Schedule K

TECHNICAL PARTICULARS FOR DRY TYPE POWER TRANSFORMERS
Revision 2
A. DRY TYPE POWER
TRANSFORMERS


1.0 General :
1.1 Make : Voltamp Transformers Ltd.
1.2 Type : Cast Resin Encapsulated Dry
1.3 Number of Windings per phase : Two
1.4 Number of Phases : Three
1.5 Service / Duty Indoor / Continuous
1.6 Reference Standard : IS : 11171
2.0 Rating :
2.1 Type of Cooling : AN
2.2 Rated Output MVA : 1.6
2.3 Rated Voltage (No-Load) kV
H.V. : 6.6 (+/-10%)
L.V. : 0.433
2.4 Rated Current A
H.V. : 139.96
L.V. : 2133.40
2.5 Rated Frequency Hz : 50 (+/-5%)
2.6 Connection
H.V. : Delta
L.V. : Star
2.7 Vector Group Reference : Dyn11
2.8 Voltage withstand Time s
a. 110% of rated voltage : Continuous
b. 125% of rated voltage : 60 sec
c. 140% of rated voltage : 5 sec
d. 150% of rated voltage : 1 sec
2.9 Overfluxing Capability
a. For Overfluxing Factor 1.1 : Continuous
b. 1.25 : 60 sec
c. 1.4 : 5 sec
3.0 Temperature
3.1 Reference ambient temperature C 50

Project : 2X135 TPP at
Meenakshi Energy
Package:
LV Auxiliary Transformer
Bidders Name:
Voltamp Transformers Ltd.


Page 2 of 9


3.2 Temperture rise over referene
ambient Deg. C :
a. Of winding by resistance


C


70
b. Hot spot temperature limited in
winding
C : 135
3.3 Maximum continuous over loading
capacity of the transformer without
exceeding the specified winding
temperature
: As per IEC-905
3.4 Thermal time constant h Approx. 45 min.
4.0 Tappings
4.1 Type : Off Circuit Tap Switch
4.2 Capacity : Full
4.3 Range - Steps x % variation : +/-5% in steps of 2.5%
4.4 Taps provided on HV/LV Winding : HV side
5.0 Insulation Level
5.1 Separate source power
frequency voltage withstand
kV
RMS

Winding Bushing
H.V : 20 28
L.V. : 3 3
L.V. Neutral (for bushing) : 3 3
5.2 Induced overvoltage withstand kV
RMS

Winding Bushing
H.V :
L.V. :
L.V. Neutral ( for bushing) :

}Twice the rated }voltage and
}double }frequency
5.3 Full wave lightning impulse
withstand voltage
kV
Peak

Winding Bushing
H.V : 60 75
L.V. : NA NA
6.0 Impedance at Principal
Tap at Rated Frequency
and 75C winding temperature
with 100% rating
:
6.1 Impedance at principal tap % : 6.25% (without negative
tolerance with +10% tol.)
6.2 Impedance at maximum voltage
tap
% : 6.70% (Approx.)
6.3 Impedance at minimum voltage tap % 6.30% (Approx.)

Project : 2X135 TPP at
Meenakshi Energy
Package:
LV Auxiliary Transformer
Bidders Name:
Voltamp Transformers Ltd.


Page 3 of 9


6.4 Reactance at rated current for
principal tap
% : 6.154 (Approx)
6.5 Resistance at 75C. % 1.094 (Approx)
6.6 Zero Sequence Impedance at 75
C at principal tap.
% : 6.05% (approx.)
6.7 Capacitance of Windings F /
phase
:
a. H.V. - Earth
b. L.V. - Earth
c. H.V - L.V
: 1.5 nf (Approx.)
2.5nf (Approx.)
500 pf(Approx.)
7.0 Guaranteed Losses at Principal
Tap, Full Load and 75C.

7.1 No load losses at rated voltage
and at rated frequency and without
any +ve tolerances
kW : 2.50 KW (max.)
7.2 Load Losses at rated current
without any +ve tolerances
kW : 17.50 KW (max.)
7.3 Total losses kW : 20.00 KW (max.)
8.0 Efficiency at 75C and 0.8
Power Factor Lag and at unity
power factor
:
0.8 p.f. unity p.f.
8.1 At full load % : 98.46 98.77
8.2 At 3/4 full load % : 98.73 98.98
8.3 At 1/2 full load % : 98.94 99.15
8.4 Maximum efficiency % : 99.18
8.4.1 Load and Power Factor at which it
occures
: 37.79 % at Unity PF
9.0 Regulation at Full Load
at 75C
:
9.1 At unity power factor % : 1.283
9.2 At 0.8 power factor lagging % : 4.658
10.0 No Load Current referred to HV at
rated frequency

10.1 At 90% rated voltage A : Approx. 1% of FLRC
10.2 At 100% rated voltage A : Approx. 2% of FLRC
10.3 At 110% rated voltage A : Approx. 3% of FLRC
11.0 Approximate Maximum Flux
Density

11.1 At 90% rated voltage Wb /
m
2
: 1.485
11.2 At 100% rated voltage Wb /
m
2
: 1.65

Project : 2X135 TPP at
Meenakshi Energy
Package:
LV Auxiliary Transformer
Bidders Name:
Voltamp Transformers Ltd.


