ELECTRICAL WORK

FOR
BORIVALLI SCHOOL
BILL OF QUANTITIES DATED 14.08.09
Qty. Supply Installation Total
Item No.Description Rate Amount Rate Amount Rate Amount
A METER
BOARD

1 Providin
g &
installati
on
followin
g
equipme
nts on
teak
wood
/marine
ply meter
board.

i 40 Amp
TPN
MCB (9
KA) -
1No. for
Bank
1 No.

2 Isolato
rs
Supply
&
Installati
on of
Outgoing
isolators
in M.S.
powder
coated
enclosure
with in
built
cable
end
boxes for
incoming
and
outgoing
cables.

i 125
Amp.
TPN
MCCB
( For
Hall
Ground
floor ) 1 No.
ii. 150
Amp.
TPN
MCCB
( For
Hall 2nd
floor &
Fire
Hydrant
system )
2 Nos.
iii 40 Amp.
TPN
MCCB
( For
Utilty
Panel )
1 No.
iv 100
Amp.
TPN
MCCB
( For
Common
Services
)
1 No.
v 200
Amp.
TPN
MCCB
( For
Ground
to 9th
floor
load )
1 No.

3 METER
BOARD
WIRIN
G

1 Providin
g &
fixing
looping
cables/wi
res from
meter to
out going
MCB's
including
PVC
flexibles,
lugs &
terminati
on etc
i 4 Nos. x
10sqmm
+ 2 No. x
2.5
sqmm
cu. Wires

3 Mtrs
ii 3.5C X
150sqm
m AYFY 3 Mtrs
iii 3.5C X
95sqmm
AYFY 6 Mtrs
iv 3.5C X
70sqmm
AYFY 3 Mtrs
v 3.5C X
50sqmm
AYFY 3 Mtrs
vi 4C X 6
sqmm
YFY 3 Mtrs
Total

B L.T.
PANEL
S
Design,
fabricatio
n,
providin
g,
erection
connecti
on,
testing &
commissi
oning of
cubical
indoor,
floor
mounting
type,
sheet
steel,
clad dust,
and
vermin
proof,
I.P. - 55
protectio
n L.T.
Panel
Boards,
suitable
for 440
Volts, 3
Phase, 4
1.1 POWER
PANEL
FOR
COMM
ON
SERVIC
ES

1 No.
Incomer
1 No. -
100
Amp.
Auto
Transfer
Switch
(ATS)
1 No.
-100
Amp.
MCCB's
TPN

1 Set - 0
- 500 V -
Voltmete
r with
Selector
switch

1 Set - 0
-100 A -
Ammeter
with
Selector
switch &
CT's
100 / 5
Amp.

1 Set -
Phase
indicatin
g lamps
Bus Bar
- 200
Amps
TPN
copper

Outgoin
g
3 Nos . -
40 Amp.
TPN
MCB's
(9 KA)

6 Nos . -
32 Amp.
TPN
MCB's
(9 KA)
1.2 POWER
PANEL
FOR
UTILTY
LOAD

1 No.
Incomer
1 No. -
40 Amp.
MCCB's
TPN
1 Set - 0
- 500 V -
Voltmete
r with
Selector
switch

1 Set - 0
- 40 A -
Ammeter
with
Selector
switch &
CT's 40
/ 5 Amp.

1 Set -
Phase
indicatin
g lamps
Bus Bar
- 100
Amps
TPN
copper

Outgoin
g
3 Nos. -
32 Amp
TPN
MCB's
(9 KA)
1.3 Power
Panel
for Fire
Hydrant
System (
In the
scope of
Fire
Agency)
R.O No.
Incomer
1 No.
-150
Amp.
TPN
MCCB's

1 Set - 0
- 500 V -
Voltmete
r with
Selector
switch

1 Set - 0
- 150 A -
Ammeter
with
Selector
switch &
CT's
150 / 5
Amp.

1 Set -
Phase
indicatin
g lamps
Bus Bar
- 200
Amps
TPN
copper

Outgoin
g
2 No. -
125 Amp
TPN
MCCB's
(25 KA)

2 Nos. -
32 Amp
TPN
MCB's
(9 KA)

1.4 POWER
PANEL
FOR
Hall
Ground
floor

1 No.
Incomer
1 No.
-125
Amp.
MCCB's
TPN

1 Set - 0
- 500 V -
Voltmete
r with
Selector
switch

1 Set - 0
-125 A -
Ammeter
with
Selector
switch &
CT's
125 / 5
Amp.
1 Set -
Phase
indicatin
g lamps
Bus Bar
- 200
Amps
TPN
copper

Outgoin
g
3 Nos . -
63 Amp.
TPN
MCB's
(9 KA)

2 Nos . -
32 Amp.
TPN
MCB's
(9 KA)

1.5 POWER
PANEL
FOR
Hall 2nd
floor

1 No.
Incomer
1 No.
-150
Amp.
MCCB's
TPN

1 Set - 0
- 500 V -
Voltmete
r with
Selector
switch
1 Set - 0
-150A -
Ammeter
with
Selector
switch &
CT's
150 / 5
Amp.

1 Set -
Phase
indicatin
g lamps
Bus Bar
- 200
Amps
TPN
copper

Outgoin
g
3 Nos . -
63 Amp.
TPN
MCB's
(9 KA)

2 Nos . -
32 Amp.
TPN
MCB's
(9 KA)

1.6 POWER
PANEL
FOR
Ground
to 9th
floor
load

1 No.
Incomer
1 No.
-200
Amp.
MCCB's
TPN

1 Set - 0
- 500 V -
Voltmete
r with
Selector
switch

1 Set - 0
-200A -
Ammeter
with
Selector
switch &
CT's
200 / 5
Amp.

1 Set -
Phase
indicatin
g lamps
Bus Bar
- 300
Amps
TPN
copper

Outgoin
g
4 Nos . -
40 Amp.
TPN
MCB's
(9 KA)

8 Nos . -
32 Amp.
TPN
MCB's
(9 KA)
Providin
g, fixing,
Testing
and
commissi
oning 32
Amps
TPN
Switch
Fuse unit
in
powder
coated
enclosure
for lift
power in
Lift
Machine
1.7 Room 2 Nos.

Providin
g, fixing,
Testing
and
commissi
oning 25
Amps 4
pole
ELCB ,
100mA
Sensitivit
y in
powder
coated
enclosure
1.8 for lift 2 Nos.
Total

C. MCB
DISTRI
BUTIO
N
BOARD
Providin
g,
installing
,
commissi
oning &
testing,
MCB
distributi
on
boards
IP-42
protectio
n with
MCB,
RCCB,
inter
connecti
ons,
earthing,
DB chart
etc.
complete
as per
specificat
ions &
make as
specified
.

