Instruction manual

PROFIBUS DP slave interface


for digital multibus
Mass Flow / Pressure instruments
Doc. no.: 9.17.025P Date: 27-08-2013

ATTENTION
Please read this instruction manual carefully before installing and operating the instrument.
Not following the guidelines could result in personal injury and/or damage to the equipment.

HeadOffice:Nijverheidsstraat1a,NL7261AKRuurlo,TheNetherlands,Tel.+31573458800,info@bronkhorst.com

BRONKHORST

Disclaimer

Eventhoughcarehasbeentakeninthepreparationandpublicationofthecontentsofthismanual,wedonotassume
legalorotherliabilityforanyinaccuracy,mistake,misstatementoranyothererrorofwhatsoevernaturecontained
herein.Thematerialinthismanualisforinformationpurposesonly,andissubjecttochangewithoutnotice.

BronkhorstHighTechB.V.
July2011

Symbols

Importantinformation.Discardingthisinformationcouldcauseinjuriestopeopleordamagetothe
Instrumentorinstallation.

Helpfulinformation.Thisinformationwillfacilitatetheuseofthisinstrument.

Additionalinfoavailableontheinternetorfromyourlocalsalesrepresentative.

Warranty

TheproductsofBronkhorstHighTechB.V.arewarranteedagainstdefectsinmaterialandworkmanshipforaperiod
ofthreeyearsfromthedateofshipment,providedtheyareusedinaccordancewiththeorderingspecifications
andtheinstructionsinthismanualandthattheyarenotsubjectedtoabuse,physicaldamageor
contamination.Productsthatdonotoperateproperlyduringthisperiodmayberepairedorreplacedatnocharge.
Repairsarenormallywarrantedforoneyearorthebalanceoftheoriginalwarranty,whicheveristhelonger.

Seealsoparagraph9oftheConditionsofsales:
http://www.bronkhorst.com/files/corporate_headquarters/sales_conditions/en_general_terms_of_sales.pdf

Thewarrantyincludesallinitialandlatentdefects,randomfailures,andundeterminableinternalcauses.

Itexcludesfailuresanddamagecausedbythecustomer,suchascontamination,improperelectricalhookup,physical
shocketc.

Reconditioningofproductsprimarilyreturnedforwarrantyservicethatispartlyorwhollyjudgednonwarrantymay
bechargedfor.

BronkhorstHighTechB.V.oraffiliatedcompanyprepaysoutgoingfreightchargeswhenanypartyoftheserviceis
performedunderwarranty,unlessotherwiseagreeduponbeforehand.However,iftheproducthasbeenreturned
collecttoourfactoryorservicecenter,thesecostsareaddedtotherepairinvoice.Importand/orexportcharges,
foreignshippingmethods/carriersarepaidforbythecustomer.

Page2

PROFIBUSDPinterface

9.17.025

BRONKHORST

Tableofcontents

GENERALPRODUCTINFORMATION....................................................................................................4
1.1
INTRODUCTION ............................................................................................................................................. 4
1.2
MULTIBUSTYPES ........................................................................................................................................... 4
1.3
REFERENCESTOOTHERAPPLICABLEDOCUMENTS ................................................................................................... 5
1.3.1
Manualsanduserguides: ........................................................................................................................... 5
1.3.2
TechnicalDrawings: .................................................................................................................................... 5
1.3.3
Softwaretooling: ........................................................................................................................................ 5
1.4
SHORTFORMSTARTUP................................................................................................................................... 6
1.5
OPERATINGPRINCIPLES ................................................................................................................................... 7

FIELDBUSINSTALLATION ...................................................................................................................8
2.1
2.2
2.3
2.4
2.5
2.6

CONFIGURATION..............................................................................................................................12
3.1
3.2
3.3
3.4
3.5

GENERAL ..................................................................................................................................................... 8
PROFIBUSCONNECTOR ................................................................................................................................. 8
PROFIBUSDPCABLES .................................................................................................................................. 9
MAXIMALCABLELENGTHWITHPROFIBUSDP .................................................................................................... 9
SPURLINESWITHPROFIBUSDP.................................................................................................................... 10
NETWORKTERMINATION ............................................................................................................................... 11
GSDFILE .................................................................................................................................................. 12
CONFIGURATIONSOFTWARE ........................................................................................................................... 13
ADDSLAVETOPROFIBUSDP ....................................................................................................................... 14
SLAVECONFIGURATIONSETTINGS .................................................................................................................... 15
SLAVEPARAMETERSETTINGS .......................................................................................................................... 16

SLAVEADDRESSING..........................................................................................................................17
4.1
4.2
4.3
4.4
4.5
4.6

