NR Electric Co., Ltd. Preface CZX-22R Interposing Relay Set i Date: 2011-04-12 Preface Introduction This guide and the relevant operating or service manual documentation for the equipment provide full information on safe handling, commissioning and testing of this equipment. Documentation for equipment ordered from NR is dispatched separately from manufactured goods and may not be received at the same time. Therefore, this guide is provided to ensure that printed information normally present on equipment is fully understood by the recipient. Before carrying out any work on the equipment, the user should be familiar with the contents of this manual, and read relevant chapter carefully. This chapter describes the safety precautions recommended when using the equipment. Before installing and using the equipment, this chapter must be thoroughly read and understood. Health and Safety The information in this chapter of the equipment documentation is intended to ensure that equipment is properly installed and handled in order to maintain it in a safe condition. When electrical equipment is in operation, dangerous voltages will be present in certain parts of the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger personnel and equipment and cause personal injury or physical damage. Before working in the terminal strip area, the equipment must be isolated. Proper and safe operation of the equipment depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing. For this reason, only qualified personnel may work on or operate the equipment. Qualified personnel are individuals who: Are familiar with the installation, commissioning, and operation of the equipment and of the system to which it is being connected; Are able to safely perform switching operations in accordance with accepted safety engineering practices and are authorized to energize and de-energize equipment and to isolate, ground, and label it; Are trained in the care and use of safety apparatus in accordance with safety engineering practices; Are trained in emergency procedures (first aid). Instructions and Warnings The following indicators and standard definitions are used: Preface CZX-22R Interposing Relay Set ii Date: 2011-04-12
DANGER! It means that death, severe personal injury, or considerable equipment damage will occur if safety precautions are disregarded.
WARNING! It means that death, severe personal, or considerable equipment damage could occur if safety precautions are disregarded.
CAUTION! It means that light personal injury or equipment damage may occur if safety precautions are disregarded. This particularly applies to damage to the device and to resulting damage of the protected equipment.
WARNING! The firmware may be upgraded to add new features or enhance/modify existing features, please make sure that the version of this manual is compatible with the product in your hand.
WARNING! During operation of electrical equipment, certain parts of these devices are under high voltage. Severe personal injury or significant equipment damage could result from improper behavior. Only qualified personnel should work on this equipment or in the vicinity of this equipment. These personnel must be familiar with all warnings and service procedures described in this manual, as well as safety regulations. In particular, the general facility and safety regulations for work with high-voltage equipment must be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER! Never allow the current transformer (CT) secondary circuit connected to this equipment to be opened while the primary system is live. Opening the CT circuit will produce a dangerously high voltage.
WARNING! Exposed terminals Do not touch the exposed terminals of this equipment while the power is on, as the high voltage generated is dangerous Preface CZX-22R Interposing Relay Set iii Date: 2011-04-12 Residual voltage Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It takes a few seconds for the voltage to discharge.
CAUTION! Earth The earthing terminal of the equipment must be securely earthed Operating environment The equipment must only be used within the range of ambient environment detailed in the specification and in an environment free of abnormal vibration. Ratings Before applying AC voltage and current or the DC power supply to the equipment, check that they conform to the equipment ratings. Printed circuit board Do not attach and remove printed circuit boards when DC power to the equipment is on, as this may cause the equipment to malfunction. External circuit When connecting the output contacts of the equipment to an external circuit, carefully check the supply voltage used in order to prevent the connected circuit from overheating. Connection cable Carefully handle the connection cable without applying excessive force.
Copyright Version: R1.00
P/N: EN_CZXL3113.0086.0001
Copyright NR 2011. All rights reserved
NR ELECTRIC CO., LTD. 69 Suyuan Avenue. Jiangning, Nanjing 211102, China Tel: +86-25-87178185, Fax: +86-25-87178208 Website: www.nrelect.com, www.nari-relays.com Email: nr_techsupport@nari-relays.com
We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination to third parties is strictly forbidden except where expressly authorized.
The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.
We reserve the rights to make technical improvements without notice.
Table of Contents CZX-22R Interposing Relay Set iv Date: 2011-04-12 Table of Contents Preface ..................................................................................................... i Introduction ................................................................................................................ i Health and Safety ....................................................................................................... i Instructions and Warnings ........................................................................................ i Table of Contents .................................................................................. iv 1 Introduction ......................................................................................... 1 1.1 Application ........................................................................................................... 1 1.2 Features ............................................................................................................... 1 1.3 Ordering Options ................................................................................................ 1 2 Technical Data ..................................................................................... 3 2.1 Electrical Specifications ..................................................................................... 3 2.1.1 Power Supply ........................................................................................................................ 3 2.1.2 Binary Input ........................................................................................................................... 3 2.1.3 Binary Output ........................................................................................................................ 3 2.2 Mechanical Specifications ................................................................................. 4 2.3 Ambient Temperature and Humidity Range ...................................................... 4 2.4 Type Tests ............................................................................................................ 4 2.4.1 Environmental Tests .............................................................................................................. 4 2.4.2 Mechanical Tests................................................................................................................... 4 2.4.3 Electrical Tests ...................................................................................................................... 5 2.4.4 Electromagnetic Compatibility ............................................................................................... 5 2.5 Certifications ....................................................................................................... 6 2.6 Relay Performance.............................................................................................. 6 3 Operation Theory ................................................................................ 7 Table of Contents CZX-22R Interposing Relay Set v Date: 2011-04-12 3.1 Schematic Diagrams ........................................................................................... 7 3.1.1 Auto-Reclosing and Manual Closing Circuit .......................................................................... 7 3.1.2 Phase-Segregated Closing Circuit ........................................................................................ 8 3.1.3 Phase-Segregated Tripping Circuit (Group 1) ....................................................................... 9 3.1.4 Phase-Segregated Tripping Circuit (Group 2) ..................................................................... 10 3.1.5 Trip and Auto-reclosing Target Circuit ................................................................................. 11 3.1.6 Low Pressure Blocking Circuit ............................................................................................ 12 3.1.7 Accelerated Circuit when Manual Closing ........................................................................... 12 3.1.8 Output Contacts .................................................................................................................. 13 3.2 Power Supply .................................................................................................... 15 3.3 Closing Circuits ................................................................................................. 16 3.3.1 Auto-reclosing Circuit .......................................................................................................... 16 3.3.2 Manual and Remote Closing Circuit .................................................................................... 16 3.3.3 Phase-Segregated Closing Circuit ...................................................................................... 16 3.4 Trip Circuit ......................................................................................................... 17 3.4.1 Manual and Remote Trip ..................................................................................................... 18 3.4.2 Three Phase Trip Signal Inputs from Protection .................................................................. 18 3.4.3 Phase-Segregated Trip Circuit 1 ......................................................................................... 18 3.4.4 Phase-Segregated Trip Circuit 2 ......................................................................................... 20 3.5 KKJ ..................................................................................................................... 21 3.6 Pressure Supervision ....................................................................................... 21 3.6.1 Low Pressure to Block Trip ................................................................................................. 22 3.6.2 Low Pressure to Block Auto-reclosing ................................................................................. 22 3.6.3 Low Pressure to Block Closing ........................................................................................... 22 3.6.4 Low Pressure to Block Switching ........................................................................................ 23 3.7 Pole Disagreement ............................................................................................ 23 3.8 Control Circuit Failure ...................................................................................... 23 3.9 Spare Relays ...................................................................................................... 23 4 Hardware ........................................................................................... 25 Table of Contents CZX-22R Interposing Relay Set vi Date: 2011-04-12 4.1 Overview ............................................................................................................ 25 4.2 Device Layout .................................................................................................... 25 4.3 Front View .......................................................................................................... 25 4.4 Terminals ........................................................................................................... 27 4.4.1 Definition of Connector A .................................................................................................... 28 4.4.2 Definition of Connector B .................................................................................................... 29 4.4.3 Definition of Connector C .................................................................................................... 30 4.4.4 Definition of Connector D .................................................................................................... 31 4.4.5 Definition of Connector E .................................................................................................... 32 4.4.6 Definition of Connector F .................................................................................................... 33 4.4.7 Definition of Connector G .................................................................................................... 34 4.4.8 Definition of Connector H .................................................................................................... 35 4.4.9 Definition of Connector I ..................................................................................................... 35 4.5 Adjustment Method for Latching Current of Tripping & Closing .................. 37 5 Installation ......................................................................................... 39 5.1 Overview ............................................................................................................ 39 5.2 Safety Information............................................................................................. 39 5.3 Check the Shipment .......................................................................................... 40 5.4 Material and Tools Required ............................................................................ 41 5.5 Device Location and Ambient Conditions ...................................................... 41 5.6 Mechanical Installation ..................................................................................... 41 5.7 Electrical Installation ........................................................................................ 42 5.7.1 Grounding Guidelines ......................................................................................................... 42 5.7.2 Cubicle Grounding .............................................................................................................. 43 5.7.3 Making Electrical Connections ............................................................................................ 44 6 Commissioning ................................................................................. 45 6.1 Overview ............................................................................................................ 45 6.2 Safety Instructions ............................................................................................ 45 Table of Contents CZX-22R Interposing Relay Set vii Date: 2011-04-12 6.3 Insulation Test (if required) .............................................................................. 46 6.4 Product Checks ................................................................................................. 46 6.4.1 General Description ............................................................................................................ 46 6.4.2 Visual Inspection ................................................................................................................. 47 6.4.3 Check the Jumpers ............................................................................................................. 47 6.4.4 External Wiring .................................................................................................................... 48 6.4.5 Auxiliary Supply ................................................................................................................... 48 6.5 Final Check ........................................................................................................ 48 7 Maintenance ...................................................................................... 49 7.1 Routine Check ................................................................................................... 49 7.2 Replace Failed Modules ................................................................................... 49 7.3 Cleaning ............................................................................................................. 50 7.4 Storage ............................................................................................................... 50 8 Decommissioning and Disposal ...................................................... 51 8.1 Decommissioning ............................................................................................. 51 8.2 Disposal ............................................................................................................. 51 9 Manual Version History .................................................................... 53
Table of Contents CZX-22R Interposing Relay Set viii Date: 2011-04-12
1 Introduction CZX-22R Interposing Relay Set 1 Date: 2011-04-12 1 Introduction 1.1 Application CZX-22G interposing relay set provides auxiliary relays for switching of circuit breaker with two group phase-segregated tripping circuits, one group phase-segregated closing circuit and an accelerated circuit when manual closing and selecting faulty feeder. The device can be used for circuit breaker with one and a half breakers arrangement. Protection device, BCU and other relevant devices can trip or close circuit breaker via this device. 1.2 Features The device is an IEC standard 4U high and 19 wide rack with modular structure. It uses an integral faceplate and plug terminal blocks on rear panel for external connections. It has features of compact design, high security, flexibility and convenience. Sealed relays with high impedance and low power dissipation are used in this device. As a result, the power dissipation and heating is reduced largely, moisture proof is improved, ensuring a long life even in extreme mechanical and ambient conditions. Seal-in current of trip and close circuit can be configured easily by jumpers on site according to the rated current of trip and close coil. A special relay is equipped in the relay set, which will pick up and latch when circuit breaker is closed manually, and reset when circuit breaker is tripped manually. The contacts of this special relay can be used by substation automation system to issue an accident signal whenever the circuit breaker is tripped un-manually. Moreover, together with normal closed auxiliary contact of circuit breaker (52b), the contacts of this special relay can also be used to initiate auto-reclosing in case that circuit breaker trips especially without any trip commands from protection and manual switch. Spare relays are provided for future application. For these circuits, initiating AR and BFP, initiating BFP but not AR, three-phase circuit of machnical protection, manual tripping, manual closing and auto-reclosing, their initiation power are all greater than 5W. 1.3 Ordering Options Four options are available for rated auxiliary voltage: 250V, 220V, 125V, 110V. The rated current of target and seal-in relays in trip and closing circuit can be configured as 0.5-4.0A with a step of 0.5A. They should be selected based on the amount of current the trip and closing circuit drawn when operated. 1 Introduction CZX-22R Interposing Relay Set 2 Date: 2011-04-12 The rated auxiliary voltage and nominal current of trip and close coil shall be claimed clearly when ordering.
