036-21537-001-A-0403

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE


TECHNICAL GUIDE
SUNLINE 2000
TM
SINGLE PACKAGE
HEAT PUMPS
MODEL BP180
15 NOMINAL TONS
(WORLD 50 HZ)

DESCRIPTION
York Sunline 2000 Heat Pumps are convertible single package
units. All models have dual refrigerant circuits for efficient part load
operation. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground level
or set on steel beams above a finished roof.
These heat pumps utilize a unique ambient compensated time-
temperature defrost system. The defrost module automatically
increases the time interval between defrost cycles as the outdoor
ambient temperature decreases. This helps to eliminate unneces-
sary and costly defrosts.
All units include:
Simplicity Control Board
Powder Paint finish that meets ASTM-B-117 750 hour salt
spray standards
Two-stage cooling provided by dual independent refrigeration
circuits with expansion valves, filter-driers, high and low pres-
sure/loss of charge switches and freezestats
Hermetically sealed compressors with crankcase heaters
Permanently lubricated motors
Bottom or side air discharge configuration capability (field con-
vertible)
Belt Drive Blower Motor
Manufactured under the quality standards of ISO9001
Twenty-four volt control circuit with compressor lock-out
Zero-25% fixed air damper with hood
Copper tube/aluminum fin coils
Easy access to all components
Rigging holes in base rails for lifting
Single point power connection
Complete factory package - tested, charged and wired
Agency approvals on all units
RETURN
036-21537-001-A-0403
2 Unitary Products Group
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . . . . . . 9
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . . 9
LIST OF FIGURES
Fig. # Pg. #
1 SUNLINE 2000 HEAT PUMP . . . . . . . . . . . . . . . . . 11
2 ELECTRONIC THERMOSTAT FIELD WIRING . . . . . 17
3 FIELD WIRING 24 VOLT THERMOSTAT . . . . . . . . . 17
4 FIELD WIRING DISCONNECT . . . . . . . . . . . . . . . . . . 18
5 UNIT DIMENSIONS - 15 TON . . . . . . . . . . . . . . . . . . 21
6 DETAIL X ACCY. SIDE SUPPLY & RETURN AIR
OPENINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7 DETAIL Y UNIT WITH RAIN HOODS . . . . . . . . . . . 22
8 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . 22
9 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . . 23
10 ROOF CURB DIMENSIONS - 15 TON . . . . . . . . . . . . 23
11 ROOF CURB BENEFITS . . . . . . . . . . . . . . . . . . . . . . 24
12 UNIT AND CURB APPLICATIONS . . . . . . . . . . . . . . . 24
13 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . 24
14 TYPICAL ROOF-TOP INSTALLATION . . . . . . . . . . . 25
15 SIMPLICITY CONTROL WIRING DIAGRAM . . . . . 25
LIST OF TABLES
Tbl. # Pg. #
1 CAPACITY RATINGS - COOLING . . . . . . . . . . 11
2 CAPACITY RATINGS - HEATING . . . . . . . . . . . . . . 11
3 COOLING CAPACITIES (M
3
/S AIRFLOW) -
180 UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4 COOLING CAPACITIES (CFM AIRFLOW) -
180 UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5 HEATING CAPACITIES (M
3
/S AIRFLOW) -
180 UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6 HEATING CAPACITIES (CFM AIRFLOW) -
180 UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7 BP180 SUPPLY AIR WITH DOWNFLOW DUCT
APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . 16
9 POWER EXHAUST PERFORMANCE . . . . . . . . . . . 16
10 BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . 16
11 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . 18
12 ELECTRICAL DATA -WITHOUT POWERED
CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . . 19
13 ELECTRICAL DATA -WITH POWERED
CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . . 19
14 ELECTRIC HEAT CORRECTION FACTORS . . . . . 19
15 PHYSICAL DATA - BASIC UNIT . . . . . . . . . . . . . . . 20
16 OPERATING WEIGHTS (KG. / LBS.) . . . . . . . . . . . 20
17 MINIMUM CLEARANCES (MM/IN.) . . . . . . . . . . . . . 21
18 UTILITIES ENTRY DATA (MM/IN.) . . . . . . . . . . . . . . 21
19 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . 23
036-21537-001-A-0403
Unitary Products Group 3
PRODUCT NOMENCLATURE
15TSunline2000ModelNumberNomenclature
B P 180 C 00 A 7 A AA 1
ProductCategory
B=HeatPump,SinglePackage
ProductGeneration
1=FirstGeneration
ProductIdentifier
InstallationOptions AdditionalOptions
A=NoOptionsInstalled
(SeeNextPage)
Voltage B=Option1
C=Option2
7=380/415-3-50
D=Options1&2
NominalCooling
Capacity-MBH
E=Option3
F=Options4
G=Options1&3
H=Options1&4
J=Options1,2&3
K=Options1,2,&4
A=StdMotor/Drive
L=Options1,3&4
B=StdMtr/Drive/SingleInputEcono
M=Options1,2,3,&4
C=StdMtr/Drive/SingleInputEcono/PowerExhaust*
N=Options2&3
D=StdMtr/Drive/MotorizedDamper
P=Options2&4
HeatType&NominalHeatCapacity
F=StdMtr/Drive/4"Filters
Q=Options2,3,&4
C00=CoolingOnly.Nofieldinstalledelectricheat
G=StdMtr/Drive/4"Filters/SingleInputEcon
R=Options3&4
H=StdMtr/Drive/4"Filters/SingleInputEcon/PowerExhaust*
S=Option5
L=StdMtr/Drive/BASReadyEcon(NoBASController)w/2"PleatedFilters
T=Options1&5
M=StdMtr/Drive/BASReadyEcon(NoBASController)/PowerExhaustw/2"PleatedFilters*
U=Options1,3,&5
N=HiStaticDrive
V=Options1,4,&5
P=HiStaticDrive/SingleInputEcono
W=Options1,3,4,&5
ElectricHeatOptions
Q=HiStaticDrive/SingleInputEcono/PowerExhaust*
X=Options3&5
E18=18KW
R=HiStaticDrive/MotorizedDamper
Y=Options4&5
E36=36KW
T=HiStaticDrive/4"Filters
Z=Options3,4,&5
E54=54KW
U=HiStaticDrive/4"Filters/SingleInputEcon
Options
E72=72KW
V=HiStaticDrive/4"Filters/SingleInputEcon/PowerExhaust*
1=Disconnect
Y=HiStaticDrive/BASReadyEcon(NoBASController)w/2"PleatedFilters
2=Non-Pwr'dConvOultet
Z=HiStaticDrive/BASReadyEcon(NoBASController)/PowerExhaustw/2"PleatedFilters*
3=SmokeDetectorS.A.
4=SmokeDetectorR.A.
5=Pwr'dConv.Outlet
Airflow
YorkBrand
180=15Ton
P=R-22HighEfficiencyHeatPump
036-21537-001-A-0403
4 Unitary Products Group
PRODUCT NOMENCLATURE - CONTINUED
15T Sunline 2000 Model Number Nomenclature
Additional Options
AA None
AB Phase Monitor
AC Coil Guard
AD Dirty Filter Switch
AE Phase Monitor & Coil Guard
AF Phase Monitor & Dirty Filter Switch
AG Coil Guard & Dirty Filter Switch
AH Phase Monitor, Coil Guard, & Dirty Filter Switch
BA Hinged Filter Door & Tooless Access Panels
BB Phase Monitor, Hinged Filter Door & Tooless Access Panels
BC Coil Guard, Hinged Filter Door & Tooless Access Panels
BD Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
BE Phase Monitor & Coil Guard, Hinged Filter Door & Tooless Access Panels
BF Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
BG Coil Guard & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
BH Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
CA CPC Controller with Dirty Filter Switch & Air Proving Switch
CB CPC Controller, DFS, APS & Phase Monitor
CC CPC Controller, DFS, APS & Coil Guard
CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CE CPC Controller, DFS, APS & Technicoat Cond. Coil
CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CJ CPC Controller, DFS, APS & Technicoat Evap. Coil
CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
DA CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels
DB CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels
DC CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels
DD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DE CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels
DF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
DG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DJ CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels
DK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
DL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels
DP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
DQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
036-21537-001-A-0403
Unitary Products Group 5
EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels
EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels
EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels
ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels
EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels
EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels
EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels
ER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access
Panels
GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels
GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels
GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels
GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels
GF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access
Panels
GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels
GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access
Panels
GN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels
GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access
Panels
GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels
GR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless
Access Panels
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