GENERAL ................................................................................................................................................... 17
VIAROTARYSWITCHESONTHESIDEOFINSTRUMENT(IFPRESENT) ........................................................................... 17
VIAPROFIBUS:......................................................................................................................................... 17
VIARS232:FLOWFIX .................................................................................................................................. 18
VIARS232:OTHERPROGRAMS ...................................................................................................................... 19
VIAMICROSWITCHANDLEDSONTOPOFINSTRUMENT ........................................................................................ 19

DOWNLOADTOMASTER..................................................................................................................20

TESTCOMMUNICATION ...................................................................................................................21

SAFESTATE ......................................................................................................................................22

TROUBLESHOOTING .........................................................................................................................23
8.1
8.2

LEDINDICATION .......................................................................................................................................... 23
TROUBLESHOOTINGHINTSANDTIPS ................................................................................................................. 24

SERVICE............................................................................................................................................25

Page3

PROFIBUSDPinterface

9.17.025

BRONKHORST

1 GENERALPRODUCTINFORMATION
1.1 INTRODUCTION

This manual will explain how to install a Bronkhorst1 instrument to


your PROFIBUS DP system. It only contains information which is
neededmost.

More detailed information about PROFIBUS can be


obtained on the website of the (international)
PROFIBUS organization: www.profibus.com or on
the website of the (local) PROFIBUS organization of
yourcountry(whenavailable).

ExampleofaBronkhorstinstrument
withPROFIBUSinterface

1)

Bronkhorst:

ThisincludesBronkhorstHighTechB.V.,BronkhorstCoriTechB.V.and
M+WInstrumentsGmbH.

1.2 MULTIBUSTYPES

In2000Bronkhorstdevelopedtheirfirstdigitalinstrumentsaccordingtothe
multibusprinciple.Thebasicpcboardontheinstrumentcontainedallof
the general functions needed for measurement and control, including
alarm,totalizinganddiagnosticfunctions.IthadanalogI/Osignalsandalso
anRS232connectionasastandardfeature.Inadditiontothisthereisthe
possibilityofintegratinganinterfaceboardwithDeviceNet,ProfibusDP,
Modbus , FLOWBUS or EtherCAT protocol. The first generation (MBCI)
wasbasedona16bitFujitsucontroller.Itwassupersededin2003bythe
Multibustype2(MBCII).Thisversionwasalsobasedonthe16bitFujitsu
controllerbutithadseveralimprovementstotheMBCI.Oneofthemisthe
current steering of the valve. It reduced heat production and improved
controlcharacteristics.ThelatestversionMultibuscontrollertype3(MBC3)isintroducedin2011.Itisbuildarounda
72MHz32bitNXPARMcontroller.IthasADandDAcontrollersonboardwhichmakesitpossibletomeasurenoise
freeandcontrolvalveswithoutdelays.Theinternalcontrolloopruns6timesfastercomparedtotheMBCIItherefore
control stability has improved significantly. It also has several improved functions like reverse voltage protection,
inrushcurrentlimitationandovervoltageprotection.

MBC3instrumentscanberecognisedbytheMBC3placedonlowerleftside
oftheinstrumentlabel(seeexample).

Page4

PROFIBUSDPinterface

9.17.025

BRONKHORST

1.3 REFERENCESTOOTHERAPPLICABLEDOCUMENTS

Manualsandguidesfordigitalinstrumentsaremodular.Generalinstructionsgiveinformationaboutthefunctioning
and installation of instruments. Operational instructions explain the use of the digital instruments features and
parameters. Field bus specific information explains the installation and use of the field bus installed on the
instrument.

1.3.1

Manualsanduserguides:
Generalinstructions
Instrumenttypebased

Operational
instructions

Document9.17.022

Fieldbusspecific
information

Document9.17.023

BronkhorstHighTech
GeneralinstructionsdigitalMassFlow/Pressure

Document9.17.024

FLOWBUSinterface

Operationalinstructions
fordigitalmultibus
MassFlow/Pressure
instruments

Document9.17.031
BronkhorstCoriTech
GeneralinstructionsCORIFLOW

Document9.17.050
BronkhorstCoriTech
GeneralinstructionsminiCORIFLOW

Document9.17.044
BronkhorstHighTech
GeneralinstructionsdigitalLIQUIFLOWL30

Document9.17.025

PROFIBUSDPinterface

Document9.17.026

DeviceNetinterface

Document9.17.035

Modbusinterface

Document9.17.027
RS232interfacewith
FLOWBUSprotocol

M+WInstruments
InstructionmanualMASSSTREAMD6300

Document9.17.063

EtherCATinterface

1.3.2

TechnicalDrawings:

