0 оценок0% нашли этот документ полезным (0 голосов)
17 просмотров7 страниц
Some widely accepted coupling recommendations for power line carrier systems (PLC) do not prevent modal cancellation. Computer programs for calculating line frequency response may fail to detect modal cancellation conditions. A method of PLC system design, for multitransposed horizontal and delta transmission lines is proposed. It is based in Senn's technique [61 for calculating PLC frequency responses.
Some widely accepted coupling recommendations for power line carrier systems (PLC) do not prevent modal cancellation. Computer programs for calculating line frequency response may fail to detect modal cancellation conditions. A method of PLC system design, for multitransposed horizontal and delta transmission lines is proposed. It is based in Senn's technique [61 for calculating PLC frequency responses.
Some widely accepted coupling recommendations for power line carrier systems (PLC) do not prevent modal cancellation. Computer programs for calculating line frequency response may fail to detect modal cancellation conditions. A method of PLC system design, for multitransposed horizontal and delta transmission lines is proposed. It is based in Senn's technique [61 for calculating PLC frequency responses.
I EEE Transactions on Power Delivery ,Vol. 6, No. 3, July 1991
DESIGN OF POWER LINE CARRIER SYSTEMS ON MULTITRANSPOSED DELTA TRANSMISSION LINES. Jos6 Luis Naredo V. Student member. Avrum C. Soudack The University of British Columbia Department of Electrical Engineering Vancouver, B. C. V6T 1W5, Canada ABSTRACT. It is shown in this paper that some of the most widely accepted coupling recommendations for power line carrier systems (PLC) do not prevent modal cancellation. It is also shown that computer programs for calculating line frequency response may fail to detect modal cancellation conditions. A method of PLC system design, for multitransposed horizontal and delta transmission lines is proposed. It is based in Senn's technique [61 for calculating PLC frequency responses and allows for the consideration of line data uncertainties and line parameter variations. Another technique proposed in the paper makes use of shunt capacitors connected at a few points along the line. The risk of nodal cancellation is decreased and, in some cases, it can be eliminated. Key words: power line carrier, modal analysis, transmission line modeling. horizontal lines, delta lines, teleprotection. 1. INTRODUCTION. Communication signal loss due to modal cancellation is a major concern in the design of power line carrier systems (PLC). An electromagnetic wave on a multiconductor line can be considered as an ensemble of modes, each one with its own propagation velocity and attenuation [ I ] . Due to velocity differences, the phase angles between modes change as the wave propagates along the line. Sometimes in PLC systems hvo 0: more modes arrive at the far end of the line with a phase difference such as to make the signal at the receiver's input practically zero 121. Delta transmission lines, for which horizontal lines are a particular case, are considered the most prone to modal cancellation [61. They are also among the most commonly found ones in practice. The work here reported focusses on these types of lines. PLC design is restricted to the selection of couplings and of carrier frequencies only. Coupling selection is. done either by applying a set of given recommendations or by comparing the calculated frequency responses of each coupling alternative. It is shown in this paper that neither of these approaches guarantees a modal cancellation-free system response, Section 2 provides an ovewiew of the method of analysis used throughout the paper. In section 3, it is shown that some of the most widely accepted coupling recommendations present modal cancellation and, furthermore, that for some line transposition schemes it is not possible to obtain cancellation-free couplings. In section 4 the limitations of frequency response calculations as applied to practical design are discussed. Line calculations are based on field data which, in most practical situations, cannot be obtained with the 90 SiI Lu3-0 P;C?D P. paper recommended and approved by the I EEZ Power Syster'i Communications Committee of tie IETk Power Engi neeri ng Soci ety for presentati on at the ILEE/FES 1990 Summer bi eeti ng, K i nneapol i s, .i i nnesota, J ul y 15-19, 1990. Si anuscri pt submi tted September 1, lqb9; nade avai l abl e f or pri nti ng J une 6, 1990. required detail and accuracy; moreover, some of these data may be subjected to climatic changes. Calculated responses, may not then show the risk of modal cancellation. Because of the limitations of the aforesaid design methods, an alternative is proposed in section 5. It is based on Senn's technique for calculating PLC response [6,71 and allows for the consideration of line parameter variztions and of field information uncertainties. In section 6, a technique of recent consideration by the authors is introduced. This technique requires the connection of shunt capacitors at some points along the line in order to improve the sensitivity of the PLC system response to line parameter changes. In some cases, modal cancellation can be completely eliminated. 