Air Conditioner Maintenance

Guidance
Air Conditioner Description



The DC series air conditioner is a cooling product developed
for cabinet which is supplied DC power. The internal cycle air
path absorbs the hot air from the upside, and discharges the
cold air from the downside of the air conditioner. The external
cycle air path absorbs the external cold air from the downside,
and discharges the hot air from the upside after heat exchange.
Technical Parameters
Model
EC08 air conditioner
Input Power w 220V
Cooling Capacity @ L35/L35 w 800
Power consumption @ L35/L35 w 390
Input current @ L35/L35 A 2.02
Refrigerant R134a
Working temperature range -15~55
Noise level dB(A) 63
Dimensions
(height*width*depth)
mm 750430195
Protection from dust, water
and wind driven rain
IP55
Internal airflow CMH 135
Commonly Used Spare Parts
Commonly used spare parts
Name Model
Controller ENVICOOL EC03U17
Inlet fan ADDA AD1248HB-F91GP
Outlet fan AVC BN17569B48M
Compressor
Sensor ENVICOOL NTC0001
Membrane keyboards ENVICCOL EC03-008
Prepared tools
Phillips screwdriver:
Remove the panel screws


Small screwdriver:
Inspect &
maintain control lines

Clamp Multi-meter:
Test electronic
control components,
test voltage and current.
Adjustable wrench:
Fasten, remove fan & motor

Oblique mouth clamp:
Cut & strip wire

Needle nose pliers:
Wiring, test electronic control
Temperature tester:
Test the temperature

System introduce
Main
controller
Outlet fan
Compressor
Inlet fan
Heater
EC08Menu List
ShutDown

ShutDown
Starting

English
Normal interface
Ta:26.5
Cool
Password input
PSW:****
Set Point
CoolSP:23
CoolT:03
HeatSP:15
HeatT:05
Engy:22
EngyT:03
INHT:30
INLT:05
OUHT:38
OULT:05
EmsFan:30
InFan:23
SpeedH:80%
SpeedL:40%
OutFan:40
Alarm Menu
Active Alarm
Alarm Log
Alarm Output
Alarm Input
Status Menu
Sensor Value
Run Status
Set Up
Setup Para
Diagnosis
VersionInfo
Sensor Value
Tin1:26.5
Tin2:25.8
Hin:--
Tout:30.0
Tp:10.2
Te:59.3
Vdc:50.5V
Run Status
InFan: RUN
Comp: RUN
Heater: --
OutFan: RUN
EMSFan
STOP
Main Menu
Set Point
Alarm Menu
Status Menu
Set Up
Setup Para
Change Psw
Para set
MonitorSetup
Restore
Diagnosis
SelfTest
VersionInfo
Name:BP-ASP
SoftVer:2.0
Monitor:2.1
Active Alarm
Wam:00/00
NoAlarm
Alarm Log
In HT:0Ts
In LT:0Ts
OUT HT:0Ts
OUT LT:0Ts
Tin S:0Ts
Tout S:0Ts
Tp S:0Ts
Te S:0Ts
InFan:0Ts
OutFan:0Ts
HP:0Ts
Comp:0Ts
Exst:0Ts
Frost:0Ts
EEPROM:0Ts
DC OV:0Ts
DC UV:0Ts
Door:0Ts
Shock:0Ts
Water:0Ts
Smoke:0Ts
SPD:0Ts
Alarm Input
Door:NO
Shock:NO
Water:NO
Smoke:NO
SPD:NO
Alarm Output
In HT:Pt1
In LT:Pt1
OUT HT:Pt1
OUT LT:Pt1
Tin S:Pt1
Tout S:Pt1
Tp S:Pt1
Te S:Pt1
InFan:Pt1
OutFan:Pt1
HP:Pt1
Comp:Pt1
Exst:Pt1
Frost:Pt1
EEPROM:Pt1
DC OV:Pt1
DC UV:Pt1
Door:Pt1
Shock:Pt1
Water:Pt1
Smoke:Pt1
SPD:Pt1
Change Psw
NewPsw:****
Conf:****
MonitorSetup
Monitor Addr
Monitor Type
IP Address
Port Number
Para Set
Wam:NO
Dely:30S
Int:24H
RunT:05M
Door:Close
Monitor Addr
Monitor Addr
01H
Monitor Type
RS485
GPRS
IP Address
192.168
125.125
Port Number
Port Number
05002
Error
Password
ec08 Menu List
STEP1:Observe LCD
screen and inlet fan
LCD screen Inlet fan Check
OFF OFF
Input power
Main controller
ON OFF Inlet fan
STEP2:Check active
alarm and alarm log
STEP3:Selftest and
test the system current
Refer to common alarm analysis
Cooling
Compressor Outlet fan Current Others Check
OFF OFF
Around0.3A TpTin
TeTout
Main controller
OFF ON
Around0.6A TpTin
TeTout
Compressor controller
ON OFF -----
Te30 Outlet fan
ON ON -----
Tin-Tp4 Refrigerant, compressor,
filter, inlet fan, outlet fan
ON ON
Above2.2
-------
Refrigerant, compressor,
filter, inlet fan, outlet fan
Common alarm analysis
Alarm Possible Cause
Check or
Maintenance
High temperature(HT) Alarm
The AC failure Check AC alarm menu
Inlet is failure Repalce inlet fan
Wrong set point Check AC set point
Over Voltage alarm
Input power is overtop ac220v+15% Check input power
Controller is failure Replace controller
Under Voltage alarm
Input power is lower than 220-15% Check input power
Controller is failure Replace controller
Sensor Fault alarm
The inlet /outlet /coil /discharge
temperature sensor fault
Replace sensor
AC controller is failure Replace controller
Common alarm analysis
Alarm Possible Cause
Check or
Maintenance
High Pressure(HP) Alarm
The outlet fan is failure Replace outlet fan
The filter screen is dirty Clean the filter screen
Compressor failure alarm
Compressor failure Replace air conditioner
System have no refrigerant(R134a) Replace air conditioner
Inlet or coil temperature sensor fault Replace sensor
Frost alarm
The inlet fan is failure Replace inlet fan
System have no refrigerant Replace air conditioner
Fault Feedback Form
Fault Feedback Form
Date Model
Adress SN
Fault
Description

Alarm Menu
Active Alarm Alarm Log
Alarm1 Tp S
Alarm2 Te S
Alarm3 HP
Alarm4 Comp
Alarm5 Frost
Alarm6 DC OV
DC UV
..
..
Sensor Value
Tin1 Te
Tin2 Tp
Tout Cond
.. Vdc
Current Test
System Compressor
Inlet Fan Outlet Fan
What did you test and judgment?

Do you think the possible reasons?
Others