HookupdiagramlaboratorystylePROFIBUS
HookupdiagramindustrialstylePROFIBUS
HookupdiagramCORIFLOWPROFIBUS
HookupdiagramLIQUIFLOWL30digitalPROFIBUS

1.3.3

(documentnr.9.16.061)
(documentnr.9.16.053)
(documentnr.9.16.049)
(documentnr.9.16.072)

Softwaretooling:

Flowfix
FlowDDE
GDSfile

Page5

Allthesedocumentscanbefoundat:
http://www.bronkhorst.com/en/downloads

PROFIBUSDPinterface

9.17.025

BRONKHORST

1.4 SHORTFORMSTARTUP

AllnecessarysettingsforthismodulearealreadyperformedatBronkhorst.
To follow next steps carefully is the quickest way to get this module operational in your own PROFIBUS
environment.

START

Master
present

MakesureyourmasterhasbeeninstalledtothePROFIBUSsystem

LoadGDS

LoadGDSfileintotheconfigurationtool.(SoftwareatPROFIBUSmaster)
Bitmaps(withflowcontrollers)canbecopiedintheproperdirectory(mostly
automatic,sometimesbyhand;dependsonprogram)

Copybitmaps

AddslavetoPROFIBUS
system

Select"Bronkhorst meter/controller"andaddnewinstrumenttothebus (with


configurationtool)

Setslaveconfiguration

Selectwantedmodulesoutofavailablelistwithmodules.Thesemodulesarethe
parametersforinstrumentswhichareavailableforcyclicreading/writingbya
PROFIBUSDPmaster.Minimumselectionwillbeprobably"measure,integer
(read)"and"setpoint,integer(write)".Theseparameterswillbestackedinto
yourmasterI/Omemory.InputsandOutputswillbestackedseparatelyinorder
ofappearanceofinsertingthemodules.
E.g.:ifyoualsowanttoreadbacksetpointfromPROFIBUS,alsoselect:"setpoint,
integer(read)"
Thesesettingswillbecopiedtotheinstrumentonlyatstartup.Examplesof
usefulparametersare:Fluidnumber,controlmode,setpoint,counterand
alarmsettings.Settingparameterdataisnotnecessary,butoptional.

Setparameterdata

Setslavestationaddress

Downloadconfiguration

Defaultinstrumentswillbedeliveredtocustomersonaddress126.Thisisthe
agreedstationaddressforPROFIBUSDPsystemsforinstallingnewinstruments
toasystem. Severalmethodsforsettingthestationsaddresscanbefoundinthis
manual.
Downloadallconfigurationsettingsintoyourmaster
Testdataexchangecommunicationbetweenyourmasterandthe
instrument(s)

Testdataexchange

Ready

Page6

PROFIBUSDPinterface

9.17.025

BRONKHORST

1.5 OPERATINGPRINCIPLES

PROFIBUS DP is a 2wire industrial data communication standard (Field bus) which allows automation components
likesensors,actuatorsandcontrollerstoexchangeinformation.

SimplePROFIBUSsystem.

PROFIBUSDPisamaster/slavebussystem.Bronkhorstinstrumentsareallslaves.Thereisnomutualcommunication
betweenPROFIBUSDPslaves,onlybetweenamasterandslave.Eachslavemusthaveitsownuniquestationaddress
onthebus,otherwisethereisnocommunicationpossible.Settingslavestationaddresscanbeperformedbyeither:

Viarotaryswitches(Nonindustrialinstruments)
Masterconfigurationsoftware.
Forexample:
SyconV2.6.2.fromHilscherG.m.b.H.(inthismanual)
Step7V5.1fromSiemensforPLCtypeS73002DP.
Mostmasterconfigurationsoftwaretoolsworkinthesameway,becausePROFIBUSDPisastandardizedfield
bussystem.Onlyondetailsandprogramoperationthingscouldbedifferent.
ReadusermanualcarefullyforcorrectoperationofotherprogramsthanSyconandStep7.
Bronkhorsttoolingsoftware:eqFlowFix
TheBronkhorsttoolingsoftwareisabletocommunicatewiththeinstrumentviaRS232usingaspecialcable.If
youdonthavesuchacableaskyourlocalsalesrepresentative.
ViaMicroswitchandLeds

PROFIBUSDPslavesusing,willadaptautomaticallytobaudratesdeterminedbythemasteronabus
segment.