Additional Options
036-21537-001-A-0403
6 Unitary Products Group
JB Johnson UNT Controller, DFS, APS & Phase Monitor
JC Johnson UNT Controller, DFS, APS & Coil Guard
JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
JJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NB Novar ETC-3 Controller, DFS, APS & Phase Monitor
NC Novar ETC-3 Controller, DFS, APS & Coil Guard
ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels
PB Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels
PC Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels
PD Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels
PF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
PG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels
PK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
PL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels
PP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
PQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access
Panels
TA Technicoat Condenser Coil
TB Technicoat Condenser Coil & Phase Monitor
TC Technicoat Condenser Coil & Coil Guard
TD Technicoat Condenser Coil & Dirty Filter Switch
TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard
Additional Options
036-21537-001-A-0403
Unitary Products Group 7
TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TJ Technicoat Evaporator Coil
TK Technicoat Evaporator Coil & Phase Monitor
TL Technicoat Evaporator Coil & Coil Guard
TM Technicoat Evaporator Coil & Dirty Filter Switch
TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TS Technicoat Evaporator & Condenser Coils
TT Technicoat Evaporator & Condenser Coils & Phase Monitor
TU Technicoat Evaporator & Condenser Coils & Coil Guard
TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
UA Technicoat Condenser Coil, Hinged Filter Door & Tooless Access Panels
UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Tooless Access Panels
UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Tooless Access Panels
UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UJ Technicoat Evaporator Coil, Hinged Filter Door & Tooless Access Panels
UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Tooless Access Panels
UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Tooless Access Panels
UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Tooless Access Panels
UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Tooless Access Panels
UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Tooless Access Panels
UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
Additional Options
036-21537-001-A-0403
8 Unitary Products Group
FEATURES
All models are available with a wide variety of factory-
mounted options such as phase monitor, dirty filter switch,
and coil guard to make them suitable for almost every appli-
cation.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at
the factory to simplify the field installation and to provide
years of dependable operation.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. Models with
factory installed power exhaust are suitable for bottom
duct connections only. For bottom duct, you remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you replace
the supply and return air panels on the rear of the unit with a
side duct flange accessory.
All models are available with these factory mounted outdoor
air damper options:
Single enthalpy economizer
Single enthalpy economizer with power exhaust
Motorized outdoor air damper
A fixed outdoor air intake assembly will be shipped in the
return air compartment of all units ordered without an econo-
mizer or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10, 15
or 25% outdoor air. With bottom duct connections, the intake
damper assembly should be mounted over the opening in the
return air panel. With horizontal ductwork, it should be
mounted on the return air duct.
All supply air blowers are equipped with a belt drive that can
be adjusted to meet the exact requirements of the job. A high
static drive option is available for applications with a higher
CFM and/or static pressure requirement.
All compressors have internal pressure relief. Every refriger-
ant circuit includes an expansion valve, a liquid line filter-
drier, a discharge line high pressure switch and a suction line
with a freezestat and low pressure/loss of charge switch to
protect all system components.
Simplicity Controls - Simplicity control boards
have standardized a number of features previously avail-
able only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0F outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit con-
trol board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
three times, youre out philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All units have long lasting powder paint cabinets with 750
hour salt spray test approval under ASTM-B117 procedures.
All models are CSA approved.
Electric Heat Operation - All electric heat models (fac-
tory installed only) are wired for a single power source
and include a bank of nickel chromium elements
mounted at the discharge of the supply air blower to pro-
vide a high velocity and uniform distribution of air across
the heating elements. Every element is fully protected
against excessive current and temperature by fuses and
two thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection in the base pan
of the unit or through a knockout in the wiring panel on
the front of the unit.
BAS Controls - Yorks Sunline series units offer fac-
tory mounted BAS controls such as Novar, Honeywell,
Johnson, and CPC.
036-21537-001-A-0403
Unitary Products Group 9
FACTORY-INSTALLED OPTIONS
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed
option.
POWER EXHAUST - Our single economizer options are
available with power exhaust. Whenever the outdoor air
intake dampers are opened for free cooling, the exhaust
fan will be energized to prevent the conditioned space
from being over-pressurized during economizer opera-
tion.
The exhaust fan, motor and controls are installed and
wired at the factory. The rain hood and the back-draft
damper need to be assembled and installed in the field.
The power exhaust option can only be used on bot-
tom duct configurations.
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS - Special coating process that utilizes
Technicoat 10-1" processes. Coating is applied by total
immersion of the complete coil for maximum protection.
ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
FILTER OPTIONS - Standard units are shipped with 2
throw-away filters installed. 2 pleated and 4 pleated fil-
ters are offered as a factory installed option.
CONVENIENCE OUTLET - This 110 volt outlet can be
powered by the unit with a stepdown transformer or
you may order the unit with a non-powered conve-
nience outlet that can be wired in the field.
DISCONNECT SWITCH - For heat pump units, a HACR
breaker sized to the name plate max fuse size for the
particular unit is provided. Factory installed option only.
BAS - See Additional Options section in the product
nomenclature.
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
HIGH SPEED DRIVE - Includes a belt and blower pulley
upgrade to enhance blower performance.
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
HINGED FILTER DOOR/TOOLESS BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
NOTE: Knobs are shipped separately within the unit to
prevent shipping damage. These must be field
installed for tool-less operation.
FIELD-INSTALLED ACCESSORIES
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed option.
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
Power exhaust is not available as a field installed option.
ROOF CURBS - Fourteen-inch high roof curbs provide a
water-tight seal between the unit and the finished roof.
036-21537-001-A-0403
10 Unitary Products Group
These full perimeter curbs meet the requirements of the
National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.
They're designed to fit inside the base rails of the unit
and include both a wood nailing strip and duct hanger
supports.
SIDE DUCT FLANGES - One-inch flanges replace the
supply and return air panels on the rear of the unit to
accommodate horizontal duct connections. These
flanges can also be used individually for bottom supply/
horizontal return or horizontal supply/bottom return. They
cannot be used on units with power exhaust.
BAROMETRIC RELIEF DAMPER - This damper acces-
sory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
HIGH SPEED DRIVE - A smaller blower pulley and a
shorter belt increase the speed of the supply air blower
for applications with a higher CFM and/or static pressure
requirements.
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
WOOD SKID - Allows unit to be handled with 90 forks.
CO
2
SENSOR - Senses CO
2
levels and automatically
overrides the economizer when levels rise above the
present limits.
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
036-21537-001-A-0403
Unitary Products Group 11

