Вы находитесь на странице: 1из 52

Instructions included in this booklet:

IOM # Description Page(s)


461335 CFSD-XXX Series 25
461336 FSD-XXX, DFD-XXX & CFSD-XXX Series 715
461337 OFSD-XXX, ODFD-XXX, OFD-XXX and OSSFD-XXX Series 1627
461666 FSD-3XXV Series 2835
461868 FSDR-XXX, SEFSDR-XXX, & SSFSDR-XXX Models 3642
472477 GFSD Models 43-45
474015 Single Side Retaining Angle 46-51
KIT # 826249
MULTI-BLADE FIRE DAMPERS
DFD / FSD / CFSD / OFSD
INSTALLATION INSTRUCTION BOOKLET
FOR MULTI-BLADE FIRE &
COMBINATION FIRE SMOKE DAMPERS
1
Installation Supplements
Refer to the appropriate Greenheck installation
supplements for special requirements:
Concrete Floor with Steel Deck
Drive Slip Breakaway Connection
Quick Connect Breakaway Connection
Single Side Retaining Angle
Sealant Usage in Conjunction with Fire Rated
Dampers
Smoke Detector Supplement
Resettable Link (RRL)
Open or Close Indicator (OCI)
Safety Warning
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the
job is complete.
Warranty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the shipment date. Any units or parts which
prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not
be responsible for any service work or backcharges
without prior written authorization.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
UL CLASSIFIED (see complete marking on product)
UL CLASSIFIED to Canadian safety standards (see
complete marking on product)
UL Standard 555 & 555S (Classification #R13317)
CFSD models meet the requirements for corridor ceiling
dampers, smoke dampers and combination fire/smoke
dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshal (Listing #3225-0981:106)
and (Listing #3230-0981:105)
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and le a claim with
the nal carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100F (38C).
Document Number 461335
CFSD-XXX SERIES
Corridor Ceiling Dampers
(with factory installed actuator and sleeve)
Installation, Operation and Maintenance Instructions
Electrical Guidelines
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specications.
Safety Caution!
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit caused
by incorrect field wiring. To avoid causing death or serious
bodily harm to building occupants, follow all instructions
carefully. Dampers must close completely to preserve the
integrity of the fire smoke separation.

2
Return to Table of Contents
2 in. x 4 in. wood
or 2 x 2 1/2 in.
steel studs
Retaining angle
(See Section 3)
Grille (supplied by others)
1 in. x 2 1/2 in. 16 ga.
angles either inside
or outside of sleeve
Opening lined with UL
rated 5/8 in. gypsum
board (wood studs only)
Configuration #2
(Actuator in airstream or out of airstream)
Retaining angles
(See Section 3)
2 in. x 4 in. wood
or 2 in x 2 1/2 in.
steel studs
1 in. x 2 1/2 in. 16 ga.
angles either inside or
outside of sleeve
Grille (supplied by others)
Opening lined with UL
rated 5/8 in. gypsum
board (wood studs only)
Configuration #1
(Actuator in airstream only)
Allows access to the actuator through the grille or diffuser.
These instructions cover the installation of CFSD-XXX
leakage rated combination fire/smoke dampers with
factory installed actuators and sleeves in corridor
ceiling applications. These instructions meet the
requirements of UL555, UL555S and the Uniform
Building Code.
There are three different configurations available for
this application. Configurations 1 & 2 apply when the
fire rated ceiling is also the finished ceiling and the
damper is installed behind a grille, register or diffuser.
Configuration 3 applies when the fire rated ceiling is
above the finished ceiling and the grille, register or
diffuser is somewhere below the corridor damper.
1. MAXIMUM SIZES
Corridor dampers have a maximum size of
24 in. W x 24 in. H (610mm x 610mm) and a
minimum size of 8 in. W x 6 in. H. (203mm x
152mm).
2. CLEARANCES REQUIRED BETWEEN CORRIDOR
DAMPER SLEEVES AND CEILING OPENINGS
The interior dimension of the prepared ceiling
opening
should be
1
/4 in. (6mm) larger than the overall size
of the damper and sleeve assembly.
These are total clearances (ignoring fastener
heads) and do not need to be spaced equally
around the damper.
3. SECURING CORRIDOR DAMPER SLEEVES TO FIRE
RATED CEILING OPENINGS
Corridor damper and sleeve assemblies must
be installed in fire rated ceiling openings using
retaining angles on each side of the ceiling as
described below:
Installation of Configurations 1 & 2:
Retaining angles must be a minimum of 20 ga.
(1mm)steel and have a minimum of 1 in. x 1
in. (38mm x 32mm) legs on the ducted side of the
installation and 1 in. x 2 in. (25mm x 64mm) legs
on the diffuser, grille or register side.
The 1 in. x 2 in. (25mm x 64mm) angle may be
mounted with the 2 in. (64mm) leg inside or
outside the sleeve
Installation of Configuration 3:
Retaining angles must be a minimum of 20 ga.
(1mm) steel with 1 in. x 1 in. (38mm x 32mm)
legs.
Retaining angles must be attached to the sleeve
using:
Tack or spot welds
No. 10 sheet metal screws
in. (6mm) bolts and nuts
3/16 in. (5mm) steel pop rivets
The angles must be attached to all 4 sides of the
sleeve with butt joints at each corner. A minimum of
2 attachments are required on each side, top and
bottom. The angles may (but need not) be attached
to each other at the corners.
Retaining angles must cover the clearance space
between the sleeve and the ceiling opening.
Installation - Failure to follow these instructions will void all warranties.
3
Configuration #3
(Actuator in airstream or out of airstream)
Actuator can be installed either above or below ceiling
construction
2 in. x 4 in. wood
or 2 x 2 1/2 in.
steel studs
Retaining angle
(See Section 3)
Retaining angle
(See Section 3)
Opening lined with UL
rated 5/8 in. gypsum
board (wood studs only)
6. PREPARATION OF OPENINGS IN WOOD AND
METAL STUD CORRIDOR CEILINGS
Corridor dampers are rated in ceiling
constructions with a fire resistance rating of one
hour.
Frame openings as shown below. Maximum size
of opening is 24 in. x 24 in. (610mm x 610mm).
See Fig. 1 & 2.
Corridor ceiling must be covered with a minimum
of one sheet of 5/8 in. (16mm) UL rated gypsum
board on both sides.
All construction and fasteners must meet the
requirements of the appropriate corridor ceiling
design. Gypsum panels should be attached , 12
in. (305mm) O.C. maximum, to all stud and runner
flanges surrounding opening with fasteners as
designated by the appropriate corridor ceiling
design.
Steel
studs
2 in. x 4 in.
(nominal)
wood studs
Steel Stud Assembly
Wood Stud Assembly
24 in.
max.
24 in. o.c. max.
24 in.
max.
24 in. o.c. max.
Opening lined
with UL rated
5/8 in. gypsum
board
Steel
studs
2 in. x 4 in.
(nominal)
wood studs
Steel Stud Assembly
Wood Stud Assembly
24 in.
max.
24 in. o.c. max.
24 in.
max.
24 in. o.c. max.
Opening lined
with UL rated
5/8 in. gypsum
board
Fig. 1
Fig. 2
4. DUCT TO SLEEVE CONNECTIONS
Dampers are supplied with sleeves and actuators
from the factory and can be installed without the
need for additional field installed sleeves.
Gauge of factory furnished sleeve determines
the type of duct to sleeve connections required.
Any duct connection other than those breakaway
connections described on page three are
considered rigid. Factory furnished round duct
collars on type R and CR are also considered
breakaway.
5. ACTUATOR CONNECTIONS
Electrical and/or pneumatic connections to
damper actuators should be made in accordance
with wiring and piping diagrams developed in
compliance with the job or project design and
specifications.
4
Traditional Breakaway Style Transverse
Joints
Transverse joints illustrated at right have always
been approved as breakaway connections. SMACNA
testing has also approved the following variations as
breakaway connections.
The breakaway connections shown below (Fig. 3)
can be applied with maximum of (2) #10 sheet metal
screws on each side and on the bottom located in
the center of the slip pocket and penetrating both
sides of the slip pocket.
Transverse joints illustrated can be applied as top
and bottom joints with Drive Slip - side joints in
duct heights up to 20 inches (508mm). See Fig. 4.
Proprietary Flange System Breakaway
Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems (see Fig.
6) are approved as breakaway
connections when installed as
described in the TDC or TDF
addendum to the SMACNA Duct
Construction Standards except
the corners may not be bolted.
Standard 6 in. (152mm) metal clip
may be used with spacing as shown in diagram (see
Fig. 7). 3/8 in. (9.5mm) metal bolts and nuts may be
used to fasten together corner pieces together (see
Fig. 8).
Duct
Sleeve
6
9
7 7
5 5
5 5
6
Std. Clip
Length
C
L
Duct
60 Duct
4 Reqd.
48 Duct
3 Reqd.
36 Duct
3 Reqd.
24 Duct
2 Reqd.
18 Duct &
Smaller
1 Reqd.
Clip Spacing
Typical TDC/TDF
joint
6
Fig. 6
Duct
Sleeve
6
9
7 7
5 5
5 5
6
Std. Clip
Length
C
L
Duct
60 Duct
4 Reqd.
48 Duct
3 Reqd.
36 Duct
3 Reqd.
24 Duct
2 Reqd.
18 Duct &
Smaller
1 Reqd.
Clip Spacing
Typical TDC/TDF
joint
6
Fig. 7
Duct End
Flange
Corner Piece
3/8 in. bolt
(optional)
Fig. 8
Fire Damper Sleeve
Neoprene gasket
between all angles
Flanged system angles
(Attach per
manufacturer's
instructions)
Duct
Do not bolt corners
6 in. long
1
/16in. max.
thickness plastic cleats;
12 in. c-c (min. 1 per side)
Manufactured Flanged System Breakaway
Connections
Flanged connection systems manufactured by
Ductmate, Ward, and Nexus are approved as
breakaway connections when installed as illustrated.
Fig. 5
Round and Oval Duct Breakaway
Connections
Round or flat oval ducts connected to Type R, CR or
CO damper collars may use no. 10 sheet metal screws
as follows:
Ducts to 22 in. (559mm) wide (or dia.) and smaller
may use 3 screws.
Ducts larger than 22 in. (559mm) wide (or dia.) may
use 5 screws.
NOTE: All breakaway connections described may have
duct sealant applied, PA2084T Duct Sealant Adhesive
manufactured by Precision, DP1010 water base duct
sealant manufactured by Design Polymetrics, Grey
Pookie, Ductmate PROseal

or CL Ward S Seal in
accordance with SMACNA recommendations.
Plain S Slip Hemmed S Slip Double S Slip
Inside Slip Joint Standing S Standing S (Alt.)
Standing S (Alt.) Standing S Standing S
(Bar Reinforced) (Angle Reinforced)
Fig. 3
BREAKAWAY CONNECTIONS
Drive Slip Joint
Fig. 4
5
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom Possible Cause Corrective Action
Damper does not
fully open and/or
close
Frame is 'racked' causing blades
to bind on jamb seals
Adjust frame such that it is square and plumb
Actuator linkage loose Close damper, disconnect power, adjust and
tighten linkage
Defective motor Replace
Screws in damper linkage Damper installed too far into wall. Move out
to line as designated on damper label
Contaminants on damper Clean with a non-oil based solvent (see
Damper Maintenance)
RRL or TOR sensor
tripped
Heat Push reset button located on backside of
RRL or TOR
Damper does not
operate
No power supplied to the actuator Add power supply
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary,
use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft
bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such
as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
Actuator manufacturer recommendations.
461335 CFSD Series Rev. 9, March 2013 Copyright 2013 Greenheck Fan Corporation
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specications without
notice.
Specic Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library
under Warranties.

Phone: (715) 359-6171 Fax: (715) 355-2399 E-mail: gfcinfo@greenheck.com Website: www.greenheck.com
Our Commitment
6
Document Number 461336
FSD-XXX, DFD-XXX, DFDTF-XXX
CFSD-XXX, SEDFD-XXX, SEFSD-XXX,
IMO-XXX, AND SSFSD-XXX SERIES
1
1
2 and 3 Hour
Fire & Combination Fire Smoke Dampers
(with factory installed sleeve and actuator)
Vertical and Horizontal Mount
Safety Warning:
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the
job is complete.
Typical Actuator
RRL Control Device
Standard
Warranty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which
prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not
be responsible for any service work or backcharges
without prior written authorization.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
UL CLASSIFIED (see complete marking on prod-
uct)
UL CLASSIFIED to Canadian safety standards
(see complete marking on product)
UL Standard 555 & 555S (Classification #R13317)
FSD-XXX, SEFSD-XXX, SSFSD-XXX, DFD-XXX, SEDFD-
XXX, and CFSD-XXX Series Dampers are intended for
installation in accordance with combination fire smoke
damper requirements established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshal
(Listing #3225-0981:103) & (Listing #3230-0981:104) - FSD
& SSFSD models; (Listing #3225-0981:103) - DFD models;
(Listing #3230-0981:105) & (Listing 3225-0981:106) - CFSD
models
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and le a claim with
the nal carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100F (38C).
Installation, Operation and Maintenance Instructions
Installation Supplements
Refer to the appropriate Greenheck installation supplements
for special requirements:
Concrete Floor with Steel Deck
Drive Slip Breakaway Connection
Field Installed Sleeve
Fire Resistant Ventilated Duct Assembly
Firestop Material
Greenheck Test Switch
Grille Installation
Metal Stud in Shaftwall
No Flow Smoke Detector
Open or Close Indicator
Quick Connect Breakaway Connections
Resettable Link
Sealant Supplement
Single Side Retaining Angle
Single 3-Sided Retaining Angle
Sleeve Extension
Smoke Detector
Tunnel Corridor