Page7

PROFIBUSDPinterface

9.17.025

BRONKHORST

2 FIELDBUSINSTALLATION
2.1 GENERAL

The following installation guidelines only apply to data transfer using copper cables (RS 485) to EN
50170.Furthermore,operatorsofPROFIBUSequipmentarestronglyrecommendedonlytousefieldbus
devicesandcomponentswhichhavebeencertifiedbythePROFIBUSUserOrganizatione.V.(PNO).
Certified products have undergone extensive tests carried out by specialists to demonstrate their
compliance to the PROFIBUS standard EN 50170 in combination with PROFIBUS devices from other
manufacturers.PROFIBUSdatatransferisbasedontheRS485standard1.Therelevantfeaturesforuse
withPROFIBUSDParedescribedinEN50170.

PROFIBUSDPfieldbuswiringisthecauseofmanyproblemsifnotproperinstalled.
Pleaseusetheinstructionsbelowandthosementionedonwww.profibus.com

2.2 PROFIBUSCONNECTOR

ThechassisfemalePROFIBUSDP(subminiature9pin)Dconnectorhasthefollowingpinconfiguration:
Pinnumber
Description
1
notconnected
2
notconnected
3
RxD/TxDP

plus(Bwire)
4
RTS
5
DGnd
6
VP(+5V)
7
notconnected
8
RxD/TxDN

minus(Awire)
9
notconnected

ThechassisfemalePROFIBUSM12Bcodedconnector(IP65)hasthefollowingpinconfiguration:
Pinnumber
Signal
Description
1
VP
Powersupplyplus,(P5V)
2
RxD/TxDN
Receive/TransmitdataN,Aline
3
DGND
Dataground(referencepotentialtoVP)
4
RxD/TxDP
Receive/Transmitdataplus,Bline
5
notconnected

Thread
Shield
ShieldorPE

Page8

PROFIBUSDPinterface

9.17.025

BRONKHORST

5
3

1
Bcoded

2.3 PROFIBUSDPCABLES

PROFIBUS cables are shielded twistedpair copper cables which differ from each other in the type of wire
(fixed/flexible) and/or sheath. The two inner cores of a PROFIBUS cable have green and red insulation. The
specifications in this chapter are primarily intended to provide a general introduction and describe the cable
propertiestobeconsidered(seealsoIEC6178453).

The cables for PROFIBUS DP are assigned to categories, the socalled line types, which define specific physical
parameters.TheindividuallinetypesareidentifiedbythecapitallettersA,B,CandD.Whenplanninganetworkyou
shouldexclusivelyuselinetypeA.
ThetablebelowshowstheparametersoflinetypeAthatmustbecompliedwith.

Parameter
Specifiedlimits
Impedance
135..165withf=3...20MHz
Operationalcapacity
30pF/m
Loopresistance
110/km
Wirediameter
>0.64mm
WireCSA
>0.34mm2

2.4 MAXIMALCABLELENGTHWITHPROFIBUSDP

Themaximumtransmissiondistance(TrunkLine),thatcanbeachievedusingcoppercablesisdirectlyrelatedtothe
transmissionspeedchosenforthePROFIBUSDPnetwork.Asaresult,thesetwovariablesmustalwaysbeconsidered
together.ThedatatransmissionrateofPROFIBUSDPisadjustableindefinedstepsbetween9.6and12.000kbits/s.
The data transmission rate must be identical for all segments of a PROFIBUS line. The table below shows the
maximumpossibletransmissiondistancesthatcanbereachedwhenusingcoppercables.Theminimalcabledistance
betweentwodeviceconnectionsisone(1)meter.

Transmissionrate(kbits/s)
maximumTransmissiondistance*(LT)(meter)
9.6
1200
19.2
1200
45.45
1200
93.75
1200
187.5
1000
500
400
1500
200
3000
100
6000
100
12000
100
*CalculatedforPROFIBUScabletypeAat30pF/m

Page9

PROFIBUSDPinterface

9.17.025

BRONKHORST

2.5 SPURLINESWITHPROFIBUSDP

(Alsoknownasstubsorbranches)

Intable5themaximumspurcapacitanceissetouttothebaudrate.
WiththeuseofPROFIBUScabletypeAthiswillresultinthestatedlength.

Spurlinesarenotallowedwhenusinghigherbaudrates(>1.5Mbit/s).
Atbaudrateslowerthan1.5Mbit/s,spurlinesarealloweduptothemaximumcapacitanceforthe
baudrate.