1 Lighting
DB for
Ground
, 2nd,
5th to
9th floor

8 Way
TPN
MCB
DB
comprisi
ng of
7 Nos.
Incomm
er
1 No. 32
Amp.
TPN
MCB
3 Nos. -
25A DP
RCCB
100mA
sensitivit
y
Outgoin
g
24 Nos.
10/20
Amp.
S.P.
MCB (9
KA)

2 Lighting
DB for
1st, 3rd
& 4th
floor

8 Way
TPN
MCB
DB
comprisi
ng of
3 Nos.
Incomm
er
1 No. 40
Amp.
TPN
MCB
3 Nos. -
25A DP
RCCB
100mA
sensitivit
y
Outgoin
g
24 Nos.
10/20
Amp.
S.P.
MCB (9
KA)

3 External
Lighting
DB
4 Way
TPN
MCB
DB
comprisi
ng of
1 No.
Incomm
er
1 No. -
32 Amp.
TPN
MCB's
(9 KA)

3No. -
25A DP
RCCB
100mA
sensitivit
y
Outgoin
g
12 Nos. -
10/20
Amp
S.P.
MCB's
(9 KA)

4 Staircas
e
Lighting
DB
4 Way
TPN
MCB
DB
comprisi
ng of
1 No.
Incomm
er
1 No. -
32 Amp.
TPN
MCB's
(9 KA)

3No. -
25A DP
RCCB
100mA
sensitivit
y
Outgoin
g
12 Nos. -
10/20
Amp
S.P.
MCB's
(9 KA)

5 Ground
to 9th
floor
passage
& lift
lobby
lighting
& power
DB

6 Way
TPN
MCB
DB
comprisi
ng of
1 No.
Incomm
er
1 No. -
32 Amp.
TPN
MCB's
(9 KA)

3No. -
25A DP
RCCB
100mA
sensitivit
y
Outgoin
g
18 Nos. -
10/20
Amp
S.P.
MCB's
(9 KA)

6 Ground
floor
Hall
Lighting
DB

4 Way
TPN
MCB
DB
comprisi
ng of
1 No.
Incomm
er
1 No. -
32 Amp.
TPN
MCB's
(9 KA)
3No. -
25A DP
RCCB
100mA
sensitivit
y
Outgoin
g
12 Nos. -
10/20
Amp
S.P.
MCB's
(9 KA)

7 2nd
floor
Hall
Lighting
DB

4 Way
TPN
MCB
DB
comprisi
ng of
1 No.
Incomm
er
1 No. -
32 Amp.
TPN
MCB's
(9 KA)

3No. -
25A DP
RCCB
100mA
sensitivit
y
Outgoin
g
12 Nos. -
10/20
Amp
S.P.
MCB's
(9 KA)

8 Bank
Lighting
& Power
DB

8 Way
TPN
MCB
DB
comprisi
ng of
1 No.
Incomm
er
1 No. -
40 Amp.
TPN
MCB's
(9 KA)

3No. -
25A DP
RCCB
100mA
sensitivit
y
Outgoin
g
24 Nos. -
10/20
Amp
S.P.
MCB's
(9 KA)
9 4 Way
SPN
MCB
D.B.
FOR
LIFT
CAGE
&
SHAFT
LIGHTI
NG
( LIFT
MACHI
NE
ROOM)

1 No.
Incomm
er
1 No. 32
Amp
TPN
MCB (9
KA)

Outgoin
g
4 Nos.. -
10/16
Amp
S.P.
MCB (9
KA)

Total

D SUB
MAIN
WIRIN
G
a Providin
g, laying
Sub main
wiring
using
copper
conducto
r PVC
insulated
wires in
25mm /
32mm
dia
heavy
duty
PVC
conduit
partly
open in
electrical
duct &
partly
conceale
d in
slabfrom
MCB in
meter
room to
MCB
DB at
respectiv
i 4 Nos. x
10 sqmm
+ 2 No. x
2.5
sqmm
cu. Wires

80 RM
OR
a Providin
g,
laying /
fixing,
testing &
commissi
oning of
followin
g size of
1.1 KA
grade
PVC
insulated
Copper
conducto
r
armoured
cables
partly
open in
electrical
Shaft &
partly
conceale
d in slab
from
MCB in
meter
room to
MCB
DB at
i 4 C x 10
Sq.mm
YFY
RO RM
b Providin
g and
fixing
followin
g rigid
PVC
conduits
&
conduits
accessori
es
thickness
not less
than
2mm
below
false
ceiling
and
partly
conceale
d in wall

i. 32mm 100 RM
dia.
ii. 20mm R.O RM
dia.
iiii 25mm 100 RM
dia.
iv 25mm R.O RM
dia.
( Flexibl
e pipe)

E CABLE
S
Providin
g
installati
on,
testing
commissi
oning
followin
g size
1100
volts
grade,
stranded
aluminiu
m /
copper
conducto
r, PVC
insulated
PVC
inner
sheathed
armoured
cable
laid
surface
to wall,
in
electrical
ducts,
on ready
i. 3.5 C x
300
Sq.mm
AYFY
RO RM
ii. 3.5 C x
240
Sq.mm
AYFY
RO RM
iii 3.5 C x
185
Sq.mm
AYFY
RO RM
iv 3.5 C x
150
Sq.mm
AYFY
100 RM
v 3.5 C x
120
Sq.mm
AYFY
50 RM
vi 3.5 C x
95
Sq.mm
AYFY
100 RM
vii 3.5 C x
70
Sq.mm
AYFY
50 RM
viii 3.5 C x
50
Sq.mm
AYFY
80 RM
ix 3.5C C x
35
Sq.mm
AYFY
RO RM
x 4 C x 25
Sq.mm
YFY
RO RM
xi 4 C x 16
Sq.mm
YFY
150 RM
xii 4 C x 10
Sq.mm
YFY
100 RM
xiii 4 Cx6
Sq.mm
YFY 150 RM
xiv 3 C x
2.5
Sq.mm
YFY
RO RM
xv 4Cx 4
Sq.mm
YFY 400 RM
xvi 3Cx 4
Sq.mm
YFY 100 RM
Total

CABLE
END
TERMI
NATIO
NS

Providin
g end
terminati
on for
the
above
cables
flange
type
brass
cable
glands,
crimping
type
Aluminiu
m /
Copper
lugs
earthing
complete
as per
Specifica
tion.