7
Return to Table of Contents
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the
re or re smoke damper in, not to, the opening in such a
manner as to prevent distortion and disruption of damper
operation. This is accomplished by allowing the re or re
smoke damper in rated separation openings to expand
and for the connecting duct to separate in the event of the
collapse of the hanging system. The following items will
aid in completing the damper installation in a timely and
effective manner.
1) Check the schedules for proper damper locations
within the building. Visually inspect the damper for
damage and verify that the Reusable Resettable Link
(RRL) is in place or has not activated. Never install a
re damper without the proper UL approved RRL in
place. (RRL is standard control option. These electric
links have a button for resetting.) If damper is furnished
with fusible link, visually inspect the link to verify its not
missing or broken. Replace link as necessary.
2) Lift or handle damper using sleeve or frame. Do not lift
damper using blades or actuators.
3) Damper has label on outside of sleeve indicating a
No Screw area. Do not install screws into this area as
screws may interfere with unexposed blade linkage and
prevent damper blades from opening and/or closing.
4) Damper has label indicating position of damper
and sleeve assembly in the wall. Install accordingly
to comply with manufacturers appropriate UL
Classication le number.
5) Damper must be installed into duct or opening square
and free of twist or other misalignment. Damper must
not be squeezed or stretched into duct or opening. Out
of square, racked, twisted or misaligned installations
can cause excessive leakage and/or torque
requirements to exceed damper/actuator design.
6) Damper and actuator must be kept clean and
protected from dirt, dust and other foreign materials
prior to and after installation. Examples of such foreign
materials include but are not limited to:
a) Mortar dust
b) Drywall dust
c) Firesang materials
d) Wall texture
e) Paint overspray
7) Damper should be sufciently covered as to prevent
overspray if wall texturing or spray painting will be
performed within 5 feet of the damper. Excessive dirt
or foreign material deposits on damper can cause
excessive leakage and/or torque requirements to
exceed damper/actuator design.
8) Caulking is not necessary, nor is it allowed, between
the damper sleeve and the wall or oor opening
(annular space). However, caulking may be applied to
the retaining angles.
9) ACCESS: Suitable access (such that RRLs and
actuators can be maintained, etc.) must be provided
for damper inspection and servicing. Where it is not
possible to achieve sufcient size access, it will be
necessary to install a removable section of duct. (Refer
to NFPA 90A).
10) The Code Authority Having Jurisdiction (AHJ) must
evaluate and provide approval of nal installation
where variations to these instructions are necessary.
Electrical Guidelines
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specications.
Safety Caution!
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit
caused by incorrect field wiring. To avoid causing death
or serious bodily harm to building occupants, follow all
instructions carefully. Dampers must close completely to
preserve the integrity of the fire smoke separation.
Electrical Guidelines
Table of Contents
Pre-Installation Guidelines ................................................................................................................................ 8
Electrical Guidelines .......................................................................................................................................... 8
Installation .....................................................................................................................................................9-14
Clearances Required Between Fire Damper Sleeves and Wall/Floor Openings ............................ 9
Sleeve Length and Wall Thickness .................................. ............................................................9-10
Duct to Sleeve Connections .......................................... .................................................................. 10
Securing the Damper/Sleeve Assembly to Wall and Floor Openings ........................ ................... 10
Actuator Connections ..................................... ................................................................................. 11
Installing Multiple Damper Section Assemblies .............................................................................. 11
Connection and Operation of Temperature Control Devices ......................................................... 12
Recommended Preparation of Openings in Wood and Metal Stud Walls ........................... ..........13
Breakaway Connections ........................................ ......................................................................... 14
Maintenance ..................................................................................................................................................... 15
Troubleshooting ................................................................................................................................................ 15
8
These instructions apply to 1
1
/2 and 3 hour rated combination fire smoke dampers mounted (blades must be horizontal) in: 1)
masonry, block or stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory. Dampers
must be installed in accordance with these instructions to meet the requirements of UL 555 and UL 555S. The installation of the
damper and all duct connections to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard for the
Installation of Air Conditioning and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Damper Installation
Guide, and UL Classifications R13317.
Note: Combination fire smoke dampers are manufactured and labelled for either vertical or horizontal installation. The
dampers must be installed in accordance with labelling.
Installation - Failure to follow these instructions will void all warranties.
Optional blade indicator
and/or electric link.
LINE OF WALL
DO NOT INSTALL SCREWS BETWEEN THESE LINES AROUND ENTIRE DAMPER
Clearance for expansion
(1/4 in. min., 1 1/2 in. max.)
Retaining Angles
(see Section 4)
LIne of Wall
Airow
Detail 1
DO NOT INSTALL SCREWS
BETWEEN THESE LINES
AROUND ENTIRE DAMPER
Access door required on
jackshaft side of damper.
Refer to the latest edition
of NFPA 90A. Jackshaft
Actuator
Damper
Sleeve
Sleeve Length (L)
6 in. max. 16 in. max.
A Dim.
(Distance from
end of sleeve to
face of damper)
458549
T
w
C
L
Dampers may be mounted either vertically or horizontally. Blade axis must always be horizontal.
Fig. 1
1. CLEARANCES REQUIRED BETWEEN FIRE DAMPER
SLEEVES AND WALL/FLOOR OPENINGS
Fire damper and sleeve assemblies expand during periods
of intense heat. Therefore, it is essential that openings in
walls or floors be larger than the fire/smoke damper and
sleeve assembly to allow for this expansion. Minimum
clearances required between the outside of fire damper
sleeve assemblies and wall/floor openings are:
Galvanized steel fire dampers and sleeves:
1
8 in. per
foot (3mm per .3 m) of damper width and
1
8 in. per foot
(3mm per .3 m) height with a minimum clearance of
1
4 in.
(6mm), maximum of 1
1
2 in. (38mm).
Recommended clearances, for width and/or height
dimensions of:
1) 48 in. (1219mm) or less:
1
2 in. (13mm) clearance
2) More than 48 in. (1219mm) and 96 in. (2438mm) or
less: 1 in. (25mm) clearance
3) More than 96 in. (2438mm): 1
1
2 in. (38mm) clearance
Stainless steel fire/smoke dampers and stainless steel
or galvanized sleeves:
3
16 in. per foot (5mm per .3 m) of
damper width and height with a minimum clearance of
1/4 in. (6mm), maximum of 2 in. (51mm).
Recommended clearances, for width and/or height
dimensions of:
1) 48 in. (1219mm) or less:
3
4 in. (19mm) clearance.
These are total clearances (ignoring fastener heads) and
do not need to be equally spaced around the damper.
Refer to Section 4 and Figure 6 for additional installation
considerations.
Example:
A 12 in. x 12 in. (305mm x 305mm) will
require a minimum clearance of 1/4
in. (6mm) width and 1/4 in. (6mm) on
height
A 36 in. x 12 in. (914mm x 305mm)
damper will required a minimum
clearance of 1/2 in. (13mm) on width
and 1/4 in. (13mm) on height.
2. SLEEVE LENGTH AND WALL THICKNESS
Insert the sleeved damper assembly into the prepared
opening, to appropriate depth (refer to label on outside
of sleeve for location of damper in wall; see
Dimension A and Detail 1, Fig. 1).
Recommended maximum and minimum insertion depth
can be exceeded if:
1) The operation of the damper is not impeded and
2) The C
L
of the damper frame remains within the plane
of the wall and
3) Attachments made through the retaining angle do not
penetrate the No Screw area designated on the
damper sleeve.
9
3. DUCT TO SLEEVE CONNECTIONS
Dampers are supplied with sleeves and actuators from
the factory and can be installed without the need for
additional field installed sleeves.
Gauge of factory furnished sleeve determines the
type of duct to sleeve connections required (see table
below). Any duct connection other than the breakaway
connections described on page 7 are considered rigid.
Factory furnished duct collars, type R and O, are also
considered breakaway (see Fig. 2).
Wall or Floor
Sleeve
Duct
Damper
Type B
Wall or Floor
Sleeve
Duct Damper
Type C, R
Type R and O
factory furnished
duct collars qualify
as breakaway
connections.
Fig. 2
Wall Thickness
Dimension (T
W
)
Sleeve Length
Dimension (L)
4 - 6 in.
(102mm - 152mm)
16 in.
(406mm)
7 - 10 in.
(178mm - 254mm)
21 in.
(533mm)
11 - 13 in.
(279mm - 330mm)
24 in.
(610mm)
Sleeve Gauge Duct Dimension
Type of Duct
to Sleeve
Connection
Permitted
14 ga. (0.075 in.)
- 10 ga. (0.138
in.)
[2mm - 3.5mm]
All duct sizes
Rigid or
Breakaway
16 ga. (0.060 in.)
[1.5mm]
36 in. (914mm) max. width
24 in. (610mm) max.
height
24 in. (610mm) diameter
Rigid or
Breakaway
16 ga. (0.060 in.)
[1.5mm]
All duct sizes
Breakaway only
18 ga. (0.048 in.)
[1.2mm]
85 in. (2159mm) wide and
over
20 ga. (0.036 in.)
[0.9mm]
55 in. - 84 in. wide
(1397mm - 2134mm)
22 ga. (.030 in.)
[0.76mm]
31 in. - 54 in. wide
(787mm - 1372mm)
24 ga. (0.024)
[0.6mm]
13 in. - 30 in. wide
(330mm - 762mm)
26 ga. (0.018 in.)
[0.46mm]
12 in. wide and under
(305mm)
See page 7 for additional information on breakaway sleeve connections.
Sleeve thickness must not be less than the gauge of the connecting duct.
UL Standard 555 requires all ducts to terminate at re damper sleeves.
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO
WALL AND FLOOR OPENINGS (for single side retaining
angle instructions, see supplements)
Damper/sleeve assemblies must be installed in wall and
floor openings using retaining angles on at least one side
of the wall or floor as described below:
Retaining angles for 1 hour rated dampers with a
width and height 48 in. (1219mm) or less must be a
minimum of 20 ga. (1mm). Retaining angles for all 3 hour
rated dampers and all dampers with a width or height
greater than 48 in. (1219mm) must be a minimum of 16
gauge (1.5mm). The leg of the retaining angle on the
damper sleeve shall be a minimum of 1 in. (32mm).
The leg of the retaining angle on the wall/floor shall be
long enough to cover the annular space and overlap the
wall/floor by a minimum of 1 in. (25mm).
Retaining angles must be attached to the damper using
one or more of the following methods of attachment
(refer to label on outside of sleeve for No Screw area):
Tack or spot welds
#10 (
3
/4 in. [19mm] max.) sheet metal screws

1
/4 in. (6mm) bolts and nuts

3
/16 in. (5mm) steel pop rivets
A minimum of two connections per side, top, and bottom,
12 in. (305mm) O.C. maximum for openings of
48 in. W x 36 in. H (1219mm x 914mm) and less, and 6 in.
(152mm) O.C. for openings 80 in. W x 50 in. H
(2032mm x 1270mm), 50 in. W x 72 in. H (1270mm x
1829mm), and 40 in. W x 72 in. H (1016mm x 1829mm)
or less. The angles must be attached to all 4 sides of the
sleeve. Ensure that attachment device does not interfere
with the operation of the damper and the free movement
of the damper blades. The angles need not be attached
to each other at the corners. Do not secure the retaining
angle to the fire separation (see Fig. 3).
Retaining angles should not be fastened to the wall/
floor material. The angles should only sandwich the
wall/floor and allow for damper expansion during
periods of intense heat.
IMPORTANT SAFETY DANGER! : To avoid causing
death or serious bodily harm to building occupants, do
not penetrate the No Screw area designated on the
damper sleeve or the damper may not close properly.
The sleeve may extend a maximum of 16 in. (406mm)
beyond the wall or floor on the actuator side of the
damper and a maximum of 6 in. on the opposite side.
Recommended standard sleeve lengths for various wall
thicknesses are:
10
Horizontal Mount
Damper Model
Maximum Single
Section Size
Maximum Over-
all Size for
Multi-Section
Dampers
CFSD-211, 212 24 x 24 NA
DFD-210 36 x 36 or 32 x 50 64 x 50
DFD-230 36 x 36 or 32 x 48 64 x 48
DFDAF-310 32 x 50 96 x 50
DFDTF-210
32 x 36 96 x 72
32 x 48 64 x 48 or 32 x 96
FSD-211, 212, 213 36 x 48 or 32 x 50 144 x 96
FSD-231 36 x 36 or 32 x 48 72 x 48
FSD-311, 311M, 312,
312M
32 x 50 96 x 50
IMO-310 32 x 50 NA
IMO-311 32 x 50 NA
SEDFD-210, SEFSD-
211
24 x 30 48 x 30
SSFSD-211 24 x 30 48 x 30
2 in. M
ax.
6 in. M
ax.
Sleeve
Retaining
Angle
Damper
Duct
Min. 1 in.
Overlap*
Wall or
Floor
Retaining
Angle
*only applicable for damper sizes above 36 in. x 36 in.
6 in. M
ax.
2 in. M
ax.

Both vertical and horizontal damper installations are typified by these
drawings. Fig. 3
5. ACTUATOR CONNECTIONS
Electrical and/or pneumatic connections to damper
actuators should be made in accordance with wiring and
piping diagrams developed in compliance with applicable
codes, ordinances and regulations (see Electrical
Guidelines).
6. INSTALLING MULTIPLE DAMPER SECTION
ASSEMBLIES
A damper assembly is not restricted to a maximum
number of sections, but must not exceed the section
sizes and overall sizes shown (see chart).
Two section high dampers require reinforcement using a
14 gauge (2mm), 5 in. (127mm) wide mullion as shown in
Fig. 4 below, or two individually sleeved units stacked
vertically, shown below in Fig. 5. When using two
individually sleeved units, the sleeve acts as the mullion,
therefore no mullion is required.
The damper sections must be attached together with
#10 (
3
/4 in. max. [19mm]) sheet metal screws,
1
/4 in. (6mm)
diameter nuts and bolts, tack or spot welds, or
3
/16 in.
(48mm) diameter steel pop rivets. Attachments must be
spaced a minimum of 6 in. (152mm) on centers and a
maximum of 2 in. (51mm) from corners. Attachments must
be made on front face and back face (air entering and air
exiting side) of damper sections.
Note: Dampers ordered for individual installation may
not be installed together. The full assembly size must be
specified at the time the dampers are ordered.
14 ga.
5 in. wide
support
mullion
Fig. 4
Fig. 5
Single Sleeve Around Outside with
Support Mullion
Two Individually Sleeved Units
with No Mullions
NOTE: FSD model dampers fitted with a fusible link closure
device are limited to single section sizes. Dampers with a
fusible link and spring assembly closure device may not be
used for multiple section applications.
Vertical Mount
Damper Model Maximum Single
Section Size
Maximum
Overall Size for
Multi-section
Dampers
DFD-210 36 x 36 or 32 x 50 64 x 50
DFD-230 36 x 36 or 32 x 50 64 x 48
DFDAF-310 32 x 50 96 x 50
DFDTF-210
32 x 36 96 x 72
32 x 50 64 x 50
FSD-211, 212, 213 36 x 48 or 32 x 50 128 x 100
FSD-231 36 x 36 or 32 x 48 72 x 48
FSD-311, 311M,
312, 312M
32 x 50 128 x 100
IMO-311
32 x 50 NA
32 x 50 NA
SEDFD-210,
SSDFD-210
24 x 30 or 22 x 36 48 x 30
SEFSD-211
SSFSD-211
24 x 30 or 22 x 36 88 x 72
FSD-331 32 x 36 or 30 x 48 120 x 96
11
7. CONNECTION AND OPERATION OF TEMPERATURE
RESPONSE DEVICES (RRL STANDARD, OCI OPTION,
AND TOR OPTION)
RRL - Dampers will be supplied with a thermostat-type
temperature response device, as a standard. The device
is a RRL (resettable link device), which only incorporates
one thermostat and therefore the damper remains
closed as soon as its sensor temperature is reached.
The RRL does not contain blade indication switches.
Refer to Fig. 6 for wiring of the RRL thermostat.
OCI - The OCI (open or closed indicator) option
contains a single pole, double throw switch used
to indicate the damper blade position. The switch
provides a positive open or closed signal when used in
conjunction with remote indicator lights. Refer to Fig. 7
& 8 for wiring of the OCI option.
TOR - The TOR (temperature override device) option
incorporates two thermostats with fixed settings (usually
165F [74C] and 350F [177C]). The primary sensor
(the sensor with the lower temperature setting) can be
bypassed by an external electrical signal allowing the
damper to reopen until the temperature reaches the
setting of the secondary sensor (the sensor with the
higher temperature setting).
See Fig. 8.
When the temperature of the secondary sensor is
exceeded the damper closes and remains closed
thereafter.
The TOR assembly also contains a single pole, double
throw switch used to indicate damper blade position. The
switch provides a positive open or closed signal when
used in conjunction with remote indicator lights. See
Fig. 8 for wiring of the TOR thermostats and indicator
switches.
If either the TOR or the RRL is ordered with a pneumatic
actuator, an EP switch is required with an appropriate
electric power circuit to allow the electric thermostat to
control the pneumatic actuator.
PRV - The PRV (pneumatic relief valve) option is heat
responsive device used with pneumatic actuators. This
can be used in place of EP switch where a RRL is used.
The PRV activates when temperature in excess of the
temperature of the fusible link are detected. When the
fusible link melts, air from the actuator is exhausted to
close the dampers. Pneumatic actuators are to be piped
per local code.
RATINGS (Fig. 6, 7, 8 & 9)
Integral Switch Type: Single Pole, double throw
Electrical Capacity: 10 Amps,
1
/3 hp, 120 or 240 Vac