Transmissionrate
(kbit/s)
19.2
93.75
187.5
500
1500
>1500

Totalallowablespurcapacitance
TotalSpurcablelength*(LS)
(nF)
(m)
15
500
3.0
100
1.0
33
0.6
20
0.2
6.7
none
None
*CalculatedforPROFIBUScabletypeAat30pF/m

ThemaximalSpurlinelengthis0.25m
ThetotalSpurlinelengthofasegmentrepresentsthesumofallSpursattachedtothatsegment.
TheminimalTrunklinelengthshouldbelongerthenthesumofallSpurlines
SpursonDPsegmentsshouldbeavoidedwherepossible.
EachPROFIBUSdevicewillhaveashortSpurlinecarryingthebussignalsbetweentheexternalbus
connectoranditsRS485driverchip(forcalculationsuseabout5cmpernode).
Devicesaretestedforreflectionsaspartofthecertificationprocess.
Uncertifieddevicescancausereflections.

Example:
WeareinstallingaM12systemwith19nodesandaspurlengthof25cm.
Additional30SubDinstrumentsareinstalled.
Transmissionrateat1500kbits/s.

Isthisallowed?
(19nodesx25cm+19nodesx5cm)+32nodesx5cm=7.3m
Themaximumspurlengthat1500kbits/sis6.7msothisisnotallowed.

Whenspurlinesareinstalled,additionalterminationattheendofaspurlineshouldnotbeused!
Therulethatwemustneverexceedtwoterminationspersegment,stillappliesevenifusingspurs.

References:
http://PROFIBUScentre.com.au/docs/DP_Spur_Lines.pdf

Page10

PROFIBUSDPinterface

9.17.025

BRONKHORST

2.6 NETWORKTERMINATION

APROFIBUSDPnetworksegmentisbasedonanRS485standardandrequirestwo(2)andonlytwo(2),termination
resistornetworks,ateachofthefurthestendsofthePROFIBUSDPcabling.Theseresistornetworksareintegratedin
theIP20connectorsandcanbeenabledbyaslideswitchonthesideoftheconnector.Ifconnectorswithoutthese
integratedresistorsareused,aspecialterminationplugcontainingthisresistormustbeplaced.

ExampleofaVP=5Vbusterminationnetwork.
Laboratory style
Industrial style

VP (pin 6)
VP (pin 1)

390 Ohm
390 Ohm

B-line (pin 3)
B-line (pin 4)

220 Ohm
220 Ohm

A-line (pin 8)
A-line (pin 2)

390 Ohm
390 Ohm

DGND (pin 5)
DGND (pin 3)

To allow correct bus termination, each station must connect the signals DGND and VP (5 V) to pins 5 and 6 of the
connector,respectively.The5Vsupplyfortheterminatingresistors(VP)shouldhaveaminimumcurrentratingof10
mA (thecurrent load can increase to 12mA if a NULLsignal is sent through thebus). Thecurrent rating shouldbe
increasedtoapp.90mAifyouneedtobeabletosupplyothertypesofdevicesonthebussuchasbusterminalsand
opticalfibercabledrivers.

The electrical equipment in a plant is generally connected to a functional ground. It is used to lead away potential
equalizationandinterferencecurrentsandtoensurecompliancewithEMCregulationsandshouldthusbeinstalled
withregardtotherequirementsofhighfrequencycurrents.

Duetothecapacitiveloadofthestationandtheresulting
cablereflections,busconnectorsshouldbeprovidedwith
builtinseriesinductorsasshownbelow.

Duetothebuiltinseriesinductorsinthebusconnectors,
allbusconnectorsinthenetworkshouldbeattachedtothe
fieldbus.

References:
http://PROFIBUScentre.com.au/docs/DP_Spur_Lines.pdf
http://www.PROFIBUS.com

Page11

PROFIBUSDPinterface

9.17.025

BRONKHORST

3 CONFIGURATION
3.1 GSDFILE

Each type PROFIBUS DP instrument should have its own GSDfile with instrument specifications to tell the master
configuration software which facilities/features the instruments offers to the PROFIBUS system. For Bronkhorst
meter/controllerthefileiscalled:BHT_0586.GSD.ThisfileisavailableontheMultibusdocumentation/softwaretool
CD.

ThisGSDfileisatextfilecontaining:

Identificationinfo:

Modelname: Bronkhorstmeter/controller
Vendorname: BronkhorstHighTechB.V.
Indentnumber: 0x0586
Bitmapdevice: 0586_dev

Bitmapdiag:
0586_dia
BitmapSF:
0586_spf
(Bitmapfilesareusedinconfigurationsoftwaretoindicateinstrumentstatus)

Revisionnumbers

Hardwarecharacteristics:
SPC3ASIC/VPC3+Cdependableproperties

Softwarecharacteristics:
SupportedfeaturesofPROFIBUS:Freeze,Sync,autobaudratedetection

Max.busdatalengths:
Sizeofuseddatabuffers

Parameterdialogboxesandparameterdataforacyclicinstrumentvariablesettings.

Moduleswithcyclicinput/outputvariablesfortheinstrument.