Page 4 of 9


11.3 At 110% rated voltage Wb /
m
2
: 1.815
12.0 Maximum Current Density :
12.1 H.V. Winding A /
cm
2
: 240
12.2 L.V. Winding A /
cm
2
: 150
12.3 Maximum Current Density under
short circuit
:
12.3.1 H.V. Winding A /
cm
2
: 3840
12.3.2 L.V. Winding A /
cm
2
: 2400
13.0 Withstand Time without injury
for

13.1 Three phase dead short circuit at
terminal with rated voltage
maintained on the other side
s : 3
13.2 Single phase short-circuit at
terminal with rated voltage
maintained on other side
s : 3
14.0 Core
14.1 Type - Core or shell : Core
14.2 Core material : CRGO silicon steel laminations
14.3 Thickness of lamination mm : 0.27 to 0.3 mm
14.4 Insulation of lamination : Carlite
14.5 Equivalent cross-sectional area cm : 520 cm (Approx.)
14.6 Type of joint between core and
yoke
Mitred interleaved
14.7 Percentage silicon content Approx. 4%
15.0 Coils
15.1 Type of Coil :
a. H.V : Layer
b. L.V. : Foil
15.2 Conductor Material : Electrolytic copper
15.3 Insulating Material :
a. H.V - Turn : Super enamel coating
b. L.V - Earth DMD Paper
c. L.V. - Earth : Resin +Air

Project : 2X135 TPP at
Meenakshi Energy
Package:
LV Auxiliary Transformer
Bidders Name:
Voltamp Transformers Ltd.


Page 5 of 9


d. H.V. - L.V. : DMD Paper+Resin+Air
15.4 Magnetising inrush current A Approx. 8 to 10 times of FLRC
15.5 Magnetising current at rated
frequency and at rated voltage
A Approx. 2% of FLRC
15.6 Conductor area approx

HV

LV

In sq. mm (approx.)

34.00

1530.0

16.0 Off-circuit tap changer details
16.1 Make : ALWAYE
16.2 Type : OCTC
16.3 Rated Voltage class of tap changer kV : 6.6 KV
16.4 Rated Current A : 250 A
16.5 Auxiliary Power kW : NA
16.6 Step voltage V 165 volts
16.7 Number of steps 4
16.8 Control Manual
16.9 Maximum Short Circuit
Current withstand
capability :

a. Current A : Same as transformer
b. Time s : Same as transformer
16.10 Local indicator
furnished for :

a. Tap position : Provided Tap Indication
b. Operation counter : NA
16.11 Number of revolutions
to complete one step
: NA
16.12 Time to complete one
step on Manual
operation
s : NA
16.13 Approximate overall
weight
kg 6030 (Approx)

16.14 Approximate overall
dimensions
mm 2800 x 2800 x 2425 (mm)
(Subject to 5% Tol.
16.15 Whether the following
provisions are
provided?




Project : 2X135 TPP at
Meenakshi Energy
Package:
LV Auxiliary Transformer
Bidders Name:
Voltamp Transformers Ltd.


Page 6 of 9



a) Padlocking

b) Auxiliary switch
for interlocking

c) Safety limit
switch
NA

NA

Provided On HV side openable
doors.

17.0 Bushings (for HV /
LV / LVN)
: HV/ LV/LVN
17.1 Make : HV, LV & LVN BB/CJI/JP/AP
Type : HV Epoxy, LV & LVN
Porcelain
17.3 Reference Standard : IS:2099
17.4 Voltage Class kV : 12/1.1/1.1
17.5 Type of atmosphere : Sea Shore Corrosive & Salt Laden
Atmosphere
17.6 Creepage Distance mm : 25 mm /KV
17.7 Free space required
for bushing removal
: 800 mm
17.8 One minute power
frequency
withstand voltage
kV RMS : 28/5/5
17.9 Impulse withstand
voltage
kV Peak

: 75/NA/NA
17.10 Rated current A 1250/3150/2000
17.11 Rated short circuit
current and duration
kA/
s
HV-40kA for 3 sec.
LV-50kA for 1 sec.
17.12 Cantilever strength of
the bushing
kg As per IS: 2099; 3347
17.13 Weight of the
assembled bushings
kg As per IS: 2099; 3347
17.14 Mounting
arrangement of the
bushing
HV Cable box
LV Bus duct flange
18.0 Minimum Clearance For Transformers & Bushings
18.1 Between Phases :
a. In air
I. HV
ii. LV

mm
mm

:
:

120
25.4
b. In oil
I. HV

mm

:


} NA

Project : 2X135 TPP at
Meenakshi Energy
Package:
LV Auxiliary Transformer
Bidders Name:
Voltamp Transformers Ltd.