2 Technical Data CZX-22R Interposing Relay Set 3 Date: 2011-04-12 2 Technical Data 2.1 Electrical Specifications 2.1.1 Power Supply Rated Voltage 110Vdc, 125Vdc, 220Vdc, 250Vdc Variation (80%~120%)Un Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:1979 Voltage dips and voltage short interruptions Per IEC 60255-11:1979 20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms Burden Quiescent condition <40W Operating condition <70W 2.1.2 Binary Input Rated Voltage 110Vdc 125Vdc 220Vdc 250Vdc Pickup voltage 77.0Vdc 87.5Vdc 154Vdc 175.0Vdc Dropout voltage 60.5Vdc 68.8Vdc 121Vdc 137.5Vdc Maximum permitted voltage 150Vdc 150Vdc 300Vdc 300Vdc Withstand 2kVac Resolving time for logic input 1ms 2.1.3 Binary Output Contact Type Tripping contact Signal contact Output mode Potential free contact Rated Voltage 250Vac/dc 250Vac/dc Test voltage across open contact > 1000Vac rms Continuous carry 8A 5A Short duration current (200ms) 50A Pickup time (Typ/Max) 5ms/10ms 10ms/15ms Dropout time (Typ/Max) 4ms/10ms 8ms/10ms Bounce time < 1ms < 1ms Breaking capacity at 250Vdc 0.4A resistance 0.2A inductive (L/R=40ms) 0.2A resistance 0.05A inductive (L/R=40ms) 2 Technical Data CZX-22R Interposing Relay Set 4 Date: 2011-04-12 Durability Loaded contact Unloaded contact
100,000 operations minimum 10,000,000 operations minimum 2.2 Mechanical Specifications Enclosure dimensions (WHD) 482.6177308 (unit: mm) Trepanning dimensions (WH) 450179, M6 screw Mounting Way Flush mounted Weight per device Approx. 10kg Housing material Aluminum Housing color Silver grey Location of terminal Rear panel of the device Protection class: Per IEC60529:1989 Front side IP40, Up to IP51 (Flush mounted) Other sides IP30 Rear side, connection terminals IP20 2.3 Ambient Temperature and Humidity Range Standard IEC 60255-6:1988 Operating temperature -25C~+60C Transport and storage temperature range -40C~+70C Permissible humidity 5%~95%, condensation not permissible 2.4 Type Tests 2.4.1 Environmental Tests Dry cold test IEC 60068-2-1:1974 Test Ad for 16 h at -25C Dry heat test IEC 60068-2-2:1990 Test Bd for 16 h at +55C Damp heat test, cyclic IEC 60068-2-30:1980 Test Db Two (12+12) hour cycles 95%RH, low temperature +25C, high temperature +55C 2.4.2 Mechanical Tests Vibration IEC60255-21-1:1988 Class I Shock and bump IEC 60255-21-2:1988 Class I 2 Technical Data CZX-22R Interposing Relay Set 5 Date: 2011-04-12 2.4.3 Electrical Tests Dielectric tests IEC 60255-5:2000 Test voltage 2kV, 50Hz, 1min Impulse voltage tests IEC 60255-5:2000 Test voltage 5kV, unipolar impulses waveform 1.2/50s,source energy 0.5J Insulation resistance measurements IEC 60255-5:2000 Isolation resistance >100M, 500Vdc 2.4.4 Electromagnetic Compatibility 1MHz burst disturbance test Per IEC 60255-22-1:1988 (idt IEC61000-4-12:1995) Common mode: class III 2.5KV Differential mode: class III 1.0KV Electrostatic discharge test Per IEC60255-22-2:1996 (idt IEC 61000-4-2:2006) class IV For contact discharge: 8kV For air discharge: 15kV Radio frequency interference tests Per IEC 60255-22-3:2000 (idt IEC 61000-4-3:1995) class III Frequency sweep Radiated amplitude-modulated 10V/m (rms), f=801000MHz Spot frequency Radiated amplitude-modulated 10V/m (rms), f=80MHz/160MHz/450MHz/900MHz Radiated pulse-modulated 10V/m (rms), f=900MHz Fast transient disturbance tests Per IEC 60255-22-4:2002 (idt IEC 61000-4-4:2004) Power supply, I/O, Earth: Class IV, 4kV, 2.5 kHz, 5/50ns Communication terminals: Class IV, 2kV, 5 kHz, 5/50ns Surge immunity test Per IEC 60255-22-5:2002 (idt IEC 61000-4-5:1995) class III Power supply, AC input, I/O port: 2kV, line to earth; 1kV line to line, 1.2/50us Conducted RF Electromagnetic Disturbance Per IEC 60255-22-6:2001 Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz Power Frequency Magnetic Field Immunity Per IEC 61000-4-8:1993 Class V: 100A/m for 1min, 1000A/m for 3s Pulse Magnetic Field Immunity Per IEC 61000-4-9:1993 Class V: 6.4/16s, 1000A/m for 3s Damped oscillatory magnetic field immunity IEC 61000-4-10:1993 Class V: 100kHz & 1MHz100A/m 2 Technical Data CZX-22R Interposing Relay Set 6 Date: 2011-04-12 2.5 Certifications 1. ISO9001: 2000 2. ISO14001:2004 3. OHSAS18001:1999 4. ISO10012:2003 5. CMMI L3 6. EMC: 89/336/EEC, EN50263:2000 7. Products safety(PS): 73/23/EEC, EN61010-1: 2001, EN60950: 2002 2.6 Relay Performance Seal-in current of trip & closing circuit: 0.5A~4.0A (Configurable with a step of 0.5A) Drop-off time of manual closing relay (21SHJ, 22SHJ, 23SHJ): >0.4s Drop-off time of low pressure blocking relay for auto-reclosing (21YJJ, 22YJJ): >0.3s Drop-off time of low pressure blocking relay for closing (3YJJ): >0.3s Pulse width of trip relay 11TJF, 12TJF, 21TJF, 22TJF0.3S Power supply burden: <25W Pickup voltage of relay: 55%~70% of nominal voltage
3 Operation Theory CZX-22R Interposing Relay Set 7 Date: 2011-04-12 3 Operation Theory 3.1 Schematic Diagrams 3.1.1 Auto-Reclosing and Manual Closing Circuit Spare relays Group 1 Group 2 Auto-reclosing Manual closing Manual tripping Initiate AR and BFP F o r
t r i p p i n g
c o i l
( G r o u p
1 ) T h r e e - p h a s e
t r i p p i n g KKJ Initiate BFP but not AR S u p e r v i s i o n o n
D C
p o w e r n6 Not initiate AR and BFP F o r
t r i p p i n g
c o i l
( G r o u p
2 ) Initiate AR and BFP Initiate BFP but not AR Not initiate AR and BFP
Figure 3.1-1 Auto-reclosing and manual closing circuit 3 Operation Theory CZX-22R Interposing Relay Set 8 Date: 2011-04-12 3.1.2 Phase-Segregated Closing Circuit Closing Open state supervision A - p h a s e
c l o s i n g
c i r c u i t Anti-pump O p e r a t i o n
m e c h a n i s m
o f
c i r c u i t
b r e a k e r
Closing Open state supervision B - p h a s e
c l o s i n g
c i r c u i t Anti-pump Closing Open state supervision C - p h a s e
c l o s i n g
c i r c u i t Anti-pump
Figure 3.1-2 Phase-segregated closing circuit 3 Operation Theory CZX-22R Interposing Relay Set 9 Date: 2011-04-12 3.1.3 Phase-Segregated Tripping Circuit (Group 1) Closed state supervision A-phase tripping O p e r a t i o n
m e c h a n i s m
o f
c i r c u i t
b r e a k e r
T r i p p i n g
c i r c u i t
( G r o u p
1 ) Closed state supervision B-phase tripping Closed state supervision C-phase tripping
Figure 3.1-3 Phase-segregated tripping circuit (Group 1) 3 Operation Theory CZX-22R Interposing Relay Set 10 Date: 2011-04-12 3.1.4 Phase-Segregated Tripping Circuit (Group 2) Closed state supervision A-phase tripping O p e r a t i o n
m e c h a n i s m
o f
c i r c u i t
b r e a k e r
Closed state supervision B-phase tripping C-phase tripping Closed state supervision T r i p p i n g
c i r c u i t
( G r o u p
2 )
Figure 3.1-4 Phase-segregated tripping circuit (Group 2) 3 Operation Theory CZX-22R Interposing Relay Set 11 Date: 2011-04-12 3.1.5 Trip and Auto-reclosing Target Circuit A-phase tripping Auto- reclosing Manual reset T a r g e t
Figure 3.1-5 Trip and auto-reclosing target circuit 3 Operation Theory CZX-22R Interposing Relay Set 12 Date: 2011-04-12 3.1.6 Low Pressure Blocking Circuit Low pressure to block trip Low pressure to block auto- reclosing Low pressure to block closing Low pressure to block switching
Figure 3.1-6 Low pressure blocking circuit 3.1.7 Accelerated Circuit when Manual Closing AC voltage circuit Accelerated circuit after manual closing
Figure 3.1-7 Accelerated circuit after manual closing 3 Operation Theory CZX-22R Interposing Relay Set 13 Date: 2011-04-12 3.1.8 Output Contacts C o o p e r a t i o n
w i t h
B F P
a n d
A R Spare 52b Three-phase tripping to initiate BFP but not AR Low pressure to block AR Block AR To main protection 1 of line 1 (for example 902 or 931) Spare relays To main protection 2 of line 1 (for example 902 or 931) To independent backup protection (for example 921) To transfer trip protection 1 of line 1 (for example 925) To transfer trip protection 2 of line 1 (for example 925) Spare three- phase tripping relay To main protection 1 of line 2 (for example 902 or 931) Spare relays To main protection 2 of line 2 (for example 902 or 931) To independent backup protection (for example 921) To transfer trip protection 1 of line 2 (for example 925) To transfer trip protection 2 of line 2 (for example 925) Spare three- phase tripping relay Three-phase tripping to initiate AR and BFP Loss power to block AR
Figure 3.1-8 Output contacts (Part 1) 3 Operation Theory CZX-22R Interposing Relay Set 14 Date: 2011-04-12 Pole disagreement of circuit breaker or pole discrepancy condition C o n t r o l
c i r c u i t
f a i l u r e Group 1 Group 2 AR S i g n a l
c i r c u i t T r i p p i n g
o u t p u t Group 1 Group 2 DC power supply failure (group 1) DC power supply failure (group 2) Low pressure to block tripping Low pressure to block auto-closing Low pressure to block closing Low pressure to block tripping and closing
Figure 3.1-9 Output contacts (Part 2) 3 Operation Theory CZX-22R Interposing Relay Set 15 Date: 2011-04-12 CB position R e m o t e
s i g n a l KKJ spare contacts KKJ post closing S i g n a l
c i r c u i t 52a 52b CB position R e c o r d e r Phase- segregated tripping Three-phase tripping AR
