200 milliseconds.
The necessary power supply, electrical cables, and amplifier and logic circuitry are to be provided by the
Purchaser.
For proper utilization of the redundancy afforded by two flame detectors, the Purchasers logic circuitry
must be designed such that both detectors sense loss of flame before logic or control action initiates a
shut down.
It is recommended that the user employ a signal conditioning system which incorporates provisions for a
http://inside-aep.ps.ge.com/insideaep/aep/iad/engine_prod_delv/idms/lm2500/10uvsensor... 19/11/2005
Instrumentation
Page 2 of 2
visual indication on the control panel, capable of indicating either momentary or permanent loss of
flame from either flame sensor channel.
Figure 1 is a schematic block diagram of a typical amplifier with logic circuit, suitable for use with the
flame detector kit, as manufactured by the Avionics Division of Minneapolis Honeywell, or equivalent.
Figure 1. Recommended Flame Detector System Block Diagram