1
/2 Amp, 125 Vdc;

1
/4 Amp 250 Vdc
5 Amps, 120 Vac L ( lamp load)
1.0 Amps, 24 Vac
1.5 Amps, 24 Vdc
Temperature Limit: 165 F ( standard primary sensor)
212 F ( optional primary sensor)
250 F ( secondary sensor )*
350 F (secondary sensor)*
* based on actuator temperature rating
Fig. 6 RRL Wiring
Fig. 7 OCI Wiring
Fig. 9 TOR Wiring
Fig. 8 RRL/OCI Wiring
12
Metal Stud Construction
Wooden Stud Construction
In wood stud construction,
gypsum wallboard must cover
all wood stud surfaces.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
In metal stud construction,
exposed steel surfaces need
not be covered with gypsum
wallboard.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
Fig. 11
8. Recommended Preparation of Openings in Wood and Metal Stud Walls
Frame wall openings as shown below(see Fig. 12 & 12A).
Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening (see
Fig. 12 & 12A).
Prepare opening between studs and sleeve assembly as shown below (see Fig. 10 & 11).
All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance
Directory) and/or local codes.
12 in.
24 in. o.c.
Maximum
Floor Runner
Ceiling Runner
24 in. o.c.
Maximum
(metal studs)
24 in. o.c.
Maximum
(metal studs)
16 in. o.c.
Maximum
(wood studs)
16 in. o.c.
Maximum
(wood studs)
2 in. (51mm)
2 in. (51mm)
2 Panhead
Screws
Fig. 12
Metal Stud Construction
Wooden Stud Construction
In wood stud construction,
gypsum wallboard must cover
all wood stud surfaces.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
In metal stud construction,
exposed steel surfaces need
not be covered with gypsum
wallboard.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
Fig. 10
Second set of studs are not required on openings
36 in. x 36 in. (914mm x 914mm) or smaller.
Metal stud only
Fig. 12A
13
Duct
Sleeve
6 in.
Std. Clip
Length
C
L
Duct
60 in. Duct
4 Reqd.
48 in. Duct
3 Reqd.
36 in. Duct
3 Reqd.
24 in. Duct
2 Reqd.
18 in. Duct &
Smaller
1 Reqd.
Clip Spacing
Typical TDC/TDF joint
6 in. 6 in.
9 in.
7 in. 7 in.
5 in. 5 in.
5 in. 5 in.
Fig. 17
Duct End
Flange
Corner Piece
3/8 in. bolt
(optional)
Fig. 18
9. DUCT-SLEEVE CONNECTIONS
Traditional Breakaway Style Transverse Joints
Transverse joints illustrated at right have always been
approved as breakaway connections. SMACNA testing
has also approved the following variations as breakaway
connections.
The breakaway connections shown (Fig. 14) can be
applied with maximum of two #10 (19mm) sheet metal
screws on each side and on the bottom located in the
center of the slip pocket and penetrating both sides of
the slip pocket.
Transverse joints illustrated
can be applied as top and
bottom joints with Drive Slip -
side joints in duct heights up
to 20 inches (508mm)
See Fig. 13.
Drive Slip Joint
Fig. 13
Plain S Slip Hemmed S Slip Double S Slip
Inside Slip Joint Standing S Standing S (Alt.)
Standing S (Alt.) Standing S Standing S
(Bar Reinforced) (Angle Reinforced)
Fig. 14
Round and Oval Duct Breakaway Connections
Round or flat oval ducts connected to Type R or O damper
collars shall be attached with #10 (19mm) sheet metal
screws as follows:
Ducts to 22 in. (558mm) wide (or dia.) and smaller
shall have three screws.
Ducts larger than 22 in. (558mm) wide (or dia.) up to
and including 36 in. (914mm) wide (or dia.) shall have
five screws.
NOTE: All breakaway connections described may have duct
sealant applied, PA2084T duct sealant adhesive
manufactured by Precision, DP1010 water base duct
sealant manufactured by Design Polymetrics, Grey Pookie,
Ductmate PROseal

, or CL Ward S Seal in accordance with


SMACNA recommendations.
Manufactured Flanged System Breakaway
Connections
Flanged connection systems manufactured by Ductmate,
Ward, and Nexus are approved as breakaway connections
when installed as illustrated (Fig. 15).
Fire Damper Sleeve
Neoprene gasket
between all angles
Flanged system angles
(Attach per
manufacturer's
instructions)
Duct
Do not bolt corners
6 in. long
1
/16in. max.
thickness plastic cleats;
12 in. c-c (min. 1 per side)
Fig. 15
Proprietary Flange System Breakaway Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway
connections when installed as described in the TDC or
TDF addendum to the SMACNA
Duct Construction. Standard 6 in.
(152mm) metal clip may be used
with spacing as shown in diagram
(see Fig. 15 & 16). 3/8 in. (9.5mm)
metal bolts and nuts may be used
to fasten together corner pieces.
(see Fig. 17)
Duct
Sleeve
6 in.
Std. Clip
Length
C
L
Duct
60 in. Duct
4 Reqd.
48 in. Duct
3 Reqd.
36 in. Duct
3 Reqd.
24 in. Duct
2 Reqd.
18 in. Duct &
Smaller
1 Reqd.
Clip Spacing
Typical TDC/TDF joint
6 in. 6 in.
9 in.
7 in. 7 in.
5 in. 5 in.
5 in. 5 in.
Fig. 16
14
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom Possible Cause Corrective Action
Damper does not fully
open and/or close
Frame is 'racked' causing blades to bind
on jamb seals
Adjust frame such that it is square and plumb
Actuator linkage loose Close damper, disconnect power, adjust and tighten
linkage
Defective motor Replace
Screws in damper linkage Damper installed too far into wall. Move out to line as
designated on damper label
Contaminants on damper Clean with a non-oil based solvent (see Damper
Maintenance)
RRL or TOR sensor
tripped
Heat Push reset button located on backside of RRL or TOR
Damper does not
operate
No power supplied to the actuator Add power supply
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild
detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do
not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
Actuator manufacturer recommendations.
461336 FSD DFD CFSD Series Rev. 18, August 2013 Copyright 2013 Greenheck Fan Corporation
As a result of our commitment to continuous improvement, Greenheck reserves the right to
change specications without notice.
Specic Greenheck product warranties are located on greenheck.com within the product
area tabs and in the Library under Warranties.

Phone: (715) 359-6171 Fax: (715) 355-2399 E-mail: gfcinfo@greenheck.com Website: www.greenheck.com
Our Commitment
15
Document Number 461337
OFSD-XXX, ODFD-XXX,
OFD-XXX, and OSSFD-XXX Series
1 Hour Combination Fire Smoke or Curtain Fire Dampers
Out of Wall or Out of Floor
Vertical or Horizontal Mount
Installation, Operation, and Maintenance Instructions
OFSD-XXX, ODFD-XXX, OFD-XXX, and OSSFD-XXX
series dampers are intended for installation in accordance
with combination re smoke dampers requirements
established by:
NFPA National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing # 260-91-M)
California State Fire Marshal
Listing #3225-0981:103 & 3230-0981:104
UL Classied (see complete marking on product)
UL Classied to Canadian safety standards (see
complete marking on product)
UL Standard 555 & 555S (Classication R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and le a claim with
the nal carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess
of 100F (38C).
Warranty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which
prove to be defective during the warranty period will
be repaired or replaced at our option. Greenheck shall
not be liable for damages resulting from misapplication
or misuse of its products. Greenheck will not be
responsible for any installation or removal costs.
Greenheck will not be responsible for any service work
or backcharges without prior written authorization.
Safety Warning:
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
Electrical Guidelines
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specications.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when
the job is complete.
Safety Caution!
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit
caused by incorrect field wiring. To avoid causing death
or serious bodily harm to building occupants, follow all
instructions carefully. Dampers must close completely to
preserve the integrity of the fire smoke separation.

