Вы находитесь на странице: 1из 13

BRIEF SCOPE OF WORK

The brief scope of work comprises of, but not limited to, the following:
a. Design, supply, installation and commissioning of Integrated Building Management system
comprising of the following:
i. Building Automation system for
HVAC Lower Side (AHUs etc). Electrical System (HT/LT) including DG operation, Vertical Transportation
(Lift Management) system and Water Management System

ii. Integrated building management system including the IBMS software to integrate and monitor
the following services from a central location

Fire Detection & Alarm
Public Address
Access Control
Closed Circuit Surveillance & Digital Video Recording
Lighting Control
Water Management
Fire Fighting

Iii The following system specific to the requirement of the Data centre.:
Gas based Fire Suppression systems.
Water leak detection
Smoke Detection
Ultrasonic Pest Repellent system





















CHECK LIST FOR BMS

SUB-SECTION-1

INPUT AND OUTPUT SUMMARY FOR BAS.
S l.
NO
DESCRIPTION FUNCTI ONS LOCA
TION
AI AO D
I
D
O
STA
TUS
ALA
RM
CON
TROL
CONTROL/
MONITORING
1 DDC TYPE - A (For chiller) -
Chillers: - AHU
ROO
M - 1
AT
SEC
O
N D
FLO
O R.
1
Chiller ON/OFF command. Command from
PC/DDC to the chi l l er
MCC panel.
2 Chiller ON/OFF status. From chiller panel
3 Chiller Auto / Manual status. signal from A/M switch.
4
Chiller trip status. signal from potential
free contact.
5
Motorized Vavle ON/OFF Command signal from potential
free contact.
6 Motorized Vavle ON/OFF Status
7
Immersion type Temp sensor for In
and out
Signal from Immersion
type Temp sensor .
Primary Chilled Water Pumps-
8
Primary Chilled Water pumps ON /
OFF command.
Command from
PC/DDC to the primary
CHW Pumps panel.
9
Primary Chilled Water pumps ON /
OFF Status.
Differential pressure
switch.
10
Primary Chilled Water pumps Auto /
Manual status.
signal from A/M switch.
11
Primary Chilled Water pumps trip
status.
signal from potential
free contact.
12
Immersion type Flow switch signal For dry run
status



13 Secondary Chilled Water Pumps-

14 Secondary CHW pumps ON / OFF
Command.
Command from
PC/DDC to the
MCC panel.
15 Secondary CHW pumps ON / OFF
status.
Differential
pressure switch.
16 Secondary CHW pumps VFD speed
Control.
Proportional
signal from
DDC to the VFD
panel.
17 Secondary CHW pumps VFD speed
feedback.
signal from VFD.
18 Secondary CHW pumps trip status. VFD trip status .
19 Secondary CHW pumps A/M status &
Bypass status.
signal from A/M
switch.
20 Immersion type Flow switch signal for Dry
Run status
21 Differential pressure Switch across the
supply & return headers.(4 nos Pr
Pump, 3 Nos Sec pump)
Signal from DP
switch for flow.
22 Differential pressure sensor across the
common supply & return headers.
Differential
pressure
sensor.
23 CHW flow measurement Pulse O/P from
flow meter.
24 MCC power supply status. Command from
PC/DDC to the
MCC panel.
Total



2 TYPE - B ( For 1 NO AHU with VFD.) -
4Nos

1 AHU ON/OFF Command. 1 * At local control
panel
R E
F
D D
C
LO
CA
TI O
N
DR
2
AHU ON/OFF Status. 1 * At local control
panel
3
AHU Auto/Manual Status 1 * At Auto / Manual
switch
4 Filter status. 1 * DP switch
5
RA Temparature status 1 * F r o m
Temparature
sensor
7 CHW 2-Way Valve Control. 1 2 Way Valve



6 RA Rh status From Rh sensor AWI
NG.

with Actuator
8
Fire trip status. From Fire Relay
9
Fire Damper On/Off Status At local control
panel
10
VFD speed control. At VFD Panel
11
VFD speed refference. At VFD Panel
12
VFD trip status. At VFD Panel
13
Duct static pressure sensor. Pressure sensor
14
VFD Bypass status. At VFD Panel
Total


3 TYPE - C (3 Nos AHU's/CAHU with Starter
) - 2 Nos

1 AHU ON/OFF Command. At local control
panel
REF
DDC
LOCA
TION
DRA
W
ING.
2 AHU ON/OFF Status. At local control
panel
3 AHU Auto/Manual Status At Auto / Manual
switch
4 Filter status. DP switch
5 RA Temparature status F r o m
Temparature
sensor
6 RA Rh status From Rh sensor
6 CHW 2-Way Valve Control. 2 Way Valve with
Actuator
7 Fire trip status. From Fire Relay
8 Fire Damper On/Off Status At local control
panel
9 Duct static pressure sensor. Pressure sensor
Total




