation.
Let`s calculate the inductances in each tower section which is related to the time it takes to the
traveling wave to cross the total tower height. At the beginning we Iind the traveling time x and
International Students Conference of Civil Engineering, ISCCE 2012, 10-11 Mav 2012, Epoka Universitv, Tirana, Albania
the inductances. This calculation is made Ior the tower top and is repeated Ior each separate
tower according to his length.
j s
J
H
=
2
(1.5)
) ( , ) (
2 3 2 1 1
mH R L L mH R L = = = (1.6)
Eor the tower bottom we calculate:
) (
ln 2
4
4
4
4
O
= l
l
Z
R
T
(1.7)
) (
4 4
mH R L = (1.8)
Table 1. Summary table of the line towers parameters
Fig. 5 Tower model with
constant distributed parameters
Tower parameters
Tower
No.1
h17m
Tower
No.2
h19m
Tower
No.3
h21m
Time constant x 0.2233s 0.21 s 0.1967 s
Resistance R O
R1 20.153 20.153 20.153
R2 14.146 14.146 14.146
R3 14.146 14.146 14.146
R4 42.5 40.256 39.228
Tower inductance
mH
L1 4.5 4.232 3.963
L2 3.1587 2.97 2.7825
L3 3.1587 2.97 2.7825
L4 9.49 8.454 7.716
Grounding resistance Ro
and soil resistivity
9 O
o400Om
8.5 O
o400
Om
3.3 O
o5 Om
Grounding resistance
taking into account soil
ionization Rf
8.175 7.796 2.019
The tower surge impedance
Tower top
(is equal Ior both the 3
towers)
Tower top surge impedance
217.04 (O)
Tower bottom which
changes according to the
tower height
Tower bottom surge
impedance
Z (O)
21 (m)
182.40 (O)
19 (m) 180.35 (O)
17 (m) 175.75 (O)
International Students Conference of Civil Engineering, ISCCE 2012, 10-11 Mav 2012, Epoka Universitv, Tirana, Albania
2. Calculation of tower parameters and reactances
In the beginning are givenn the contuctor and opgw earth wire characterirctic
After performing the calculations we are comparing the results of the handmade calculations
with the ones from the line check command with the A1P Software:
a) First span e400Oxm L178m
b) Second span e5Oxm L307.3m
Conductor ACSR 120/20mm OPGW 60mm
Aluminum cross Section 120.05mm Total cross section 64mm
Total cross section 141.4mm Diameter 10.8mm
Diameter 15.5mm Unit weight per Km 385Kg/Km
Rated tensile strength 44500N Module oI elasticity 162kN/mm
Resistance at 20C 0.2376O/Km DC resistance ( T20C ) 0.93/Km
Line Parameters
for the first span e400Oxm
Results taken from the
handmade Calculations
Result taken from the
line check command in
ATP (J Marti) Method
Z
S
e
l
f
i
m
p
e
d
a
n
c
e
Positive sequence impedance
Z10.0423i0.077 O
L1: 0.0221i0.0736 O
L2: 0.0224i0.0744 O
Zero sequence impedance
single circuit without earth
wire
Z00.0386i0.247 O
L1: 0.0386i0.247 O
L2: 0.0386i0.2466 O
Zero sequence impedance oI
earth wire
ZEE0.0423i0.077 O 0.0618i0.1442 O
Z
.
m
u
t
u
a
l
i
m
p
.