i. 3.5 C x
300
Sq.mm
AYFY
RO Nos.
ii. 3.5 C x
240
Sq.mm
AYFY
RO Nos.
iii 3.5 C x
185
Sq.mm
AYFY
RO Nos.
iv 3.5 C x
150
Sq.mm
AYFY
2 Nos.
v 3.5 C x
120
Sq.mm
AYFY
2 Nos.
vi 3.5 C x
95
Sq.mm
AYFY
4 Nos.
vii 3.5 C x
70
Sq.mm
AYFY
2 Nos.
viii 3.5 C x
50
Sq.mm
AYFY
RO Nos.
ix 3.5C C x
35
Sq.mm
AYFY
RO Nos.
x 4 C x 25
Sq.mm
YFY
RO Nos.
xi 4 C x 16
Sq.mm
YFY
8 Nos.
xii 4 C x 10
Sq.mm
YFY
4 Nos.
xiii 4 Cx6
Sq.mm
YFY 10 Nos.
xiv 3 C x
2.5
Sq.mm
YFY
RO Nos.
xv 4Cx 4
Sq.mm
YFY 30 Nos.
xvi 3Cx 4
Sq.mm
YFY 10 Nos.
Total

F CABLE
TRAYS
Providin
g,
assembli
ng and
install
followin
g size of
perforate
d trays
(149)
and
necessar
y support
for wall
& ceilig
including
all
hardware
s and 2
Nos. 25
x 3mm
G.I.
Earthing
strips as
per site
requirem
ent
complete
as per
specificat
ion and
(Note:
25 x
6mm
G.I..
Earth
conducto
r Item
covered
in
earthing
section)

i. 900mm
Width RO RM
ii. 600mm
Width RO RM
iii. 450mm
Width 100 RM
iv. 300mm
Width 100 RM
Total

G SWITC
H FUSE
UNITS
IN M.S.

ENCLO
SURES
Providin
g,
installati
on,
testing &
commissi
oning the
followin
g rating
of fuse
switch
unit with
HRC
fuses
earthing,
M.S.
bracket,
hardware
complete
as per
Specifica
tion

i 63 Amp
TPN -
SFU
with
HRC
fuse
R.O No.
ii. 32 Amp
TPN -
SFU
with
HRC
fuse
R.O No.
Total

H EARTH
ING &
LIGHTI
NG
PROTE
CTION
1 Providin
g, earth
pit with
600 x
600 x
6.3mm
G.I. Plate
and
necessar
y length
of 50 x
6mm
G.I. Strip
upto test
link
watering
G.I.
Perforate
d pipe
funnel
masonry
chamber,
complete
as per IS
3043
latest
Rate to
include
all
excavatio
n and 10 Nos.
2 Providin
g and
laying on
the
followin
g size of
earthing
conducto
r,
cleated
to
wall/ceili
ng laying
on cable
trays,
buried in
ground
to depth
of
450mm
below
ground
level.

Rate to
include
all
excavatio
n
backfillin
g &
clamps
etc.
complete
as per
specificat
ion &
requirem
ent

i 40 x
3mm
Cu . 50 RM
Strips
ii. 50 x
6mm
G.I.
Strips
RO RM
iii. 25 x
6mm
G.I.
Strips
50 RM
iv. 25 x
3mm Cu.
Strips 50 RM
v. 8 SWG
bare GI
Strips 100 RM
vi. 8 SWG
bare Cu
Strips 100 RM
3 Providin
g, earth
pit with
600 x
600 x
3.15mm
Copper
Plate and
necessar
y length
of 40 x
3mm
Copper
Strip
upto test
link
watering
G.I.
Perforate
d pipe
funnel
masonry
chamber,
complete
as per IS
3043
latest
Rate to
include
all
excavatio 2 No.
4 Providin
g &
making
earth
station as
specified
in
earthing
using
75mm
dia. 3
meter
long G.I.
Pipe
earth
electrode
,
perforate
d for
watering
fixed
with
funnel at
the top
and all
required
materials
.

4 No.
5 Providin
g and
fixing 25
x 6mm
G.I.
Earth
strip
including
test joint
from
respectiv
e earth
station to
lightenin
g arrestor
partly
under
ground,
partly
run
vertically
on
external
surface
of
building
wall.
The
under
ground
portion 100 RM
6 Providin
g of
lightenin
g arrestor
with
20mm
dia. 1
meter
long
copper
rod
having
200 x
200 x
6mm
brass
plate as a
base
plate and
arrestor
with
copper
rod of
75mm
dia. 5
Nos.
6mm
dia.,
100mm
long
spokes 1 No.
7 Providin
g of
earth
terminal
test joint
boxes
fabricate
d and out
14 gauge
CRCA
sheet
galvanize
d with
250mm
long 40 x
6mm
G.I.
Earth
terminal
plate
with long
brass nut
bolts
duly
fixed in a
box

4 No.
Total

J LIGHTI
NG
AND
POWER
POINT
WIRIN
G
1 Providin
g point
wiring
for
followin
g points
using 3
Nos. x
1.5
Sq.mm
FRLS
copper
conducto
r wires in
2mm
thick
PVC
conduit
of
minimu
m 25mm
dia.
With
necessar
y conduit
accessori
es,
complete
with
flush
mounted
Point
control
by
Switch
board

Light
Point
Control
by 6
Amp.
S.P.
Switch
i 185 Nos.
Two
Light
Point
Control
by 6
Amp.
S.P.
Switch
ii 43 Nos.
Three
Light
Point
Control
by 6
Amp.
S.P.
Switch
iii 91 Nos.

Group
light
Providin
g point
wiring
for
followin
g points
using 2
Nos. x
2.5
Sq.mm
+1 No. x
1.5
sqmm
FRLS
copper
2 conducto
r wires in
2mm
thick
PVC
conduit
of
minimu
m 25mm
dia.
With
necessar
y conduit
accessori
es,
complete
Four
Light
Point
Control
by 6
Amp.
S.P.
Switch
i RO Nos.
Five
Light
Point
Control
by 6
Amp.
S.P.
Switch
ii 2 Nos.
Six Light
Point
Control
by 6
Amp.
S.P.
Switch
iii RO Nos.
Seven
Light
Point
Control
by 6
Amp.
S.P.
Switch
iv RO Nos.
Eight
Light
Point
Control
by 6
Amp.
S.P.
Switch
v RO Nos.
Nine
Light
Point
Control
by 6
Amp.
S.P.
Switch
vi RO Nos.
Ten
Light
Point
Control
by 6
Amp.
S.P.
Switch
vii RO Nos.
Exhaust
fan point
controlle
d by 6
Amp.
S.P.
switch
viii 101 Nos.
Fan point
controlle
d by 6
Amp
S.P.
Switch,
electroni
c step
regulator
and box
type fan
hook.