Figure 3.1-10 Output Contacts (Part 3) 3.2 Power Supply Please refer to Figure 3.1-1 and Figure 3.1-6. Two independent auxiliary power supplies are used. Auxiliary power 1 is supplied via terminal n6 and n98 to power the following circuits: closing circuit, manual trip repetition, trip and auto-reclosing circuit, and trip circuit 1. Auxiliary power 2 is supplied via terminal n9 and n99 to power trip circuit 2. These two power supplies are supervised by relays 12JJ & 2JJ respectively as shown in Figure 3.1-1, if the power supply fails, then an alarm will be issued by the normal closed contact of 12JJ or 2JJ via terminal n82-n83 and n82-n84 respectively. An additional power supply namely auxiliary power 3 comes from terminal n10 and n100. If applicable, low pressure blocking circuit shown in Figure 3.1-6 and spare relays 1ZJ, 2ZJ in Figure 3.1-1 are powered by this supply. Normally, this power supply comes from a switchover circuit of auxiliary power 1 and 2 via relay 11JJ refer to Figure 3.1-1. 3 Operation Theory CZX-22R Interposing Relay Set 16 Date: 2011-04-12 3.3 Closing Circuits 3.3.1 Auto-reclosing Circuit Please refer to Figure 3.1-1. When auto-reclosure issues a closing signal, it will connect power supply to terminal n112, relays ZHJ and ZXJ will operate. ZHJ is a repetition relay of auto-reclosing and ZXJ is a magnetic latching target relay. The normal open contacts of ZHJ will energize phase-segregated closing circuits in figure 3-2. When ZXJ operates, as shown in Figure 3.1-5, a LED 1HX located in faceplate of the equipment will light to indicate an operation of auto-reclosing circuit. This target relay can be reset by signal from n6-n143. 3.3.2 Manual and Remote Closing Circuit When manual closing or remote closing signal arrives at terminal n101, 1SHJ, 21SHJ, 22SHJ and 23SHJ will operate, at the same time, the relay KKJ will operate and latch, please refer to section 3.5 for details of KKJ. The normal open contacts of 1SHJ will energize phase-segregated close circuits as shown in Figure 3.1-2. The normal open contacts of 21SHJ will block auto-reclosure via terminal n172-n173, as Figure 3.1-8 shows. The normal open contacts of 22YJJ and 3YJJ in the circuit are provided to prevent manual closing under low pressure. When the pressure is reduced to a limit that closing shall be blocked, these two relays will drop out and cut the manual closing circuit. Please refer to section 3.6. The normal open contact of 23SHJ in parallel with coils of 21SHJ, 22SHJ and 23SHJ provides the path to charge the capacitors when pickup and this circuit will prolong the signal pulse to ensure that it is longer than 0.4s. This is essential to provide signal to protective relays to initiate switch onto fault protection. 3.3.3 Phase-Segregated Closing Circuit Phase-segregated closing circuit is shown in Figure 3.1-2. Terminal n104, n106, and n108 shall connect to phase closing coils (CC) in series with normal closed auxiliary contact of circuit breaker (52b). 3.3.3.1 Circuit Breaker Open State and Close Coil Supervision The auxiliary relays 1TWJa, 2TWJa, 3TWJa, 1TWJb, 2TWJb, 3TWJb, 1TWJc, 2TWJc, 3TWJc, are applied to supervise the open state of circuit breaker when terminal n103, 105, 107 is connected to the negative pole of power supply in series with normal closed auxiliary contact of each phase of circuit breaker (52b). In addition, if terminal n103, 105, 107 is connected to terminal n104, n106 and n108 respectively, i.e. connected to normal closed auxiliary contact of circuit breaker (52b) and its close coil (CC) of each phase respectively, these auxiliary relays can provide supervision on health of close coil as well. As Figure 3.1-8, Figure 3.1-9 and Figure 3.1-10 shows, these relays can be regarded as multiplication relays of 52b, many contacts of these supervision relays are provided for protection 3 Operation Theory CZX-22R Interposing Relay Set 17 Date: 2011-04-12 and auto-reclosing. Anyway, the protection and auto-reclosing can uses auxiliary contacts 52b directly from circuit breaker. But this feature provides a convenient solution in case there arent enough auxiliary contacts available. The multiplication contacts of 52b for protection and auto-reclosure can be used in logic scheme of pole discrepancy protection, switch onto fault protection, breaker 52b switch keying with echo for pilot protection, auto-reclosing reclaim and initiation, and VT circuit supervision. Some contacts are used in pole disagreement alarm and control circuit failure alarm, please refer to section 3.7, section 3.8 and Figure 3.1-9. 3.3.3.2 Closing Signal Whenever auto-reclosing or manual/remote closing signal comes, the contacts of ZHJ or 1SHJ will energize phase-segregated closing circuits. Please refer to section 3.3.1 and section 3.3.2. 3.3.3.3 Low Pressure Blocking 11YJJ is the low pressure blocking contact. Please refer to section 3.6.1 for details. If this built-in feature is not used, just shorten the associated normal open contacts of 11YJJ (terminal n6-n198). 3.3.3.4 Seal-in Relays Seal-in relays SHJa, SHJb and SHJc are used in closing circuit. When closing signal disappears, the normal open contacts of these relays will keep closing to maintain closing circuits working till circuit breaker closed. The pickup current can be configured as 0.5-4.0A with a step of 0.5A, please refer to section 4.5. 3.3.3.5 Anti-pump Circuit 1TBUJa, 2TBUJa, 1TBUJb, 2TBUJb, 1TBUJc, 2TBUJc are applied to achieve anti-pump function. In the event that a breaker is closed onto a fault, while the operator is applying a close signal via a close control switch, the circuit breaker will trip and prevent closing again until the closing circuit has been de-energized by the operators releasing the control switch. When trip signal comes and at the same time close signal persists, the contacts of trip seal-in relays 12TBIJa, 22TBIJa, 12TBIJb, 22TBIJb, 12TBIJc, 22TBIJc (please refer to section 3.4.3.4 and section 3.4.4.4) will close to activate 1TBUJa, 1TBUJb, 1TBUJc; then the contacts of 1TBUJa, 1TBUJb, 1TBUJc will activate 2TBUJa, 2TBUJb, 2TBUJc; 2TBUJa, 2TBUJb, 2TBUJc will operate and keep sealed with their own normal open contacts until closing signal disappears. The normal closed contacts of 1TBUJa, 2TBUJa, 1TBUJb, 2TBUJb, 1TBUJc, 2TBUJc will cut off closing circuits to prevent any further closing. If there are anti-pump circuits in circuit breaker itself, this built-in anti-pump function can be released by shortening terminal n109-n104, n110-n106 and n111-n108 to bypass the normal closed contacts of 1TBUJa, 2TBUJa, 1TBUJb, 2TBUJb, 1TBUJc, 2TBUJc. 3.4 Trip Circuit 3 Operation Theory CZX-22R Interposing Relay Set 18 Date: 2011-04-12 3.4.1 Manual and Remote Trip When manual trip or remote trip signal arrives at terminal n114, the interposing relays 1STJ, STJa, STJb and STJc will operate, and the relay KKJ will drop out. Please refer to section 3.5 for the details of KKJ. The normal open contacts of STJa, STJb, and STJc will energize phase-segregated trip circuits, as shown in Figure 3.1-3 and Figure 3.1-4. The normal open contact of 1STJ will block auto-reclosure via terminal n170-n171, as Figure 3.1-8 shows. 3.4.2 Three Phase Trip Signal Inputs from Protection Please refer to Figure 3.1-1. Two groups of trip-signal correspond to two groups of trip-coil respectively. Two types of trip signals are adopted: 3.4.2.1 Three-phase Tripping and Initiate AR This kind of trip signal from protective relays is desired to initiate auto-reclosing. The first trip signal from terminal n115 will activate 11TJQ, 12TJQ and 13TJQ; the second trip signal from terminal n124 will activate 21TJQ, 22TJQ and 23TJQ. The normal open contacts of 11TJQ, 12TJQ, 21TJQ, 22TJQ will energize two groups of phase-segregated trip circuits respectively, as shown in Figure 3.1-3 and Figure 3.1-4. One group of their contacts is wired through terminal n23-n24 to initiate auto-reclosure and breaker failure protection, and two spare contacts are provided through terminal n61-n62, n65-n66, please refer to Figure 3.1-8. 3.4.2.2 Three-phase Tripping and Block AR This kind of trip signal from protective relays is desired to block auto-reclosing. The first trip signal from terminal n116 will activate 11TJR, 12TJR and 13TJR; the second trip signal from terminal n125 will activate 21TJR, 22TJR and 23TJR. The normal open contacts of 11TJR, 12TJR, 21TJR, 22TJR will energize two groups of phase-segregated trip circuits respectively, as shown in Figure 3.1-3 and Figure 3.1-4. One group of their contact is wired through terminal n25-n26 to block auto-reclosure and initiate breaker failure protection, and two spare contacts are provided through terminal n61-n62, n65-n66, please refer to Figure 3.1-8. 3.4.2.3 Mechanical Relay Three-phase Tripping This kind of trip signal from mechanical protection is desired to tripping of mechanical protection of main transformer. The first trip signal from terminal n158 will activate 11TJF, 12TJF and 13TJF. The second trip signal from terminal n159 will activate 21TJF, 22TJF and 23TJF. They are connected to two groups of DC power supply. 11TJF, 12TJF and 13TJF will energize first group of phase-segregated tripping circuit, and 21TJF, 22TJF and 23TJF will energized second group of phase-segregated tripping circuit. The operating time of these relays is 0.3s, to prevent TJF circuit from always active if mechanical tripping signal can not drops off in time. 3.4.3 Phase-Segregated Trip Circuit 1 Phase-segregated trip circuit 1 is shown in Figure 3.1-3. Terminal n118, n119, and n120 shall 3 Operation Theory CZX-22R Interposing Relay Set 19 Date: 2011-04-12 connect to the first group of phase trip coils in series with normal open auxiliary contact of circuit breaker (52a). 3.4.3.1 Circuit Breaker Closed State and Trip Coil Supervision circuit 1 The auxiliary relays 11HWJa, 12HWJa, 13HWJa, 11HWJb, 12HWJb, 13HWJb, 11HWJc, 12HWJc, 13HWJc are applied to supervise the closed state of circuit breaker when terminal n118, n119, n120 are connected to the negative pole of power supply in series with normal open auxiliary contact of each phase of circuit breaker (52a). Health of trip coils is monitored at the same time. In Figure 3.1-9, some contacts are provided as multiplication of 52a. Some contacts are used in pole disagreement alarm and control circuit failure alarm, please refer to section 3.7, section 3.8 and Figure 3.1-9. LED PH A OK, PH B OK and PH C OK which located on the faceplate of the device indicate the closed position and health of trip coil 1 of circuit breaker. 3.4.3.2 Trip Signal Manual/remote trip signals come from the contacts of STJa, STJb, STJc, please refer to section 3.4.1. Three phase trip signals of protection come from the contacts of 11TJQ, 12TJQ, 11TJR, 12TJR. Please refer to section 3.4.2. The first group of phase-segregated trip contacts from protective relays can be connected between n198-n121 for phase A, n198-n122 for phase B and n198-n123 for phase C respectively. 3.4.3.3 Low Pressure Blocking 11YJJ is the low pressure blocking contact. Please refer to section 3.6.1 for details. If this built-in feature is not used, just shorten the associated normal open contacts of 11YJJ (terminal n6-n198). 3.4.3.4 Seal-in Relays Seal-in relays 11TBIJa, 12TBIJa, 11TBIJb, 12TBIJb, 11TBIJc, 12TBIJc are used in trip circuit. When tipping signal disappears, the normal open contacts of these relays will keep closing to maintain trip circuits working till circuit breaker tripped. The pickup current can be configured as 0.5-4.0A with a step of 0.5A, please refer to section 4.5. In addition, the contacts of 12TBIJa, 12TBIJb, 12TBIJc are also used in anti-pump logic scheme. Please refer to section 3.3.3.5. 3.4.3.5 Target Relays The normal open contacts of 11TBIJa, 11TBIJb, 11TBIJc will activate magnetic latching target relays 1TXJa, 1TXJb and 1TXJc respectively, as Figure 3.1-5 shows. The contacts of 1TXJa, 1TXJb and 1TXJc will light LEDs 1TXa, 1TXb and 1TXc. A group of contacts of 1TXJa, 1TXJb and 1TXJc are provided via n139-n140, n141, n142, for event recording or central annunciation. A group of contacts of 1TXJa, 1TXJb and 1TXJc are 3 Operation Theory CZX-22R Interposing Relay Set 20 Date: 2011-04-12 provided via n82-n80 for annunciation. LEDs PH A TRIP, PH B TRIP and PH C TRIP located in faceplate of the device show that certain protective relays have tripped circuit breaker via the first group of trip coils. Please note that the contacts of STJa, STJb, and STJc are in series with the activating circuits of 1TXJa, 1TXJb, 1TXJc, that means manual/remote trip will not activate target relays. The magnetic latching target relays 1TXJa, 1TXJb and 1TXJc can be reset by signal from n6-n143, as shown in Figure 3.1-5. 