16
Return to Table of Contents
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the
re or re smoke damper in, not to, the opening in such a
manner as to prevent distortion and disruption of damper
operation. This is accomplished by allowing the re or re
smoke damper in rated separation openings to expand
and for the connecting duct to separate in the event of the
collapse of the hanging system. The following items will
aid in completing the damper installation in a timely and
effective manner.
1) Check the schedules for proper damper locations
within the building. Visually inspect the damper for
damage and verify that the Reusable Resettable Link
(RRL) is in place or has not activated. Never install
a re damper without the proper UL approved RRL
in place. (RRL is standard control option. These
electric links have a button for resetting.) If damper
is furnished with fusible link, visually inspect the link
to verify its not missing or broken. Replace link as
necessary.
2) Lift or handle damper using sleeve or frame. Do not
lift damper using blades or actuators.
3) Damper has label on outside of sleeve indicating a
No Screw area. Do not install screws into this area
as screws may interfere with unexposed blade linkage
and prevent damper blades from opening and/or
closing.
4) Damper has label indicating position of damper
and sleeve assembly in the wall. Install accordingly
to comply with manufacturers appropriate UL
Classication le number.
5) Damper must be installed into duct or opening square
and free of twist or other misalignment. Damper
must not be squeezed or stretched into duct or
opening. Out of square, racked, twisted or misaligned
installations can cause excessive leakage and/or
torque requirements to exceed damper/actuator
design.
6) Damper and actuator must be kept clean and
protected from dirt, dust and other foreign materials
prior to and after installation. Examples of such foreign
materials include but are not limited to:
a) Mortar dust
b) Drywall dust
c) Firesang materials
d) Wall texture
e) Paint overspray
7) Damper should be sufciently covered as to prevent
overspray if wall texturing or spray painting will be
performed within 5 feet of the damper. Excessive dirt
or foreign material deposits on damper can cause
excessive leakage and/or torque requirements to
exceed damper/actuator design.
8) Caulking is not necessary, nor is it allowed, between
the damper sleeve and the wall or oor opening
(annular space). However, caulking may be applied to
the retaining angles.
9) ACCESS: Suitable access (such that RRLs and
actuators can be maintained, etc.) must be provided
for damper inspection and servicing. Where it is not
possible to achieve sufcient size access, it will be
necessary to install a removable section of duct. (Refer
to NFPA 90A).
10) The Code Authority Having Jurisdiction (AHJ) must
evaluate and provide approval of nal installation
where variations to these instructions are necessary.
Table of Contents
Pre-Installation Guidelines ................................................................................................................................17
Installation ................................................................................................................................................... 18-27
Clearances Requirements ........................................................................................................... 18-24
Duct to Sleeve Connections ...................................... .......................................................................24
Securing the Damper/Sleeve Assembly to Wall and Floor Openings ................... ....................24-25
Actuator Connections ................................... ................................................................................... 25
Recommended Preparation of Openings in Wood and Metal Stud Walls .................................25-26
Breakaway Connections ...................................... .......................................................................26-27
Maintenance ..................................................................................................................................................... 27
Troubleshooting ................................................................................................................................................ 27
These instructions apply to 1 hour rated combination re smoke dampers and curtain re dampers mounted in masonry,
block, wood or metal stud walls, or concrete oors. Specic requirements in these instructions are mandatory. These
instructions meet the requirements of UL555. Installation shall comply with the requirements of NFPA 90A (Installation of Air
Conditioning and Ventilating Systems) and UL listing R13317.
Installation - Failure to follow these instructions will void all warranties.
17
1. DAMPER IS INSTALLED OUTSIDE OF WALL PLANE
OFSD-XXX
Figure 1 shows two approved installations for
combination fire smoke dampers: 1) Through the
grille access and 2) installation in continuing duct.
To provide through the grille access to the damper
actuator, the damper is located toward the back of the
sleeve and the actuator is installed between the damper
and grille. Actuator and damper can be accessed and
serviced by removing the grille. To provide access to the
damper actuator for continuing ductwork, refer to the
requirements of NFPA 90A.
Steel stud
Flange
Grille
(Supplied
by others)
Factory Supplied
Thermal Blanket
Factory Supplied
Thermal Blanket
7 1/2 in.
Max.
7 1/2 in.
Max.
Damper
Damper
#10 2 1/2 in. long sheet metal
screws spaced 6 in. on center
and maximum of 2 in. from the
corners (minimum of 2 screws
per side) through the sleeve into
the header, sill and jamb framing
members. Screw into rear
portion of the studs so as to
avoid space conicts with the
grille assembly.
Masonry
oor
Duct Continues
Horizontal or Vertical Mount
Wooden Stud Construction
Gypsum Wallboard
Stud or Runner
Retaining Angle
(Refer to section 4)
(Duct Terminates)
In wood stud construction,
gypsum wallboard must cover
all wood stud surfaces.
Grille
(Supplied
by others)
Factory Supplied
Thermal Blanket
Fire damper or
combination re
smoke damper
6 1/2 in.
Max.
#10 sheet metal screws, 2
1/2 inches long, spaced
6 in. on center and
maximum of 2 in. from
corners (minimum of 2
screws per side). Screw
into rear portion of the
studs so as to avoid
space conicts with
the grille assembly.
Figure 1: Installation configurations for Out of Wall combination fire smoke dampers.
Duct Terminates Wood Stud Duct Terminates Metal Stud
Steel stud
Flange
Grille
(Supplied
by others)
Factory Supplied
Thermal Blanket
Factory Supplied
Thermal Blanket
7 1/2 in.
Max.
7 1/2 in.
Max.
Damper
Damper
#10 2 1/2 in. long sheet metal
screws spaced 6 in. on center
and maximum of 2 in. from the
corners (minimum of 2 screws
per side) through the sleeve into
the header, sill and jamb framing
members. Screw into rear
portion of the studs so as to
avoid space conicts with the
grille assembly.
Masonry
oor
Note: Both installations for vertical mount.
ODFD-XXX, OFD-XXX, and OSSFD-XXX: Figure 2
shows installations that are also approved for curtain fire
dampers. For access to inspect the damper and fusible
link, refer to the requirements of NFPA 90A.
2. CLEARANCE REQUIREMENTS
There is no minimum clearance requirement between
the wall/floor opening and the sleeve exterior (with
thermal blanket attached). However, to facilitate
installation, clearances between the wall/floor opening
and the damper sleeve are recommended. although
there is no maximum allowable clearance, the minimum
overlap requirements between the wall/floor and the
flange/retaining angle must be met. On grill mount
installations the flange must overlap the wall/floor by
in. (13mm). On continuous duct installations, the
retaining angles must overlap the wall/floor by 1 in.
(25mm). Because no clearances are required between
the wall/floor opening and the sleeve, dampers may not
be installed in the plane of the wall using this installation
method.
18
Figure 2
Steel Stud
Flange
Flange Flange
Factory
Supplied
Thermal
Blanket
7 1/2 in. (191mm)
maximum
Concrete or
Masonry
Wall
Wood
Stud
Damper
Type A- Vertical Mount, Duct Terminates
Flange Method
Type A- Vertical Mount, Duct Terminates
Single Angle Method
Type A - Horizontal Mount Above Floor/Wall,
Duct Terminates Single Angle Method
Type A - Horizontal Mount Below Floor/Wall, Duct
Terminates Flange Method
Type A - Horizontal Mount Below Floor/Wall, Duct
Terminates Single Angle Method
Flange
7 1/2 in. (191mm)
max.
Factory Supplied
Thermal Blanket
Masonry or
Concrete
Floor
Damper
7 1/2 in.
(191mm)
max.
Factory Supplied
Thermal Blanket
Retaining
Angle
Alternate
Retaining
Angle
Location
Concrete or
Masonry Wall
Wood
Stud
Steel Stud
Damper
7 1/2 in. (191mm)
max.
Retaining
Angle
Factory Supplied
Thermal Blanket
Concrete or
Masonry
Floor
Damper
Retaining
Angle
Concrete or
Masonry
Floor
Damper
7 1/2 in. (191mm)
max.
Factory Supplied
Thermal Blanket
19
Figure 2 cont...
Type A- Vertical Mount, Thru Duct with Two
Retaining Angles
Type A- Vertical Mount, Thru Duct with
Single Retaining Angle
Type A - Horizontal Mount Above Floor/Wall,
Thru Duct with Two Retaining Angles
Type A - Horizontal Mount Above Floor/Wall,
Thru Duct with Single Retaining Angle
Type A - Horizontal Mount Below Floor/Wall, Thru
Duct with Two Retaining Angles
Type A - Horizontal Mount Below Floor/Wall, Thru
Duct with Single Retaining Angle
Retaining
Angle
Retaining
Angle
7 1/2 in. (191mm)
max.
Factory Supplied
Thermal Blanket
Damper
Masonry or
Concrete Wall
Metal
Stud
Wood
Stud
Masonry or
Concrete
Floor
7 1/2 in. (191mm)
max.
Retaining
Angle
Factory Supplied
Thermal Blanket
Damper
Retaining
Angle
7 1/2 in. (191mm)
max.
Retaining
Angle
Retaining
Angle
Factory Supplied
Thermal Blanket
Masonry or
Concrete
Floor
Damper
Concrete or
Masonry Wall
Wood Stud
7 1/2 in. (191mm)
maximum
Factory Supplied
Thermal Blanket
Retaining
Angle
Alternate Retaining
Angle Location
Damper
7 1/2 in. (191mm)
maximum
Factory Supplied
Thermal Blanket
Retaining
Angle
Concrete or
Masonry
Floor
Damper
7 1/2 in. (191mm)
maximum Factory Supplied
Thermal Blanket
Retaining
Angle
Concrete or
Masonry Floor
20
Figure 2 cont....
Type B2- Vertical Mount, Duct Terminates
Flange Method
Type B2 - Horizontal Mount Below Floor/Wall, Duct
Terminates Flange Method
Factory Supplied
Thermal Blanket
7 1/2 in. (191mm)
maximum Damper
Wood Stud
Masonry or
Concrete
Flange
Steel
Stud
7 1/2 in. (191mm)
maximum
Factory Supplied
Thermal Blanket
Flange
Masonry or
Concrete
Damper
Type B2- Vertical Mount, Thru Duct with
Two Retaining Angles
Type B2 - Horizontal Mount Above Floor/Wall,
Thru Duct with Two Retaining Angles
Type B2 - Horizontal Mount Below Floor/Wall, Thru
Duct with Two Retaining Angles
Wood
Stud
Masonry or
Concrete
7 1/2 in.(191mm)
Maximum
Retaining
Angle
Retaining
Angle
Damper
Factory Supplied
Thermal Blanket
Metal
Stud
Damper
Masonry or
Concrete
Retaining
Angle
Retaining
Angle
Factory Supplied
Thermal Blanket
7 1/2 in. (191mm)
maximum
7 1/2 in. (191mm)
maximum
Retaining
Angle
Retaining
Angle
Damper
Masonry or
Concrete
Factory Supplied
Thermal Blanket
21
Figure 2 cont....
Type B2- Vertical Mount, Thru Duct with
Single Retaining Angle
Type B2 - Horizontal Mount Above Floor/Wall,
Thru Duct with Single Retaining Angle
Type B2 - Horizontal Mount Below Floor/Wall, Thru
Duct with Single Retaining Angle
7 1/2 in. (191mm)
maximum
Factory Supplied
Thermal Blanket
Metal Stud
Damper
Retaining
Angle
Alternate Retaining
Angle Location
Concrete or
Masonry
Wood
Stud
Retaining
Angle
Factory Supplied
Thermal Blanket
Damper
Concrete or
Masonry
7 1/2 in. (191mm)
maximum
Factory Supplied
Thermal Blanket
Retaining Angle
Concrete or
Masonry
7 1/2 in. (191mm)
maximum
Damper
Type B2- Vertical Mount, Duct Terminates
Single Angle Method
Type B2 - Horizontal Mount Above Floor/Wall,
Duct Terminates Single Angle Method
Type B2 - Horizontal Mount Below Floor/Wall, Duct
Terminates Single Angle Method
7 1/2 in. (191mm)
maximum
Retaining
Angle
Alternate Retaining
Angle Location
Concrete or
Masonry
Factory Supplied
Thermal Blanket
Damper
7 1/2 in. (191mm)
maximum
Retaining
Angle
Factory Supplied
Thermal Blanket
Concrete or
Masonry
Damper
7 1/2 in. (191mm)
maximum
Factory Supplied
Thermal Blanket
Damper
Concrete or
Masonry
Retaining
Angle
22
Figure 2 cont....
Type C2- Vertical Mount, Thru Duct with
Two Retaining Angles
Type C2 - Horizontal Mount Above Floor/Wall,
Thru Duct with Two Retaining Angles
Type C2 - Horizontal Mount Below Floor/Wall, Thru
Duct with Two Retaining Angles
7 1/2 in. (191mm)
maximum
Factory Supplied
Thermal Blanket Retaining
Angle
Retaining
Angle
Metal Stud
Wood Stud
Concrete or
Masonry
Factory Supplied
Thermal Blanket
Retaining
Angle
Retaining
Angle
Concrete or
Masonry
7 1/2 in. (191mm)
maximum
Damper
Retaining
Angle
Retaining
Angle
Factory Supplied
Thermal Blanket
7 1/2 in. (191mm)
maximum
Concrete or
Masonry
Damper
Type C2- Vertical Mount, Duct Terminates
Flange Method
Type C2 - Horizontal Mount Above Floor/
Wall, Duct Terminates Flange Method
Type C2 - Horizontal Mount Below Floor/Wall, Duct
Terminates Flange Method
7 1/2 in. (191mm)
maximum
Factory Supplied
Thermal Blanket
Flange
Metal
Stud
Concrete or
Masonry
Wood
Stud
Damper
Flange
Factory Supplied
Thermal Blanket
Damper
7 1/2 in. (191mm)
maximum
Concrete or
Masonry
Flange
Factory Supplied
Thermal Blanket
7 1/2 in. (191mm)
maximum
Damper
Concrete or
Masonry
23
Figure 2 cont....
Type C2- Vertical Mount, Thru Duct with
Single Retaining Angle
Type C2 - Horizontal Mount Above Floor/Wall,
Thru Duct with Single Retaining Angle
Type C2 - Horizontal Mount Below Floor/Wall, Thru
Duct with Single Retaining Angle
7 1/2 in. (191mm)
maximum
Factory Supplied
Thermal Blanket
Wood Stud
Metal Stud
Alternate Retaining
Angle Location
Concrete or
Masonry
Factory Supplied
Thermal Blanket
Retaining
Angle
7 1/2 in. (191mm)
maximum
Damper
Concrete or
Masonry
Retaining
Angle
Factory Supplied
Thermal Blanket
Damper
7 1/2 in. (191mm)
maximum
Concrete or
Masonry
3. DUCT TO SLEEVE CONNECTIONS
Dampers are supplied with actuators (on applicable
models) and sleeves from the factory and can be installed
without the need for additional field installed sleeves.
Sleeve gauges of 20-14 (.9mm - 2mm) are to be used.
UL Standard 555 requires all ducts to terminate at fire
damper sleeves. Sleeve thickness must not be less than
the gauge of the connecting duct.
Duct to sleeve breakaway connections must be of the
type described on page 5. Factory furnished round duct
collars on type R and CR dampers are also considered to
be breakaway connections and may be used.
Thermal Blanket
(installed around entire
outside surface of sleeve)
Wall
Flange
Figure 3: Sleeved damper with Thermal
Blanket (duct termination).
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO
WALL OPENINGS.
Damper/sleeve assemblies must be installed in wall
openings using flanges and sheet metal screws as
illustrated and described below.
Flange on front (grille end) of sleeve must be a minimum
of 16 gauge (1.5mm) steel and have a
5
8 in. (16mm)
minimum flange leg (refer to Figure 3). Using #10
(19mm) sheet metal screws, screw from inside of sleeve
through the rear portion of the studs (as shown in
Figure 1). Space screws a maximum of 6 in. (152mm)
on center and a maximum of 2 in. (51mm) from the
corners (minimum of 2 screws per side). No retaining
angles are required on the side of wall opposite from the
grille.
Retaining angles for 1 hour rated dampers with a
width and height 48 in. (1219mm) or less must be a
minimum of 20 ga. (1mm). Retaining angles for all 3 hour
rated dampers and all dampers with a width or height
greater than 48 in. (1219mm) must be a minimum of 16
gauge (1.5mm). The leg of the retaining angle on the
damper sleeve shall be a minimum of 1 in. (32mm).
The leg of the retaining angle on the wall/floor shall be
long enough to cover the annular space and overlap the
wall/floor by a minimum of 1 in. (25mm)(see Figure 4).
24
Retaining Angle
Thermal Blanket
(installed around
entire outside
surface of sleeve)
2
in
. M
a
x
.
6
in
. M
a
x
.
6
in
. M
a
x
.
2
in
. M
a
x
.
Wall
Figure 4: Sleeved damper with Thermal
Blanket (duct continuation).
Note: Thermal blanket is riveted to the damper sleeve and
the seam is taped with acrylic adhesive tape, FSK facing
tape 152 5CWnt, manufactured by Venture Tape Company.
12 in.
24 in. o.c.
Maximum
Floor Runner
Ceiling Runner
24 in. o.c.
Maximum
(metal studs)
24 in. o.c.
Maximum
(metal studs)
16 in. o.c.
Maximum
(wood studs)
16 in. o.c.
Maximum
(wood studs)
2 in. (51mm)
2 in. (51mm)
2 Panhead
Screws
Figure 5
5. ACTUATOR CONNECTIONS
Electrical and/or pneumatic connections to damper
actuators should be made in accordance with wiring
and piping diagrams developed in compliance with
applicable codes, ordinances and regulations (see
Electrical Guidelines).
6 Recommended Preparation of Openings in
Wood and Metal Stud Walls
Frame wall openings as shown (see Figure 5 & 5A)
Gypsum wall board must be fastened 12 in. (305mm)
on center to all stud and runner flanges surrounding
opening (see Figure 5 & 5A).
Prepare opening between studs and sleeve assembly
as shown (Figure 6 & 7).
All construction and fasteners must meet the
requirements of the appropriate wall design (See UL
Fire Resistance Directory) and/or local codes.
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO
WALL OPENINGS continued....
Retaining angles must be attached to the sleeve using
one or more of the following methods of attachment:
Tack or spot welds
#10 (19mm) sheet metal screws

1
4 in. (6mm) bolts and nuts

3
16 in. (4.7mm) steel pop rivets
Attachments must be spaced a minimum of 6 in.
(152mm) on center and a maximum of 2 in. (51mm) from
corners. The angles must be attached to all 4 sides of
the sleeve. A minimum of two attachments are required
on each side, top and bottom. The angles need not be
attached to each other at the corners.
CAUTION! Do not tear the thermal blanket during
installation.
Dampers are tested for correct operation and are
square and straight before shipment from the factory.
Dampers must be installed square and straight and
must not be twisted or racked. Failure to install the
damper square and straight may prevent the damper
blades from operating open and closed.
Second set of studs are not required on openings
36 in. x 36 in. (914mm x 914mm) or smaller.
Metal stud only
Figure 5A
25
Breakaway Connections
Traditional Breakaway Style Transverse Joints
Transverse joints illustrated at right have always been
approved as breakaway connections. SMACNA testing
has also approved the following variations as breakaway
connections.
The breakaway connections shown (Figure 8) can
be applied with maximum of
two #10 (19mm) sheet metal
screws on each side and on
the bottom located in the
center of the slip pocket and
penetrating both sides of the
slip pocket.
Transverse joints illustrated can be applied as top
and bottom joints with Drive Slip - side joints in duct
heights up to 20 inches (508mm)
See Figure 7.
Round and Oval Duct Breakaway Connections
Round or flat oval ducts connected to Type R or O damper
collars shall be attached with #10 (19mm) sheet metal
screws as follows:
Ducts to 22 in. (558mm) wide (or dia.) and smaller
shall have three screws.
Ducts larger than 22 in. (558mm) wide (or dia.) up to
and including 36 in. (914mm) wide (or dia.) shall have
five screws.
NOTE: All breakaway connections described may have
duct sealant applied, PA2084T duct sealant
adhesive manufactured by Precision, DP1010
water base duct sealant manufactured by Design
Polymetrics, Grey Pookie, Ductmate PROseal

,
or CL Ward S Seal in accordance with SMACNA
recommendations.
Manufactured Flanged System Breakaway
Connections
Flanged connection systems manufactured by Ductmate,
Ward, and Nexus are approved as breakaway connections
when installed as illustrated (Figure 9).
Drive Slip Joint
Figure 7
Plain S Slip Hemmed S Slip Double S Slip
Inside Slip Joint Standing S Standing S (Alt.)
Standing S (Alt.) Standing S Standing S
(Bar Reinforced) (Angle Reinforced)
Figure 8
Fire Damper Sleeve
Neoprene gasket
between all angles
Flanged system angles
(Attach per
manufacturer's
instructions)
Duct
Do not bolt corners
6 in. long
1
/16in. max.
thickness plastic cleats;
12 in. c-c (min. 1 per side)
Figure 9
Proprietary Flange System Breakaway Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway
connections when installed as described in the TDC or TDF
addendum to the SMACNA Duct Construction Standards
except the corners may not be bolted. Standard 6 in.
(152mm) metal clip may be used
with spacing as shown in Figure
10. 3/8 in. (9.5mm) metal bolts
and nuts may be used to fasten
together corner pieces (see
Figure 11).
Duct
Sleeve
6 in.
Std. Clip
Length
C
L
Duct
60 in. Duct
4 Reqd.
48 in. Duct
3 Reqd.
36 in. Duct
3 Reqd.
24 in. Duct
2 Reqd.
18 in. Duct &
Smaller
1 Reqd.
Clip Spacing
Typical TDC/TDF joint
6 in. 6 in.
9 in.
7 in. 7 in.
5 in. 5 in.
5 in. 5 in.
Metal Stud Construction
Wooden Stud Construction
In wood stud construction,
gypsum wallboard must cover
all wood stud surfaces.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
In metal stud construction,
exposed steel surfaces need
not be covered with gypsum
wallboard.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
Figure 7
Metal Stud Construction
Wooden Stud Construction
In wood stud construction,
gypsum wallboard must cover
all wood stud surfaces.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
In metal stud construction,
exposed steel surfaces need
not be covered with gypsum
wallboard.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
Figure 6
26
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom Possible Cause Corrective Action
Damper does not
fully open and/or
close
Frame is 'racked' causing blades
to bind on jamb seals
Adjust frame such that it is square and plumb
Actuator linkage loose Close damper, disconnect power, adjust and
tighten linkage
Defective motor Replace
Screws in damper linkage Damper installed too far into wall. Move out
to line as designated on damper label
Contaminants on damper Clean with a non-oil based solvent (see
Damper Maintenance)
RRL or TOR sensor
tripped
Heat Push reset button located on backside of
RRL or TOR
Damper does not
operate
No power supplied to the actuator Add power supply
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild
detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do
not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
Actuator manufacturer recommendations.
Duct End
Flange
Corner Piece
3/8 in. bolt
(optional)
Figure 11
Duct
Sleeve
6 in.
Std. Clip
Length
C
L
Duct
60 in. Duct
4 Reqd.
48 in. Duct
3 Reqd.
36 in. Duct
3 Reqd.
24 in. Duct
2 Reqd.
18 in. Duct &
Smaller
1 Reqd.
Clip Spacing
Typical TDC/TDF joint
6 in. 6 in.
9 in.
7 in. 7 in.
5 in. 5 in.
5 in. 5 in.
Figure 10: Detail of proprietary flanged system
breakaway connections.
461337 ODFD OFD Rev. 14, August 2013 Copyright 2013 Greenheck Fan Corporation
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specications without
notice.
Specic Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library
under Warranties.