2. OVERVIEW OF THE METHOD OF ANALYSIS OF PLC SYSTEMS. 2.1 Preliminaries. For a transmission line where wave propagation can be described by only two dominant modes and where reflected waves are neglected, the attenuation is given by the following relationship [31: - 20 /0g1,/L K i =O 2 ci xi j ,..(I) where a, is mode 1 attenuation, L is the length of the line, n is the minimum number of homogeneous sections of equal length into which the line can be divided, K. CO, C 1 , C2 ..., Cn are coefficients that depend on the transposition scheme, on the coupling connections and on the elements of the modal transformation matrices. X stands for: X = exp[-(Aa+jAe)] J 2) where Da and A0 are, respectively, the difference of attenuation and of phase shift between mode 2 and mode 1 as they travel along any of the homogeneous line sections into which the line has been divided. Since by convention [5], mode 1 is the lowest attenuation mode, the first term of (1) corresponds to the theoretical minimum attenuation of the line and is denoted by "A 1 'I. After an elementary manipulation, A 1 becomes: A1 = 8.686 ( a1 L). J3) The second term of (I ), known as supplementary attenuation and denoted by "A,": ... (4) accounts for the interactions between the two propagating modes as well as foi the losses in the couplings. While the calculation of A1 is straightfoward. that of A, is quite irwolved. Senn's method [6,7] provides a simple way for determining " As" . Authorized licensed use limited to: IEEE Xplore. Downloaded on April 29, 2009 at 21:55 from IEEE Xplore. Restrictions apply. 953 2.2 Senn's method. The key point in the development of Senn's method i s that when the modal transformation matrices are constant, the coefficients K, CO, C ,, C,, ... and C, are independent of the physical parameters of the line. They depend, instead, on its topological properties only; i. e., the transposition schemes and the coupling connections. There is always, therefore, a polynomial known as "the propagation polynomial" p ( x ) = CO + c, x + c*x, + ... +c,x" which is associated with each line topology. The roots of p( X ) are the values of X that make A S infinite. Only the roots known as "poles" or "cancellation poles", where: 0 s 1x1 5 1 ... (5) represent the possibility of modal cancellation [6,7,131. It is well known [ 7] that the modal transformation matrices of a horizontal line are approximated very closely by the Clarke components. In the more general case of delta lines, it has been shown in [14] that it is still possible to approximate the modal matrices by real constant matrices. Senn's method can thus be extended to these types of lines. Furthermore, for most delta lines, Senn's method can be applied as a first approximation 1141. As an example, consider the PLC system layout of figure la. By applying the Clarke components, the following propagation polynomial i s obtained I121: p( X) = X3 + 3Xz + 15X - 3 ... (6) and K = 16. The loots of the polynomial are X, =0.192 Xz =-1.6+3.6/ and X,=-l.6--3.6; According to (5). the first root is a pole. TRANSMI ~ER RECEIVER t" U3 4 u3+ U 3 4 a) L= 210 km Phase conductors. Hcavg __- Dhc - conductors- Db - Ground wires. Mavg - Dhg - radius- material- 15.24m 12.65m 2x1113 ACSR 0.40m 23.00m 11.00m 0.489cm ALUMOWELD A,, as defined in (3), i s a function of the complex variable X, or, of the two independent variables Aa and AB. Its graphical representation is thus a surface in a tridimensional space. Senn introduced a bidimensional representation of A, in the A a 4 0 plane by means of contour maps. The contour map corresponding to the line topology of figure l a is shown in figure 2. The map i s obtained by replacing p( X) of (6) in (3) and by assigning values to AS. Figure 2. Contour map corresponding to figure l a 'PLC system layout. A,, as well as its contour representation, depends on the line topology only. The physical properties of the line are required only to determine specific values of Aa and A0 and, subsequently, of A S and A t o t . To this end, Senn has introduced another type of plot [6,71 known as the "modal plot". Given the physical data of a specific line, the values of AB are plotted against the corresponding ones of Aa with the frequency as a running parameter. Figure 3, for example, shows five modal plots for the line data of figure I b, each one corresponding to a different value of earth resistivity. Figure 1. PLC system example. a) System layout. b)Line data. Figure 3. Modal plots corresponding to figure t b line data for five different resistivities. Authorized licensed use limited to: IEEE Xplore. Downloaded on April 29, 2009 at 21:55 from IEEE Xplore. Restrictions apply. 