Mutual impedance between
circuit and earth wire
ZCE0.088i0.0595 O
L1L3: 0.007i0.04 O
L2L3: 0.007i0.04 O
Mutual impedance between
line circuits
ZC1C20.0112i0.0614 O L1L2:0.0165i0.1502O
Line Parameters
for the first span e400Oxm
Results taken from the
handmade Calculations
Result taken from the
line check command in
ATP (J Marti) Method
Z
S
e
l
f
i
m
p
e
d
a
n
c
e
Positive sequence
impedance
Z10.0841i0.133 O
L1: 0.0365i0.127 O
L2: 0.036 i0.1172 O
Zero sequence impedance
single circuit without earth
wire
Z00.1185i0.367 O
L1: 0.072 i0.3394 O
L2: 0.0386i0.2466 O
Zero sequence impedance
oI earth wire
ZEE0.3i0.252 O ZEE 0.101i0.2274 O
Z
.
m
u
t
u
a
l
i
m
p
e
d
a
n
c
e
Mutual impedance between
circuit and earth wire
ZCE0.01515i0.06045 O
L1E: 0.004i0.0461 O
L2E: 0.006i0.0434 O
Mutual impedance between
line circuits
ZL1L20.0193i0.06373 O L1L2: 0.0348i0.1733 O
International Students Conference of Civil Engineering, ISCCE 2012, 10-11 Mav 2012, Epoka Universitv, Tirana, Albania
3. Simulations of the line insulation applying different lighting strokes on the line.
Fig. 6 Double circuit overhead line modeled in ATP software
AIter the whole system (lines, generators, insulation and other elements) had been
modeled in ATP we start making simulations on this system.
First we apply a current of 1kA in order to simulate a lighting stroke in the earth wire of the
first tower. In our insulation model that we have created we have put a minimal Ilashover
voltage oI 520kV so in order to happen this Ilashover the voltage applied in the phase insulator
must be more than 520kV, and Irom the graphics (Eig. 7) oI the voltage applied on the line
insulators, created by the ATP soItware we see that the Ilashover did not happened because the
conditioned implemented in the Ilash model was not IulIilled.
(f ile Exa_99n. pl4; x-v ar t ) v : XX0047-L11A v : XX0049-L11B v : XX0052-L11C
0 5 10 15 20 25 [us]
-150
-50
50
150
250
350
450
550
[kV]
(f ile Exa_99n. pl4; x-v ar t ) c: XX0047-L11A c: XX0049-L11B c: XX0052-L11C
0 5 10 15 20 25 [us]
-1
0
1
[A]
Fig.7 Applied voltage on insulator strings 10kA Fig.8 Current Jalues on insulator strings. 10kA
In the second simulation we apply a current of 15kA for simulating a stronger lighting stroke
and we see again the voltage and current on the line insulators
(f ile Ex a_99n. pl4; x -v ar t ) v : XX0047-L11A v : XX0049-L11B v : XX0052-L11C
0 5 10 15 20 25 [us]
-400
-200
0
200
400
600
[kV]
(f ile Ex a_99n. pl4; x -v ar t ) c : XX0047-L11A c : XX0049-L11B c : XX0052-L11C
0 5 10 15 20 25 [us ]
0
500
1000
1500
2000
2500
[A ]
Fi.g 9 Applied voltages on insulator strings 10kA Fi.g 10 Current Jalues on insulator strings 15kA
International Students Conference of Civil Engineering, ISCCE 2012, 10-11 Mav 2012, Epoka Universitv, Tirana, Albania
As was predicted beIore Irom the initial conditions the Ilashover happens in the insulators oI the
B phase (Eig. 9) oI the Iirst circuit with a Ilashover current oI 2140A (Eig. 10).
Aow let us apply a current impulse of kA and see the behavior of the elements on the
circuit. In the line insulators we will have the following voltages and currents:
(f ile Exa_99n.pl4; x-v ar t) v :XX0047-L11A v :XX0049-L11B v :XX0052-L11C
0 5 10 15 20 25 [us]
-100
0
100
200
300
400
500
600
[kV]
(f ile Exa_99n.pl4; x-v ar t) c:XX0047-L11A c:XX0049-L11B c:XX0052-L11C
0 5 10 15 20 25 [us]
-2
0
2
4
6
8
10
[kA]
Fig. 11 Applied voltage on insulator strings 60kA Fig. 12 Current Jalues on insulator strings 60kA
Watching the voltages and the currents on the line insulators we notice that the Ilashover has
happened on all the insulators oI the Iirst circuit oI the line (Eig. 11 and Eig. 12).