ix 205 Nos.
5 Amp.
switch
socket
outlet
point
( Commo
n with
the
switchbo
ard)
x RO Nos.
3 Providin
g point
wiring
for
followin
g points
using 2
Nos. x
2.5
Sq.mm +
1 Nos. x
1.5
Sqmm
FRLS
copper
conducto
r wires in
2mm
thick
PVC
conduit
of
minimu
m 25mm
dia.
With
necessar
y conduit
accessori
es,
complete
Light
point
control
by MCB

i Three Lig 5 Nos.


ii Four Ligh RO Nos.
iii Five Ligh RO Nos.
iv Six Light 7 Nos.
v Seven Lig 7 Nos.
vi Eight Lig RO Nos.
vii Ten Ligh 4 Nos.
viii Eleven L RO Nos.
ix Twelve L RO Nos.
4 Providin
g wiring
for 3
Pin, 6
Amp.
Switch
socket
outlet
(indepen
dently)
for local
socket
using 3
Nos. x
1.5
Sq.mm
FRLS
copper
conducto
r wires
including
earth
wire in
green
colour
for
continuo
us
earthing
to socket
outlet
One 5 57 Nos.
Amp
switch
with
socket
5 Providin
g wiring
for 5
Pin, 5 /
15 Amp.
Switch
socket
outlet
Modular
type for
power
socket
using 2
Nos. x 4
Sq.mm +
1 Nos. x
1.5
Sq.mm
FRLS
copper
conducto
r wires
including
earth
wire in
green
colour
for
continuo
us
earthing
One 15 12 Nos.
Amp
switch
with
socket

6 POWER
POINT
FOR
A.C.
UNIT
Providin 12 Nos.
g point
wiring
for single
phase
AC unit
using 2 x
4 sqmm
+ 1 x 2.5
sqmm
single
PVC
( FRLS)
wires in
25mm
dia rigid
PVC
pipe
heavy
duty with
necessar
y conduit
accessori
es
including
supply
and
fitting 20
Amps 2
pin &
earth

7 Isolator
for 3
Phase
AC
Outdoor
Unit
63 Amp 4 Nos.
TPN
MCB in
powder
coated
enclosure
as
incomer
isolator
for AC
Outdoor
Unit

Total

J CIRCUI
T
WIRIN
G
a Providin
g, laying
circuit
wiring
using
copper
conducto
r PVC
insulated
wires in
25mm
dia in
PVC
Pipe
from
MCB
DB to
respectiv
e switch
board &
power
points

1 2Nos. x 2. 300 RM
2 2Nos. x 4 200 RM
3 4Nos. x 4 R.O RM

b Providin
g and
fixing
followin
g rigid
PVC
conduits
&
conduits
accessori
es
thickness
not less
than
2mm

i. 20mm
dia. RO RM
ii. 25mm
dia. 200 RM

Total

K TELEP
HONE
NETWO
RK
Providin
g,
installati
on of
followin
g for
Telephon
e
network.
a Providin
g &
installati
on
followin
g
telephon
e
junction
boxes
with
enclosure
(as
located)

i 100 Pair
Crone
Connecto
r (TTB)
1 No.
ii. 50 Pair
Crone
Connecto
r (TTB)
RO Nos.
iii. 20 Pair
Crone
Connecto
r (TTB)
RO Nos.
iv. 10 Pair
Crone
Connecto
r (TTB)
10 Nos.
b. Providin
g &
laying
followin
g pairs
telephon
e cable
from
main
TTB
(100
Pair) to
sub TTB
(at
ground
& all
upper
floor) in
25mm
PVC
conduit
run
vertical
in LV
duct &
from Sub
TTB to
Rooms

i. 50 Pair
Telephon
e Cable RO RM
ii. 20 Pair
Telephon
e Cable RO RM
iii 10 Pair
Telephon
e Cable 100 RM
iv. 5 Pair
Telephon
e Cable 500 RM
d Providin
g and
fixing
followin
g rigid
PVC
conduits
&
conduits
accessori
es
thickness
not less
than
2mm

i. 20mm
dia. 100 RM
ii. 25mm
dia. 100 RM
Total

L T.V.
SYSTE
M
1 Providin
g &
laying
followin
g side
T.V. co-
axial
cables in
20/25mm
dia. rigid
PVC
conduit
from
main
spliter
box to
respectiv
e floor
spliter
boxes
and from
spliter
boxes to
individua
l shops
on all
floors
with
necessar
y pull
boxes as
i. R.G. - 11
( U) Co-
axial
cables
RO RM
ii. R.G. - 6
( U ) Co-
axial
cables
RO RM
1.2 Providin
g and
fixing
followin
g spliter
boxes on
all floors
as shown
in
Layout
Drawing
ii. 6 Way
Spliter
Boxes RO Nos
ii. 4 Way
Spliter
Boxes RO Nos
1.3 Providin
g and
fixing
followin
g rigid
PVC
conduits
&
conduits
accessori
es
thickness
not less
than
2mm

i. 20mm
dia. RO RM
ii. 25mm
dia. RO RM
Total
M MISCE
LLANE
OUS
ITEMS
1 METER
BOARD
1 Providin
g &
fixing
teak
wood
varnishe
d
wooden
meter
board of
1" thick
wooden
flank /
marine
ply
25mm
thick
shall be
grouted
on wall
including
earthing
using 25
x 6mm
G.I.
Earth
strips
suitable
for :
1 No.
i. 1 Nos. 3
Phase 4
Wire
(unbalan
ce Load)
energy
meter
ii 3 Nos.
32/60
Amp
I.C.
Cutouts
with
rewirable
fuses at
415
Volts
rating

iii. 1 No. 40
Amp
TPN
MCB (9
KA)

iv 5 Nos.
CT
Meters
(As per
meter
room
layout
drawing
and
direction
of
authority
/ supply
company
)
2 Providin
g
installati
on,
testing
and
commissi
oning
followin
g switch
fuse unit
in
enclosure
(L&T/
Siemens
Make)
with
cable
end
boxes

i. 400 Amp RO Nos

ii. 250 Amp RO Nos

3 Providin
g &
fixing
followin
g rating
copper
busbars
in 14/16
gauge
CRCA
sheet
steel
enclosure
duly
painted
&
coutouts
for wires
entry.
i. 400 Amp 10 RM
TPN
Copper

ii. 250 Amp RO RM


TPN
Copper

4 Installati
on of
followin
g
equipme
nts in
meter
room
i. 40 Amp. RO No.
I.C.
cutout
rewirable
ii. 63 Amp. RO No.
I.C.
cutout
rewirable
iii. Installati RO No.
on of
followin
g meters:
3 x 20 Am RO No.
3 x 40 A RO No.
3 x 60 A RO No.
3 x 100 RO No.
100/ 5 Am RO No.
5 Providin
g,
installati
on,
testing
and
commissi
oning
followin
g power
capacitor
bank
415
Volts
(L&T
make)

i 10 RO Nos.
KVAR
Capacito
r
including
32 Amp
TP MCB
in
enclosure

ii 20 RO Nos.
KVAR
Capacito
r
including
63 Amp
TP MCB
in
enclosure
6 Providin RO Nos.
g and
fixing
300 x
100
M.S.
Junction
boxes in
all floor
electrical
duct for
pulling
main
cable
upto
each flat
(as
shown in
Schemati
c
Drawing)

7 Providin
g and
laying
followin
g size
RCC /
PVC

i. 300mm RO RM
dia. NP -
2 Class
ii. 150mm RO RM
dia. NP -
2 Class
ii. 100mm RO RM
dia.
Heavy
duty
PVC
pipe.
8 Tempora Job
ry
Electrific
ation
with all
wires
meters
etc.