FIGURE 1 - SUNLINE 2000
TM
HEAT PUMP
HIGH EFFICIENCY COMPRESSORS
WITH CRANKCASE HEATERS
COPPER TUBE/ALUMINUM FIN
OUTDOOR COILS
LOW VOLTAGE RELAY BOARD
AND TERMINAL STRIP
ELECTRICAL DISCONNECT
MOUNTING LOCATION
(Field Installed)
TERMINAL BLOCK
(For Single Point Power Supply
With Electirc Heat)
KNOCKOUT FOR
SIDE CONTROL WIRING AND
SIDE POWER WIRING ENTRY
BOTTOM & CONTROL
WIRING ENTRY
ELECTRIC HEATER LOCATION
(OPTION)
BELT-DRIVE
BLOWER MOTOR
FULL PERIMTER 14 GUAGE BASE
RAILS WITH LIFTING HOLES
NPT FEMALE
CONDENSATE DRAIN
SIDE AND BOTTOM
SUPPLY & RETURN AIR

OUTDOOR AIR OPENING
FOR INTERNAL ECONOMIZER
2" DISPOSABLE
FILTERS
ECONOMIZER HOOD
LONG LASTING POWDER PAINT FINISH
TABLE 1: CAPACITY RATINGS - COOLING
MODEL
DESIGN TEMPERATURES (C)
TOTAL OUTPUT
kW / MBH
TOTAL INPUT
kW
COP
1
EER
2
SENSIBLE
OUTPUT
kW / MBH
LATENT OUTPUT
kW / MBH
RATING
3
POINT
INDOOR
DB / WB
OUTDOOR
DB / WB
BP180
T1 27 / 19 35 / 24 43.8 / 149 17.7 2.50 8.45 38.8 / 132 5.0 / 17
T2 29 / 19 46 / 24 39.0 / 133 20.4 1.90 6.55 39.0 / 133 0.0 / 0
T3 21 / 15 27 / 19 42.7 / 146 16.1 2.65 9.05 34.8 / 119 7.9 / 27
1. COP = Coefficient of Performance - total output kW divided by the total input kW.
2. EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.
3. T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.
TABLE 2: CAPACITY RATINGS - HEATING
MODEL
DESIGN TEMPERATURES (C)
TOTAL OUTPUT
kW / MBH
TOTAL INPUT
kW
COP
1
EER
2
ELECTRIC HEAT
3
NOMINAL CAPACITY
kW
RATING
POINT
INDOOR
DB / WB
OUTDOOR
DB / WB
BP180
High 20 / 12 7 / 6 47.3 / 161 16.0 2.95 10.1
15, 27, 40, 54 Low 20 / 12 2 / 1 27.4 / 93 14.5 1.90 6.45
X-Low 20 / 12 -7 / -8 19.8 / 68 13.3 1.50 5.10
1. COP = Coefficient of Performance - total output kW divided by the total input kW.
2. EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.
3. Heaters available as factory-installed options - all with single point power supply.
036-21537-001-A-0403
12 Unitary Products Group