Afterstartingupyourmasterconfigurationsoftware,thisGSDfileshouldbeload/import/copied.
Thisisneededonlyonce(untilaneventualnextrevisionfromthefile).

Page12

PROFIBUSDPinterface

9.17.025

BRONKHORST

3.2 CONFIGURATIONSOFTWARE
InthismanualweuseasanexamplethesoftwaretoolfromHilscherG.m.b.H.

TheconfigurationtoolsofferviewingscreenstomonitorimportantGSDsettings.
Examplesofthesescreenswiththeirsettings:

Page13

PROFIBUSDPinterface

9.17.025

BRONKHORST

3.3 ADDSLAVETOPROFIBUSDP

Inyourmasterconfigurationsoftwareselect:[Insert][slave].
Select[Bronkhorstmeter/controller]andevt.press[Add].

Anexampleofthisprocedurecanbefoundbelow:

OnthemainscreentheaddedBronkhorstinstrumentcanbefound.

Page14

PROFIBUSDPinterface

9.17.025

BRONKHORST

3.4 SLAVECONFIGURATIONSETTINGS

Bronkhorst PROFIBUS DP instruments offer many available modules/parameters for operation of the instruments.
Thesemodules/parameterscanbeselectedbymeansofthemasterconfigurationtoolingsoftware(afterloadingthe
GSDfile:BHT_0586.GSD).

AfterinstallingtheslavetothePROFIBUSDPsystem,pointtoactualslaveandselect:[slaveconfiguration].Inthefirst
tableallavailablemodulesarelisted.Selectthoseinstrumentvariablesyouwanttouse.Theselectedmoduleswillbe
displayedinthesecondtable.

Page15

Moreinformationaboutmodules/parametersoranexampleofcounterandalarmusagecanbefound
inthemanual917023Operationalinstructionsdigitalinstruments
Thisdocumentcanbefoundat:
http://www.bronkhorst.com/en/downloads/instruction_manuals/

PROFIBUSDPinterface

9.17.025

BRONKHORST

3.5 SLAVEPARAMETERSETTINGS

If you want to give your instrument specific values for certain variables at startup you can do this by means of
parametersettings.Inyourmasterconfigurationtool,pointtotheactualslaveinstrumentandselect[Parameterdata]
(alsoaccessiblesometimesfromslaveconfigurationscreen).Afterpressing[common]allavailableparameterdatawill
becomevisible.

Selecting/doubleclickingonavaluetobechangedwilleitherpopupanotherwindowwithavailableoptionsora
windowwithaneditbox.

Page16

PROFIBUSDPinterface

9.17.025

BRONKHORST

4 SLAVEADDRESSING
4.1 GENERAL
When you have installed your Bronkhorst meter/controller PROFIBUS DP slave and made right settings for slave
configurationandparameterdata,youcangiveyourinstrumenttheslaveaddressyouwant.Defaultinstrumentswill
be delivered with slave address 126. This address has been agreed by the PROFIBUS organization to be free for
installingnewdevicestothebus.Changingthestationaddresscanbeperformedinfivedifferentways:

4.2 VIAROTARYSWITCHESONTHESIDEOFINSTRUMENT(IFPRESENT)

Onthesideoftheinstrumentarerotaryswitchesplacedandalabelwiththe
explanationoftheswitches.Makesuretouseasuitablescrewdriverforthe
switches.

Theswitcheshavethefollowingfunction:

ADDRESS(0099)

WiththeADDRESSswitch,theslavestationaddresscanbeset.TheMSDisthehighpartofthedecimalnumberand
theLSDthelowpart.Forinstanceaddress25meansMSDon2andLSDon5.Thedefaultswitchpositionis00.Inthis
positiontheaddressissoftwareprogrammable.Thedefaultsoftwareprogrammableaddressis126.

Duringinstrumentinitialization,theaddressswitchesareread.IftheswitchesspecifyavalidPROFIBUSslavestation
address,i.e.avaluefrom1to99,thisvalueisused.

Settingtheaddressisbytherotaryswitches(nonzero)overrulesallothermethodsofaddressing.
Thismeansthatsoftwareaddressingisnolongerpossible.

4.3 VIAPROFIBUS:

Normalwaytochangeaddresses.Pointtoactualslaveinyourmasterconfigurationtoolandselect[online][Setslave
address].Givecorrectoldaddressandnewaddressandpress[Setaddress].

Page17

PROFIBUSDPinterface

9.17.025

BRONKHORST
Readdress action can be checked using the option Live list. This gives an overview of all masters and slaves
connectedtoaPROFIBUSsegment.