9 Providin Job
g
Liasonin
g work
for
follow
up with
BEST
Authorit
y &
Elecrical
inspector
office for
obtaining
necessar
y
approval
commissi
oning of
meter
room
alternate
power
supply &
substatio
n etc

10 Supply
and
installati
on of
followin
g
i. Rubber RO Each
mat
ii. Danger RO Each
board
iii. First Aid RO Each
Box
iv. Fire RO Set
bucket
with
sand
Total
ELECTRICAL WORK
FOR
BORIVALLI SCHOOL
BILL OF QUANTITIES DATED 14.08.09
Qty. Supply
Item No. Description Rate Amount
A METER BOARD
1 Providing & installation following equipments on teak
wood /marine ply meter board.

i 40 Amp TPN MCB (9 KA) - 1No. for Bank


1 No.
2 Isolators
Supply & Installation of Outgoing isolators in M.S.
powder coated enclosure with in built cable end
boxes for incoming and outgoing cables.

i 125 Amp. TPN MCCB ( For Hall Ground floor )


1 No.
ii. 150 Amp. TPN MCCB ( For Hall 2nd floor & Fire
Hydrant system )
2 Nos.
iii 40 Amp. TPN MCCB ( For Utilty Panel )
1 No.
iv 100 Amp. TPN MCCB ( For Common Services )
1 No.
v 200 Amp. TPN MCCB ( For Ground to 9th floor
load )
1 No.

3 METER BOARD WIRING

1 Providing & fixing looping cables/wires from meter


to out going MCB's including PVC flexibles, lugs &
termination etc
i 4 Nos. x 10sqmm + 2 No. x 2.5 sqmm cu. Wires 3 Mtrs
ii 3.5C X 150sqmm AYFY 3 Mtrs
iii 3.5C X 95sqmm AYFY 6 Mtrs
iv 3.5C X 70sqmm AYFY 3 Mtrs
v 3.5C X 50sqmm AYFY 3 Mtrs
vi 4C X 6 sqmm YFY 3 Mtrs

B L.T. PANELS
Design, fabrication, providing, erection connection,
testing & commissioning of cubical indoor, floor
mounting type, sheet steel, clad dust, and vermin
proof, I.P. - 55 protection L.T. Panel Boards, suitable
for 440 Volts, 3 Phase, 4 Wire, 50 Hz, supply System.
Complete with cable allays, bus bars, solid inter
connection between bus bars to switch gears,
TOP/BOTTOM cable entries as required, powder
coated finish of approved shade etc. all as specified.

1.1 POWER PANEL FOR COMMON SERVICES


1 No.
1 No. - 100 Amp. Auto Transfer Switch (ATS)
1 No. -100 Amp. MCCB's TPN
1 Set - 0 - 500 V - Voltmeter with Selector switch
1 Set - 0 -100 A - Ammeter with Selector switch &
CT's 100 / 5 Amp.
1 Set - Phase indicating lamps
Bus Bar - 200 Amps TPN copper
Outgoing
3 Nos . - 40 Amp. TPN MCB's (9 KA)
6 Nos . - 32 Amp. TPN MCB's (9 KA)

1.2 POWER PANEL FOR UTILTY LOAD 1 No.


Incomer
1 No. - 40 Amp. MCCB's TPN
1 Set - 0 - 500 V - Voltmeter with Selector switch
1 Set - 0 - 40 A - Ammeter with Selector switch &
CT's 40 / 5 Amp.
1 Set - Phase indicating lamps
Bus Bar - 100 Amps TPN copper
Outgoing
3 Nos. - 32 Amp TPN MCB's (9 KA)

1.3 Power Panel for Fire Hydrant System ( In the


scope of Fire Agency)
R.O No.
Incomer
1 No. -150 Amp. TPN MCCB's
1 Set - 0 - 500 V - Voltmeter with Selector switch
1 Set - 0 - 150 A - Ammeter with Selector switch &
CT's 150 / 5 Amp.
1 Set - Phase indicating lamps
Bus Bar - 200 Amps TPN copper
Outgoing
2 No. - 125 Amp TPN MCCB's (25 KA)
2 Nos. - 32 Amp TPN MCB's (9 KA)

1.4 POWER PANEL FOR Hall Ground floor 1 No.


Incomer
1 No. -125 Amp. MCCB's TPN
1 Set - 0 - 500 V - Voltmeter with Selector switch
1 Set - 0 -125 A - Ammeter with Selector switch &
CT's 125 / 5 Amp.
1 Set - Phase indicating lamps
Bus Bar - 200 Amps TPN copper
Outgoing
3 Nos . - 63 Amp. TPN MCB's (9 KA)
2 Nos . - 32 Amp. TPN MCB's (9 KA)

1.5 POWER PANEL FOR Hall 2nd floor 1 No.


Incomer
1 No. -150 Amp. MCCB's TPN
1 Set - 0 - 500 V - Voltmeter with Selector switch
1 Set - 0 -150A - Ammeter with Selector switch &
CT's 150 / 5 Amp.
1 Set - Phase indicating lamps
Bus Bar - 200 Amps TPN copper
Outgoing
3 Nos . - 63 Amp. TPN MCB's (9 KA)
2 Nos . - 32 Amp. TPN MCB's (9 KA)

1.6 POWER PANEL FOR Ground to 9th floor load 1 No.


Incomer
1 No. -200 Amp. MCCB's TPN
1 Set - 0 - 500 V - Voltmeter with Selector switch
1 Set - 0 -200A - Ammeter with Selector switch &
CT's 200 / 5 Amp.
1 Set - Phase indicating lamps
Bus Bar - 300 Amps TPN copper
Outgoing
4 Nos . - 40 Amp. TPN MCB's (9 KA)
8 Nos . - 32 Amp. TPN MCB's (9 KA)

Providing, fixing, Testing and commissioning 32


Amps TPN Switch Fuse unit in powder coated
1.7 enclosure for lift power in Lift Machine Room 2 Nos.