3.4.4 Phase-Segregated Trip Circuit 2 Phase-segregated trip circuit 2 is shown in Figure 3.1-4. Terminal n127, n128, and n129 shall connect to the second group of phase trip coils in series with normal open auxiliary contact of circuit breaker (52a). 3.4.4.1 Circuit Breaker Closed State and Trip Coil Supervision circuit 2 The auxiliary relays 21HWJa, 22HWJa, 23HWJa, 21HWJb, 22HWJb, 23HWJb, 21HWJc, 22HWJc, 23HWJc are applied to supervise the closed state of circuit breaker when terminal n127, n128, n129 are connected to the negative pole of power supply in series with normal open auxiliary contact of each phase of circuit breaker (52a). Health of trip coils is monitored at the same time. In Figure 3.1-9, some contacts are provided as multiplication of 52a. Some contacts are used in pole disagreement alarm and circuit failure alarm circuits, please refer to section 3.7, section 3.8 and Figure 3.1-9. LED PH A OK, PH B OK and PH C OK which located on the faceplate of the device indicate the closed position and health of trip coil 2 of circuit breaker. 3.4.4.2 Trip Signal Manual/remote trip signals come from the contacts of STJa, STJb, STJc, please refer to section 3.4.1. Three phase trip signals of protection come from the contacts of 21TJQ, 22TJQ, 21TJR, 22TJR. Please refer to section 3.4.2. The second group of phase-segregated trip contacts from protective relays can be connected between n200-n130 for phase a, n200-n131 for phase b and n200-n132 for phase c respectively. 3.4.4.3 Low Pressure Blocking 11YJJ is the low pressure blocking contact. Please refer to section 3.6.1 for details. If this built-in feature is not used, just shorten the associated normal open contacts of 11YJJ (terminal n9-n200). 3.4.4.4 Seal-in Relays Seal-in relays 21TBIJa, 22TBIJa, 21TBIJb, 22TBIJb, 21TBIJc, 22TBIJc are used in trip circuit. When tipping signal disappears, the normal open contacts of these relays will keep closing to maintain trip circuits working till circuit breaker tripped. 3 Operation Theory CZX-22R Interposing Relay Set 21 Date: 2011-04-12 The pickup current is be configured as 0.5-4.0A with a step of 0.5A, please refer to section 4.5. In addition, the contacts of 22TBIJa, 22TBIJb, 22TBIJc are also used in anti-pump logic scheme. Please refer to section 3.3.3.5. 3.4.4.5 Target Relays The normal open contacts of 21TBIJa, 21TBIJb, 21TBIJc will activate magnetic latching target relays 2TXJa, 2TXJb and 2TXJc respectively, as Figure 3.1-5 shows. The contacts of 2TXJa, 2TXJb and 2TXJc will light LEDs 2TXa, 2TXb and 2TXc. A group of contacts of 2TXJa, 2TXJb and 2TXJc are provided via n139-n140, n141, n142, for event recording or central annunciation. A group of contacts of 2TXJa, 2TXJb and 2TXJc are provided via n82-n81 for annunciation. LEDs PH A TRIP, PH B TRIP and PH C TRIP located in faceplate of the device show that certain protective relays have tripped circuit breaker via the second group of trip coils. Please note that the contacts of STJa, STJb, and STJc are in series with the activating circuits of 2TXJa, 2TXJb, 2TXJc, that means manual/remote trip will not activate target relays. The magnetic latching target relays 2TXJa, 2TXJb and 2TXJc can be reset by signal from n9-n144, as shown in Figure 3.1-5. 3.5 KKJ Please refer to Figure 3.1-1. KKJ is a bistable auxiliary relay, which is called as post-closing position relay. When circuit breaker is closed manually, the relay KKJ will pick up and latch. When circuit breaker is tripped manually, the relay KKJ will reset. The contacts of this special relay can be used by substation automation system to issue an accident signal whenever circuit breaker is tripped un-manually. Moreover, together with normal closed auxiliary contact of circuit breaker (52b), the contacts of this special relay can also be used to initiate auto-reclosure in case that circuit breaker trips especially without any trip commands from protection and manual switch. The contacts of KKJ are wired at terminal n213-n214 and n211-n212, as shown in Figure 3.1-1 and Figure 3.1-10. 3.6 Pressure Supervision Pressure supervision circuit is shown in Figure 3.1-6. This circuit is energized by the third power supply from terminals n10-n100; please refer to section 3.2 for details. Four levels of pressure are provided: -Low pressure to block auto-reclosing from terminal n12/n68 -Low pressure to block closing from terminal n13/n70 -Low pressure to block trip from terminal n11/n67 -Low pressure to block switching (both closing and trip) from n14/n145 3 Operation Theory CZX-22R Interposing Relay Set 22 Date: 2011-04-12 3.6.1 Low Pressure to Block Trip If normal open contact of low pressure to block trip is applied, this contact can connect terminal n67 and negative pole of auxiliary power; terminal n11 shall connect to positive pole of power supply. While if normal closed contact of low pressure to block trip is applied, this contact can connect terminal n11 and positive pole of auxiliary power; terminal n67 shall keep unconnected. When the relay 4YJJ picks up, it will release 11YJJ and 12YJJ to block trip. 4YJJ is a low pressure to block switching (both trip and closing), please refer to section 3.6.4 for details. The normal open contacts of 11YJJ are used in phase-segregated closing circuit and phase-segregated trip circuit to permit switch of circuit breaker. Please refer to Figure 3.1-2, Figure 3.1-3 and Figure 3.1-4. If this built-in feature is not used, just shorten the associated normal open contacts of 11YJJ. Another normal closed contact of 12YJJ is provided via terminal n82-n76 for annunciation shown in Figure 3.1-9. 3.6.2 Low Pressure to Block Auto-reclosing If normal open contact of low pressure to block auto-reclosing is applied, this contact can connect terminal n68 and negative pole of auxiliary power; terminal n12 shall connect to positive pole of power supply. While if normal closed contact of low pressure to block auto-reclosing is applied, this contact can connect terminal n12 and positive pole of auxiliary power; terminal n68 shall keep unconnected. The diode, capacitors and resistor series-parallel connected with relay 21YJJ, 21YJJ and 22YJJ in the circuit are used to delay the dropout of 21YJJ, 21YJJ and 22YJJ by not shorter than 0.3s. This feature is useful to ensure a successful reclosing when circuit breaker pressure goes low temporarily after the auto-reclosure being initiated. In normal condition, the relays will operate and the normal open contact of 22YJJ will permit closing, please refer to section 3.3.2. One normal closed contact of 21YJJ is provided through terminal n25-n27 to block the auto-relocsure if the pressure goes low to a certain limit, please refer to Figure 3.1-8. Another normal closed contact of 22YJJ is provided via terminal n82-n77 for annunciation shown in Figure 3.1-9. 3.6.3 Low Pressure to Block Closing If normal open contact of low pressure to block closing is applied, this contact can connect terminal n70 and negative pole of auxiliary power; terminal n13 shall connect to positive pole of power supply. While if normal closed contact of low pressure to block closing is applied, this contact can connect terminal n13 and positive pole of auxiliary power; terminal n70 shall keep unconnected. In normal condition, the relay 3YJJ will operate and the normal open contact of 3YJJ will permit manual/remote closing, please refer to section 3.3.2. 3 Operation Theory CZX-22R Interposing Relay Set 23 Date: 2011-04-12 The diode, capacitors and resistor in the circuit are used to delay the dropout of 3YJJ by not shorter than 0.3s. This feature is useful to ensure a successful closing when circuit breaker pressure goes low temporarily after the closing being initiated. Another normal closed contact of 3YJJ is provided via terminal n82-n78 for annunciation shown in Figure 3.1-9. 3.6.4 Low Pressure to Block Switching If normal closed contact of low pressure to block switching (both trip and closing) is applied, this contact can connect terminal n145 and negative pole of auxiliary power; terminal n14 shall connect to positive pole of power supply. While if normal open contact of low pressure to block switching is applied, this contact can connect terminal n14 and positive pole of auxiliary power; terminal n145 shall keep unconnected. Whenever this signal comes, one normal open contact of 4YJJ will close and release 11YJJ and 12YJJ immediately to block both trip and closing circuit, please refer to section 3.6.1. The other two contacts of 4YJJ are provided via terminal n168-n169 and n176-n177 for future application in Figure 3.1-8. Another normal open contact of 4YJJ is provided via terminal n82-n79 for annunciation shown in Figure 3.1-9. 3.7 Pole Disagreement Please refer to Figure 3.1-9. A series-parallel connected circuit is employed to provide a pole disagreement signal via terminal n71-n73. Contacts of 2TWJa, 2TWJb, 2TWJc can be regarded as multiplication of 52b, and 13HWJa, 13HWJb, 13HWJc, 23HWJa, 23HWJb, 23HWJc can be regarded as multiplication of 52a. Please refer to section 3.3.3, section 3.4.3.1 and section 3.4.4.1. 3.8 Control Circuit Failure As mentioned in section 3.3.3.1 and section 3.4.3.1: -The relays 3TWJa, 3TWJb, 3TWJc can supervise the health of closing coils in open state. -The relays 11HWJa, 11HWJb and 11HWJc can supervise the health of trip coil 1 in closed state. -The relays 21HWJa, 21HWJb and 21HWJc can supervise the health of trip coil 2 in closed state. Whenever there is a failure in trip coil under closed state or a failure in closing coils under open state, an alarm will be issued via terminal n72-n74, n72-n75, refer to Figure 3.1-9. 3.9 Spare Relays Please refer to Figure 3.1-1. Two spare relays 1ZJ, 2ZJ are provided for future application. This circuit is energized by the third power supply from terminals n10-n100; please refer to section 3.2 for details. 3 Operation Theory CZX-22R Interposing Relay Set 24 Date: 2011-04-12 The diode, capacitors and resistor series-parallel connected with relay 1ZJ are used to prolong the signal pulse to ensure that it is longer than 0.4s. The contacts of 1ZJ and 2ZJ are shown in Figure 3.1-8.