TABLE 3: COOLING CAPACITIES (M
3
/S AIRFLOW) - 180 UNIT
AIR ON
INDOOR COIL
TOTAL
1
CAP.
kW
POWER
2
INPUT
KW
SENSIBLE CAPACITY
1
, kW
ENTERING DRY BULB TEMPERATURE, C
m
3
/s WB C 32 30 28 26 24 22
@ 27C AIR TEMPERATURE ON OUTDOOR COIL
3.40
23 60.8 16.3 51 44 38 32 25 -
21 57.4 16.1 57 51 44 38 32 25
19 54.0 15.8 54 54 51 45 38 32
17 52.2 15.7 52 52 52 49 43 36
15 50.5 15.5 50 50 50 47 41 35
2.83
23 59.0 16.2 44 39 33 27 22 -
21 55.7 16.0 50 44 39 33 28 22
19 52.4 15.7 52 50 44 39 33 28
17 50.7 15.6 51 51 48 42 37 31
15 48.9 15.4 49 49 49 46 41 35
2.12
23 54.2 15.8 37 33 28 24 20 -
21 51.1 15.6 42 38 33 29 25 20
19 48.1 15.4 47 43 38 34 30 25
17 46.5 15.2 47 46 42 37 33 29
15 45.0 15.0 45 45 45 40 36 32
@ 35C AIR TEMPERATURE ON OUTDOOR COIL
3.40
23 58.7 21.0 45 38 32 26 19 -
21 54.4 19.1 53 46 40 34 27 21
19 50.2 17.3 50 50 48 41 35 29
17 49.5 18.5 50 50 50 43 37 31
15 48.8 19.7 49 49 49 45 39 32
2.83
23 54.7 17.9 41 35 30 24 19 -
21 50.7 16.3 48 43 37 32 26 20
19 46.8 14.7 47 47 45 39 33 28
17 46.1 15.8 46 46 46 41 35 30
15 45.5 16.8 45 45 45 42 37 31
2.12
23 51.6 20.6 32 28 24 19 15 -
21 47.9 18.7 38 34 30 25 21 17
19 44.1 16.9 44 40 35 31 27 22
17 43.5 18.1 44 41 37 32 28 24
15 42.9 19.3 43 42 38 34 29 25
@ 46C AIR TEMPERATURE ON OUTDOOR COIL
3.40
23 50.2 20.3 44 38 31 25 19 -
21 47.3 19.8 47 44 38 31 25 19
19 44.4 19.3 44 44 44 38 32 25
17 43.4 19.3 43 43 43 40 34 27
15 42.3 19.2 42 42 42 39 33 26
2.83
23 48.1 20.1 39 34 28 22 17 -
21 45.3 19.6 45 39 34 28 23 17
19 42.5 19.1 43 43 39 34 28 23
17 41.5 19.0 42 42 41 36 30 24
15 40.5 18.9 41 41 41 37 32 26
2.12
23 44.8 19.5 32 28 23 19 15 -
21 42.3 19.0 37 32 28 24 19 15
19 39.7 18.6 40 37 33 29 24 20
17 38.7 18.5 39 39 34 30 26 21
15 37.8 18.4 38 38 36 32 27 23
1. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance
Table for the kW of the supply air blower motor.
2. These ratings include the outdoor fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.
036-21537-001-A-0403
Unitary Products Group 13

TABLE 4: COOLING CAPACITIES (CFM AIRFLOW) - 180 UNIT
AIR ON
INDOOR COIL
TOTAL
1
CAP.
MBH
POWER
2
INPUT
KW
SENSIBLE CAPACITY
1
, MBH
ENTERING DRY BULB TEMPERATURE, F
CFM WB F 90 86 82 79 75 72
@ 80F AIR TEMPERATURE ON OUTDOOR COIL
7200
73 207 16.3 173 151 129 108 86 -
70 196 16.1 195 173 152 130 108 87
66 184 15.8 184 184 174 152 130 109
63 178 15.7 178 178 178 167 145 123
59 172 15.5 172 172 172 161 140 118
6000
73 201 16.2 151 132 113 94 75 -
70 190 16.0 170 151 132 113 94 75
66 179 15.7 179 170 151 132 113 94
63 173 15.6 173 173 164 145 126 107
59 167 15.4 167 167 167 158 139 120
4500
73 185 15.8 127 112 97 82 68 -
70 175 15.6 143 129 114 99 84 70
66 164 15.4 160 145 131 116 101 86
63 159 15.2 159 157 142 127 112 98
59 153 15.0 153 153 153 138 123 109
@ 95F AIR TEMPERATURE ON OUTDOOR COIL
7200
73 200 21.0 153 131 109 88 66 -
70 186 19.1 179 158 136 114 93 71
66 171 17.3 171 171 163 141 120 98
63 169 18.5 169 169 169 147 126 104
59 167 19.7 167 167 167 154 132 110
6000
73 187 17.9 140 121 102 83 64 -
70 173 16.3 165 146 127 108 89 70
66 160 14.7 160 160 152 133 114 95
63 157 15.8 157 157 157 139 120 101
59 155 16.8 155 155 155 145 126 107
4500
73 176 20.6 110 96 81 66 51 -
70 163 18.7 130 115 101 86 71 56
66 151 16.9 150 135 121 106 91 76
63 148 18.1 148 140 125 110 96 81
59 146 19.3 146 145 130 115 100 86
@ 115F AIR TEMPERATURE ON OUTDOOR COIL
7200
73 171 20.3 150 129 107 85 64 -
70 161 19.8 161 151 129 107 86 64
66 152 19.3 152 152 151 129 108 86
63 148 19.3 148 148 148 136 114 93
59 144 19.2 144 144 144 134 112 90
6000
73 164 20.1 133 114 95 76 57 -
70 155 19.6 153 134 115 96 77 58
66 145 19.1 145 145 134 115 96 77
63 142 19.0 142 142 140 121 102 83
59 138 18.9 138 138 138 127 108 89
4500
73 153 19.5 109 94 80 65 50 -
70 144 19.0 125 111 96 81 66 52
66 135 18.6 135 127 112 98 83 68
63 132 18.5 132 132 117 103 88 73
59 129 18.4 129 129 123 108 93 78
1. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance
Table for the kW of the supply air blower motor.
2. These ratings include the outdoor fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.
036-21537-001-A-0403
14 Unitary Products Group