954 Assuming that the supplementary attenuation of the system specified by figure 1 is to be obtained, the modal plot corresponding to the earth resistivity of p=7000m should be superimposed on figure 2 contour plot. The values of A,, read at the crossings of the modal plot and the contour curves, are plotted in figure 4 along with the values of A1 obtained from (2). The addition of A, and X I , which is also plotted in figure 4, yields the total line attenuation A t o t . 0 THEOR. MIN. ATTENUATION. I 0 SUPPLEMENTARY ATTENUATION. ATTENUATION. 0 0 0 0 FREQUENCY - KHZ Figure 4. Plots of total attenuation, supplementary attenuation and theoretical minimum attenuation for the PLC system specified in figure 1. 3. CONSIDERATIONS OF COUPLING RECOMMENDATIONS FOR PLC DESIGN. 3.1 Analysis of the IEC PLC coupling Recommendations. The two most common PLC coupling configurations are phase to ground and phase to phase in differential mode [41. The latter is also known as push-pull coupling. On a three phase line these two configurations provide up to eighteen alternatives of coupling. In order to make a selection, design engineers usually resort to given sets of recommendations. The ones issued by the International Electrotechnical Commission (IEC) are perhaps the most widely adopted [81. Figures 5, 6 and 7 show the couplings recommended by the IEC for nontransposed, single transposed and double transposed horizontal lines, respectively. The couplings of figures 5, 6 and 7 are referred to in 181 as "optimum" couplings. This designation, however, can cause confusion. Only the coupling of figure Sa is optimum in the usual sense that its attenuation is lower than that of any other phase to ground coupling alternative [121. The TRANSMITTER RECEIVER TRANSMIlTER RECEIVER Figure 5. Couplings recommended by the IEC transposed lines, a) Phase to ground Configuration. b) phase configuration. coupling for non Phase to of figure Sb, for instance, often produces more attenuation than that of figure 8a; the region of the Pa-A0 plane in which this happens is the shadowed one of figure 8b [12]. It has been shown in I131 that in the case of single transposed lines, some couplings may produce lower attenuation than those of figures 6a and 6b. Although figures 5b, 6a and 6b couplings are not optimum in the sense stated above, the fact that they prevent modal cancellation and that their supplementary attenuation levels are well below 20 dB make them highly recommendable. TRANSMI ~ER RECEIVER 77 a) b) TRANSMITTER RECEIVER x 0 Figure 6. Couplings recommended by the IEC for single transposed lines. a) Phase to ground configuration. b) Phase to phase configuration. RECEIVER TRANSMIlTER TRANSMITTER RECEIVER Figure 7. Couplings recommended by the IEC for double transposed lines. a) Phase to ground configuration. b) Phase to phase configuration. TRANSMmR RECEIVER a) T 3600E13 270 A0 180 b) oo Fftf-ttl 10 20 30 Figure 8. Phase to phase coupling on a non transposed line. a) Layout. b) The shadowed region corresponds to the cases in which coupling 8a presents lower attenuation than the one in figure 5b. Authorized licensed use limited to: IEEE Xplore. Downloaded on April 29, 2009 at 21:55 from IEEE Xplore. Restrictions apply. 955 For the case of double transposed lines, the couplings recommended by the IEC (figures 7a and 7b) present a risk of modal cancellarion. This has been shown already for figure 7b coupling in the previous example in section 2. For the phase to ground coupling of figure 7a, the following propagation polynomial is obtained I121: p( X ) = 3x - 1. ... (7) The only root of (7) i s X = 113 which, according to ( S) , is a cancellation pole. The corresponding contour map is shown in figure 9. Instead of pursuing the concept of "optimum" couplings further, the authors consider that a more useful approach is to identify those couplings that can be prescribed in the most general practical situations. Couplings preventing modal cancellation and whose supplementary attenuation levels are below 20 dB [5] will thus be referred to as "recommended" couplings. Whereas figures 5, 6 and 8a couplings fall into this cathegory, the ones in figures 7a and 7b do not. Their application requires a careful analysis. 