Providing, fixing, Testing and commissioning 25


Amps 4 pole ELCB , 100mA Sensitivity in powder
1.8 coated enclosure for lift 2 Nos.

C. MCB DISTRIBUTION BOARD


Providing, installing, commissioning & testing, MCB
distribution boards IP-42 protection with MCB,
RCCB, inter connections, earthing, DB chart etc.
complete as per specifications & make as specified.

1 Lighting DB for Ground , 2nd, 5th to 9th floor

8 Way TPN MCB DB comprising of 7 Nos.


Incommer
1 No. 32 Amp. TPN MCB
3 Nos. - 25A DP RCCB 100mA sensitivity
Outgoing
24 Nos. 10/20 Amp. S.P. MCB (9 KA)

2 Lighting DB for 1st, 3rd & 4th floor


8 Way TPN MCB DB comprising of 3 Nos.
Incommer
1 No. 40 Amp. TPN MCB
3 Nos. - 25A DP RCCB 100mA sensitivity
Outgoing
24 Nos. 10/20 Amp. S.P. MCB (9 KA)
3 External Lighting DB
4 Way TPN MCB DB comprising of 1 No.
Incommer

1 No. - 32 Amp. TPN MCB's (9 KA)


3No. - 25A DP RCCB 100mA sensitivity
Outgoing

12 Nos. - 10/20 Amp S.P. MCB's (9 KA)

4 Staircase Lighting DB
4 Way TPN MCB DB comprising of 1 No.
Incommer
1 No. - 32 Amp. TPN MCB's (9 KA)
3No. - 25A DP RCCB 100mA sensitivity
Outgoing
12 Nos. - 10/20 Amp S.P. MCB's (9 KA)

5 Ground to 9th floor passage & lift lobby lighting &


power DB
6 Way TPN MCB DB comprising of 1 No.
Incommer
1 No. - 32 Amp. TPN MCB's (9 KA)
3No. - 25A DP RCCB 100mA sensitivity
Outgoing
18 Nos. - 10/20 Amp S.P. MCB's (9 KA)

6 Ground floor Hall Lighting DB


4 Way TPN MCB DB comprising of 1 No.
Incommer
1 No. - 32 Amp. TPN MCB's (9 KA)
3No. - 25A DP RCCB 100mA sensitivity
Outgoing
12 Nos. - 10/20 Amp S.P. MCB's (9 KA)

7 2nd floor Hall Lighting DB


4 Way TPN MCB DB comprising of 1 No.
Incommer
1 No. - 32 Amp. TPN MCB's (9 KA)
3No. - 25A DP RCCB 100mA sensitivity
Outgoing
12 Nos. - 10/20 Amp S.P. MCB's (9 KA)

8 Bank Lighting & Power DB


8 Way TPN MCB DB comprising of 1 No.
Incommer
1 No. - 40 Amp. TPN MCB's (9 KA)
3No. - 25A DP RCCB 100mA sensitivity
Outgoing
24 Nos. - 10/20 Amp S.P. MCB's (9 KA)

9 4 Way SPN MCB D.B. FOR LIFT CAGE &


SHAFT LIGHTING ( LIFT MACHINE ROOM)
1 No.
Incommer
1 No. 32 Amp TPN MCB (9 KA)
Outgoing
4 Nos.. - 10/16 Amp S.P. MCB (9 KA)

D SUB MAIN WIRING


a Providing, laying Sub main wiring using copper
conductor PVC insulated wires in 25mm / 32mm dia
heavy duty PVC conduit partly open in electrical duct
& partly concealed in slabfrom MCB in meter room to
MCB DB at respective floor level

i 4 Nos. x 10 sqmm + 2 No. x 2.5 sqmm cu. Wires 80 RM


OR
a Providing, laying / fixing, testing & commissioning of
following size of 1.1 KA grade PVC insulated Copper
conductor armoured cables partly open in electrical
Shaft & partly concealed in slab from MCB in meter
room to MCB DB at respective floor level

i 4 C x 10 Sq.mm YFY RO RM
b Providing and fixing following rigid PVC conduits &
conduits accessories thickness not less than 2mm
below false ceiling and partly concealed in wall
i. 32mm dia. 100 RM

ii. 20mm dia. R.O RM

iiii 25mm dia. 100 RM

iv 25mm dia. ( Flexible pipe) R.O RM

E CABLES

Providing installation, testing commissioning


following size 1100 volts grade, stranded aluminium /
copper conductor, PVC insulated PVC inner
sheathed armoured cable laid surface to wall, in
electrical ducts, on ready made cable trays in ready
made trenches, including all clamps & hardwares,
ferules, identification tags etc. make as specified

i. 3.5 C x 300 Sq.mm AYFY RO RM


ii. 3.5 C x 240 Sq.mm AYFY RO RM
iii 3.5 C x 185 Sq.mm AYFY RO RM
iv 3.5 C x 150 Sq.mm AYFY 100 RM
v 3.5 C x 120 Sq.mm AYFY 50 RM
vi 3.5 C x 95 Sq.mm AYFY 100 RM
vii 3.5 C x 70 Sq.mm AYFY 50 RM
viii 3.5 C x 50 Sq.mm AYFY 80 RM
ix 3.5C C x 35 Sq.mm AYFY RO RM
x 4 C x 25 Sq.mm YFY RO RM
xi 4 C x 16 Sq.mm YFY 150 RM
xii 4 C x 10 Sq.mm YFY 100 RM
xiii 4 C x 6 Sq.mm YFY 150 RM
xiv 3 C x 2.5 Sq.mm YFY RO RM
xv 4 C x 4 Sq.mm YFY 400 RM
xvi 3 C x 4 Sq.mm YFY 100 RM
CABLE END TERMINATIONS
Providing end termination for the above cables flange
type brass cable glands, crimping type Aluminium /
Copper lugs earthing complete as per Specification.

i. 3.5 C x 300 Sq.mm AYFY RO Nos.


ii. 3.5 C x 240 Sq.mm AYFY RO Nos.
iii 3.5 C x 185 Sq.mm AYFY RO Nos.
iv 3.5 C x 150 Sq.mm AYFY 2 Nos.
v 3.5 C x 120 Sq.mm AYFY 2 Nos.
vi 3.5 C x 95 Sq.mm AYFY 4 Nos.
vii 3.5 C x 70 Sq.mm AYFY 2 Nos.
viii 3.5 C x 50 Sq.mm AYFY RO Nos.
ix 3.5C C x 35 Sq.mm AYFY RO Nos.
x 4 C x 25 Sq.mm YFY RO Nos.
xi 4 C x 16 Sq.mm YFY 8 Nos.
xii 4 C x 10 Sq.mm YFY 4 Nos.
xiii 4 C x 6 Sq.mm YFY 10 Nos.
xiv 3 C x 2.5 Sq.mm YFY RO Nos.
xv 4 C x 4 Sq.mm YFY 30 Nos.
xvi 3 C x 4 Sq.mm YFY 10 Nos.