Phone: (715) 359-6171 Fax: (715) 355-2399 E-mail: gfcinfo@greenheck.com Website: www.greenheck.com
Our Commitment
27
Installation, Operation and Maintenance Instructions
Safety Warning:
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the
job is complete.
Warranty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which
prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not
be responsible for any service work or backcharges
without prior written authorization.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
UL CLASSIFIED (see complete marking on
product)
UL CLASSIFIED to Canadian safety standards
(see complete marking on product)
UL Standard 555 & 555S (Classification R13317)
FSD-3XXV Series Dampers are intended for installation
in accordance with combination fire smoke damper
requirements established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshal
Listing #3225-0981:103 and 3230-0981:104
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and le a claim with
the nal carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100F (38C).
Typical
Actuator
RRL Control
Device Standard
Document Number 461666
FSD-3XXV Series
1 1/2 Hour
Combination Fire Smoke Dampers
(with factory installed sleeve and actuator)
Vertical Blade
Installation Supplements
Refer to the appropriate Greenheck installation supplements
for special requirements:
Concrete Floor with Steel Deck
Drive Slip Breakaway Connection
Field Installed Sleeve
Fire Resistant Ventilated Duct Assembly
Firestop Material
Greenheck Test Switch
Grille Installation
Metal Stud in Shaftwall
No Flow Smoke Detector
Open or Close Indicator
Quick Connect Breakaway Connections
Resettable Link
Sealant Supplement
Single Side Retaining Angle
Single 3-Sided Retaining Angle
Sleeve Extension
Smoke Detector
Tunnel Corridor

28
Return to Table of Contents
Table of Contents
Pre-Installation Guidelines ................................................................................................................................ 29
Electrical Guidelines .......................................................................................................................................... 29
Installation ...................................................................................................................................................... 30-34
Clearances Required Between Fire Damper Sleeves and Wall/Floor Openings ............................ 30
Sleeve Length and Wall Thickness ................................................................................................... 30
Duct to Sleeve Connections .......................................................................................................... .30-31
Securing the Damper/Sleeve Assembly to Wall and Floor Openings ............................................ .31
Actuator Connections ..................................... ...................................................................................31
Connection and Operation of Temperature Control Devices ...........................................................32
Recommended Preparation of Openings in Wood and Metal Stud Walls ...................................... 33
Breakaway Connections ....................................................................................................................34
Maintenance ...................................................................................................................................................... 35
Troubleshooting ................................................................................................................................................. 35
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the
re or re smoke damper in, not to, the opening in such a
manner as to prevent distortion and disruption of damper
operation. This is accomplished by allowing the re or re
smoke damper in rated separation openings to expand
and for the connecting duct to separate in the event of the
collapse of the hanging system. The following items will
aid in completing the damper installation in a timely and
effective manner.
1) Check the schedules for proper damper locations
within the building. Visually inspect the damper for
damage and verify that the Reusable Resettable Link
(RRL) is in place or has not activated. Never install a
re damper without the proper UL approved RRL in
place. (RRL is standard control option. These electric
links have a button for resetting.) If damper is furnished
with fusible link, visually inspect the link to verify its not
missing or broken. Replace link as necessary.
2) Lift or handle damper using sleeve or frame. Do not lift
damper using blades or actuators.
3) Damper has label on outside of sleeve indicating a
No Screw area. Do not install screws into this area as
screws may interfere with unexposed blade linkage and
prevent damper blades from opening and/or closing.
4) Damper has label indicating position of damper
and sleeve assembly in the wall. Install accordingly
to comply with manufacturers appropriate UL
Classication le number.
5) Damper must be installed into duct or opening square
and free of twist or other misalignment. Damper must
not be squeezed or stretched into duct or
opening. Out of square, racked, twisted or misaligned
installations can cause excessive leakage and/or torque
requirements to exceed damper/actuator design.
6) Damper and actuator must be kept clean and protected
from dirt, dust and other foreign materials prior to and
after installation. Examples of such foreign materials
include but are not limited to:
a) Mortar dust
b) Drywall dust
c) Firesang materials
d) Wall texture
e) Paint overspray
7) Damper should be sufciently covered as to prevent
overspray if wall texturing or spray painting will be
performed within 5 feet of the damper. Excessive dirt
or foreign material deposits on damper can cause
excessive leakage and/or torque requirements to
exceed damper/actuator design.
8) Caulking is not necessary, nor is it allowed, between the
damper sleeve and the wall or oor opening (annular
space). However, caulking may be applied to the
retaining angles.
9) ACCESS: Suitable access (such that RRLs and
actuators can be maintained, etc.) must be provided
for damper inspection and servicing. Where it is not
possible to achieve sufcient size access, it will be
necessary to install a removable section of duct. (Refer
to NFPA 90A).
10) The Code Authority Having Jurisdiction (AHJ) must
evaluate and provide approval of nal installation where
variations to these instructions are necessary.
Electrical Guidelines
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specications.
Safety Caution!
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit
caused by incorrect field wiring. To avoid causing death
or serious bodily harm to building occupants, follow all
instructions carefully. Dampers must close completely to
preserve the integrity of the fire smoke separation.
Electrical Guidelines
29
These instructions apply to 1
1
/2 hour rated combination fire smoke dampers mounted (blades must be vertical) in: masonry,
block, or stud walls. Specific requirements in these instructions are mandatory. Dampers must be installed in accordance with
these instructions to meet the requirements of UL555 and UL555S. The installation of the damper and all duct connections
to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard for the Installation of Air Conditioning
and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Damper Installation Guide, and UL Classifications
R13317.
Installation - Failure to follow these instructions will void all warranties.
Example: A 12 in. x 12 in. (305mm x 305mm) damper
would require a minimum clearance of
1
/4 in. (6mm.)
A 36 in. x 12 in. (914mm x 350mm) damper would require
a minimum clearance of
1
/2 in. (13mm) on width and
1
/4 in.
(6mm) on height.
Clearance for Expansion
(1/4in. Min, 1 1/2in. Max.)
Retaining Angles
(See Section 4)
6 in. max.
Detail 1
(Located on Bottom of Damper)
Airlfow
Sleeve Length (L)
16 in. max
"A" Dim.
(Distance from
end of Sleeve to
Face of Damper)
Actuator
Damper
Sleeve
Standard RRL Control Device
with Optional Blade Indication
J ackshaft
Tw
Line of Wall
Do not install screws
between these lines
around entire damper
Fig. 1
1. CLEARANCES REQUIRED BETWEEN FIRE DAMPER
SLEEVES AND WALL/FLOOR OPENINGS
Fire damper and sleeve assemblies expand during
periods of intense heat. Therefore, it is essential that
openings in walls or floors be larger than the fire damper
and sleeve assembly to allow for this expansion.
Minimum clearances required between the outside of fire
damper sleeve assemblies and wall/floor openings are:
Galvanized steel fire dampers and sleeves:
1
8 in.
(3mm) per foot of damper width and height with a
minimum clearance of
1
4 in. (6mm), maximum of 1
1
2
in. (38mm).
Recommended clearances, for width and/or height
dimensions of:
1) 36 in. (914mm) or less:
1
2 in. (13mm) clearance
These are total clearances (ignoring fastener heads) and do
not need to be equally spaced around the damper.
2. SLEEVE LENGTH AND WALL THICKNESS
Insert the sleeved damper assembly into the prepared
opening, to appropriate depth (refer to label on outside
of sleeve for location of damper in wall; see Dimension A
and Detail 1, Fig. 1).
Recommended maximum and minimum insertion depth
can be exceeded if:
1) The operation of the damper is not impeded and
2) The C
L
of the damper frame remains within the plane of
the wall and
3) Attachments made through the retaining angle do
not penetrate the No Screw area designated on the
damper sleeve.
IMPORTANT SAFETY DANGER! : To avoid causing
death or serious bodily harm to building occupants, do
not penetrate the No Screw area designated on the
damper sleeve or the damper may not close properly.
The sleeve may extend a maximum of 16 in. beyond the
wall on the actuator side of the damper and a maximum
of 6 in. on the opposite side. Recommended standard
sleeve lengths for various wall thicknesses are:
Clearance for Expansion
(1/4in. Min, 1 1/2in. Max.)
Retaining Angles
(See Section 4)
6 in. max.
Detail 1
(Located on Bottom of Damper)
Airlfow
Sleeve Length (L)
16 in. max
"A" Dim.
(Distance from
end of Sleeve to
Face of Damper)
Actuator
Damper
Sleeve
Standard RRL Control Device
with Optional Blade Indication
J ackshaft
Tw
Line of Wall
Do not install screws
between these lines
around entire damper
Wall Thickness
Dimension (T
W
)
Sleeve Length
Dimension (L)
4 - 6 in.
(102mm - 152mm)
16 in.
(406mm)
7 - 10 in.
(178mm - 254mm)
21 in.
(533mm)
11 - 13 in.
(279mm - 330mm)
24 in.
(610mm)
3. DUCT TO SLEEVE CONNECTIONS
Dampers are supplied with sleeves and actuators from
the factory and can be installed without the need for
additional field installed sleeves.
Gauge of factory furnished sleeve determines the type
of duct to sleeve connections required (see table below).
Any duct connection other than those breakaway
connections described on page 6 are considered rigid.
Factory furnished duct collars, type R and O, are also
considered breakaway (see Fig. 2).
30
Sleeve Gauge Duct Dimension
Type of Duct
to Sleeve
Connection
Permitted
14 ga. (0.075 in.)
- 10 ga. (0.138
in.)
[2mm - 3.5mm]
All duct sizes
Rigid or
Breakaway
16 ga. (0.060 in.)
[1.5mm]
36 in. (914mm) max. width
24 in. (610mm) max. width
24 in. (610mm) diameter
Rigid only
16 ga. (0.060 in.)
[1.5mm]
All duct sizes
Breakaway only
18 ga. (0.048 in.)
[1.2mm]
85 in. (2159mm) wide and
over
20 ga. (0.036 in.)
[0.9mm]
55 in. - 84 in. wide
(1397mm - 2134mm)
22 ga. (.030 in.)
[0.76mm]
31 in. - 54 in. wide
(787mm - 1372mm)
24 ga. (0.024)
[0.6mm]
13 in. - 30 in. wide
(330mm - 762mm)
26 ga. (0.018 in.)
[0.46mm]
12 in. wide and under
(305mm)
See page 6 for additional information on breakaway sleeve connections.
Sleeve thickness must not be less than the gauge of the connecting duct.
UL Standard 555 requires all ducts to terminate at re damper sleeves.
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO
WALL OPENINGS
Damper/sleeve assemblies must be installed in wall
openings using retaining angles on at least one side of
the wall as described below:
Retaining angles for 1 hour rated dampers with a
width and height 48 in. (1219mm) or less must be a
minimum of 20 ga. (1mm). Retaining angles for all 3
hour rated dampers and all dampers with a width or
height greater than 48 in. (1219mm) must be a minimum
of 16 gauge (1.5mm). The leg of the retaining angle
on the damper sleeve shall be a minimum of 1 in.
(32mm). The leg of the retaining angle on the wall/floor
shall be long enough to cover the annular space and
overlap the wall/floor by a minimum of 1 in. (25mm).
Damper
Model
Maximum Single
Section Size
Maximum Multiple
Section Size
FSD-311V 50 x 32 100 x 32
Type R and O
Factory Furnished
Duct Collars Qualify
As Breakaway
Connections
Duct
Damper
Sleeve
Wall or Floor
Type C, O, R
Fig. 2
Damper with type R or O transition factory
furnished.
2 in. M
ax.
6 in. M
ax.
Sleeve
Retaining
Angle
Damper
Duct
Min. 1 in.
Overlap*
Wall or
Floor
Retaining
Angle
*only applicable for damper sizes above 36 in. x 36 in.
6 in. M
ax.
2 in. M
ax.
Both vertical and horizontal damper installations are
typified by these drawings.
Fig. 3
5. ACTUATOR CONNECTIONS
Electrical and/or pneumatic connections to damper
actuators should be made in accordance with wiring and
piping diagrams developed in compliance with applicable
codes, ordinances and regulations (see Electrical
Guidelines).
Retaining angle must be attached to the damper using
one or more of the following methods of attachment
(refer to label on outside of sleeve for No Screw area):
Tack or spot welds
#10 (
3
/4 in. max. [19mm]) sheet metal screws

1
/4 in. (6mm) bolts and nuts

3
/16 in. (5mm) steel pop rivets
A minimum of two connections per side, top, and bottom,
12 in. (305mm) O.C. (on center) maximum for openings of
48 in. W x 32 in. H (1219mm x 812mm) and less, and 6 in.
(152mm) O.C. for openings 100 in. W x 32 in. H (2540mm
x 32mm) or less. The angles must be attached to all 4
sides of the sleeve with butt joints at each corner. A
minimum of two attachments are required on each side,
top and bottom. Ensure that attachment device does not
interfere with the operation of the damper and the free
movement of the damper blades. The angles need not be
attached to each other at the corners. Do not secure the
retaining angle to the fire separation (see Fig. 3).
Retaining angles should not be fastened to the wall
material. The angles should only sandwich the wall and
allow for damper expansion during periods of intense
heat.
31
RATINGS (Fig. 4, 5, 6 & 7)
Integral Switch Type: Single Pole, double throw
Electrical Capacity: 10 Amps,
1
/3 hp, 120 or 240 Vac

1
/2 Amp, 125 Vdc;