TABLE 5: HEATING CAPACITIES
1
(M
3
/S AIRFLOW) - 180 UNIT
m
3
/s
RETUR
N AIR
C
CAP.
(C)
PWR.
(P)
(KW)
OUTDOOR AIR TEMPERATURE, C (72% RH)
-20 -15 -10 -5 0 5 10 15 20
2.12
13
(C)
(P)
13.3
8.8
17.1
9.4
21.8
10.1
27.4
10.8
33.8
11.5
41.0
12.3
49.2
13.2
58.2
14.1
68.1
15.1
20
(C)
(P)
12.7
9.0
16.2
9.7
20.5
10.6
25.5
11.4
31.4
12.2
38.6
13.0
46.0
13.9
54.2
14.9
63.0
15.9
27
(C)
(P)
12.1
9.2
15.3
9.9
19.1
10.7
23.8
11.5
29.1
12.3
35.1
13.2
41.8
14.1
49.2
15.1
57.1
16.1
2.83
13
(C)
(P)
13.7
8.3
17.6
8.8
22.4
9.4
28.1
10.1
34.6
10.8
42.1
11.6
50.4
12.4
59.7
13.2
69.8
14.2
20
(C)
(P)
13.2
8.9
16.9
9.6
21.5
10.3
26.9
11.0
33.3
11.8
41.1
12.7
49.3
13.6
58.3
14.6
68.2
15.6
27
(C)
(P)
12.8
9.1
16.3
9.9
20.6
10.6
25.8
11.5
31.9
12.4
38.9
13.4
46.8
14.4
55.6
15.4
65.3
16.5
3.40
13
(C)
(P)
14.0
7.8
18.0
8.3
22.9
8.9
28.8
9.5
35.5
10.1
43.2
10.9
51.8
11.6
61.2
12.4
71.6
13.3
20
(C)
(P)
13.8
8.6
17.7
9.2
22.6
9.9
28.4
10.7
35.3
11.5
43.8
12.4
52.7
13.3
62.7
14.3
73.7
15.3
27
(C)
(P)
13.5
9.0
17.3
9.8
22.1
10.6
28.0
11.5
35.0
12.5
43.1
13.5
52.4
14.6
62.9
15.8
74.6
17.0
1. The MBH and kW values do not include the supply air blower.
TABLE 6: HEATING CAPACITIES
1
(CFM AIRFLOW) - 180 UNIT
CFM
RETURN AIR
F
CAP. (MBH)
PWR. (kW)
OUTDOOR AIR TEMPERATURE, F (72% RH)
-4 5 14 23 32 41 50 59 68
4500
55
MBH
kW
45
8.8
58
9.4
74
10.1
93
10.8
115
11.5
140
12.3
168
13.2
199
14.1
232
15.1
68
MBH
kW
43
9.0
55
9.7
70
10.6
87
11.4
107
12.2
132
13.0
157
13.9
185
14.9
215
15.9
80
MBH
kW
41
9.2
52
9.9
65
10.7
81
11.5
99
12.3
120
13.2
143
14.1
168
15.1
195
16.1
6000
55
MBH
kW
47
8.3
60
8.8
76
9.4
96
10.1
118
10.8
144
11.6
172
12.4
204
13.2
238
14.2
68
MBH
kW
45
8.9
58
9.6
73
10.3
92
11.0
114
11.8
140
12.7
168
13.6
199
14.6
233
15.6
80
MBH
kW
44
9.1
55
9.9
70
10.6
88
11.5
109
12.4
133
13.4
160
14.4
190
15.4
223
16.5
7200
55
MBH
kW
48
7.8
62
8.3
78
8.9
98
9.5
121
10.1
147
10.9
177
11.6
209
12.4
244
13.3
68
MBH
kW
47
8.6
60
9.2
77
9.9
97
10.7
120
11.5
150
12.4
180
13.3
214
14.3
251
15.3
80
MBH
kW
46
9.0
59
9.8
76
10.6
96
11.5
120
12.5
147
13.5
179
14.6
215
15.8
254
17.0
1. The MBH and kW values do not include the supply air blower.
036-21537-001-A-0403
Unitary Products Group 15
NOTES: 1.Blower performance includes fixed outdoor air, 2 T/A filters, a dry evaporator coil and no electric heat.
2.Refer to Table 8 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
TABLE 7: BP180 SUPPLY AIR WITH DOWNFLOW DUCT APPLICATIONS
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
2.10 m
3
/s 2.45 m
3
/s 2.80 m
3
/s 3.10 m
3
/s 3.40 m
3
/s
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
STANDARD DRIVE (m
3
/s)
845 6.0 173 1.8 2.2 138 2.2 2.6 83 2.6 3.1 18 3.0 3.5 - - -
885 5.0 208 1.9 2.3 172 2.3 2.8 115 2.7 3.3 49 3.1 3.7 - - -
925 4.0 245 2.0 2.4 208 2.4 2.9 149 2.9 3.4 82 3.3 3.9 - - -
960 3.0 281 2.1 2.6 242 2.6 3.1 182 3.0 3.6 114 3.4 4.1 30 3.8 4.6
1000 2.0 323 2.3 2.7 283 2.7 3.2 222 3.2 3.8 152 3.6 4.3 67 4.0 4.8
1040 1.0 369 2.4 2.9 327 2.9 3.4 264 3.3 4.0 193 3.8 4.5 107 4.2 5.1
HIGH SPEED DRIVE (m
3
/s)
1030 6.0 357 2.4 2.8 316 2.8 3.4 253 3.3 3.9 183 3.7 4.5 97 4.2 5.0