F CABLE TRAYS

Providing, assembling and install following size of


perforated trays (149) and necessary support for wall
& ceilig including all hardwares and 2 Nos. 25 x 3mm
G.I. Earthing strips as per site requirement complete
as per specification and as directed

(Note: 25 x 6mm G.I.. Earth conductor Item covered


in earthing section)

i. 900mm Width RO RM
ii. 600mm Width RO RM
iii. 450mm Width 100 RM
iv. 300mm Width 100 RM
G SWITCH FUSE UNITS IN M.S. ENCLOSURES

Providing, installation, testing & commissioning the


following rating of fuse switch unit with HRC fuses
earthing, M.S. bracket, hardware complete as per
Specification

i 63 Amp TPN - SFU with HRC fuse R.O No.


ii. 32 Amp TPN - SFU with HRC fuse R.O No.

H EARTHING & LIGHTING PROTECTION


1 Providing, earth pit with 600 x 600 x 6.3mm G.I. Plate
and necessary length of 50 x 6mm G.I. Strip upto test
link watering G.I. Perforated pipe funnel masonry
chamber, complete as per IS 3043 latest Rate to
include all excavation and back filling upto depth of
3.0 meter and bringing the surface to the original
finish. 10 Nos.
2 Providing and laying on the following size of earthing
conductor, cleated to wall/ceiling laying on cable
trays, buried in ground to depth of 450mm below
ground level.

Rate to include all excavation backfilling & clamps


etc. complete as per specification & requirement

i 40 x 3mm Cu . Strips 50 RM
ii. 50 x 6mm G.I. Strips RO RM
iii. 25 x 6mm G.I. Strips 50 RM
iv. 25 x 3mm Cu. Strips 50 RM
v. 8 SWG bare GI Strips 100 RM
vi. 8 SWG bare Cu Strips 100 RM
3 Providing, earth pit with 600 x 600 x 3.15mm Copper
Plate and necessary length of 40 x 3mm Copper Strip
upto test link watering G.I. Perforated pipe funnel
masonry chamber, complete as per IS 3043 latest
Rate to include all excavation and back filling upto
depth of 3.0 meter and bringing the surface to the
original finish.

2 No.
4 Providing & making earth station as specified in
earthing using 75mm dia. 3 meter long G.I. Pipe
earth electrode, perforated for watering fixed with
funnel at the top and all required materials.

4 No.
5 Providing and fixing 25 x 6mm G.I. Earth strip
including test joint from respective earth station to
lightening arrestor partly under ground, partly run
vertically on external surface of building wall. The
under ground portion of the strip shall be painted and
wrapped with bituminised jute taps with necessary
clamping hardwares. 100 RM
6 Providing of lightening arrestor with 20mm dia. 1
meter long copper rod having 200 x 200 x 6mm brass
plate as a base plate and arrestor with copper rod of
75mm dia. 5 Nos. 6mm dia., 100mm long spokes
duly fixed on surface with anchor fasteners

1 No.
7 Providing of earth terminal test joint boxes fabricated
and out 14 gauge CRCA sheet galvanized with
250mm long 40 x 6mm G.I. Earth terminal plate with
long brass nut bolts duly fixed in a box

4 No.

J LIGHTING AND POWER POINT WIRING


1 Providing point wiring for following points using 3
Nos. x 1.5 Sq.mm FRLS copper conductor wires in
2mm thick PVC conduit of minimum 25mm dia.
With necessary conduit accessories, complete with
flush mounted shock proof switch accessories and
modular type switches of approved make fixed
manufactures standard G.I. outlet boxes with earthing
screw , flush with wall / wooden panel and
continuous earthing upto fixture and switch board
using 1.5 Sq.mm FRLS green colour copper earth
wire, all complete as per direction

Point control by Switch board


i Light Point Control by 6 Amp. S.P. Switch 185 Nos.
ii Two Light Point Control by 6 Amp. S.P. Switch 43 Nos.
iii Three Light Point Control by 6 Amp. S.P. Switch 91 Nos.

Group light
Providing point wiring for following points using 2
Nos. x 2.5 Sq.mm +1 No. x 1.5 sqmm FRLS copper
conductor wires in 2mm thick PVC conduit of
minimum 25mm dia. With necessary conduit
accessories, complete with flush mounted shock proof
switch accessories and modular type switches of
2 approved make fixed manufactures standard G.I.
outlet boxes with earthing screw , flush with wall /
wooden panel and continuous earthing upto fixture and
switch board using 1.5 Sq.mm FRLS green colour
copper earth wire, all complete as per direction

i Four Light Point Control by 6 Amp. S.P. Switch RO Nos.


ii Five Light Point Control by 6 Amp. S.P. Switch 2 Nos.
iii Six Light Point Control by 6 Amp. S.P. Switch RO Nos.
iv Seven Light Point Control by 6 Amp. S.P. Switch RO Nos.
v Eight Light Point Control by 6 Amp. S.P. Switch RO Nos.
vi Nine Light Point Control by 6 Amp. S.P. Switch RO Nos.
vii Ten Light Point Control by 6 Amp. S.P. Switch RO Nos.
viii Exhaust fan point controlled by 6 Amp. S.P. switch 101 Nos.
Fan point controlled by 6 Amp S.P. Switch, electronic
step regulator and box type fan hook.
ix 205 Nos.
5 Amp. switch socket outlet point ( Common with the
x switchboard) RO Nos.

3 Providing point wiring for following points using 2


Nos. x 2.5 Sq.mm + 1 Nos. x 1.5 Sqmm FRLS copper
conductor wires in 2mm thick PVC conduit of
minimum 25mm dia. With necessary conduit
accessories, complete with continuous earthing upto
fixture excluding the cost of MCB which is covered
elsewhere , all complete as per direction

Light point control by MCB


i Three Light Point Control by MCB 5 Nos.
ii Four Light Point Control by MCB RO Nos.
iii Five Light Point Control by MCB RO Nos.
iv Six Light Point Control by MCB 7 Nos.
v Seven Light Point Control by MCB 7 Nos.
vi Eight Light Point Control by MCB RO Nos.
vii Ten Light Point Control by MCB 4 Nos.
viii Eleven Light Point Control by MCB RO Nos.
ix Twelve Light Point Control by MCB RO Nos.