4 TYPE -D(4 Nos CAHU's with Starter )- 1
No

1 AHU ON/OFF Command. At local control
panel
REF
DDC
LOCA
TION
DRA
W
ING.
2 AHU ON/OFF Status. At local control
panel
3 AHU Auto/Manual Status At Auto / Manual
switch
4 Filter status. DP switch
5 RA Temparature status F r o m
Temparature
sensor
6 RA Rh status From Rh sensor
6 CHW 2-Way Valve Control. 2 Way Valve with
Actuator
7 Fire trip status. From Fire Relay
8 Fire Damper On/Off Status At local control
panel

9 Duct static pressure sensor. Pressure sensor
Total



5 TYPE -E (22 Nos PAC )- 1 No
1 AHU ON/OFF Command. At local control
panel
PAC
ROO
M AT
1ST
FLOO
R
Total



6 TYPE -F (7 Nos PAC )- 1 No
1 AHU ON/OFF Command. At local control
panel
PAC
ROO
M AT
1ST
FLOO
R
Total




SUB-SECTION 2

I/O SUMMARY

SECTION I: I/O LIST FOR HT/LT ELECTRICAL MONITORING
S.No
.
DESCRIPTION DI AI STATUS ALARM CONTR
OL
LINK LOCATI
ON
SUBSTATIION FUNCTIONS Signals
are
to be
acquired
from
Circuit
Breakers
&
Relays
over
serial
interface.
Electrical
contractor
shall
make
available
CBs and
relays
with
RS 485
port and
MODBUS
RTU
PROTOC
OL
SUB-
STATION
BLDG-
HT
ROOM

1. 0 11KV SWITCHGEAR SIGNALS
(HPCL HT PANEL SIDE)

1. 1 11 KV INCOMING VCB 630A
350 MVA

ON/OFF/Auto trip - functions
I n c o m i n g H T
voltage/current/frequency,pow
er,M VA - Measurements

1.2 MICROPROCESSOR BASED
RELAYS - Trip circuit Un-
Healthy

1.3 MANUAL OPERATION
STATUS -

1.4 11 KV RECEIVING VCB 630A
350 MVA

ON/OFF/trip - functions
I n c o m i n g H T
voltage/current/frequency,pow
er,M VA - Measurements

1.5 MANUAL OPERATION
STATUSon/off

1.6 MICROPROCESSOR BASED
RELAYS - Trip circuit Un-
Healthy

BATTERY CHARGER:
1.7 BATTERY CHARGER - Mains
on/ DC supply on/fails




1.8 BATTERY VOLTAGE -
Measurement

S.No
.
DESCRIPTION DI AI STATUS ALARM CONTR
OL
LINK LOCATI
ON
MAIN POWER CONTROL
CENTER
Signals
are
to be
acquired
from
Circuit
Breakers
&
Relays
over
serial
interface.
Electrical
contractor
shall
make
available
CBs and
relays
with
RS 485
port and
MODBUS
RTU
PROTOC
OL
SUB-
STATION
BLDG-
MPCC
ROOM

2.0 433 V INCOMING FEEDERS
For TRANSFORMERS

2.1 INCOMING 433 V 3200 AMPS
ACBS

2.2 ON/OFF/Auto trip - functions
2.3 I n c o m i n g L T
voltage/current/frequency,power,
M VA - Measurements

2.4 MICROPROCESSOR BASED
RELAYS - Trip circuit Un-
Healthy

2.5 MANUAL OPERATION
STATUS

BUSCOUPLER: - 1 NO
2.6 BUS Coupler - On/off/trip
2.7 MANUAL OPERATION STATUS
- On/off

DG INCOMER feeders: - 2 NOS
2.8 DG INCOMER - ACBS -
On/off/trip

2.9 I n c o m i n g L T
voltage/current/frequency, KW,
kVA - Measurements

3.0 MICROPROCESSOR BASED
RELAYS - Trip circuit Un-
Healthy

3.1 MANUAL OPERATION
STATUS-

4.0 UPS MONITORING



1.0 STATUS MONITORING,
VOLTAGE, CURRENT, LOAD,
BATTERY VOLTAGE ETC
6 NOS 200 AND 2 NOS 100
KVA UPS - Total around 80
soft points
RS 485
port and
MODBUS
RTU
PROTOC
OL t o be
provided
by UPS
vendor
Ground
floor
U P S
room
S.No
.
DESCRIPTION DI AI STATUS ALARM CONTR
OL
LINK LOCATI
ON
2.0 KW. Voltage, Amps from each
feeder through DATA Load
manager meter - Total 28
feeder each 5 soft points =
140 soft points
* RS 485
port and
MODBUS
RTU
PROTOC
O L t o
be
provided
by
Electrical
vendor
AT
METER
LEVEL
SUB-
STATION
BLDG-
MPCC.
The
wiring
shall be
takenout
and
terminte
d at one
common
chamber
by
electrical
vendor.
3.0 DG set - ON/Off status, KW,
Amps, Voltage, Frequency
etc through PLC -
Approximately - 50 soft point
RS 485
port and
MODBUS
RTU
PROTOC
O L t o
be
provided
by
Electrical
vendor IN
PLC
PANEL
SUB-
STATION
BLDG-
MPCC
ROOM
Total
DI = DIGITAL INPUTS AI= ANALOG INPUTS
SECTION-II

