Maintenance Factor 0.8
3100 lm (Cool daylight) 1300lm (Warm white)
Brand: Master TL5 High Efficiency
Fluorescent Lamp
Brand: Philips LED Bulb 10-60W E27
6500K
N = E x A
F x UF x MF
N = 200 x 98.34
3100 x 0.79 x 0.8
N= 10
N = E x A
F x UF x MF
N = 100 x 98.34
1300 x 0.79 x 0.8
N= 11.9 = 12
Conclusion:
10 units of 3100lm incandescent pendant light fixture and 12 units of 1300lm wall mounted
incandescent light fixture can give a total illuminance of 300 lux to the dining area, which fulfils the
requirement of MS1525.
Food market 2
Total Floor Area (m) 189.23m
Standard Illuminance Required (lux) 300
Assumption of Reflection White plaster ceiling, exposed concrete wall
= 0.7 , 0.5
Room Index (K)
( )
()
= 3.6 = 4
Utilization Factor
Maintenance Factor 0.8
3100 lm (Cool daylight) 1300lm (Warm white)
Brand: Master TL5 High Efficiency
Fluorescent Lamp
Brand: Philips LED Bulb 10-60W E27
6500K
N = E x A
F x UF x MF
N = 200 x 189.23
3100 x 0.83 x 0.8
N= 18.4 =19
N = E x A
F x UF x MF
N = 100 x 189.23
1300 x 0.83 x 0.8
N= 21.9 = 22
Conclusion:
19 units of 3100lm incandescent pendant light fixture and 22 units of 1300lm wall mounted
incandescent light fixture can give a total illuminance of 300 lux to the dining area, which fulfils the
requirement of MS1525.
Supermarket
Total Floor Area (m) 66.88
Standard Illuminance Required (lux) 200
Assumption of Reflection White plaster ceiling, exposed concrete wall
= 0.7 , 0.5
Room Index (K)
( )
()
= 6
Utilization Factor
Maintenance Factor 0.8
3100 lm (Cool daylight) 1300lm (Warm white)
Brand: Master TL5 High Efficiency
Fluorescent Lamp
Brand: Philips LED Bulb 10-60W E27
6500K
N = E x A
F x UF x MF
N = 100 x 66.88
3100 x 0.7 x 0.8
N= 3.85 = 4
N = E x A
F x UF x MF
N = 100 x 66.88
1300 x 0.7 x 0.8
N= 9.2 = 10
Conclusion:
19 units of 3100lm incandescent pendant light fixture and 22 units of 1300lm wall mounted
incandescent light fixture can give a total illuminance of 300 lux to the dining area, which fulfils the
requirement of MS1525.
2.1 Reverberation Time
Zone: Retail store
Material Surface Area (m) Absorption coefficient at
1000 Hz
SA
Ceiling plasterboard 10mm thick
backed with 25mm thick bitumen
54.4 0.05 2.75
Brick wall 104 0.04 4.16
Timber finish on concrete floor 54.4 0.06 3.26
4mm glass wall 20.97 0.03 0.63
glass sliding door 3.78 0.03 0.023
2 x leather covered seats 24 0.61 14.64
3 x timber table 6 0.10 0.6
20 x adults 24 0.46 11.04
Total absorption 37.1
()
= 1.05
Conclusion:
The reverberation time for the indoor dining area is 1.05s, which is almost 1s. the reverberation time for
a small room is 1s standard. This proves that this area has good reverberation time.
2.2 External Noise Sound Pressure Level
Traffic noise at Jalan Tun HS Lee, 83db Activity noise at Jalan Tun HS Lee, 80db
) (
) (
Total intensities (
) (
Combined SPL =
= 10 x 8.476
= 84.76dB
Conclusion:
The combined SPL of the external noises of Jalan Tun HS Lee is 84.76dB
2.3 Sound Transmission Class
Figure above shows the sound pressure levels of common sound sources.
Zone : Restaurant
According to the standards table, average sound pressure level produced by restaurant
(cafeteria) is 80dB .
The restaurant consist of 116.4m of concrete bricks wall (42dB)
TL for concrete brick wall
Antilog
Tconcretewall
Toverall
(
SRI overall
= 42dB
84.76dB 42dB = 42.76dB
Conclusion:
Usage of materials has reduced 42dB of restaurants maximum estimated noise.
2.4 Power Addition Method Combined SPL of Internal Noises
Noise at street view dining area, 42.76dB Human conversation, 50db
) (
) (
Total intensities (
) (
Combined SPL =
= 10 x 5.076
= 50.76dB
Conclusion:
The total noise in the restaurant is 50.76dB.
Types of lights Rationale Lumen
Philips LED Bulb 10-60W
E27 6500K
Used as
pendant light
for warm
comfort light
1300
Master TL5 High
Efficiency Fluorescent
Lamp
Used as
primary light
3100