1070 5.0 405 2.5 3.0 362 3.0 3.6 298 3.5 4.2 226 3.9 4.7 - - -
1115 4.0 461 2.7 3.2 416 3.2 3.8 351 3.7 4.4 278 4.2 5.0 - - -
1155 3.0 514 2.9 3.4 468 3.4 4.0 401 3.9 4.7 - - - - - -
1200 2.0 577 3.1 3.7 529 3.6 4.3 461 4.1 5.0 - - - - - -
1240 1.0 636 3.3 3.9 587 3.8 4.5 - - - - - - - - -
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
4450 CFM 5190 CFM 5930 CFM 6565 CFM 7200 CFM
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
STANDARD DRIVE (CFM)
845 6.0 0.7 2.4 2.2 0.6 2.9 2.6 0.3 3.5 3.1 0.1 4.0 3.5 - - -
885 5.0 0.8 2.6 2.3 0.7 3.1 2.8 0.5 3.7 3.3 0.2 4.2 3.7 - - -
925 4.0 1.0 2.7 2.4 0.8 3.3 2.9 0.6 3.8 3.4 0.3 4.4 3.9 - - -
960 3.0 1.1 2.9 2.6 1.0 3.4 3.1 0.7 4.0 3.6 0.5 4.6 4.1 0.1 5.2 4.6
1000 2.0 1.3 3.0 2.7 1.1 3.6 3.2 0.9 4.2 3.8 0.6 4.8 4.3 0.3 5.4 4.8
1040 1.0 1.5 3.2 2.9 1.3 3.8 3.4 1.1 4.5 4.0 0.8 5.1 4.5 0.4 5.7 5.1
HIGH SPEED DRIVE (CFM)
1030 6.0 1.4 3.2 2.8 1.3 3.8 3.4 1.0 4.4 3.9 0.7 5.0 4.5 0.4 5.6 5.0
1070 5.0 1.6 3.4 3.0 1.5 4..0 3.6 1.2 4.7 4.2 0.9 5.3 4.7 - - -
1115 4.0 1.9 3.6 3.2 1.7 4.3 3.8 1.4 5.0 4.4 1.1 5.6 5.0 - - -
1155 3.0 2.1 3.9 3.4 1.9 4.5 4.0 1.6 5.2 4.7 - - - - - -
1200 2.0 2.3 4.1 3.7 2.1 4.8 4.3 1.8 5.5 5.0 - - - - - -
1240 1.0 2.6 4.4 3.9 2.4 5.1 4.5 - - - - - - - - -
036-21537-001-A-0403
16 Unitary Products Group
* Factory Setting
Power Exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
TABLE 8: STATIC RESISTANCES
1
DESCRIPTION
RESISTANCE, IWG/Pa
m
3
/s (CFM)
15 TON
2.12 (4500) 2.83 (6000) 3.39 (7200)
WET INDOOR COIL 0.1/25 0.1/25 0.1/25
ELECTRIC HEAT OPTIONS
18 KW 0.1/25 0.1/25 0.1/25
36 KW 0.1/25 0.2/50 0.3/75
54 KW 0.2/50 0.3/75 0.4/100
72 KW 0.2/50 0.4/100 0.6/150
ECONOMIZER OPTION 0.1/25 0.1/25 0.1/25
HORIZONTAL DUCT CONNECTIONS
2
0.1/25 0.2/50 0.3/75
1. Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table (See Note 2 for
exception.)
2. Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values
on the respective units blower performance table.
TABLE 9: POWER EXHAUST PERFORMANCE
MOTOR
SPEED
STATIC RESISTANCE OF RETURN DUCTWORK, IWG/Pa
0.2/50 0.3/75 0.4/100 0.5/125 0.6/150
m
3
/s (CFM)
KW
m
3
/s (CFM)
KW
m
3
/s (CFM)
KW
m
3
/s (CFM)
KW
m
3
/s (CFM)
KW
HIGH* 2.47 (5250) 0.83 2.12 (4500) 0.85 1.98 (4200) 0.88 1.77 (3750) 0.93 1.41 (3000) 0.99
MEDIUM 2.31 (4900) 0.77 1.84 (3900) 0.79 1.65 (3500) 0.82 1.37 (2900) 0.85 - -
LOW 2.07 (4400) 0.72 1.74 (3700) 0.74 1.41 (3000) 0.78 - - - -
TABLE 10: BLOWER MOTOR AND DRIVE DATA
UNIT
SIZE
(MBH)
BLOWER
RANGE
(RPM)
MOTOR
1
ADJUSTABLE MOTOR PULLEY
2
FIXED BLOWER PULLEY
BELT
(NOTCHED)
kW/HP
FRAME
SIZE
EFF.
(%)
PITCH DIA.
(mm / in.)
BORE
(mm / in.)
DESIG-
NATION
PITCH DIA.
(mm / in.)
BORE
(mm / in.)
DESIG-
NATION
PITCH
LENGTH
(mm/in.)
DESIG-
NATION
QTY.
180
STD
DRIVE
845 - 1040 3.0/4.0 184T 83
109 - 135 /
4.3 - 5.3
29 / 1-1/8 1VP56 188 / 7.4 25 / 1 BK80 1773 / 69.8 BX68 1
HIGH
SPEED
DRIVE
1030 - 1240 3.7/5.0 184T 84
124-150
4.9-5.9
29 / 1-1/8 1VP62 175 / 6.9 25 / 1 BK75 1773 / 69.8 BX68 1
1. All motors are 1450 RPM, have sold bases and a 1.10 service factor.
2. Do NOT close this pulley below 1 turn open.
036-21537-001-A-0403
Unitary Products Group 17