4 Providing wiring for 3 Pin, 6 Amp. Switch socket


outlet (independently) for local socket using 3 Nos. x
1.5 Sq.mm FRLS copper conductor wires including
earth wire in green colour for continuous earthing to
socket outlet complete with 6 Amp. Modular type
switch and 6 Amp. 2 Pin and earth socket flush
mounted, complete as specified

One 5 Amp switch with socket 57 Nos.

5 Providing wiring for 5 Pin, 5 / 15 Amp. Switch socket


outlet Modular type for power socket using 2 Nos. x
4 Sq.mm + 1 Nos. x 1.5 Sq.mm FRLS copper
conductor wires including earth wire in green colour
for continuous earthing to socket outlet complete with
15 Amp.switch and 15 Amp. 2 Pin and earth socket
flush mounted, complete as specified

One 15 Amp switch with socket 12 Nos.

6 POWER POINT FOR A.C. UNIT


Providing point wiring for single phase AC unit using 12 Nos.
2 x 4 sqmm + 1 x 2.5 sqmm single PVC ( FRLS) wires
in 25mm dia rigid PVC pipe heavy duty with
necessary conduit accessories including supply and
fitting 20 Amps 2 pin & earth metal clad socket and 20
amp SP MCB in powder coated enclosure

7 Isolator for 3 Phase AC Outdoor Unit


63 Amp TPN MCB in powder coated enclosure as 4 Nos.
incomer isolator for AC Outdoor Unit

J CIRCUIT WIRING
a Providing, laying circuit wiring using copper
conductor PVC insulated wires in 25mm dia in PVC
Pipe from MCB DB to respective switch board &
power points

1 2Nos. x 2.5 sqmm + 1 No. x 1.5 Sq.mm wires 300 RM


2 2Nos. x 4 sqmm + 1 No. x 2.5 Sq.mm wires 200 RM
3 4Nos. x 4 sqmm + 2 Nos. x 2.5 Sq.mm wires R.O RM

b Providing and fixing following rigid PVC conduits &


conduits accessories thickness not less than 2mm
i. 20mm dia. RO RM
ii. 25mm dia. 200 RM

K TELEPHONE NETWORK
Providing, installation of following for Telephone
network.
a Providing & installation following telephone junction
boxes with enclosure (as located)

i 100 Pair Crone Connector (TTB) 1 No.


ii. 50 Pair Crone Connector (TTB) RO Nos.
iii. 20 Pair Crone Connector (TTB) RO Nos.
iv. 10 Pair Crone Connector (TTB) 10 Nos.
b. Providing & laying following pairs telephone cable
from main TTB (100 Pair) to sub TTB (at ground & all
upper floor) in 25mm PVC conduit run vertical in LV
duct & from Sub TTB to Rooms

i. 50 Pair Telephone Cable RO RM


ii. 20 Pair Telephone Cable RO RM
iii 10 Pair Telephone Cable 100 RM
iv. 5 Pair Telephone Cable 500 RM
d Providing and fixing following rigid PVC conduits &
conduits accessories thickness not less than 2mm

i. 20mm dia. 100 RM


ii. 25mm dia. 100 RM

L T.V. SYSTEM
1 Providing & laying following side T.V. co-axial
cables in 20/25mm dia. rigid PVC conduit from main
spliter box to respective floor spliter boxes and from
spliter boxes to individual shops on all floors with
necessary pull boxes as required

i. R.G. - 11 ( U) Co-axial cables

RO RM
ii. R.G. - 6 ( U ) Co-axial cables

RO RM
1.2 Providing and fixing following spliter boxes on all
floors as shown in Layout Drawings

ii. 6 Way Spliter Boxes


RO Nos
ii. 4 Way Spliter Boxes
RO Nos
1.3 Providing and fixing following rigid PVC conduits &
conduits accessories thickness not less than 2mm

i. 20mm dia. RO RM
ii. 25mm dia. RO RM

M MISCELLANEOUS ITEMS
1 METER BOARD
1 Providing & fixing teak wood varnished wooden meter
board of 1" thick wooden flank / marine ply 25mm
thick shall be grouted on wall including earthing using
25 x 6mm G.I. Earth strips suitable for :

1 No.
i. 1 Nos. 3 Phase 4 Wire (unbalance Load) energy meter

ii 3 Nos. 32/60 Amp I.C. Cutouts with rewirable fuses


at 415 Volts rating
iii. 1 No. 40 Amp TPN MCB (9 KA)

iv 5 Nos. CT Meters

(As per meter room layout drawing and direction of


authority / supply company)

2 Providing installation, testing and commissioning


following switch fuse unit in enclosure (L&T/
Siemens Make) with cable end boxes

i. 400 Amp RO Nos


ii. 250 Amp RO Nos

3 Providing & fixing following rating copper busbars in


14/16 gauge CRCA sheet steel enclosure duly painted
& coutouts for wires entry.

i. 400 Amp TPN Copper 10 RM


ii. 250 Amp TPN Copper RO RM

4 Installation of following equipments in meter room


i. 40 Amp. I.C. cutout rewirable RO No.
ii. 63 Amp. I.C. cutout rewirable RO No.
iii. Installation of following meters: RO No.
3 x 20 Amp energy meter RO No.
3 x 40 Amp energy meter RO No.
3 x 60 Amp energy meter RO No.
3 x 100 Amp energy meter RO No.
100/ 5 Amp C.T. operated meter. RO No.

5 Providing, installation, testing and commissioning


following power capacitor bank 415 Volts (L&T
make)
i 10 KVAR Capacitor including 32 Amp TP MCB in RO Nos.
enclosure

ii 20 KVAR Capacitor including 63 Amp TP MCB in RO Nos.


enclosure
6 Providing and fixing 300 x 100 M.S. Junction boxes RO Nos.
in all floor electrical duct for pulling main cable upto
each flat (as shown in Schematic Drawing)

7 Providing and laying following size RCC / PVC


i. 300mm dia. NP - 2 Class RO RM
ii. 150mm dia. NP - 2 Class RO RM
ii. 100mm dia. Heavy duty PVC pipe. RO RM

8 Temporary Electrification with all wires meters etc. Job

9 Providing Liasoning work for follow up with BEST Job


Authority & Elecrical inspector office for obtaining
necessary approval commissioning of meter room
alternate power supply & substation etc

10 Supply and installation of following


i. Rubber mat RO Each
ii. Danger board RO Each
iii. First Aid Box RO Each
iv. Fire bucket with sand RO Set
09
Installation Total
Rate Amount Rate Amount

Total
Total
Total
Total
Total

Total
Total
Total
Total
Total
Total

Total