1
/4 Amp 250 Vdc
5 Amps, 120 Vac L ( lamp load)
1.0 Amps, 24 Vac
1.5 Amps, 24 Vdc
Temperature Limit: 165 F ( standard primary sensor)
212 F ( optional primary sensor)
250 F ( secondary sensor )*
350 F (secondary sensor)*
* based on actuator temperature rating
Fig. 4 RRL Wiring
Fig. 5 OCI Wiring
Fig. 6 RRL/OCI Wiring
Fig. 7 TOR Wiring
6. CONNECTION AND OPERATION OF TEMPERATURE
RESPONSE DEVICES (RRL STANDARD, OCI OPTION,
AND TOR OPTION)
RRL - Dampers will be supplied with a thermostat-type
temperature response device, as a standard. The device
is a RRL (resettable link device), which only incorporates
one thermostat and therefore the damper remains closed
as soon as its sensor temperature is reached. The RRL
does not contain blade indication switches. Refer to Fig.
4 for wiring of the RRL thermostat.
OCI - The OCI (open or closed indicator) option contains
a single pole, double throw switch used to indicate the
damper blade position. The switch provides a positive
open or closed signal when used in conjunction with
remote indicator lights. Refer to Fig. 5 & 6 for wiring of
the OCI option.
TOR - The TOR (temperature override device) option
incorporates two thermostats with fixed settings (usually
165F [74C] and 350F [177]). The primary sensor
(the sensor with the lower temperature setting) can be
bypassed by an external electrical signal allowing the
damper to reopen until the temperature reaches the
setting of the secondary sensor (the sensor with the
higher temperature setting). When the temperature of the
secondary sensor is exceeded the damper closes and
remains closed thereafter (Figure 7).
The TOR assembly also contains a single pole, double
throw switch used to indicate damper blade position. The
switch provides a positive open or closed signal when
used in conjunction with remote indicator lights. See
Fig. 7 for wiring of the TOR thermostats and indicator
switches.
If either the TOR or the RRL is ordered with a pneumatic
actuator, an EP switch is required with an appropriate
electric power circuit to allow the electric thermostat to
control the pneumatic actuator.
PRV - The PRV (pneumatic relief valve) option is heat
responsive device used with pneumatic actuators. This
can be used in place of EP switch where a RRL is used.
The PRV activates when temperature in excess of the
temperature of the fusible link are detected. When the
fusible link melts, air from the actuator is exhausted to
close the dampers. Pneumatic actuators are to be piped
per local code.
32
Metal Stud Construction
Wooden Stud Construction
In wood stud construction,
gypsum wallboard must cover
all wood stud surfaces.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
In metal stud construction,
exposed steel surfaces need
not be covered with gypsum
wallboard.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
Fig. 9
12 in.
24 in. o.c.
Maximum
Floor Runner
2 in.
Ceiling Runner
2 Panhead
Screws
24 in. o.c.
Maximum
(metal studs)
24 in. o.c.
Maximum
(metal studs)
16 in. o.c.
Maximum
(wood studs)
16 in. o.c.
Maximum
(wood studs)
2 in.
Fig. 10
Second set of studs are not required on openings
36 in. x 36 in. (914mm x 914mm) or smaller.
Metal stud only
Fig. 10A
Metal Stud Construction
Wooden Stud Construction
In wood stud construction,
gypsum wallboard must cover
all wood stud surfaces.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
In metal stud construction,
exposed steel surfaces need
not be covered with gypsum
wallboard.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
Fig. 8
7. RECOMMENDED PREPARATION OF OPENINGS IN
WOOD AND METAL STUD WALLS
Frame wall openings as shown. (see Fig. 10 & 10A)
Gypsum wall board must be fastened 12 in. (350mm)
on center to all stud and runner flanges surrounding
opening. (see Fig. 10 & 10A).
Prepare opening between studs and sleeve assembly as
shown (see Fig. 8 & 9).
All construction and fasteners must meet the
requirements of the appropriate wall design (See UL Fire
Resistance Directory) and/or local codes.
33
8. DUCT-SLEEVE CONNECTIONS
Traditional Breakaway Style Transverse Joints
Transverse joints illustrated at right have always been
approved as breakaway connections. SMACNA testing
has also approved the following variations as breakaway
connections.
The breakaway connections shown to the right (Fig.
12) can be applied with maximum of two #10 (19mm)
sheet metal screws on each side and on the bottom
located in the center of the slip pocket and penetrating
both sides of the slip pocket.
Transverse joints illustrated
can be applied as top and
bottom joints with Drive Slip -
side joints in duct heights up
to 20 inches (508mm) see Fig. 11.
Round and Oval Duct Breakaway Connections
Round or flat oval ducts connected to Type R or O damper
collars shall be attached with #10 (19mm) sheet metal
screws as follows:
Ducts to 22 in. (558mm) wide or diameter and smaller
shall have three screws.
Ducts larger than 22 in. wide (558mm) or diameter
up to and including 36 in. (914mm) wide or diameter
shall have five screws.
NOTE: All breakaway connections described may have duct
sealant applied, PA2084T duct sealant adhesive
manufactured by Precision, DP1010 water base duct
sealant manufactured by Design Polymetrics, Grey
Pookie, or Ductmate PROseal

, or CL Ward S Seal
in accordance with SMACNA recommendations.
Drive Slip Joint
Fig. 11
Plain S Slip Hemmed S Slip Double S Slip
Inside Slip Joint Standing S Standing S (Alt.)
Standing S (Alt.) Standing S Standing S
(Bar Reinforced) (Angle Reinforced)
Fig. 12
Fire Damper Sleeve
Neoprene gasket
between all angles
Flanged system angles
(Attach per
manufacturer's
instructions)
Duct
Do not bolt corners
6 in. long
1
/16in. max.
thickness plastic cleats;
12 in. c-c (min. 1 per side)
Fig. 13
Proprietary Flange System Breakaway Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway
connections when installed as described in the TDC or
TDF addendum to the SMACNA
Duct Construction. Standard 6 in.
(152mm) metal clip may be used
with spacing as shown in diagram
(Fig. 14 & 15). 3/8 in. (9.5mm)
metal bolts and nuts may be used
to fasten together corner pieces.
(see Fig. 16)
Duct
Sleeve
6 in.
Std. Clip
Length
C
L
Duct
60 in. Duct
4 Reqd.
48 in. Duct
3 Reqd.
36 in. Duct
3 Reqd.
24 in. Duct
2 Reqd.
18 in. Duct &
Smaller
1 Reqd.
Clip Spacing
Typical TDC/TDF joint
6 in. 6 in.
9 in.
7 in. 7 in.
5 in. 5 in.
5 in. 5 in.
Fig. 14
Manufactured Flanged System Breakaway Connections
(Fig. 13)
Flanged connection systems manufactured by Ductmate,
Ward, and Nexus are approved as breakaway connections
when installed as illustrated (Fig. 13).
Fig. 15
Duct
Sleeve
6 in.
Std. Clip
Length
C
L
Duct
60 in. Duct
4 Reqd.
48 in. Duct
3 Reqd.
36 in. Duct
3 Reqd.
24 in. Duct
2 Reqd.
18 in. Duct &
Smaller
1 Reqd.
Clip Spacing
Typical TDC/TDF joint
6 in. 6 in.
9 in.
7 in. 7 in.
5 in. 5 in.
5 in. 5 in.
Duct End
Flange
Corner Piece
3/8 in. bolt
(optional)
Fig. 16
34
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild
detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do
not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
Actuator manufacturer recommendations.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom Possible Cause Corrective Action
Damper does not fully
open and/or close
Frame is 'racked' causing blades to bind
on jamb seals
Adjust frame such that it is square and plumb
Actuator linkage loose Close damper, disconnect power, adjust and tighten
linkage
Defective motor Replace
Screws in damper linkage Damper installed too far into wall. Move out to line as
designated on damper label
Contaminants on damper Clean with a non-oil based solvent (see Damper
Maintenance)
RRL or TOR sensor
tripped
Heat Push reset button located on backside of RRL or TOR
Damper does not oper-
ate
No power supplied to the actuator Add power supply
461666 FSD-3XXXV Series Rev. 13, August 2013 Copyright 2013 Greenheck Fan Corporation
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifcations without notice.
Specifc Greenheck product warranties are located on greenheck.com within the product area tabs and in
the Library under Warranties.

Phone: (715) 359-6171 Fax: (715) 355-2399 E-mail: gfcinfo@greenheck.com Website: www.greenheck.com
Our Commitment
35
Document Number 461868
FSDR-XXX, SEFSDR-XXX,
AND SSFSDR-XXX MODELS
1
1
2 Hour Fire & Combination Fire
Smoke Dampers
Vertical and Horizontal Mount
SAFETY WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment. To avoid causing death or serious bodily harm
to building occupants, follow all instructions carefully.
Dampers must close completely to preserve the integrity
of the fire smoke separation.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the
job is complete.
WARRANTY
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the shipment date. Any units or parts which
prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not
be responsible for any service work or backcharges
without prior written authorization.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
UL CLASSIFIED (see complete marking on
product)
UL CLASSIFIED to Canadian safety standards (see
complete marking on product)
UL Standard 555 & 555S (Classification #R13317)
FSDR-XXX, SEFSDR-XXX, and SSFSDR-XXX Model
Dampers are intended for installation in accordance
with combination fire smoke damper requirements
established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshal (CSFM)
Fire Listing (3225-0981:0112)
Leakage Listing (3230-0981:0113)
RECEIVING AND HANDLING
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100F (38C).
Installation, Operation and Maintenance Instructions
INSTALLATION SUPPLEMENTS
Refer to the appropriate Greenheck installation
supplements for special requirements:
Steel Deck Supplement
SAFETY CAUTION!
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit
caused by incorrect field wiring.
ELECTRICAL GUIDELINES
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specifications.

36
Return to Table of Contents
Table of Contents
Pre-Installation Guideline ..............................................................................................................................................37
Installation ............................................................................................................................................................... 38-41
Clearances Required Between Fire Damper Sleeves and Wall/Floor Openings ................................................... 38
Sleeve Length and Wall Thickness ............................................................................................................................38
Round Duct Connections ...........................................................................................................................................38
Securing the Damper Assembly to Wall and Floor Openings ........................................................................... 38-39
Actuator Connections ................................................................................................................................................39
Connection and Operation of Temperature Control Devices .............................................................................39-40
FSDR-XXX and DFDR-XXX Blade Orientation ..........................................................................................................40
Recommended Preparation of Openings in Wood and Metal Stud ........................................................................41
Maintenance ..................................................................................................................................................................42
Troubleshooting .............................................................................................................................................................42
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the fire smoke or fire damper in the opening in such a manner
as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire or fire smoke
damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse
of the hanging system. The following items will aid in completing the damper installation in a timely and effective
manner.
These instructions apply to 1 hour rated combination fire smoke and fire dampers mounted in: 1) masonry, block or
stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory. Dampers must be
installed in accordance with these instructions to meet the requirements of UL 555 and UL 555S. The installation of the
damper and all duct connections to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard
for the Installation of Air Conditioning and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Damper
Installation Guide, and UL Classifications R13317.
Installation - Failure to follow these instructions will void all warranties.
1) Check the schedules for proper damper locations
within the building. Visually inspect the damper for
damage and verify that the fusible link is in place or
has not separated. If fusible link is not present or has
separated, replace link. Never install a fire damper
without the proper UL approved fusible link in place.
(Fusible link is standard control option. An electric
link may have been provided. Electric links have a
button for resetting.)
2) Lift or handle damper using the frame. Do not lift
damper using blades or actuators.
3) Do not install screws into the main body area of
the damper frame as screws may interfere with and
prevent damper blade from opening and/or closing.
4) Damper has label indicating position of damper
assembly in the wall. Install accordingly to comply
with manufacturers appropriate UL Classification file
number.
5) Damper must be installed into duct or opening free of
distortion or other misalignment. Damper must not be
squeezed or stretched into duct or opening. Out of
round, racked, twisted or misaligned installations can
cause excessive leakage and/or torque requirements
to exceed damper/actuator design.
6) Damper and actuator must be kept clean and
protected from dirt, dust and other foreign materials
prior to and after installation. Examples of such
foreign materials include but are not limited to:
a) Mortar dust
b) Drywall dust
c) Firesafing materials
d) Wall texture
e) Paint overspray
7) Damper should be sufficiently covered as to prevent
overspray if wall texturing or spray painting will be
performed within 5 feet of the damper. Excessive dirt
or foreign material deposits on damper can cause
excessive leakage and/or torque requirements to
exceed damper/actuator design.
8) Caulking is not necessary, nor is it allowed, between
the damper sleeve and the wall or floor opening
(annular space). However, caulking may be applied to
the retaining plates.
9) ACCESS: Suitable access (such that fusible links,
RRLs, actuators, and linkages can be maintained)
must be provided for damper inspection and
servicing. Where it is not possible to achieve
sufficient size access, it will be necessary to install a
removable section of duct. (Refer to NFPA 90A).
10) The Code Authority Having Jurisdiction (AHJ) must
evaluate and provide approval of final installation
where variations to these instructions are necessary.
37
3.375 IN.
FUSIBLE
LINK
LOCATION
CLEARANCE FOR
EXPANSION
TOP VIEW OF DAMPER
6 IN. MAX
SLEEVE LENGTH
TW
DUCT
CONNECTION
AREA
AIRFLOW
2.00 IN.
ACTUATOR
16.00 IN MAX
OPTIONAL BLADE POSITION
INDICATOR AND/OR ELECTRIC
LINK.
DUCT
CONNECTION
AREA
2.00 IN.
1.50 IN.
Optional
Second
Retaining
Plate
Do not place retainer
plate in this groove
Fig. 1
2. SLEEVE LENGTH AND WALL/FLOOR
THICKNESS
Insert the damper assembly into the prepared opening,
to appropriate depth (see Fig. 1).
Recommended maximum and minimum insertion depth
can be exceeded if:
1) the operation of the damper actuator is not
impeded and
2) the C
L
of the damper blade remains within
the plane of the wall/floor
IMPORTANT SAFETY DANGER! : To avoid
causing death or serious bodily harm to
building occupants, do not insert screws
into the damper frame unless used for duct
connection within 2 in. (51mm) of the frame
end.
The sleeve may extend a maximum of 16 in. (406mm)
beyond the wall or floor on the actuator side of the
damper and a maximum of 6 in. (152mm) on the
opposite side.
4. SECURING THE DAMPER/SLEEVE ASSEMBLY
TO WALL AND FLOOR OPENINGS
Damper assemblies must be installed in wall/floor
openings using a single retaining plate on either side of
the wall/floor or by using a retaining plate on both sides
of the wall/floor. The use of a second retaining plate is
allowed, but is not necessary. A single retaining plate
is provided with the dampers. A second retaining plate
can be ordered as an option. The outside dimension of
the supplied retainer plate is nominal dia. + 4 inches
(114mm).
3. ROUND DUCT CONNECTIONS
Round duct connections to shall be attached with #8 or
#10 sheet metal screws as follows:
Ducts 22 in. (558mm) dia. and smaller shall have
three screws.
Ducts larger than 22 in. (558mm) dia. up to and
including 24 in. (610mm) dia. shall have five screws.
NOTE: All connections described may have duct
sealant, PA2084T duct sealant adhesive manufactured
by Precision, DP1010 water base duct sealant
manufactured by Design Polymetrics, Grey Pookie,
Ductmate PROseal