NOTE: This unit does NOT REQUIRE a heat pump thermo-
stat. It is designed to work with a standard two-stage
cool, two-stage heat thermostat; however, the ther-
mostat must provide a G signal when there is a call
for W1.


FIGURE 2 - ELECTRONIC THERMOSTAT FIELD WIRING
W2
RC
RH
Y1
Y2
W1
G
C
X1
X3
X4
A1
|
A2
|
T
T
THERMOSTAT*
TERM NALS
UN T TERM NALS
STR P TB1
* El ectroni c programmabl e Thermostat 2ET077001 0024 (i ncl udes subbase).
|
Termi nal s A1 and A2 provi de a rel ay output to cl ose the outdoor
economi zer dampers when the thermostat swi tches to the set-back posi ti on.
24 Vol t
Transformer
TO REMOTE SENSOR
2ET04701 324 F USED
OCC
W1
W2
Y1
G
Y2
X
R
SD
C
R
E
M
O
T
E
M

N

P
O
S
FIGURE 3 - FIELD WIRING 24 VOLT THERMOSTAT
OCC
W1
W2
Y1
G
Y2
X
R
SD
C
R
E
M
O
T
E
M

N

P
O
S
W1
W2
Y1
G
Y2
C
UN T CONTROL
BOARD
T-STAT
RH
RC
The thermostat must provide a G signal
when there is a call for W1.The unit control
board will energize the indoor blower when
the compressors are energized; however, if
the thermostat calls for W2 during the anti-
short-cycle delay, the electric heat (when
installed) will be energized immediately
upon the call for W2.
The thermostat must provide a G signal
when there is a call for W1.The unit control
board will energize the indoor blower when
the compressors are energized; however, if
the thermostat calls for W2 during the anti-
short-cycle delay, the electric heat (when
installed) will be energized immediately
upon the call for W2.
036-21537-001-A-0403
18 Unitary Products Group

Note 1: Maximum HACR breaker of the same amp size is
acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW
electric heat can be simultaneously energized with the
mechanical heating. The full heater kW operates only if
both compressors are locked out.
FIGURE 4 - FIELD WIRING DISCONNECT
TERM NAL BLOCK TB1
GROUND
LUG
THREE
PHASE
POWER
SUPPLY
FACTORY OR F ELD
SUPPL ED D SCONNECT
TABLE 11: VOLTAGE LIMITATIONS
POWER SUPPLY
VOLTAGE
MIN. MAX.
380/415-3-50 342 456
036-21537-001-A-0403
Unitary Products Group 19

Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.

Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
TABLE 12: ELECTRICAL DATA -WITHOUT POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
2
STAGES AMPS
BP180
380 12.8 128 2.1 8.3 0.0
- 0.0 - - 41.3 50
E18 11.3 1 17.1 62.8 70
E36 22.6 2 34.3 62.8 60
E54 33.8 2 51.4 74.6 80
E72 45.1 2 68.6 96.0 100
415 12.8 128 2.1 8.3 0.0
- 0.0 - - 41.3 50
E18 13.5 1 18.7 64.8 70
E36 26.9 2 37.4 64.8 70
E54 40.4 2 56.2 80.6 90
E72 53.8 2 74.9 88.1 100
TABLE 13: ELECTRICAL DATA -WITH POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
2
STAGES AMPS
BP180
380 12.8 128 2.1 8.3 6.3
- 0.0 - - 47.6 60
E18 11.3 1 17.1 69.1 70
E36 22.6 2 34.3 69.1 70
E54 33.8 2 51.4 82.4 90
E72 45.1 2 68.6 103.9 110
415 12.8 128 2.1 8.3 6.3
- 0.0 - - 47.6 60
E18 13.5 1 18.7 71.1 80
E36 26.9 2 37.4 71.1 80
E54 40.4 2 56.2 88.5 90
E72 53.8 2 74.9 94.4 100
TABLE 14: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE VOLTAGE KW CAP. MULTIPLIER
380 380 0.627
415 415 0.75
036-21537-001-A-0403
20 Unitary Products Group
TABLE 15: PHYSICAL DATA - BASIC UNIT
MODEL BP180
SUPPLY AIR
BLOWER
CENTRIFUGAL BLOWER
(Dia. x Wd. mm.)
(Dia. x Wd. in.)
381 x 381
15 x 15
FAN MOTOR (KW/HP) 3.0/4
INDOOR COIL
ROWS DEEP 4
FINS PER INCH 13
FACE AREA (Sq. M./Sq. Ft.) 1.45/15/5
OUTDOOR
FAN
(Two Per Unit)
PROPELLER DIA. (mm/in.) (Each) 762/30
FAN MOTOR (KW/HP) (Each) 0.8/1.25
NOM. M
3
/S/CFM TOTAL (Each)
3.06/6500
OUTDOOR COIL
ROWS DEEP 3
FINS PER INCH 15
FACE AREA (Sq. M./Sq. Ft.) 3.35/36.0
COMPRESSOR
(Qty. Per Unit)
7-1/2 TON SCROL 2
AIR
FILTERS
QUANTITY PER UNIT (457 X 610 X 51 mm) / (18" X 24" X 2") 5
TOTAL FACE AREA (Sq. M./Sq. Ft.) 1.4/15.0
CHARGE REFRIGERANT 22
SYSTEM NO. 1 (Kg./Lbs.) 10.2/22.5
SYSTEM NO. 2 (Kg./Lbs.) 10.2/22.5
TABLE 16: OPERATING WEIGHTS (KG. / LBS.)
MODEL BP180
Basic Unit BP (Heat Pump) 862/1900
Options
Economizer 73/160
Economizer with Power Exhaust 111/245
Motorized Damper 68/150
Electric Heater
18 KW 11/25
36 KW 14/30
54 KW 16/35
72 KW 18/40
Accessories
Roof Curb 79175
Barometric Damper 20/45
Wood Skid 91/200
036-21537-001-A-0403
Unitary Products Group 21