4.4 VIARS232:FLOWFIX

OfflineviaRS232servicecommunicationportbymeansofaspecialtoolingprogram,calledFlowFix.
FlowFixisatoolformultibusinstrumentswhichcanbeusedforallfieldbussesenablingtheuserto:

Changeslavestationaddress
Readandevt.changebaudrate(dependsonfieldbussystem)
MakeaservicelogfiletobesendtoBronkhorstincaseoftrouble

FlowFixsoftwarecanbefoundattheBronkhorstwebsite
http://www.bronkhorst.com/en/products/accessories/software_tools/

ConnectyourBronkhorstmeter/controllerPROFIBUSDPslaveinstrumenttoafreeCOMportusingthecable
mentionedbelow.

Page18

AspecialRS232cable(7.03.366)canbeorderedseparately.ItconsistsofaTpartwith1maleand1
femalesubD9connectorononeinstrumentsideandanormalfemalesubD9connectoronthesideof
thecomputer.BymeansofthiscableitispossibletoofferRS232communicationandstillbeableto
connectpowersupplyandanaloginterfacethroughthe(analog)subD9connector.

PROFIBUSDPinterface

9.17.025

BRONKHORST

StartupFlowFix.exeandselectCOMport.Thentheconfigurationscreenwillappear.

Enterslavestationaddressandpress[OK].ChangingbaudratewillhavenoeffectforPROFIBUSdevicesbecausethe
slavewilladaptautomaticallytothebaudrateofthemaster.Baudrateisonlymeanttoberead.Readdressaction
canbecheckedusingtheoptionLivelist.ThisgivesanoverviewofallmastersandslavesconnectedtoaPROFIBUS
segment(seeexampleinpreviousparagraph).

4.5 VIARS232:OTHERPROGRAMS

ItisalsopossibletoreadandorchangeslavestationaddressorbaudratebymeansofanyprogramviaRS232using
theCOMportofyourPCon38400Baud.ThiscanbeachievedusingtheFLOWBUSprotocol.

Process Parameter Type R/W Initmode Description


125
9
LONG R/W
Softinit Baudrateforfieldbusinterface(PROFIBUS:Readonly)
125
10
CHR
R/W
Softinit Fieldbusstationaddress/MACID
Table6:AddresssettingandBaudratereadingbyRS232Propar

MoredetailedinformationabouttheRS232protocol(document9.17.027)canbefoundat:
http://www.bronkhorst.com/en/downloads/instruction_manuals/

4.6 VIAMICROSWITCHANDLEDSONTOPOFINSTRUMENT

With the microswitch on top of the instrument it is possible to change and readout the settings for slave station
address and baud rate. The Leds will indicate the tens of the address with green flashes and the units with red
flashes. For baud rateindication both Leds will flash (baud rate will adjust to master setting automatically and is
thereforereadonly).

Seedocument9.17.023foradetaileddescription
Thisdocumentcanbefoundat:
http://www.bronkhorst.com/en/downloads/instruction_manuals/

Page19

PROFIBUSDPinterface

9.17.025

BRONKHORST

5 DOWNLOADTOMASTER

When slave has been installed and all settings are done, everything has to be downloaded to the master. Point to
actualmasterandselect[online][download].Whenthisisready,fromthatmomentontherewillbedataexchange
betweenmasterandslave.TheredLedontheinstrumentwillstopblinkingslowlyandwillgooffwhendataexchange
isO.K.

DataexchangebetweenmasterandslavescanbecheckedwithSycon.
Select[online][startdebugmode].WheneverythingisO.K.thescreenlookslikethis:

Itispossiblethatyourmasterconfigurationsoftwaredoesnotsupportthisoption.
Whenthereissomethingwrong,seedevicediagnosticfordetails.

Page20

PROFIBUSDPinterface

9.17.025

BRONKHORST

6 TESTCOMMUNICATION

SomemasterconfigurationtoolprogramsofferfacilitiestoreadinputI/OandwriteoutputI/Odata.
Inthismonitoronlythefirst32bytesfromyourinputandoutputdataareawillbedisplayed.

Ifyourprogramdoesnotsupportsuchoption,youhavetouseyourmastersoftwareorotheravailable
programstocheckcommunicationbetweenmasterandslave(s).

Page21

PROFIBUSDPinterface

9.17.025

BRONKHORST

7 SAFESTATE

If PROFIBUS communication problems occur, so when instrument is not in data exchange mode, the
instrument forces the valve (controllers only) into a safe state mode. This safe state depends on the
typeofvalve.NCvalveswillbeclosed,NOvalveswillbeopenedfully.ThegreenandredLedontopof
theinstrumentindicatesthismodebyashortflash:0.1secon,2secoff.Aslongasthereisnodata
exchange between master and slave the instrument will stay in this mode. It will leave this mode
automaticallywhendataexchangestarts.ViatheRS232communicationinterfaceitispossibletoforce
the instrument out of the safe state by changing the control mode to a value other than 0. At for
examplecontrolmode=18(RS232)orcontrolmode=1(Analoginput)theinstrumentwillnotgetinto
safestate.

