Вы находитесь на странице: 1из 2

IEC 61850 & IEC 61400-25 SCC

Motivation:
sustainable
interoperability
The standards IEC 61850 Communication networks and systems for power utility automation and IEC 61400-25
Communications for monitoring and control of wind power plants provide support for sustainable interopera-
bility: Information Models, Information Exchange Methods, Protocol Mappings, and System Configu-
ration Language (SCL) for Power Systems (Generation, Transmission, and Distribution for HV, MV, and LV, ).
Data Models

IEC 61850-7-4xx
NettedAutomation NettedAutomation
GmbH GmbH
Information & Communication Systems Information & Communication Systems
Substations (7-4)
160 LN
900 DO
Hydro Power (410)
63 LN
350 DO
Decentralized
Energy Res. (420)
50 LN
450 DO
IEC 61400-25-2
Wind Power
16 LN
250 DO
Logical Nodes (LN) represent real-world Inputs, Outputs, Ratings, and Settings of functions or equipment.
A LN provides a list of named data objects (DO). The LN XCBR represents a real circuit breaker with the data
object (DO) Pos (Position). IEC 61850-7-2 defines Information Exchange Methods, e.g., for the position
(with Client/Server services, GOOSE, SMV). Data flow is specified by a SCL file (IEC 61850-6).
61850-6 SCL configuration file
Real
devices in
substation
or wind
turbines
SCSM, e.g.
61850-8-1
or 9-2 ...
Virtual World
LN
LN LN
LN
OpCnt
Pos
XCBR
Logical device
virtualization
61850-7-4 logical
node (circuit breaker)
61850-7-4 data
(position)
61850-7-2
services
Single line
diagram
(topology)
Mapping
real world
to models
Models of the
real world
Objects
Information
Exchange
Services
Communication
Mappings
Communication
Network
C
o
n
f
i
r
u
r
a
t
i
o
n
f
i
l
e

(
S
C
L
)
;

p
a
r
t

6
Abstract communication
service interface (ACSI);
part 7-2 and 61400-25-3
When ?
Mapping to e.g. MMS in
part 8-1 and
WebServices, DNP3,
in IEC 61400-25-4
How ?
Logical node, data
objects, and common data
classes; parts IEC 61850-
7-4 and 7-3, 61400-25-2
What ?
IED Description (online)
m
e
s
s
a
g
e
s
m
e
s
s
a
g
e
s
IED Description (off-line)
Communication profiles
(Ethernet, TCP/IP, OSI
)
Information exchange
(publ./subscr., get, set,
control, ... reporting,
logging, get IED
description)
Information
Models
CIM
IEC 61968/70
XCBR
PDIS
WTUR
CC
TCP/IP
Network
MMS
MMS
GOOSE/SMV Layer 2
QA1
QE1
QE2
QE3
QC1
QB1
T1
Client/
subscriber
Example see reverse side
Example: Measurement LN MMXU represents power, voltages, currents, impedances, in a three-phase electrical system. The values
can be communicated by various services. The LN MMXU comprises values for measurements, monitoring, configuration, set-
tings, description, and substitution. These values can be communicated by various services like read (polling), reporting, GOOSE,
logging and log query. Recording and logging are build upon monitored value changes. The SCL configuration file .SCD (System
Configuration Description) specifies the single line diagram of the substation, the information model, the parameters of the con-
trol blocks for reporting and logging, GOOSE, SV, the binding to the process and the data flow.
.SCD
TotW
TotVAr
TotVA
TotPF
Hz
PPV
PhV
A
W
VAr
VA
PF
Z
Total Active Power (Total P)
Total Reactive Power (Total Q)
Total Apparent Power (Total S)
Average Power factor (Total PF)
Frequency
Phase to phase voltages
Phase to ground voltages
Phase currents (IL1, IL2, IL3)
Phase active power (P)
Phase reactive power (Q)
Phase apparent power (S)
Phase power factor
Phase Impedance
LN MMXU
current / voltage samples from instrument
transformers by sampled value exchange
services of IEC 61850-7-2 / IEC 61850-9-2
(e.g., from Merging Unit)
LN PhsBTCTR
Amp
LN PhsBTVTR
Vol
Log
Read
Report
Configure
Retrieve
Model
QueryLog
phsA.cVal
phsB.cVal
phsC.cVal
instVal
dead banded value
angle
range
S
V
S
V
RCB
LN and data objects
Process bus
Station bus
GOOSE
GCB
4.000
samples/sec
QA1
QE1
QE2
QE3
QC1
QB1
T1
Virtual World
...
OpCnt
Pos
XCBR
LN
LN
LN M
a
p
p
i
n
g
TCP/IP
Network
MMS
t
n+2
t
n+1
value (t
n
)
Reports/GOOSE from server/publisher to client/subscriber
(or store entries into IED log)
t
n+3
value (t
n+3
)
t
n
Time
stVal
(Status
Value)
value (t
n+1
) value (t
n+2
)
FALSE
TRUE
MMS
Log
Read, or
event-driven
Reports
GOOSE/SMV Layer 2
event-driven GOOSE message
MMS
Query
Log
status
change
Information flow (example)

www.nettedautomation.com/seminars , www.nettedautomation.com/iec61850li , www.blog.iec61850.com
NettedAutomation GmbH, 2008-2010; by Karlheinz Schwarz, SCC (Karlsruhe/Germany), schwarz@scc-online.de 2010-11-22