I/O LIST FOR /LT ELECTRICAL MONITERING
S.No
.
DESCRIPTION DI AI STATUS
ALAR
M
CONTRO
L
LINK
4.00
433V OUTGOING FEEDERS -
On/off/Trip status


LIFT FEEDER- 2NOS
4.10 FIRE HYDRANT PANEL--1
Thorugh
DDC
controllers.
BMS
vendor
to provide
the
controller
along with
wiring.
Electrical
vendor to
provide the
necessary
Potential
free
contact in
the each
breakers.
The wiring
shall be
taken out
and
terminated
at
one
common
chamber
by
electrical
vendor
4.20
CHILLER NO.1 ,2,3, AND STAND BY
FEEDER

4.30 CHILLER PUMPS PANEL - 2 NOS
4.40 WORKSTATION UPS- 2NOS
4.50 APFC PANEL - 2 NOS
4.60 SPARES- 4 NOS
4.70 SUBSTATIION PANEL
4.80 EMERGENCY LIGHTING FEEDER
4.90 AC PANELS- 5 NOS
5.00
LIGHTING AND POWER FEEDER -
2NOS

5.10 UPS FEEDERS- 2NOS
SECTION-III

WATER MANAGEMENT SYSTEM I/O LIST
FUNCTIONS
S. No DESCRIPTION AI DO AO STATUS ALARM CONTROL CONTROL/
MONITORING
LOCATION
THROUGH
DDC.
Local display
shall be
provided
indicating water
level and
pumps status
UG SUMP
AREA
AND
TERRACE
OH TANK
1 Pump ON/OFF
2 P u m p
trip,ON/OFF status

3 Linear levels for all
the sumps and tanks


Total



SECTION-IV
LIGHTING MANAGEMENT SYSTEM - I/O LIST
Sr
No.
DESCRIPTION FUNCTION CONTROL /
MONITORI
NG

DI AI DO AO STATU
S
ALARM CONTROL LOCATI
ON
I LIGHTING
MANAGEMENT
SYSTEM -
Controller-1

1 External Street Lighting
&
ON/OFF
Contactor
shall be
provided by
the
Electrical
vendor.
Controllojng
through
DDC
by BMS
vendor
SUB
STATIO
N
FACADE LIGHTING SUB
STATIO
N
Lighting MCCB
ON/OFF
SUB
STATIO
N
Controller-2 - 6 sets
2 Incomer MCCB switch
on/OFF at Ground floor,
Second floor LSSB
At floor level,
shall be
provided by
the
Electrical
vendor.
Controllojng
through DDC
by BMS
vendor
At floor
level
3 Induvidual circuit
ON/OFF controlls -
Each controller - 20
circuits

TOTAL


SECTION-V
FIRE FIGHTING PUMPS I/O LIST
FUNCTION
Sr.No DESCRIPTION DI DO AI AO STATUS ALARM CONTROL CONROL
/MONITORING

A) HYDRANT and
SPRINKLER PUMPS:
Status
monitoring
through DDC.
Suitable
potential-free
contacts shall be
Made available
by the Fire
Fighting
contractor


1 JOCKEY
PUMP: -1 NOS

Pump Trip
/ON/OFF
Status

2 HYDRANT
PUMP:- 2NOS

Pump Trip
ON/OFF Status

3 SPRINLER
PUMP
STANDBY
PUMP- 2 NOS

Pump Trip/
ON/OFF Status


TOTAL


SECTION-VI
I/O LIST FOR LIFTS
FUNCTION CONTROL
/MONITORI
NG
LOCAT
ION
Sr.
NO
DISCRIPTION SP DI AI DO AO STATU
S
ALARM CONTRO
L
1 Monitor alarm
bell status of
lifts
For
monitoring
through
DDG.
Potential free
contacts
shall be
made
available
by
Elevators
supplier.
L i f t
machin
e room
2 Mo n i t o r
Fireman's
emergency
operation
status

3 Monitor
operation of
elevator in
'Attendant
mode'

4 Monitor lift
u n d e r
inspection/test
drive

5 Moni t or l i f t
under fire drive

6 Trip Alarm
7 ON/OFF Status
8 FLOOR LEVEL
Status(each
lift 3 levels= 2
nos x 3 levels)

Total

Вам также может понравиться