Page22

PROFIBUSDPinterface

9.17.025

BRONKHORST

8 TROUBLESHOOTING

8.1 LEDINDICATION

Led

Time

Green
off
on
Shortflash

Continuously
Continuously
0.1secon,
2secoff

normalflash

Red
off
shortflash

0.2secon,
0.2secoff

Indication
Powerofforprogramnotrunning
Normalrunning/operationmode
Initializationmode
Securedparameterscanbechanged
Safestateactive
Specialfunctionmode
Instrumentisbusyperforminganyspecialfunction.
E.g.autozeroorselftest

Continuously
0.1secon,
2secoff

normalflash

longflash
on

WinkMode
slowwink

normalwink
fastwink

Noerror
Buscommunicationwarning.Instrumentfunctionso.k.
Nodataexchangebetweenmasterandslave.
Automaticrecovery.
0.2secon,
Warningmessage.
0.2secoff
Anerroroccurredofminorimportance.
Itwouldbewisetoinvestigatethecauseofthis.
Youarestillabletoworkwithyourinstrument.
2secon,
Arequestedparameterisnotavailable.
0.1secoff
SeetroubleshootinProfibusmanual.
Continuously
Criticalerrormessage.
Aseriouserroroccurredintheinstrument.
Instrumentneedsservicebeforefurtherusing.

Red
Green
Red turnbyturn
Green
0.2secon,
Winkmode
0.2secoff
ByacommandsendviaFLOWBUStheinstrumentcanwink
withLedstoindicateitspositionina(large)system
1secon,
Alarmindication:minimumalarm,limit/maximumalarm;power
1secoff
upalarmorlimitexceededorbatchreached.
0.1secon,
Switchreleased,selectedactionstarted
0.1secoff

Page23

PROFIBUSDPinterface

9.17.025

BRONKHORST

8.2 TROUBLESHOOTINGHINTSANDTIPS

PROFIBUSproblems
NoCommunication

Flowisnotreactingto
setpointcommands

Checkpowersupplyandcabling.
Checkbustermination.Atthebeginningandendofabussegment,termination
shouldbeenabledinyourconnectororbymeansofanyexternalspecialresistor
network.
CheckallPROFIBUSsettingsatyourmaster.Masterandslavesettingsforuseof
memorymodulesmustbethesame.Selectatleastonemodulee.g.Measure,
integer(read)otherwisetherewillbenodataexchange.
Checkaddressofinterface(slave)
Trytoresettheinstrumentand/orrestartyourmaster.
Makesureallsettingsforyourslavearedownloadedtoyourmaster(otherwiseit
wontwork).
ContactPROFIBUSsalesrepresentativeorservicedepartment.
IncaseofPROFIBUScommunicationproblemsinstrumentwillputitsvalveintoa
safestate.Thiswillclose(NC)oropenthevalvefully(NO).Whendataexchange
betweenmasterandslavehasbeenreestablished,instrumentwillrespondto
setpointagain.ForoverrulingsafestateviaRS232interface,seesetpoint/control
modesinchapter2.5fromdoc.nr.9.17.023,(digitalinstrumentdescription).

MakesuretherequestedparametersareavailableintheparticularBronkhorst
ProfibusDPslave.
DeletetheProfibusslaveconfigurationandaddanewslaveinyoursoftware,this
willremoveacorruptioninthesoftwareconfiguration.

RedLedhaslongflash

Page24

PROFIBUSDPinterface

9.17.025

BRONKHORST

9 SERVICE

ForcurrentinformationonBronkhorstandserviceaddressespleasevisitourwebsite:

http://www.bronkhorst.com

Doyouhaveanyquestionsaboutourproducts?OurSalesDepartmentwillgladlyassistyouselectingtherightproduct
foryourapplication.Contactsalesbyemail:

sales@bronkhorst.com

Foraftersalesquestions,ourCustomerServiceDepartmentisavailablewithhelpandguidance.TocontactCSDbye
mail:

support@bronkhorst.com

Nomatterthetimezone,ourexpertswithintheSupportGroupareavailabletoansweryourrequestimmediatelyor
ensureappropriatefurtheraction.Ourexpertscanbereachedat:

+31573458839

Page25

PROFIBUSDPinterface

9.17.025