0 0 A'ITENUATION DIFTERENCE Aa Figure 9. Contour map corresponding to the coupling of figure 7a. 3.2 Further coupling studies. A desirable feature of the recommended couplings, as they have been defined above, is that they can be applied without further analysis. The cases of lines divided in three homogeneous sections of equal length by two transpositions and of triple transposed lines in which the transpositions are located at one sixth, one half and five sixths of the line length are very common. It i s therefore attractive to look for recommended couplings for these transposition schemes. The results of an extensive search conducted by the authors are reported as follows. All the conventional coupling options (i. e., phase to ground and phase to phase differential mode) were analyzed first. For all cases of triple transposed lines and of phase to ground couplings on double transposed lines the propagation polynomials contain cancellation poles [121. Only two of the phase to phase differential coupling options for double transposed lines are pole-free; however, their contour plots show that their supplementary attenuation i s usually above 20 dB [121. The possibility that there could be some regions in the Aa-A9 plane which are seldomly crossed by the modal curves or, even better, not crossed at all was explored. It would be possible, then, to disregard the poles inside such regions. A statistical approach was adopted [11]. It was found that only the Aa-axis and its immediate neighborhood are seldomly crossed by the modal curves. Apart from this narrow region, the rest of the Aa-A0 plane for values of Aa up to 35 dB i s crossed frequently by the modal curves. The following non-conventional coupling alternatives were also analyzed: 1. Phase to phase couplings with differential mode on one side and equal polarity on the other side 2. phase to ground on one side of the line and phase to phase on the other side 3. Three phase mode 1 coupling. For all these couplings, the corresponding propagation polynomials contain cancellation poles. It can therefore be concluded that there are no recommended couplings ior the considered cases of double and triple transposed lines. The fact that mode I couplings were considered is stressed, as they are often prescribed for critical communication links [151. The contour map of mode 1 coupling for a double transposed line is provided in figure IO. The one for a triple transposed line has been provided in 1131 (Push-pullipush-push). A9 10 20 30 ha Figure 10. Contour map corresponding to mode 1 coupling on a single transposed line. 4. LINE RESPONSE CALCULATIONS I N PLC DESIGN. The results of section 3 show that for some line transposition schemes, it i s not possible to find recommended couplings. For these cases, an effective method of analysis is required to ensure the PLC system reliability. PLC frequency response can be calculated in principle through the methods described in [ 2 ] . A common design practice is to predict the frequency responses for each coupling alternative and to compare them in order to make a selection. The problem with this approach i s that PLC system calculations are based on line information which, in most practical situations, cannot be obtained within the desired accuracy. Predicted line responses, therefore, often differ substantially froin the actual line responses. Moreover, as some of the line parameters are affected by the climate. PLC system responses may not be even constant. Of all the line data, the earth resistivity is usually the most uncertain. PLC designers have to rely on rough measurements made for power transmission purposes or on information from tables of soil resistivity. To attempt a more accurate specification is impractical in most cases. Apart from the difficulties in performing this type of measurement, Authorized licensed use limited to: IEEE Xplore. Downloaded on April 29, 2009 at 21:55 from IEEE Xplore. Restrictions apply. 956 resistivity values usually change from one point to another along the line as well as at different depths under the ground [9]. Since the depth of penetration of the ground return currents depends on the frequency, the equivalent earth resistivity at each point along the line has to be a function of frequency. Although to a lesser degree than the ground resistivity, the conductor height data have a degree of uncertainty also, especially when the line runs across irregular terrain. As an example of the effects of climate on the line parameters, consider the sag of the conductors, which is affected by temperature changes. This is known to provoke recurrent loss of communications in some PLC systems. Another