NOTE: Units and ductwork are approved for zero clearance
to combustible materials when equipped with elec-
tric heaters.
NOTE: All entry holes should be field sealed to prevent rain
water entry into building.
FIGURE 5 - UNIT DIMENSIONS - 15 TON
All dimensions are in inches. They are
subject to change without notice. Certi-
fied dimensions will be provided upon
request.
TABLE 17: MINIMUM CLEARANCES (MM/IN.)
LOCATION CLEARANCE
Front 914 mm/36
Back
610 mm/24 (Less Economizer)
1245 mm/49 (With Economizer
Left Side (Filter Access)
610 mm/24 (Less Economizer)
914 mm/36 (With Economizer)
Right Side (Cond. Coil) 914 mm/36
Below Unit
1
1. Units (applicable in U.S.A. only) may be installed on
combustible floors made from wood or class A, B or C
roof covering material.
0 mm/0
Above Unit
2
2. Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct outdoor air dis-
charge outlet.
1829 mm/72 With 914 mm/36
Maximum Horizontal Overhang
(For Condenser Air Discharge)
TABLE 18: UTILITIES ENTRY DATA (MM/IN.)
HOLE OPENING SIZE (DIA.) USED FOR
A
28.6 mm/1-1/8 KO
Control Wiring
Front
19.1 mm/3/4 NPS (Fem.) Bottom
B
92.1 mm/3-5/8 KO
Power Wiring
Front
76.2 mm/3 NPS (Fem.) Bottom
036-21537-001-A-0403
22 Unitary Products Group


DUCT COVERS - Units are shipped with the bottom
duct openings covered. An accessory flange kit is available for con-
necting side ducts.
For bottom duct applications:
1. Remove the side panels from the supply and return
air compartments to gain access to the bottom
supply and return air duct covers.
2. Remove and discard the bottom duct covers. (Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.)
3. Replace the side supply and return air compartment
panels.
For side duct applications;
1. Replace the side panels on the supply and return air
compartments with the accessory flange kit panels.
2. Connect ductwork to the duct flanges on the rear of
the unit.
OUTDOOR AIR PANEL SIZE
15 TON UNITS 21-1/2" X 43"
FIGURE 6 - DETAIL X ACCY. SIDE SUPPLY & RETURN AIR OPENINGS
FIGURE 7 - DETAIL Y UNIT WITH RAIN HOODS
FIGURE 8 - CENTER OF GRAVITY
036-21537-001-A-0403
Unitary Products Group 23


FIGURE 9 - FOUR AND SIX POINT LOADS
A
E
D
B
F
C
FRONT
A
B
C
D
FRONT
4 Point Loads 6 Point Loads
TABLE 19: FOUR AND SIX POINT LOADS
UNIT
4 - POINT LOADS (Kg. / Lbs.)
TOTAL A B C D
180 952 / 2100 233 / 513 231 / 510 253 / 558 253 / 559
NOTE: These weights are with economizer and 72 kW electric heat.
UNIT
6 - POINT LOADS (Kg. / Lbs.)
TOTAL A B C D E F
180 952 / 2100 155 / 342 162 / 358 161 / 357 164 / 372 161 / 356 155 / 341
NOTE: These weights are with economizer and 72 kW electric heat.
FIGURE 10 - ROOF CURB DIMENSIONS - (180 & 240 UNITS)
036-21537-001-A-0403
24 Unitary Products Group

FIGURE 11 - ROOF CURB BENEFITS
FIGURE 12 - UNIT AND CURB APPLICATION
FIGURE 13 - TYPICAL APPLICATIONS
036-21537-001-A-0403
Unitary Products Group 25

FIGURE 14 - TYPICAL ROOF-TOP INSTALLATION
FIGURE 15 - SIMPLICITY CONTROL WIRING DIAGRAM
W1
W2
Y1
G
OCC
P
P1
Y2
X
R
SD
C
C
SD
SD
R
OCC
C
RC
G
Y2
Y1
W2
W1
Jumper
Smoke
Detector
24 VAC
Class 2
X
R
THERMOSTAT
TERMINALS
CONTROL
TERMINAL
BLOCK
TERMINALS ON
A LIMITED
NUMBER OF
THERMOSTATS
3
1
2
4
3
1
2
4
Second stage heating not required on single stage heating units.
Second stage cooling not required on single stage cooling units.
Jumper is required if there is no Smoke Detector circuit.
Jumper is required for any combination of R, RC, or RH.
6
5
5
6
OCC is an output from the thermostat to indicate the Occupied condition.
X is an input to the thermostat to display Error Status conditions.
036-21537-001-A-0403
26 Unitary Products Group
036-21537-001-A-0403
Unitary Products Group 27
Subject to change without notice. Printed in U.S.A. 036-21537-001-A-0403
Copyright by Unitary Products Group 2003. All rights reserved. Supersedes: Nothing