4 Hardware CZX-22R Interposing Relay Set 25 Date: 2011-04-12 4 Hardware 4.1 Overview The device is an IEC standard 4U high and 19 wide rack with modular structure. It uses an integral faceplate and plug terminal blocks on rear panel for external connections. It has features of compact design, high security, flexibility and convenience. There are 14 modules plugged into chassis of CZX-22G from the front side, and then an integrated faceplate is fastened to cover these modules. From left to right in front view, these modules are: Table 4.1-1 Plug-in modules Slot No. Item Description 1 QYBS low pressure blocking circuit; 2 ST1B three phases trip circuit (part 1) 3 ST2A three phases trip circuit (part 2) 4 FTHL trip circuit 1 of phase A 5 FTHL trip circuit 1 of phase B 6 FTHL trip circuit 1 of phase C 7 HZHL manual closing, auto-reclosing circuits 8 FHHL closing circuit of phase A 9 FHHL closing circuit of phase B 10 FHHL closing circuit of phase C 11 FTHL trip circuit 2 of phase A 12 FTHL trip circuit 2 of phase B 13 FTHL trip circuit 2 of phase C 14 JDY selecting accelerated bay when manual closing 15 EXT Spare extend 16 Null
4.2 Device Layout The case material of the device is constructed from pre-finished steel that has a conductive covering of aluminum and zinc. This provides good earthing at all joints giving a low impedance path to earth that is essential for performance in the presence of external noise. Medium duty soldering plug terminal blocks are used for inputs, outputs and the power supply. 4.3 Front View The front panel of the equipment includes 18 LEDs. 4 Hardware CZX-22R Interposing Relay Set 26 Date: 2011-04-12 CZX-22 INTERPOSING RELAY SET RECLOSE PH B TRIP PH B OK TRIP CIRCUIT SUPERVISION 1 TRIP SIGNAL 1 PH A TRIP PH A OK PH C TRIP PH C OK AUX DC1 AUX DC2 PH A OK CLOSE CIRCUIT SUPERVISION PH B OK PH C OK PH B TRIP PH B OK TRIP CIRCUIT SUPERVISION 2 TRIP SIGNAL 2 PH A TRIP PH A OK PH C TRIP PH C OK 1 2 3 4 5 6 7
Figure 4.3-1 Panel Layout In the figure above: 1. PH A OK, PH B OK, PH C OK They are indicator LEDs that monitor phase A, B and C tripping circuit for the first group of trip coil respectively. 2. PH A TRIP, PH B TRIP, PH C TRIP They are indicator LEDs of phase A, B and C tripping signal for the first group of trip coil respectively. 3. PH A OK, PH B OK, PH C OK They are indicator LEDs that monitor phase A, B and C tripping circuit for the second group of trip coil respectively. 4. PH A TRIP, PH B TRIP, PH C TRIP They are indicator LEDs of phase A, B and C tripping signal for the second group of trip coil respectively. 5. PH A OK, PH B OK, PH C OK They are indicator LEDs that monitor phase A, B and C closing circuit of closing coil respectively. 6. RECLOSE It is indicator LED of closing signal. 7. AUX DC1, AUX DC2 It is indicator LEDs that monitor the first and second group of DC power supplies. Table 4.3-1 Left Group of Indicators No. LED Function 1 PH A OK
ON: A-phase tripping closing is healthy and circuit breaker is on closed position, OFF: A-Phase is open or A-phase trip coil 1 is broken 4 Hardware CZX-22R Interposing Relay Set 27 Date: 2011-04-12 PH B OK
PH C OK ON: B-phase tripping closing is healthy and circuit breaker is on closed position, OFF: B-Phase is open or A-phase trip coil 1 is broken ON: C-phase tripping closing is healthy and circuit breaker is on closed position, OFF:C-Phase is open or A-phase trip coil 1 is broken 2 PH A TRIP
PH B TRIP
PH C TRIP ON: Tripping A-phase of circuit breaker by trip coil 1 through this device, OFF: under normal condition ON: Tripping B-phase of circuit breaker by trip coil 1 through this device, OFF: under normal condition ON: Tripping C-phase of circuit breaker by trip coil 1 through this device, OFF: under normal condition 3 PH A OK
PH B OK
PH C OK ON: A-phase tripping closing is healthy and circuit breaker is on closed position, OFF: A-Phase is open or A-phase trip coil 2 is broken ON: B-phase tripping closing is healthy and circuit breaker is on closed position, OFF: B-Phase is open or A-phase trip coil 2 is broken ON: C-phase tripping closing is healthy and circuit breaker is on closed position, OFF:C-Phase is open or A-phase trip coil 2 is broken 4 PH A TRIP
PH B TRIP
PH C TRIP ON: Tripping A-phase of circuit breaker by trip coil 2 through this device, OFF: under normal condition ON: Tripping B-phase of circuit breaker by trip coil 2 through this device, OFF: under normal condition ON: Tripping C-phase of circuit breaker by trip coil 2 through this device, OFF: under normal condition 5 PH A OK
PH B OK
PH C OK ON: A-phase closing circuit is normal and circuit breaker is on open position, OFF: A-phase is closed or A-phase closing coil is broken ON: B-phase closing circuit is normal and circuit breaker is on open position, OFF: B-phase is closed or B-phase closing coil is broken ON: C-phase closing circuit is normal and circuit breaker is on open position, OFF: C-phase is closed or C-phase closing coil is broken 6 RECLOSE ON: Closing circuit breaker through this device, OFF: under normal condition 7 AUX DC1 AUX DC2 ON: DC power supply 1 is normal, OFF: DC power supply 1 is abnormal ON: DC power supply 2 is normal, OFF: DC power supply 2 is abnormal 4.4 Terminals There are 9 30-pin connectors used as terminals of external connection mounted on rear plate of the device. From right to left on the rear, they are denoted as connector A to connector I respectively. 4 Hardware CZX-22R Interposing Relay Set 28 Date: 2011-04-12
Figure 4.4-2 Rear terminal of CZX-22G The definition and application of each terminal will be detailed below. 4.4.1 Definition of Connector A Table 4.4-1 Definition of Connector A Terminal No. Description n1 AC voltage n2 n3 n4 n5 n6 Positive pole of DC power supply (group 1) n7 n8 n9 Positive pole of DC power supply (group 2) n10 Positive pole of common DC power supply n11 Tripping pressure n12 Reclosing pressure n13 Closing pressure 4 Hardware CZX-22R Interposing Relay Set 29 Date: 2011-04-12 n14 Abnormal pressure n15 Spare three-phase tripping contact n16 n17 Spare pole disagreement contact n18 n19 Open position of the circuit breaker (52b) n20 n21 n22 n23 To initiate AR and BFP n24 n25 To block AR and initiate BFP n26 n27 Low pressure to block AR n28 Spare n29 Open position of the circuit breaker (52b) n30 4.4.2 Definition of Connector B Table 4.4-2 Definition of Connector B Terminal No. Description n31 Open position of the circuit breaker (52b) n32 n33 Open position of the circuit breaker (52b) n34 n35 n36 n37 Manual closing n38 n39 Manual closing n40 n41 Manual closing n42 n43 n44 n45 n46 n47 Open position of the circuit breaker (52b) 4 Hardware CZX-22R Interposing Relay Set 30 Date: 2011-04-12 n48 n49 Three-phase open position of circuit breaker (52b) n50 Open position of the circuit breaker (52b) n51 n52 Three-phase open position of circuit breaker (52b) n53 Open position of the circuit breaker (52b) n54 n55 Three-phase open position of circuit breaker (52b) n56 Open position of the circuit breaker (52b) n57 n58 Three-phase open position of circuit breaker (52b) n59 n60 4.4.3 Definition of Connector C Table 4.4-3 Definition of Connector C Terminal No. Description n60 Protection thee-phase tripping n61 n62 n63 n64 n65 Protection thee-phase tripping n66 n67 Tripping pressure n68 Reclosing pressure