,

or CL Ward S Seal applied in
accordance with SMACNA recommendations.
1. CLEARANCES REQUIRED BETWEEN FIRE
DAMPER SLEEVES AND WALL/FLOOR
OPENINGS
Fire damper assemblies expand during periods of
intense heat. Therefore, it is essential that openings in
walls or floors be larger than the fire damper assembly
to allow for this expansion. The wall/floor opening
must be a minimum of 7/8 in. (22mm) larger than the
outside diameter of the damper. Refer to Section 4 for
additional installation considerations.
38
6. CONNECTION AND OPERATION OF
TEMPERATURE RESPONSE DEVICES (Fusible
Link, RRL OPTION, OCI OPTION, TOR
OPTION, and PRV OPTION)
RRL - Dampers will be supplied with a fusible link
temperature response device, as a standard. An
optional thermostat type temperature response
device may have been installed. The device is a RRL
(resettable link device), which only incorporates one
thermostat and therefore the damper remains closed
as soon as its sensor temperature is reached. The
RRL does not contain blade indication switches. Refer
to Fig. 4.
OCI - The OCI (open or closed indicator) option
contains a single pole, double throw switch used
to indicate the damper blade position. The switch
provides a positive open or closed signal when used
in conjunction with remote indicator lights. Refer to
Fig. 5 & 6.
5. ACTUATOR CONNECTIONS
Electrical and/or pneumatic connections to damper
actuators should be made in accordance with wiring
and piping diagrams developed in compliance with
applicable codes, ordinances and regulations (see
Electrical Guidelines).
Opening + 2 in. Min.
1.00 in. Min. Typ.
Fasteners
Clamping
Screw
Nut
Retaining
Plate Assembly
Clamping Screw
Minimum Wall/Floor Opening
= Nominal Dia. + 7/8 in.
Fig. 2
Fig. 3
Fig. 4 RRL Wiring
The retaining plate(s) will open up for easy
installation when the clamping screw is loosened. If
necessary, remove the clamping screw and nut (see
Fig. 2).
Position the retaining plate between the blade axle
and the actuator shaft as shown in Figure 1. Do not
place the retaining plate in the groove. IMPORTANT:
The clamping mechanism should face away from the
wall/floor.
Place the damper and attached retainer plate into
the wall/floor opening.
If a second retaining plate is being used, secure it
on the opposite side of the wall/floor.
Verify position, blade orientation, and actuator
clearance then tighten the retainer plate clamping
screws.
The retainer plate(s) must overlap the wall/floor
opening a minimum of 1 inch (25mm).
Secure the retainer plate(s) to the wall at the four
corners of each plate when two retainer plates are
used and also within in. (19mm) of the center
of each side when one retainer plate is used. The
following fasteners shall be used:
- #8 or #10 screws of a length such that the screw
engages the steel stud/track by in. (13mm) (steel
framing)
- #8 or #10 screws of a length such that screw
engages the wood stud by 1 in. (44mm) (wood
framing)
- Steel anchors or self tapping concrete screws
penetrating masonry or block 1 in. (32mm).
39
Fig. 7 TOR Wiring
TOR - The TOR (temperature override device) option
incorporates two thermostats with fixed settings (usually
165F [74C] and 350F [177C]). The primary sensor
(the sensor with the lower temperature setting) can be
bypassed by an external electrical signal allowing the
damper to reopen until the temperature reaches the
setting of the secondary sensor (the sensor with the
higher temperature setting). When the temperature of the
secondary sensor is exceeded the damper closes and
remains closed thereafter (Fig. 7)
The TOR assembly also contains a single pole, double
throw switch used to indicate damper blade position.
The switch provides a positive open or closed signal
when used in conjunction with remote indicator lights.
See Fig. 7 for wiring of the TOR thermostats and
indicator switches.
Fig. 5 OCI Wiring
Fig. 6 RRL/OCI Wiring
RATINGS (Fig. 4, 5, 6 & 7)
Integral Switch Type: Single Pole, double throw
Electrical Capacity: 10 Amps,
1
/3 hp, 120 or 240 Vac

1
/2 Amp, 125 Vdc;

1
/4 Amp 250 Vdc
5 Amps, 120 Vac L ( lamp load)
1.0 Amps, 24 Vac
1.5 Amps, 24 Vdc
Temperature Limit: 165 F ( standard primary sensor)
212 F ( optional primary sensor)
250 F ( secondary sensor )*
350 F (secondary sensor)*
* based on actuator temperature rating
FSDR-XXX and DFDR-XXX
Blade Orientation
Normal
Axle
30 Off Horizontal (Maximum)
Axle
30
30 Off Horizontal (Maximum)
Axle
30
PRV - The PRV (pneumatic relief valve) option is heat
responsive device used with pneumatic actuators. This
can be used in place of EP switch where a RRL is used.
The PRV activates when temperature in excess of the
temperature of the fusible link are detected. When the
fusible link melts, air from the actuator is exhausted to
close the dampers. Pneumatic actuators are to be piped
per local code.
40
12 in.
24 in. o.c.
Maximum
Floor Runner
2 in.
Ceiling Runner
2 Panhead
Scr ews
24 in. o.c.
Maximum
(metal studs)
24 in. o.c.
Maximum
(metal studs)
16 in. o.c.
Maximum
(wood studs)
16 in. o.c.
Maximum
(wood studs)
2 in.
Fig. 9
8. Recommended Preparation of Openings in Wood and Metal Stud Walls
Frame wall openings as shown. (see Fig. 9 & 9A)
Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening.
(see Fig. 9 & 9A)
Prepare opening between studs and sleeve assembly as shown below (see Fig. 8).
All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance
Directory) and/or local codes.
IN THIS GROOVE.
RETAINER PLATE
DO NOT PLACE
IN THIS GROOVE.
DO NOT PLACE
RETAINER PLATE
DAMPER FRAME
DAMPER FRAME
WOOD
STUD
MIN
1.00
STUD
METAL
1.00
MIN
Fig. 8
Second set of studs are not required on openings
36 in. x 36 in. (914mm x 914mm) or smaller.
Metal stud only
Fig. 9A
41
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild
detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb
seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
Actuator manufacturer recommendations.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom Possible Cause Corrective Action
Damper does not fully
open and/or close
Frame is 'racked' causing blades to bind on
jamb seals
Adjust frame such that it is square and plumb
Actuator linkage loose Close damper, disconnect power, adjust and tighten link-
age
Defective motor Replace
Screws in damper linkage Damper installed too far into wall. Move out to line as
designated on damper label
Contaminants on damper Clean with a non-oil based solvent (see Damper Mainte-
nance)
RRL or TOR sensor tripped Heat Push reset button located on backside of RRL or TOR
Damper does not operate No power supplied to the actuator Add power supply
461868 FSDR DFDR Series Rev. 14, August 2013 Copyright 2013 Greenheck Fan Corporation
As a result of our commitment to continuous improvement, Greenheck reserves the right to
change specications without notice.
Specic Greenheck product warranties are located on greenheck.com within the product
area tabs and in the Library under Warranties.

Phone: (715) 359-6171 Fax: (715) 355-2399 E-mail: gfcinfo@greenheck.com Website: www.greenheck.com
Our Commitment
42
Document number 474015
Single Side Retaining Angle
Refer to:
Installation Instructions for FD, DFD, SSFD, & KFD Models
(Part #452763)
or
Installation Instructions for FSD-XXX, DFD-XXX, SSFSD-
XXX & CFSD-XXX Series Fire & Combination Fire Smoke
Dampers (Part #461336)
or
Installation Instructions for FD & DFD 150X Series Curtain
Fire Dampers (Part #453946) for additional details.
FD & DFD Series
1
1
/2 Hour Fire Dampers and
FSD Series
1
1
/2 Hour Combination Fire
Smoke Dampers
UL CLASSIFIED
(see complete marking on product)
UL CLASSIFIED to Canadian safety standards
(see complete marking on product)
Standards UL 555 & 555S
Classifications Filed at UL under Listing #R13317
Single side retaining angle
These instructions apply to 1 hour rated combination
re smoke dampers and curtain re dampers mounted
in masonry or block walls, metal stud walls, wood
stud walls or concrete oors. Specic requirement in
these instructions are mandatory. These instructions
meet the requirements of NFPA 90A (Standard for
the Installation of Air Conditioning and Ventilating
Systems).
Vertical mount dampers up to a maximum size of 80
in. W x 50 in. H (2032mm x 1270mm), 50 in. W x 80
in. H (1270mm x 2032mm), or 40 in. W x 100 in. H
(1016mm x 2540mm) or horizontal mount dampers up
to a maximum size of 144 in. W x 96 in. H (3658mm x
2438mm) may be installed as illustrated below. Larger
damper assemblies require retaining angles on both
sides of the partition.
Note: Model specific size limits can be found in the
base installation instruction documents noted above.
1. Clearance Requirements
On vertical mount single side angle installations there
are no minimum clearance requirements between
the wall opening and the damper sleeve. However,
to facilitate installation, clearances between the wall
opening and the damper sleeve are recommended.
On horizontal mount single side angle installations a
minimum clearance is required between the outside of
the damper sleeve and the floor opening of 1/8 in. per
foot (3mm per .3m) of damper width and 1/8 in. per
foot (3mm per .3m) height with a minimum clearance
of 1/4 in. (6mm). The maximum overall clearance is 1
1/2 in. (38mm),
2. Securing the Damper/Sleeve Assembly to Wall/
Floor Opening
Retaining angles must be attached to both the sleeve
and the partition (see figures 1-8).
Retaining angles for dampers with a width and
height of 48 in. (1219mm) or less must be a
minimum of 20 ga. (1mm). Retaining angles for
Installation Instructions Supplement
dampers with a width or height greater than
48 in. (1219mm) must be a minimum of 16 ga.
(1.5mm). The leg of the retaining angle on the
damper sleeve shall be a minimum of 1 1/4 in.
(32mm). The leg of the retaining angle on the
wall/floor shall be long enough to cover the
annular space and overlap the wall/floor by at
least 1 in. (25mm).
For metal stud partitions only, the single-side
mounting angle may be directly attached to
the metal stud prior to the installation of the
drywall.
Retaining angles must be attached to the
sleeve using one of the methods shown below:
tack or spot welds
#10 sheet metal screws
1/4 in. (6mm) nuts and bolts
Retaining angles must be attached to the
partition using one of the methods shown
below:
Drywall screws of a length such that the
screw engages the steel stud/track by
in. (13mm) (steel framing).

43
Return to Table of Contents
1
/2 in. UL Classied
Gypsum Wallboard (see
UL Rated Wall Design
for Additional Details)
2
1
/2 in. Min.
Stud or Runner
Damper
Sleeve
Angle Fastener
(see Section 2)
1
/2 in. UL Classied
Gypsum Wallboard (see
UL Rated Wall Design
for Additional Details)
Damper
Sleeve
Angle Fastener
(see Section 2)
2 1/2 in. Min.
Metal Stud
or Runner
Figure 1: 1 Hour Wall Rating
Figure 3: 1 Hour Wall Rating
Damper
Sleeve
Angle Fastener
(See Section 2)
2 1/2 in. min.
Stud or Runner
Two layers of 1/2 in. UL
Classied Gypsum
Wallboard (see UL
Rated Wall Design for
Additional Details)
Damper
Sleeve
Angle Fastener
(See Section 2)
2 1/2 in. min.
Metal Stud
or Runner
Two layers of 1/2 in. UL
Classied Gypsum
Wallboard (see UL
Rated Wall Design for
Additional Details)
Figure 2: 2 Hour Wall Rating
Figure 4: 2 Hour Wall Rating
1
/2 in. UL Classied
Gypsum Wallboard (see
UL Rated Wall Design
for Additional Details)
2
1
/2 in. Min.
Stud or Runner
Damper
Sleeve
Angle Fastener
(see Section 2)
Figure 6: 2 Hour Wall Rating
1
/2 in. UL Classied
Gypsum Wallboard (see
UL Rated Wall Design
for Additional Details)
2
1
/2 in. Min.
Stud or Runner
Damper
Sleeve
Angle Fastener
(see Section 2)
Figure 5: 1 Hour Wall Rating
Drywall screws of a length such that the
screw engages the wood stud by 1 in.
(44mm) (wood framing).
Steel anchors or self tapping concrete
screws penetrating masonry or block
1 in. (31mm).
A minimum of two connections per side are
required. Additional connections must be
2. Securing the Damper/Sleeve Assembly to the Wall/Floor opening cont.......
made at a maximum of 12 in. (305mm) O.C.
(on center) maximum for openings of 48 in. W
x 36 in. H (1219mm x 914mm) and less, and 6
in. (152mm) O.C. (on center) for openings 80
in. W x 50 in. H (2032mm x 1270mm), 50 in. W
x 80 in. H (1270mm x 2032mm), and 40 in. W x
100 in. H (1016mm x 2540mm) or less.
44
Masonry or
Concrete Floor
Damper
Sleeve
Angle Fastener
(see Section 2)
Top Side
Figure 7: Masonry or Concrete Wall Figure 8: Concrete Floor
Copyright 2013 Greenheck Corporation
474015 Single Side Retaining Angle Suppl Rev. 3 Jan 2013
Masonry or
Concrete Wall
Damper
Sleeve
Angle Fastener
(see Section 2)
2. Securing the Damper/Sleeve Assembly to the Wall/Floor opening cont.......
Grille Installations (Dampers up to 36 in. x 36 in.
[914mm x 914mm] maximum)
Angle legs may be reversed and one leg inserted
into the wall/oor opening. Retaining angles used in
conjunction with grille installations must be a minimum
of 20 gauge (1mm) steel and have a minimum of
5/8 in. x 1 in. (15mm x 25mm) 20 gauge (1mm) steel.
Space screws a maximum of 6 in. (152mm) on center
and a maximum of 2 in. (51mm) from the corners
(minimum of 2 screws per side). See Figure 9 and
Figure 10.
Note: Screws used to attach grille are allowed to
penetrate reversed angle leg.
Damper
Sleeve
Angle Fastener
(see Note 2)
Grille (supplied
by others)
#10 sheet metal screws
spaced 6 in. on center
and a maximum of 2 in.
from the corners
(minimum of 2 screws per
side). Screw into studs so
as to avoid space
conicts with the grille
1
/2 in. UL Classied
Gypsum Wallboard (see
UL Rated Wall Design
for Additional Details)
2
1
/2 in. Min.
Stud or Runner
Retaining Angle
(See Section 2)
Figure 9: 1 Hour Wall Rating
Damper
Sleeve
Angle Fastener
(see Note 2)
Grille (supplied
by others)
#10 sheet metal screws
spaced 6 in. on center
and a maximum of 2 in.
from the corners
(minimum of 2 screws per
side). Screw into studs so
as to avoid space
conicts with the grille
1
/2 in. UL Classied
Gypsum Wallboard (see
UL Rated Wall Design
for Additional Details)
2
1
/2 in. Min.
Stud or Runner Two layers of
Retaining Angle
(See Section 2)
Figure 10: 2 Hour Wall Rating
Note: For horizontal installations, retaining angles must be
mounted on top side of partition.
45
Document Number 472477
GFSD-XXX Series
1 Hour Combination Fire Smoke
Grille Access Out of Wall or Out of Floor
Vertical or Horizontal Mount
Installation, Operation, and Maintenance Instructions
GFSD-XXX series dampers are intended for installation
in accordance with combination re smoke dampers
requirements established by:
NFPA National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing # 260-91-M)
California State Fire Marshal
Listing #3225-0981:103 & 3230-0981:104
UL Classied (see complete marking on product)
UL Classied to Canadian safety standards (see
complete marking on product)
UL Standard 555 & 555S (Classication R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and le a claim with
the nal carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100F (38C).
Warranty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the shipment date. Any units or parts which
prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not
be responsible for any service work or backcharges
without prior written authorization.
Safety Warning:
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
Electrical Guidelines
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specications.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the
job is complete.
Safety Caution!
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit caused
by incorrect field wiring. To avoid causing death or serious
bodily harm to building occupants, follow all instructions
carefully. Dampers must close completely to preserve the
integrity of the fire smoke separation.
Actuator compartment