example is the earth resistivity which may be affected by seasonal changes of soil humidity. To illustrate the effect of earth resistivity the frequency response of the PLC system described by figure 1 is calculated for the following earth resistivities: p=200Slm, p=300Qm, p=50051m, p=70052m and p=1000Slm. Note that these resistivities are the same as for the modal curves of figure 3. The obtained frequency responses are plotted in figure 11. It can be seen that the frequency response is more sensitive to line parameter changes in the neighborhood of a cancellation pole. The difficulties in detecting cancellation poles by using frequency response calculations only can be observed in figure 11. The plots for p = 200 Qm and p = 300 am, for instance, do not show any sign of modal cancellation. These difficulties are further illustrated in the plots of figure 12. Both plots correspond to the PLC system of figure 1 for an earth resistivity of p = 700 am. One plot is made with ten computation intervals whilst the other is made with fifty of such intervals. It can be observed that the cancellation peak is almost missed in the ten interval plot. I b o ,000 2000 3000 4000 5000 000.0 FREQUENCY - KHZ Figure 11. Frequency responses for figure I PLC system for different values of earth resistivity. 0. 0 10.0 20.0 ATTENUATION DIFFERENCE Aa 30.0 Figure 13. Modal plots corresponding to figure I b line data for different values of conductor average heights. 5. PROPOSED METHOD FOR PLC SYSTEM DESIGN. For the cases in which there are no pole-free couplings the risk of modal cancellation can be minimized through the selection of suitable carrier frequencies. It follows from the discussion of section 4 that computed line responses are of little assistance for this task. A method of design is thus required. The one proposed here is based on Senn's technique for calculating PLC response. A major obstacle in the systematic design of PLC systems is the uncertainty of the line physical data. In this respect, Senn's technique has the advantage that physical and topological factors of signal propagation are dealt with independently. The uncertainties of physical data can be conveniently accounted for on the Senn modal plots. An example is given next in which the proposed method i s also illustrated. Consider the PLC system described by figure 1. Assume, now, that due to temperature changes mainly, the conductor average heights can vary between 14 m and 18 m. The modal plot of figure 13 is made for these values and for the line data of figure I b. The shadowed regions indicate a supplementary attenuation greater than 20 dB for the coupling of figure la. As the conductor average heights decrease from 18 m to 14 m, the frequencies inside the range 225 kHz to 450 kHz will fall inside the shadowed region and, therefore, this range should be avoided. In the same manner, a range of frequencies to avoid may be determined because of uncertainty of the earth resistivity information. For example, if a variation of resistivities between 200 Qm and 1000 Slm is assumed, the modal plot of figure 3 can be used. By superimposing the shadowed regions of figure 13 onto figure 3, it can be seen that the frequencies in the range 255 kHz and 350 kHz should be avoided. Figure 14 shows the PLC system responses for various conductor heights between 14 rn and 18 m. This figure should be compared with figure 11 in order to observe the difference of effects between earth resistivity variations and conductor height variations. The dashed lines in figure 14 mark the range of frequencies determined from figure 13 where there is a risk of modal cancellation. Note also that information concerning the dynamic range of the received signal can be obtained from figure 14. 0 0 I O00 2000 3000 FREQUENCY - 1000 5000 KHZ Figure 12. Plots of frequency response for figure 1 PLC system with p=700Qm. One plot is made with ten computational intervals and the other with fifty intervals. The limit of 20 dB for the supplementary attenuation is found to be rather conservative for this example. It can be relaxed (say to 25 dB) with the consequent increase in the dynamic range of the received signal. Although it has been assumed that earth resistivity and conductor heights vary independently, the analysis can be adapted to deal with Authorized licensed use limited to: IEEE Xplore. Downloaded on April 29, 2009 at 21:55 from IEEE Xplore. Restrictions apply. 957 simultaneous variations of both parameters as well as to bring more parameters into consideration. Finally, it should be stressed that as soon as the required modal plots have been produced, it is an easy matter to analyze additional coupling options. These plots are simply superimposed on the corresponding contour maps. I FREQUENCY - KHZ 1000 Z O O 0 3000 4000 5000 Figure 14. Frequency responses for figure 1 PLC system for different va!ues of conductor average heights. 