n69 n70 Closing pressure n71 Pole disagreement signal n72 Control circuit failure n73 Pole disagreement signal n74 Signal of control circuit failure (group 1) n75 Signal of control circuit failure (group 2) n76 Signal of low pressure to block tripping n77 Signal of low pressure to block AR n78 Signal of low pressure to block closing n79 Signal of low pressure to block switching (tripping and closing) 4 Hardware CZX-22R Interposing Relay Set 31 Date: 2011-04-12 n80 Tripping signal of group 1 n81 Tripping signal of group 2 n82 Common terminal of signal n83 Signal of DC power supply supervision (group 1) n84 Signal of DC power supply supervision (group 2) n85 To initiate audio alarm n86 n87 Closed position of the circuit breaker (52a) n88 n89 n90 4.4.4 Definition of Connector D Table 4.4-4 Definition of Connector D Terminal No. Description n91 Signal of closed position of circuit breaker (52a) n92 n93 n94 n95 n96 n97 n98 Negative pole of DC power supply (group 1) n99 Negative pole of DC power supply (group 2) n100 Negative pole of common DC power supply n101 To initiate manual closing relay n102 n103 To closing circuit of circuit breaker n104 n105 n106 n107 n108 n109 Spare anti-pump circuit of circuit breaker n110 n111 n112 To initiate repeat relay of AR 4 Hardware CZX-22R Interposing Relay Set 32 Date: 2011-04-12 n113 Manual closing without controlled by pressure relay n114 To initiate manual tripping relay n115 Terminal Q of protection tripping (group 1) n116 Terminal R of protection tripping (group 1) n117 Spare n118 Closed position supervision of circuit breaker (tripping coil 1) n119 n120 4.4.5 Definition of Connector E Table 4.4-5 Definition of Connector E Terminal No. Description n121 Phase-segregated tripping circuit (tripping coil 1) n122 n123 n124 Terminal Q of protection tripping (group 2) n125 Terminal R of protection tripping (group 2) n126 Spare n127 Closed position supervision of circuit breaker (tripping coil 2) n128 n129 n130 Phase-segregated tripping circuit (tripping coil 2) n131 n132 n133 Spare n134 n135 Remote signal of CB position n136 n137 n138 n139 Event recorder of protection tripping n140 n141 n142 n143 Signals reset (group 1) n144 Signals reset (group 2) n145 Pressure abnormality 4 Hardware CZX-22R Interposing Relay Set 33 Date: 2011-04-12 n146 To initiate spare intermediate relay n147 n148 Open position of circuit breaker (52b) n149 n150 Closed position of circuit breaker (52a) 4.4.6 Definition of Connector F Table 4.4-6 Definition of Connector F Terminal No. Description n151 Closed position of circuit breaker (52a) n152 Spare contacts of intermediate relay n153 n154 n155 n156 n157 n158 Spare three-phase tripping of group 1 n159 Spare three-phase tripping of group 2 n160 Spare contacts of intermediate relay n161 n162 n163 n164 n165 n166 n167 n168 Pressure abnormality contact n169 n170 Manual tripping n171 n172 Manual closing n173 n174 Open position of circuit breaker (52b) n175 n176 Pressure abnormality contact n177 n178 4 Hardware CZX-22R Interposing Relay Set 34 Date: 2011-04-12 n179 Three-phase open position of circuit breaker (52b) n180 4.4.7 Definition of Connector G Table 4.4-7 Definition of Connector G Terminal No. Description n181 Spare three-phase tripping contact of group 1 n182 n183 Three-phase open position of circuit breaker (52b) n184 n185 Spare three-phase tripping contact of group 2 n186 n187 Open position of circuit breaker (52b) n188 n189 n190 n191 Spare n192 n193 n194 n195 n196 n197 n198 Positive pole of DC power supply for tripping (group 1) n199 n200 Positive pole of DC power supply for tripping (group 2) n201 Spare n202 Open position of circuit breaker (52b) n203 n204 n205 n206 n207 n208 n209 n210 4 Hardware CZX-22R Interposing Relay Set 35 Date: 2011-04-12 4.4.8 Definition of Connector H Table 4.4-8 Definition of Connector H Terminal No. Description n211 Post closed contact of KKJ n212 n213 n214 n215 n216 n217 n218 n219 n220 To tripping circuit of circuit breaker (tripping coil 1) n221 n222 n223 To tripping circuit of circuit breaker (tripping coil 2) n224 n225 n226 n227 n228 n229 n230 n231 n232 n233 n234 n235 n236 n237 n238 n239 n240 4.4.9 Definition of Connector I Table 4.4-9 Definition of Connector I 4 Hardware CZX-22R Interposing Relay Set 36 Date: 2011-04-12 Terminal No. Description n241 Common terminal of phase-segregated tripping to trigger recording n242 Common terminal of three-phase tripping to trigger recording (group 1) n243 Common terminal of three-phase tripping to trigger recording (group 2) n244 Common terminal of reclosing to trigger recording (group 1) n245 n246 A-phase tripping to trigger recording n247 B-phase tripping to trigger recording n248 C-phase tripping to trigger recording n249 Three-phase tripping to trigger recording (group 1) n250 Three-phase tripping to trigger recording (group 2) n251 Reclosing to trigger recording n252 n253 Recloing signal n254 n255 n256 Contact of DC power supply failure (group 1) n257 n258 n259 n260 n261 n262 n263 n264 n265 n266 n267 n268 Protection phase-segregated closing circuit n269 n270 4 Hardware CZX-22R Interposing Relay Set 37 Date: 2011-04-12 4.5 Adjustment Method for Latching Current of Tripping & Closing In order to facilitate production and operation, the jumper mode is adopted to adjust the latching current of tripping & closing of this device and its principle is shown below: R21 R22 R23 R24 0.5A 1A 2A 2TBIT 1TBIJ R15 R16 R17 R18 0.5A 1A 2A SHIa, b, c Tripping circuit Closing circuit
Setting formula for the latching current of tripping & closing circuit
is the setting value of the latching current I is the current value flowing through shunt resistance Jumper 0.5A Jumper 1A Jumper 2A Target latching current OFF OFF OFF 0.5A ON OFF OFF 1.0A OFF ON OFF 1.5A ON ON OFF 2.0A OFF OFF ON 2.5A ON OFF ON 3.0A OFF ON ON 3.5A ON ON ON 4.0A When no jumper is connected, the latching current is 0.5A. When one jumper is connected, the corresponding current value is added (refer to the above table). When all jumpers are connected, the fixed value of the latching current is 4A. This can easily realize the adjustment of the latching current within the range of 0.5A~4A (0.5A as a stage head). It is necessary to notify that two times of operating margin has been considered when selecting shunt resistance. When setting current value, just set the value according to the actual tripping & closing current of the circuit breaker without consideration of the margin. Caution! 4 Hardware CZX-22R Interposing Relay Set 38 Date: 2011-04-12 The latching current of tripping circuit can be adjusted in the plug-in modules of #4, #5, #6, #11, #12 and #13. The latching current of closing circuit can be adjusted in the plug-in modules of #8, #9 and #10. The latching currents for tripping circuit and closing circuit are different, and they shall be set respectively according to the specific parameters of the tripping & closing circuit. The device can be delivered from factory only if all jumpers have been properly set according to the order information. In case of particular conditions, it is necessary to re-set the jumpers, shut down DC power supply of the device, wait 5s for capacitors to discharge, open the front panel, unplug the plug-in modules and then set the latching current of tripping & closing circuit.