By monitoring the surge arrester in Iront oI the transIormers we see that also the surge arrester oI
the A phases has Ilashed with a discharging current oI 14kA. (Eig.13)
(f ile Exa_99n.pl4; x-v ar t) c:X0001A- c:X0001B- c:X0001C-
0 5 10 15 20 25 [us]
0
3
6
9
12
15
[kA]
(f ile Exa_99n.pl4; x-v ar t) v :L11A v :L21A v :L1A
0 5 10 15 20 25 [us]
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
[MV]
Fig. 13 Current on transformer surge arresters Fig. 14 Traveling wave during the overhead line
We also look at the overvoltage traveling wave (Eig. 14) where we see the decrease in amplitude
oI the overvoltage wave approaching to the substation gantry.
We see that in the A phase where the current impulse is applied the voltage value is 2.7MV and
in the third tower beIore the gantry this overvoltage amplitude has decreased to 1.15MV.
While the B phase has an amplitude oI 600kV only, this explains why has Ilashed only the A
phase oI the surge arrester in Iront oI the transIormer.
International Students Conference of Civil Engineering, ISCCE 2012, 10-11 Mav 2012, Epoka Universitv, Tirana, Albania
We are making a summary table of the results from the simulations made above and the
results from the graphics of the ATP software:
CONCLUSIONS:
1- Eor small currents oI lighting strokes applied in the earth wire because oI the initial
conditions happens Iirst the Ilashover oI the insulators oI the B phase.
2- The surge arresters installed in Iront oI the transIormers start working Ior lighting strokes
oI currents near 60kA
3- The minimal Value oI the current oI the lighting stroke Ior which the insulators Ilashover
happens is 15kA
REFERENCES:
Masaru Ishii, Tatsuo Kawamura, Teruya Kouno, Eiichi Ohsaki, Kazuyuki Shiokawa Kaneyoshi
Murotani and Takemitsu Higuchi, 'Multistory transmission Tower Model Eor Lightning Surge
Analysis, IEEE Transactions on Power Delivery ,Vol. 6, No. 3, July 1991
J. A. Martinez, and E. Castro-Aranda, 'Lightning PerIormance Analysis oI Transmission Lines
Using the EMTP, IEEE Transmission,2003
M. Kizilcay, C. Neumann, 'Back Ilashover Analysis Ior 110-kV Lines at Multi-Circuit Overhead
Line Towers, 'Presented at the International ConIerence on Power Systems Transients (IPST`07)
in Lyon, Erance on June 4-7, 2007
Simulation Case
Did the
flashover
happen?
Did the
surge arrester
flashed?
Voltage values at
the substation
gantry`s form the
first circuit L1
Voltage values at
the substation
gantry`s form the
second circuit L2
Phase Phase
Lighting stroke oI
10kA in the earth
wire oI the Iirst
tower
No No
A B C A B C
67.4
KV
286
KV
-58.1
KV
74.6
KV
209
KV
-46.9
KV
Lighting stroke oI
15kA in the earth
wire oI the Iirst
tower
Yes. In the B
phase oI the Iirst
circuit oI the Iirst
tower
NO
308
kV
78.9
kV
-45.5
kV
87.5
kV
221
kV
-34.4
kV
Lighting stroke oI
60 kA in the earth
wire oI the Iirst
tower
Yes. In the Iirst
Circuit Phase A,
B, C at tower
No1 and Phase A
and B at tower
No2 and also in
the second
circuit phase A
at tower No 2.
Yes.
Only the
Surge arrester
oI
the A Phase
1.14
MV
0.71
MV
0.263
MV
1.14
MV
0.3
MV
0.584
MV