6. USE OF SHUNT CAPACITORS TO IMPROVE PLC FREQUENCY RESPONSE. Transpositions have the sole purpose of equalizing the self and the mutual impedances of long transmission lines at power frequency. At communication frequencies, however, they art as discontinuities which cause mode conveisions. Transpositions thus, tend to increase the risk of modal cancellation. One may think that there are other discontinuities that could minimize this risk. However, it has to be kept in mind that these discontinuities must not affect the primary function of power transmission. In addition, they have to be economically feasible. Recently the authors have been considering the connection of shunt capacitors at certain points along the line. The capacitors are of the type normaly used in PLC couplings and for potential transformers. Their location is determined in such a way that the poles of the corresponding propagation polynomial are in a position of the Aa-A6 plane where they exert very low influence on the PLC response. As an example, consider the system layout of figure 15 and the line data of figure l b. By assuming that the PLC signal at the point of connection is zero, the following polynomial is obtained [la?]: p(X) = x2 + 1 ... ( 8) Its poles X, =+ j and X2 =-j lie on the Pa-axis of the Aa-A0 plane. As it is shown in [12], this is a region through which modal curves seldomly pass. The system responses for earth resistivities between p =20051m and p =100051m are pi-ovided in figure 16a. Similarly, the responses for conductor heights between 14 m and 18 m are provided in figure 16b. - 1 K e - 1 K e Fi gure 15. Layout of a PLC system with shunt capacitor to improve frequency response. P i m 0 0 1000 2000 3000 1000 5000 FREQUENCY - KHZ a) n Hcavg=14m o Hcavg=15m A Hcavg =16m +Hcavg =17m x Hcavg=18m 0 0 LOO0 C OO0 3000 1d O. O 500.0 FREQUENCY - KHZ b) Figure 16. Frequency responses for figure 15 PLC system. a) Earth resistivity variations. b) Conductor average height variations. In some cases, the use of shunt capacitors results in pole-free propagation polynomials. For example, the arrangement shown in figure 17 has a propagation polynomial, p( X) = 1.0 [la?]. Its supplementary attenuation A, = 19 dB is constant all over the Aa-A0 plane. Up to now, the location of the shunt capacitors has been determined by trial and error. A systematic method for determining such locations is highly desirable. Figure 17. Layout of PLC system in which the shunt capacitor eliminates the cancellation poles. 7. CONCLUSIONS. PLC designers resort either to given sets of coupling recommendations or to computer programs that predict iine frequency response for the design of carrier systems. It has been shown here that some of the most widely accepted coupling recommendations do not prevent modal cancellation. Among them are some of the couplings recommended by the IEC and some of the mode 1 three-phase couplings. It has been shown, furthermore, that for mme common transposition schemes there are no pole-free couplings. Also convefitional computer programs that predict line response may not be well suited for the detection of modal cancellation conditions. Authorized licensed use limited to: IEEE Xplore. Downloaded on April 29, 2009 at 21:55 from IEEE Xplore. Restrictions apply. 958 A method of design of PLC systems has been proposed. This method allows for the consideration of the uncertainty which is usually present in some of the line data as well as of the variations that affect some of the line parameters. The authors believe that the application of the proposed method will result in more reliable PLC designs. Although PLC design has been restricted so far to the selection of couplings and of carrier frequencies, it has been proposed that the connection of shunt capacitors at a few points along the line may improve the line frequency response without affecting its primary function of power transmission. The authors have found that, in some cases, the possibility of modal cancellation is completely eliminated. Further work is required on this technique. For instance, the analvsis of section 6 is based on the simplified method of section 2. The authors are currently performing more accurate simulations through the methods of [21. Other future activity is the search for a systematic method to determine the most convenient capacitor locations. ACKNOWLEDGMENTS. The authors wish to express their gratitude to Prof. L. M. Wedepohl for the many valuable discussions and his assistance. The financial