5 Installation CZX-22R Interposing Relay Set 39 Date: 2011-04-12 5 Installation 5.1 Overview The equipment must be shipped, stored and installed with the greatest care. Choose the place of installation such that the communication interface and the controls on the front of the device are easily accessible. Air must circulate freely around the equipment. Observe all the requirements regarding place of installation and ambient conditions given in this instruction manual. Take care that the external wiring is properly brought into the equipment and terminated correctly and pay special attention to grounding. Strictly observe the corresponding guidelines contained in this section. 5.2 Safety Information This section contains safety information. Warning signs are presented which attend the user to be careful during certain operations in order to avoid human injuries or damage to equipment. Warning signs Warning! Strictly follow the company and country safety regulations. Working in a high voltage environment requires serious approach to avoid human injuries and damage to equipment. Do not touch circuitry during operation. Potentially lethal voltages and currents are present. Always avoid touching the circuitry when the cover is removed. The product contains electronic circuitries which can be damaged if exposed to static electricity (ESD). The electronic circuitries also contain high voltage which is lethal to humans. Always use suitable isolated test pins when measuring signals in open circuitry. Potentially lethal voltages and currents are present. Never connect or disconnect a wire and/or a connector to or from a protective device during normal operation. Hazardous voltages and currents are present that may be lethal. Operation may be disrupted and protection equipment and measuring circuitry may be damaged. Always connect the protection equipment to protective ground, regardless of the operating conditions. This also applies to special occasions such as bench testing, demonstrations and off-site configuration. Operating the protection equipment without proper grounding may damage both terminal and measuring circuitry, and may cause injuries in case of an 5 Installation CZX-22R Interposing Relay Set 40 Date: 2011-04-12 accident. Never disconnect a secondary connection of current transformer circuit without short-circuiting the transformers secondary winding. Operating a current transformer with the secondary winding open will cause a massive potential build-up that may damage the transformer and may cause injuries to humans. Never unmount the front or back cover from a powered equipment or from a protection equipment connected to powered circuitry. Potentially lethal voltages and currents are present. Caution signs
Caution! Always transport modules using certified conductive bags. Always handle modules using a conductive wrist strap connected to protective ground and on a suitable antistatic surface. Electrostatic discharge (ESD) may cause damage to the module. Do not connect live wires to the protection equipment. Internal circuitry may be damaged. Always use a conductive wrist strap connected to protective ground when replacing modules. Electrostatic discharge (ESD) may damage the module and protection equipment circuitry. Take care to avoid electrical shock if accessing wiring and connection protection equipment when installing and commissioning. Note signs Note! Changing the active setting group will inevitably change the protection equipments operation. Be careful and check regulations before making the change. The protection assembly is designed for a maximum continuous current of four times rated value. Activating the other setting group without proper configuration may seriously affect the protection equipments operation. 5.3 Check the Shipment Check that the consignment is complete immediately upon receipt. Notify the nearest NR Company or agent, should departures from the delivery note, the shipping papers or the order be found. Visually inspect all the material when unpacking it. When there is evidence of transport damage, lodge a claim immediately in writing with the last carrier and notify the nearest NR Company or 5 Installation CZX-22R Interposing Relay Set 41 Date: 2011-04-12 agent. If the equipment is not going to be installed immediately, store all the parts in their original packing in a clean dry place at a moderate temperature. The humidity should not exceed 90% at a maximum temperature of +55C; the permissible storage temperature range in dry air is -40C to +70C. 5.4 Material and Tools Required The necessary mounting kits will be provided, including screws, pincers and assembly instructions. A suitable drill and spanners are required to secure the cubicles to the floor using the plugs provided (if CZX-22G is mounted in cubicles). 5.5 Device Location and Ambient Conditions The place of installation should permit easy access especially to front of the device, i.e. to the human-machine interface of the equipment. There should also be free access at the rear of the equipment for additions and replacement of electronic boards. Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient conditions, such as: 1. The location should not be exposed to excessive air pollution (dust, aggressive substances). 2. Severe vibration, extreme changes of temperature, high levels of humidity, surge voltages of high amplitude and short rise time and strong induced magnetic fields should be avoided as far as possible. 3. Air must not be allowed to circulate freely around the equipment. The equipment can in principle be mounted in any attitude, but it is normally mounted vertically (visibility of markings).
Warning! Excessively high temperature can appreciably reduce the operating life of the CZX-22G. 5.6 Mechanical Installation The equipment adopts IEC standard chassis and is rack with modular structure. It uses an integral faceplate and plug terminal block on backboard for external connections. CZX series device is IEC 5 Installation CZX-22R Interposing Relay Set 42 Date: 2011-04-12 4U high and 19 wide. Figure 5.6-1 shows its dimensions and Figure 5.6-2 shows the panel cut-out. 482.60 465.00 1 7 7 . 0 0 1 0 1 . 6 0 3 0 8
Note! It is necessary to leave enough space top and bottom of the cut-out in the cubicle for heat emission of the CZX-22G. 5.7 Electrical Installation 5.7.1 Grounding Guidelines Switching operations in HV installations generate transient over voltages on control signal cables. There is also a background of electromagnetic RF fields in electrical installations that can induce spurious currents in the devices themselves or the leads connected to them. 5 Installation CZX-22R Interposing Relay Set 43 Date: 2011-04-12 All these influences can influence the operation of electronic apparatus. On the other hand, electronic apparatus can transmit interference that can disrupt the operation of other apparatus. In order to minimize these influences as far as possible, certain standards have to be observed with respect to grounding, wiring and screening.
Note! All these precautions can only be effective if the station ground is of good quality. 5.7.2 Cubicle Grounding The cubicle must be designed and fitted out such that the impedance for RF interference of the ground path from the electronic device to the cubicle ground terminal is as low as possible. Metal accessories such as side plates, blanking plates etc., must be effectively connected surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF interference. The contact surfaces must not only conduct well, they must also be non-corroding.
Note! If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it forming a resonant circuit at certain frequencies that would amplify the transmission of interference by the devices installed and also reduce their immunity to induced interference. Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be effectively grounded to the frame by three braided copper strips (see Figure 5.7-1). The metal parts of the cubicle housing and the ground rail are interconnected electrically conducting and corrosion proof. The contact surfaces shall be as large as possible.
Note! For metallic connections please observe the voltage difference of both materials according to the electrochemical code. The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip (braided copper). 5 Installation CZX-22R Interposing Relay Set 44 Date: 2011-04-12
Door or hinged equipment frame Cubicle ground rail close to floor Station ground Braided copper strip Conducting connection
Figure 5.7-1 Cubicle grounding system 5.7.3 Making Electrical Connections Always make sure established guidelines for this type of terminal is followed during installation. When necessary use screened twisted-pair cables to minimize susceptibility. Otherwise, use any kind of regular nonscreened tinned RK cable or equivalent. When using screened cabling always use 360 full screen cable bushing to ensure screen coupling. Ensure that all signals of the single circuit are in the same single cable. Avoid mixing current and voltage measuring signals in the same cable. Also use separate cables for control and measuring circuits. 1. Connecting the auxiliary power: All plug-in modules of the device demand to introduce DC power supply. The DC power supply will be connected to the input terminals of various plug-in modules after running in idle for some time. 2. Input/output signal connectors: The input and output circuits will be connected with the terminal board generally, external circuit will connect the relevant terminal board through dedicated cable.
