ANNEX A
Technical Specifications






1. Applicable Standards
The EEI srl quality system complies with UNI EN ISO 9001 (certificate n. 3562/00 dated
27/07/2000).
Electronic equipment made by EEI complies with the following European community
directives including latest amendments:

Council Directive 73/23/EEC dated 19/02/1973 (Low Voltage Directive)
Council Directive 93/68/EEC dated 22/07/1993 (CE Marking Directive)

The following harmonised Standards have been applied to electronic equipment design
and construction:
CEI EN 60204-1: Safety of machinery. Electrical equipment of machines. Part 1:
General requirements.
CEI EN 50178, 1999: Electronic equipment for use in power installations
CEI EN 60146-1-1, 1997: Semiconductor converters General requirements and line
commutated converters Part 1-1: Specification of basic requirements
CEI EN 61000-6-2 Electromagnetic compatibility (EMC) Part 6-2: Generic standards
Immunity for industrial environments
CEI EN 61000-6-4, 2007: Electromagnetic compatibility (EMC) - Part 6: Generic
standards - Section 4: Emission standard for industrial environments.



2. General Electrical Specifications
Mains voltage: 320 Vac 10%
Frequency : 50Hz +4% / -6%
Auxiliaries voltage: 230 Vac 10% from the customer by UPS
Fan auxiliary supply voltage: 400 Vac 10%








3. Installation
Operating temperature: 0C 50 C
Storage temperature: 0C 55 C
Relative humidity: 95% @ 40C no condensing
Altitude: <1500 m a.s.l.
Air pollution: reduced dust content, to be placed in conditioned control room
IP degree: IP21

Notes
The equipment must be stored in a ambient without condensing humidity
Technical performance mentioned above refer:
to the proper installation conditions
to the proper erection and commissioning
respect of the scheduled maintenance
All the above mentioned points refer to the user and maintenance manual that will be
provided by EEI


4. Inverter for Photovoltaic application
PV Inverter
Modular electrical cabinet made of 20/10 steel sheet.
Frontal accessibility through doors fitted with lock and key.
Side and rear accessibility through bolted panels.

Each cabinet will have the following main characteristics, as per attached one line diagram:

Grid side 3P disconnector
Grid side contactor
Filter (LC)
PV Inverter composed by:
Power circuit with IGBT air cooled (Insulated Gate Bipolar Transistors)
Film capacitors
Microcontroller and DSP software for the digital management of all control
parameters, alarms, diagnostics, signal I/O analog and digital
PV side Disconnector
PV side Fuses
Surge suppressors grid side and PV side
230Vac auxiliary voltage from UPS provided by the customer
400Vac auxiliary supply voltage for cabinet fan
HMI unit

Safety and reliability
An insulation shielded transformer LV/MV for the connection to the mains is required and it
is not included in the scope of supply.

Auxiliary and control circuits:
Auxiliary relay set.
Auxiliary 230Vca/24 VDC power supply.



Circuit Breakers, for internal fans protection.
Circuit-breakers for auxiliary circuits.
Terminal block for power cables and signal cables.

Interface and communication
Communication protocol is MODBUS RS485

Factory test
Routine Tests are included;

Documentation
Following documentation will be provided:
Electrical drawing, according to IEC norms.
Complete Conversion System user manual
User and maintenance manual


Exclusions
Supply, erection and commissioning of PV modules
String Diodes
String Boxes
EMC filter
Grid interface rel and safe protection devices
DC cables and string cabling
Design and certification of grounding system.
Geological studies, excavation and foundation works.
Cabling between inverters and DC main combiner
Cabling and connection on AC side of inverters
LV/MV transformer
LV cabinet
MV switchgear
Lightening protection
Expenses for travel, boarding and lodging for training course attendees if any.
Everything not explicitly mentioned in the present supply proposal and annexure





Technical specifications of the Air cooled PV Inverter

Model 8YF500QNAF40

AC Output Parameters
Rated AC power 500 kW
Rated Voltage ( 10 %) 320 V
Rated Frequency (+ 4% - 6%) 50 Hz
Corrente C.A. nominale 950 A
Power Factor 0,95
Grid type 3P TI
THD(I) < 3 %

DC Input Parameters
DC input with independent MPPT 1
Maximum input power 500 kW
MPPT input Voltage range 5000850 V
DC Voltage: rated/maximum 650 /1000 V
DC Current: rated 1100 A (6 x 185 A)
Surge Suppressors Included
DC fuses Included

Weight and dimensions (estimated)
L / H / D 1680/2310/600 mm
Weight 1700 kg

Auxiliary UPS grid
AC voltage, current, type 230 V - 0,65 A - 1F
Fan auxiliary voltage 400 V - 1,7 A - 3F

Environmental condition
Operative temperature range -10C / +50C
Storage temperature range -15C / +55C




Inverter Single line drawing





Inverter Mechanical dimensions