assistance of the Natural Sciences and Engineering Research Council of Canada through Operating Grant OCP 0008831 to Prof. H. W. Dommel is gratefully acknowledged. Finally, Luis Naredo thanks the National Research Council of Mexico (CONACM) for the provision of a scholarship and the Electrical Research Institute of Mexico (HE) for granting him a leave of absence to conduct graduate studies. REFERENCES. [ 11Wedepohl L. M., "Application of Matrix Methods to the Solution of Travelling-wave Phenomena in Polyphase Systems.", Proc. IEE, Vol. 110 No. 12, pp. 2200-2212, Dec. 1963. [ 2lWedepohl L. M., Wasley R. C., "Propagation of Carrier Signals in Homogeneous, Nonhomogeneous and Mixed Multiconductor Systems.", Proc. IEE, Vol. 115, No. 1, J anuary 1968. [ 31Belous B. P., Kostenko M. V., Mikutsky C. V., Sidelnikov V. V., Shkarin Yup, "investigation and Calculation of High-frequency paths of communication-channels of Transmission Lines.", ClCRE 1966, 328. [ 41Podszeck H. K., "Carrier Communication over Power Lines.", Springer-Verlag, Fourth Edition, 1972. [ 51Senn W. H., Morf K. P., "Optimum Power Line Carrier (PLC) Coupling Arrangement on Transposed Single Circuit Power Lines." CICRE, 1974, 35-02. [ 61Senn W. H,, "A New Approach to Determine the Carrier Signal Attenuation on Horizontal H. V. Lines, Both Under Normal and Abnormal Conditions. 'I, International Conference on Large High Voltage Electric Systems, CICRE 35-03, 1976 Session, Aug. 25/Sept. 2. [ 71 Eggimann F., Senn W., Morf K.,"Transmission Characteristics of High-Voltage Lines at Carrier Frequencies.", Brown-Boveri Revue. Vol. 8, pp. 1-11, 1977 [ 81 "Planning of (Single-sideband) Power Line Carrier Systems.", International Electrotechnical Commission IEC Report, Publication 66311 980. [ 91Deri A., Tevan C., Semlyen A., Castanheira A., "The Complex Ground Return Plane, a Simplified Model for Homogeneous and Multi-layered Earth Return.", IEEE Transactions on PAS, Vol. PAS-100, Pp. 3686- 3693, Aug. 1981. [I O] Naredo I . L., Cuardado L., "On Non-conventional Couplings.", internal communication, lnstituto de lnvestigaciones Electricas de M6xico, Divisibn Sistemas de Potencia, March 1984. 1111 Naredo J . L., Silva I . L., Moreno P., Romero R., "Approximated Modal Analysis Methods for PLC Attenuation Calculation and Coupling Recommendations Generation." Report submitted to the CICRE Working Croup 35-03, August 1986. [I21 Naredo J ose Luis A., "Coinmunication Frequency Response of High Voltage Power Lines.", M. A. Sc. Thesis, Department of Electrical Engineering, The University of British Columbia, April 1987. [I31 Naredo 1. L., Silva 1. L., Romero R., Moreno P., "Application of Approximated Modal Methods for PLC Systems Design.", IEEE Transactions on Power Delivery, Vol. PWRD-2, No. 1, pp. 57-63, J anuary 1987. [14] Naredo 1. L., Soudack A. C., "Extension of Senn's Method to the Analysis of PLC Systems Applied to Delta Transmission Lines.", Accepted for publication in the IEE Proceedings-C., July 15th, 1989. I151 Northwest Power Pool-Telecommunications, "Carrier Current Channel Data Telemetering & Load Control Installations, Microwave Channels as of March 1985.", Coordinating Croup Office, 11 15 Public Service Building, Portland, Oregon 97204, November 1, 1985. ]os& Luis Naredo was born in Puebla, Pue., Mgxico in 1953. In 1976 he obtained the bachelor's degree in Mechanical and Electrical Engineering from Universidad Anahuac of Mkxico DF. In 1987 he obtained the Master of Applied Sciences degree from the University of British Columbia (UBC) of Vancouver, Canada, where he is currently working towards the Ph. D. degree. Since 1978, Mr. Naredo has been with the lnstituto de lnvestigaciones Electricas de Mkxico (HE) from which, in 1984, he took a leave of absence to conduct graduate studies. At IIE he has been, consecutively, research assistant, researcher and project manager involved in microwave network design, power line communications and frequency domain transient analysis. Mr. Naredo's profesional interest is in power system analysis, electromagnetic field calculations and telecommunications. Prof. Avrum C. Soudack obtained his B. A. Sc. E. E. at the University of Manitoba in 1957 and his Ph. D. in Electrical Engineering at Stanford University in 1961. He has been with the Electrical Engineering department at the University of British Columbia since 1961, working in the area of nonlinear systems. He has published widely in diverse journals on such topics as non- linear circuits, control systems and ecological models. His present interest is in chaotic behaviour in nonlinear systems. Authorized licensed use limited to: IEEE Xplore. Downloaded on April 29, 2009 at 21:55 from IEEE Xplore. Restrictions apply.