6 Commissioning CZX-22R Interposing Relay Set 45 Date: 2011-04-12 6 Commissioning 6.1 Overview This device is fully numerical in their design, implementing all protection and non-protection functions in software. The relay employ a high degree of self-checking and in the unlikely event of a failure, will give an alarm. As a result of this, the commissioning test does not need to be as extensive as with non-numeric electronic or electro-mechanical relays. To commission numerical relays, it is only necessary to verify that the hardware is functioning correctly and the application-specific software settings have been applied to the relay. Before carrying out any work on the equipment, the user should be familiar with the contents of the safety and technical data sections and the ratings on the equipments rating label. 6.2 Safety Instructions
Warning! Hazardous voltages are present in this electrical equipment during operation. Non-observance of the safety rules can result in severe personal injury or property damage.
Warning! Only qualified personnel shall work on and around this equipment after becoming thoroughly familiar with all warnings and safety notices of this manual as well as with the applicable safety regulations. Particular attention must be drawn to the following: The earthing screw of the device must be connected solidly to the protective earth conductor before any other electrical connection is made. Hazardous voltages can be present on all circuits and components connected to the supply voltage or to the measuring and test quantities. Hazardous voltages can be present in the device even after disconnection of the supply voltage (storage capacitors!) The limit values stated in the technical data (2 Technical Data) must not be exceeded at all, not even during testing and commissioning.
Warning! 6 Commissioning CZX-22R Interposing Relay Set 46 Date: 2011-04-12 Primary test may only be carried out by qualified personnel, who are familiar with the commissioning of protection system, the operation of the plant and safety rules and regulations (switching, earthing, etc.) 6.3 Insulation Test (if required) Insulation resistance tests are only necessary during commissioning if it is required for them to be done and they have not been performed during installation. Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation tester at a DC voltage not exceeding 500V, The circuits need to be tested should include: DC power supply Output contacts The insulation resistance should be greater than 100M at 500V. Test method: To unplug all the terminals sockets of this protective device, and do the Insulation resistance test for each circuit above with an electronic or brushless insulation tester. On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected to the protection 6.4 Product Checks These product checks cover all aspects of the relay which should be checked to ensure that it has not been physically damaged prior to commissioning, is functioning correctly and all input quantity measurements are within the stated tolerances. 6.4.1 General Description The CZX series interposing relay set is fully numerical and the hardware is continuously monitored. Commissioning tests can be kept to a minimum and need only include hardware tests and conjunctive tests. The function tests are carried out according to users correlative regulations. The following tests are necessary to ensure the normal operation of the equipment before it is first put into service. Hardware tests These tests are performed for the following hardware to ensure that there is no hardware defect. Defects of hardware circuits other than the following can be detected by self-monitoring when the DC power is supplied. Binary input circuits and output circuits test Function tests Conjunctive tests 6 Commissioning CZX-22R Interposing Relay Set 47 Date: 2011-04-12 The tests are performed after the relay is connected with the primary equipment and other external equipment. On load test. 6.4.2 Visual Inspection After unpacking the product, check for any damage to the relay case. If there is any damage, the internal module might also have been affected, contact the vendor. Following items listed is necessary. Protection panel Carefully examine the protection panel, protection equipment inside and other parts inside to see that no physical damage has occurred since installation. The rated information of other auxiliary protections should be checked to ensure it is correct for the particular installation. Panel wiring Check the conducting wire which is used in the panel to assure that their cross section meeting the requirement. Carefully examine the wiring to see that they are no connection failure exists. Label Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to make sure that their labels meet the requirements of this project. Equipment plug-in modules Check each plug-in module of the equipments on the panel to make sure that they are well installed into the equipment without any screw loosened. Earthing cable Check whether the earthing cable from the panel terminal block is safely screwed to the panel steel sheet. Switch, keypad, isolator binary inputs and push button Check whether all the switches, equipment keypad, isolator binary inputs and push buttons work normally and smoothly. 6.4.3 Check the Jumpers In general, the jumpers of the relay have been set correctly before sent to user. While, checking the jumpers is a good habit before the relay is brought to service. Setting method of the jumpers is explained in section 4.5 in detail. 6 Commissioning CZX-22R Interposing Relay Set 48 Date: 2011-04-12 6.4.4 External Wiring Check that the external wiring is correct to the relevant relay diagram and scheme diagram. Ensure as far as practical that phasing/phase rotation appears to be as expected. Check the wiring against the schematic diagram for the installation to ensure compliance with the customers normal practice. 6.4.5 Auxiliary Supply The relay can be operated from either 110/125Vdc or 220/250Vdc auxiliary supply depending on the relays nominal supply rating. The incoming voltage must be within the operating range specified in the following table, before energizing the relay, measure the auxiliary supply to ensure it within the operating range. Rated Voltage 110/125Vdc 220/250Vdc Variation 80% ~ 120% 80% ~ 120% It should be noted that the relay can withstand an AC ripple of up to 15% of the rated voltage on the DC auxiliary supply.
Warning! Energize the relay only if the auxiliary supply is within the specified operating ranges. 6.5 Final Check After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been necessary to disconnect any of the external wiring from the protection in order to perform the wiring verification tests, it should be ensured that all connections are replaced in accordance with the relevant external connection or scheme diagram. Ensure that the protection has been restored to service. If the protection is in a new installation or the circuit breaker has just been maintained, the circuit breaker maintenance should be zero. If a test block is installed, remove the test plug and replace the cover so that the protection is put into service. Ensure that all event records, fault records, disturbance records and alarms have been cleared and LEDs has been reset before leaving the protection. 7 Maintenance CZX-22R Interposing Relay Set 49 Date: 2011-04-12 7 Maintenance NR numerical relay is designed to require no special maintenance. All measurement and signal processing circuit are fully solid state. All input modules are also fully solid state. The output relays are hermetically sealed. Since the device is almost completely self-monitored, from the measuring inputs to the output relays, hardware and software defects are automatically detected and reported. The self-monitoring ensures the high availability of the device and generally allows for a corrective rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are not required. Operation of the device is automatically blocked when a hardware failure is detected. If a problem is detected in the external measuring circuits, the device normally only provides alarm messages. 7.1 Routine Check The device realizes complete self-check, so routine check can only involve some typical items recommended by our company, otherwise, users can run their own check regulations. When failures are found during routine check, please confirm them by the following contents: Check or test whether the circuit is properly connected Whether the module is in correct position and located accurately Whether the voltage of DC power supply is correct Test flow strictly conforms to the requirements of debugging outline or related general rules 7.2 Replace Failed Modules If the failure is identified to be in the relay module and the user has spare modules, the user can recover the protection by replacing the failed modules. Repair at the site should be limited to module replacement. Maintenance at the component level is not recommended. Check that the replacement module has an identical module name and hardware type-form as the removed module. The module name is indicated on the top front of the module. Caution! When handling a module, take anti-static measures such as wearing an earthed wrist band and placing modules on an earthed conductive mat. Otherwise, many of the electronic components could suffer damage. 7 Maintenance CZX-22R Interposing Relay Set 50 Date: 2011-04-12 Please refer to the following steps to replace a failed plug-in module Switch off the DC power supply Disconnect the trip outputs Unscrew the screw of the front panel. Open the front panel of the device Replace the failed plug-in module by a new plug-in module Warning! Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It takes approximately 30 seconds for the voltage to discharge. Warning! Units and modules may only be replaced while the supply is switched off and only by appropriately trained and qualified personnel. Strictly observe the basic precautions to guard against electrostatic discharge. Warning! When handling a module, take anti-static measures such as wearing an earthed wrist band and placing modules on an earthed conductive mat. Otherwise, many of the electronic components could suffer damage. 7.3 Cleaning Before cleaning the relay, ensure that all AC/DC supplies, current transformer connections are isolated to prevent any chance of an electric shock whilst cleaning. Use a smooth cloth to clean the front panel. Do not use abrasive material or detergent chemicals. 7.4 Storage The spare relay or module should be stored in a dry and clean room. Based on IEC standard 60255-6 the storage temperature should be from -25 o C to 70 o C, but the temperature of from -10 o C to 40 o C is recommended for long-term storage. 8 Decommissioning and Disposal CZX-22R Interposing Relay Set 51 Date: 2011-04-12 8 Decommissioning and Disposal 8.1 Decommissioning 1. Switching off To switch off the device, switch off the external miniature circuit breaker of the power supply. 2. Disconnecting Cables Disconnect the cables in accordance with the rules and recommendations made by relational department.
Danger! Before disconnecting the power supply cables that connected with the DC module of the protective device, make sure that the external miniature circuit breaker of the power supply is switched off.
Danger! Before disconnecting the cables that are used to connect analog input module with the primary CTs and VTs, make sure that the circuit breaker for the primary CTs and VTs is switched off. 3. Dismantling The device rack may now be removed from the system cubicle, after which the cubicles may also be removed.
Danger! When the station is in operation, make sure that there is an adequate safety distance to live parts, especially as dismantling is often performed by unskilled personnel. 8.2 Disposal In every country there are companies specialized in the proper disposal of electronic waste.
Note! Strictly observe all local and national regulations when disposing of the device. 8 Decommissioning and Disposal CZX-22R Interposing Relay Set 52 Date: 2011-04-12
9 Manual Version History CZX-22R Interposing Relay Set 53 Date: 2011-04-12 9 Manual Version History In the latest version of the instruction manual, several descriptions on existing features have been modified. Manual version and modification history records Manual Version Software Version Date Description of change Source New R1.00 2011-04-12 Form the original manual.