46
Return to Table of Contents
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the
re or re smoke damper in, not to, the opening in such a
manner as to prevent distortion and disruption of damper
operation. This is accomplished by allowing the re or re
smoke damper in rated separation openings to expand
and for the connecting duct to separate in the event of the
collapse of the hanging system. The following items will
aid in completing the damper installation in a timely and
effective manner.
1) Check the schedules for proper damper locations
within the building. Visually inspect the damper for
damage and verify that the Reusable Resettable Link
(RRL) is in place or has not activated. Never install a
re damper without the proper UL approved RRL in
place. (RRL is standard control option. These electric
links have a button for resetting.) If damper is furnished
with fusible link, visually inspect the link to verify its not
missing or broken. Replace link as necessary.
2) Lift or handle damper using sleeve or frame. Do not lift
damper using blades or actuators.
3) Damper has label on outside of sleeve indicating a
No Screw area. Do not install screws into this area as
screws may interfere with unexposed blade linkage and
prevent damper blades from opening and/or closing.
4) Damper has label indicating position of damper
and sleeve assembly in the wall. Install accordingly
to comply with manufacturers appropriate UL
Classication le number.
5) Damper must be installed into duct or opening square
and free of twist or other misalignment. Damper must
not be squeezed or stretched into duct or opening. Out
of square, racked, twisted or misaligned installations
can cause excessive leakage and/or torque
requirements to exceed damper/actuator design.
6) Damper and actuator must be kept clean and
protected from dirt, dust and other foreign materials
prior to and after installation. Examples of such foreign
materials include but are not limited to:
a) Mortar dust
b) Drywall dust
c) Firesang materials
d) Wall texture
e) Paint overspray
7) Damper should be sufciently covered as to prevent
overspray if wall texturing or spray painting will be
performed within 5 feet of the damper. Excessive dirt
or foreign material deposits on damper can cause
excessive leakage and/or torque requirements to
exceed damper/actuator design.
8) Caulking is not necessary, nor is it allowed, between
the damper sleeve and the wall or oor opening
(annular space). However, caulking may be applied to
the retaining angles.
9) ACCESS: Suitable access (such that RRLs and
actuators can be maintained, etc.) must be provided
for damper inspection and servicing. Where it is not
possible to achieve sufcient size access, it will be
necessary to install a removable section of duct. (Refer
to NFPA 90A).
10) The Code Authority Having Jurisdiction (AHJ) must
evaluate and provide approval of nal installation
where variations to these instructions are necessary.
Table of Contents
Pre-Installation Guidelines ................................................................................................................................47
Installation ....................................................................................................................................................47-51
Clearances Requirements ............................................................................................................47-48
Duct to Sleeve Connections ...................................... ....................................................................... 48
Securing the Damper/Sleeve Assembly to Wall and Floor Openings ........................ ...............48-49
Actuator Connections ..................................... ..................................................................................49
Recommended Preparation of Openings in Wood and Metal Stud Walls .................................49-50
Breakaway Connections ..................................... .........................................................................50-51
Maintenance ......................................................................................................................................................51
Troubleshooting ............................................................................................................................................... .51
These instructions apply to 1 hour rated combination re smoke dampers mounted in masonry, block or metal stud walls,
or concrete oors. Specic requirements in these instructions are mandatory. These instructions meet the requirements of
UL555. Installation shall comply with the requirements of NFPA 90A (Installation of Air Conditioning and Ventilating Systems)
and UL listing R13317.
Installation - Failure to follow these instructions will void all warranties.
1. DAMPER IS INSTALLED OUTSIDE OF WALL PLANE
GFSD-XXX
Figure 1 shows two approved installations for
combination fire smoke dampers: 1) Through the
grille access and 2) installation in continuing duct.
In grille-mount applications, the damper actuator can
be accessed by removing the grille and the actuator
compartment cover plate. To provide access to the
damper actuator for continuing ductwork, refer to the
requirements of NFPA 90A.
2. CLEARANCE REQUIREMENTS
There is no minimum clearance requirement between the
wall/floor opening and the sleeve exterior (with thermal
blanket attached). However, to facilitate installation,
clearances between the wall/floor opening and the
damper sleeve are recommended. Although there is no
maximum allowable clearance, the minimum overlap
requirements between the wall/floor and the flange/
retaining angle must be met. On grille-mount installations
the flange must overlap the wall/floor by in. (6mm).
47
Duct Continues
Horizontal or Vertical Mount
Figure 1: Installation configurations for Grille access combination fire smoke dampers.
Duct Terminates Metal Stud
Vertical Mount
3/4 in. 14 ga.
Flange
#10 2 in. long sheet metal
screws spaced 6 in. on
center and maximum of 2 in.
from the corners, (minimum
of 2 screws per side),
through the sleeve into the
header, sill and jamb framing
members. Screw into rear
portion of the studs so as to
avoid space conicts with
grille assembly.
Grille
(supplied
by others)
Combination Fire
Smoke Damper
3 1/2 in.
Max.
Thermal Blanket
On continuous duct installations, the retaining angles
must overlap the wall/floor by 1 in. (25mm). Because no
clearances are required between the wall/floor opening
and the sleeve, dampers may not be installed in the
plane of the wall using this installation method.
3. DUCT TO SLEEVE CONNECTIONS
Dampers are supplied with actuators (on applicable
models) and sleeves from the factory and can be
installed without the need for additional field installed
sleeves.
Sleeve gauges of 16 or 14 (1.5mm - 2mm) are to be
used. UL Standard 555 requires all ducts to terminate at
fire damper sleeves. Sleeve thickness must not be less
than the gauge of the connecting duct.
Duct to sleeve breakaway connections must be of the
type described on page 5 . Factory furnished round duct
collars on type R and CR dampers are also considered
to be breakaway connections and may be used.
Factory Supplied
Thermal Blanket
3 1/2 in.
Max.
Combination re
smoke damper
Masonry
oor
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO
WALL OPENINGS.
Damper/sleeve assemblies must be installed in wall
openings using flanges and sheet metal screws as
illustrated and described below.
Flange on front (grille end) of sleeve must be a minimum
of 14 gauge (2mm) steel and have a in. (19mm)
minimum flange leg (refer to Figure 2). Using #10
(19mm) sheet metal screws, screw from inside of sleeve
through the rear portion of the studs (as shown in
Figure 1). Space screws a maximum of 6 in. (152mm)
on center and a maximum of 2 in. (51mm) from the
corners (minimum of 2 screws per side). No retaining
angles are required on the side of wall opposite from the
grille.
48
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO
WALL OPENINGS cont....
For continuous duct installations, the retaining angles
must be a minimum of 20 ga. (1mm). The leg of the
retaining angle on the damper sleeve shall be a
minimum of 1 in. (32mm). The leg of the retaining
angle on the wall/floor shall be long enough to cover the
annular space and overlap the wall/floor by a minimum
of 1 in. (25mm)(see Figure 3).
Retaining angles must be attached to the sleeve using
one or more of the following methods of attachment:
Tack or spot welds
#10 (19mm) sheet metal screws

1
4 in. (6mm) bolts and nuts

3
16 in. (4.7mm) steel pop rivets
Attachments must be spaced a minimum of 6 in. (152mm)
on center and a maximum of 2 in. (51mm) from corners.
The angles must be attached to all 4 sides of the sleeve.
A minimum of two attachments are required on each side,
top and bottom. The angles need not be attached to each
other at the corners.
CAUTION! Do not tear the thermal blanket during
installation.
Dampers are tested for correct operation and are square
and straight before shipment from the factory. Dampers
must be installed square and straight and must not be
twisted or racked. Failure to install the damper square
and straight may prevent the damper blades from
operating open and closed.
5. ACTUATOR CONNECTIONS
Electrical and/or pneumatic connections to damper
actuators should be made in accordance with wiring and
piping diagrams developed in compliance with applicable
codes, ordinances and regulations (see Electrical
Guidelines).
Retaining Angle
Thermal Blanket
(installed around
entire outside
surface of sleeve)
2
in
. M
a
x
.
6
in
. M
a
x
.
6
in
. M
a
x
.
2
in
. M
a
x
.
Wall
Figure 3: Sleeved damper with Thermal
Blanket (duct continuation).
Note: Thermal blanket is riveted to the damper sleeve and
the seam is taped with acrylic adhesive tape, FSK facing
tape 152 5CWnt, manufactured by Venture Tape Company.
12 in.
24 in. o.c.
Maximum
Floor Runner
Ceiling Runner
24 in. o.c.
Maximum
(metal studs)
24 in. o.c.
Maximum
(metal studs)
16 in. o.c.
Maximum
(wood studs)
16 in. o.c.
Maximum
(wood studs)
2 in. (51mm)
2 in. (51mm)
2 Panhead
Screws
Figure 4
Thermal Blanket
(installed around entire
outside surface of sleeve)
Wall
Flange
Figure 2: Sleeved damper with Thermal
Blanket (duct termination).
6 Recommended Preparation of Openings in Metal
Stud Walls
Frame wall openings as shown (see Figure 4 & 4A)
Gypsum wall board must be fastened 12 in. (305mm)
on center to all stud and runner flanges surrounding
opening (see Figure 4 & 4A).
Prepare opening between studs and sleeve assembly as
shown below (see Figure 5).
All construction and fasteners must meet the
requirements of the appropriate wall design (See UL Fire
Resistance Directory) and/or local codes.
Metal Stud Construction
Wooden Stud Construction
In wood stud construction,
gypsum wallboard must cover
all wood stud surfaces.
Gypsum Wa llboard
Stud or Runner
Retaining
Angl e
1 in. Min.
Damper
Sleeve
In metal stud construction,
exposed steel surfaces need
not be covered with gypsum
wallboard.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
Metal Stud Construction
Wooden Stud Construction
In wood stud construction,
gypsum wallboard must cover
all wood stud surfaces.
Gypsum Wa llboard
Stud or Runner
Retaining
Angl e
1 in. Min.
Damper
Sleeve
In metal stud construction,
exposed steel surfaces need
not be covered with gypsum
wallboard.
Gypsum Wallboard
Stud or Runner
Retaining
Angle
1 in. Min.
Damper
Sleeve
Figure 5
49
Breakaway Connections
Proprietary Flange System Breakaway Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are
approved as breakaway
connections when installed as
described in the TDC or TDF
addendum to the SMACNA Duct
Construction Standards except
the corners may not be bolted.
Standard 6 in. (152mm) metal
clip may be used with spacing as shown in Figure 9. 3/8
in. (9.5mm) metal bolts and nuts may be used to fasten
together corner pieces (see Figure 10).
Duct
Sleeve
6 in.
Std. Clip
Length
C
L
Duct
60 in. Duct
4 Reqd.
48 in. Duct
3 Reqd.
36 in. Duct
3 Reqd.
24 in. Duct
2 Reqd.
18 in. Duct &
Smaller
1 Reqd.
Clip Spacing
Typical TDC/TDF joint
6 in. 6 in.
9 in.
7 in. 7 in.
5 in. 5 in.
5 in. 5 in.
Traditional Breakaway Style Transverse Joints
Transverse joints illustrated at right have always been
approved as breakaway connections. SMACNA testing
has also approved the following variations as breakaway
connections.
The breakaway connections shown (Figure 7) can be
applied with maximum of two #10 (19mm) sheet metal
screws on each side and on the bottom located in the
center of the slip pocket and penetrating both sides of
the slip pocket.
Transverse joints illustrated can be applied as top
and bottom joints with
Drive Slip - side joints in
duct heights up to 20 inches
(508mm), See Figure 6.
Drive Slip Joint
Figure 6
Plain S Slip Hemmed S Slip Double S Slip
Inside Slip Joint Standing S Standing S (Alt.)
Standing S (Alt.) Standing S Standing S
(Bar Reinforced) (Angle Reinforced)
Figure 7
Round and Oval Duct Breakaway Connections
Round or flat oval ducts connected to Type R or O damper
collars shall be attached with #10 (19mm) sheet metal
screws as follows:
Ducts to 22 in. (558mm) wide (or dia.) and smaller shall
have three screws.
Ducts larger than 22 in. (558mm) wide (or dia.) up to
and including 36 in. (914mm) wide (or dia.) shall have
five screws.
Fire Damper Sleeve
Neoprene gasket
between all angles
Flanged system angles
(Attach per
manufacturer's
instructions)
Duct
Do not bolt corners
6 in. long
1
/16in. max.
thickness plastic cleats;
12 in. c-c (min. 1 per side)
Figure 8
NOTE: All breakaway connections described may have duct
sealant applied, PA2084T duct sealant adhesive
manufactured by Precision, DP1010 water base duct
sealant manufactured by Design Polymetrics, Grey
Pookie, Ductmate PROseal

, or CL Ward S Seal in
accordance with SMACNA recommendations.
Manufactured Flanged System Breakaway
Connections
Flanged connection systems manufactured by Ductmate,
Ward, and Nexus are approved as breakaway connections
when installed as illustrated (Figure 8).
Second set of studs are not required on openings
36 in. x 36 in. (914mm x 914mm) or smaller.
Metal stud only
Figure 4A
50
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom Possible Cause Corrective Action
Damper does not fully
open and/or close
Frame is 'racked' causing blades to
bind on jamb seals
Adjust frame such that it is square and plumb
Actuator linkage loose Close damper, disconnect power, adjust and
tighten linkage
Defective motor Replace
Screws in damper linkage Damper installed too far into wall. Move out to line
as designated on damper label
Contaminants on damper Clean with a non-oil based solvent (see Damper
Maintenance)
RRL or TOR sensor
tripped
Heat Push reset button located on backside of RRL or
TOR
Damper does not
operate
No power supplied to the actuator Add power supply
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild
detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do
not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
Actuator manufacturer recommendations.
Duct End
Flange
Corner Piece
3/8 in. bolt
(optional)
Figure 10
Duct
Sleeve
6 in.
Std. Clip
Length
C
L
Duct
60 in. Duct
4 Reqd.
48 in. Duct
3 Reqd.
36 in. Duct
3 Reqd.
24 in. Duct
2 Reqd.
18 in. Duct &
Smaller
1 Reqd.
Clip Spacing
Typical TDC/TDF joint
6 in. 6 in.
9 in.
7 in. 7 in.
5 in. 5 in.
5 in. 5 in.
Figure 9: Detail of proprietary flanged system
breakaway connections.
472477 GFSD Rev. 4, August 2013 Copyright 2013 Greenheck Fan Corporation
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specications without
notice.
Specic Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library
under Warranties.

Phone: (715) 359-6171 Fax: (715) 355-2399 E-mail: gfcinfo@greenheck.com Website: www.greenheck.com
Our Commitment
51
Copyright 2013 Greenheck Fan Corporation
Aug 2013