Page 7 of 9


18.2 Between Phase & Earth :
a. In air
I. HV
ii. LV

mm
mm

:
:

110
19
b. In oil
I. HV
ii. LV

mm
mm

:
:

}
} NA
18.3 Clearance between
core and coil
mm
18.4 Clearance between
coils
mm
18.5 Clearance between
neutral to ground in
air
mm
7.5 mm


25 mm

20 mm
19.0 Terminal
Connections

19.1 H.V. : Cable box with disconnection
chamber
19.2 L.V : Bus duct flange
19.3 L.V. Neutral : Inside LV bus duct flange
20.0 Marshalling Box
20.1 Weatherproof,
suitable for outdoor
duty
: Yes
20.2 Degree of protection : IPW-55
20.3 Painting shade Siemens Grey, shade RAL 7032
21.0 Terminal Blocks :
21.1 Make : Elemex/ reputed
21.2 Type : KUT 4
21.3 17% spare terminals
furnished?
: Yes
22.0 Wiring
22.1 Cable type : FRLS Cable
22.2 Voltage grade V : 1100
22.3 Conductor Size

Material

Stranded

Nos. & Type of
temperature detector
mm
2



Yes/No.



:
:
:
2.5

Copper

Yes

02nos. per Phase PT-100 Type


Project : 2X135 TPP at
Meenakshi Energy
Package:
LV Auxiliary Transformer
Bidders Name:
Voltamp Transformers Ltd.


Page 8 of 9


23.0 Trip and Alarm
Contacts Ratings
a.Transformer winding
Alarm rating
b.Transformer winding
Trip rating


C

C


125

135
23.1 Voltage V : 220VDC (+10% to -15%)
23.2 Rated :
Making current A : 1A DC
Breaking Current A : 1A DC
24.0 Accessories
Each transformer
furnished with fittings
and accessories as
per specifiation ?
Yes / No : Yes
25.0 Spare Parts



Each transformer
furnished with spare parts
as per specification
: Yes As per Order
26.0 Approximate Overall
Dimension

26.1 Length m :
26.2 Breadth m :
26.3 Height m :
2800mm
2800mm
2425 mm
(Subject to 5% Tolerance)
27.0 Approximate Weights
27.1 Core & Coil Kg 4850 (Approx)
27.2 Total Weight kg. : 6030 (Approx)
28.0 Shipping Data
28.1 Weight of the heaviest
package
kg. : 6030 (Approx)
28.2 Dimension of the largest
package (LxBxH)
mm : 2800x2800x2425 mm(approx.)
28.3 List the parts detached for
the transport
Rollers
28.4 Proposed method of
transportation for the
transformer
By Road
29.0 Tests to be conducted
on each Transformer


Project : 2X135 TPP at
Meenakshi Energy
Package:
LV Auxiliary Transformer
Bidders Name:
Voltamp Transformers Ltd.


Page 9 of 9


29.1 Routine tests as per
specification / relevant
standards will be
provided?
: All routine test as IS :11171
29.2 Core bolt withstand
voltage for 1 minute
kV : 2 kVrms
30 ACCESSORIES
A. NEUTRAL CURENT TRANSFORMER
1.0 General
1.1 Make : Pragti/Alpha
1.2 Type : Resin cast
1.3 Reference Standard : IS:2705
1.4 Use : REF & SEF
2.0 Rating
2.1 C.T.Ratio A : 2500/1A for REF
2.2 Class : 5P20
2.3 Insulation level kVr

kVp
: 1.0 kVrms

NA
2.4 Burden VA : 15
3.0 Insulation Class : E
3.1 Temperature rise at rated
burden
C : 90
4.0 Characteristics 2500/1 A, Class PS for SEF & LV Phase
4.1 Secondary resistance R
CT

at 75C
: NA
4.2 Knee point voltage V
k
V : > 15Rct + 60V
4.3 Excitation current at V
k/2
A . : < 30 mA at Vk/2
5.0 Dimension and Weights
5.1 Dimension (LxBxH) mm : Included
5.2 Weight kg : Included
6.0 Tests) : As per IS:2705
B TEMPERATURE
SCANNER

1 Manufacturer Massibus
2 Range 0-300 Deg.C
3 Accuracy % +/-1%
31 Class of Insulation F
32 Noise Level of the
Transformer
66 dB (Max.)

Project : 2X135 TPP at
Meenakshi Energy
Package:
LV Auxiliary Transformer
Bidders Name:
Voltamp Transformers Ltd.


Page 10 of 9


C ENCLOSURE
1 Material CRCA Sheet
2 Thickness 2.0 mm Minimum
3 Degree of Protection IP 32
Voltamp Reference No. : JN 18589 Revision : 2

Transformer Sr. Nos. JNC 18589/1, JNC 18589/2, JNC 18589/3, JNC 18589/4

Checked & Verified by:
Data Sheet Revision 2