Академический Документы
Профессиональный Документы
Культура Документы
DCmax
=
k
/2
- 7
Generally, short circuits occur when a system is loaded. Therefore, for accurate
calculation, pre-fault load current and the effect of passive load impedance as part of
the short circuit impedance should be considered. Therefore, equation - 6 should be
generalised to consider pre-fault load conditions. Hence
| | i I e
dc k
t T
k
a
=
2 " sin( )
( / )
| |
i i i
I t e
k ac dc
k k
t T
k
a
= +
= +
DC
k
k b k
I I
max
tan
sin( )
" / cos( )
=
1
-1
-0.5
0
0.5
1
0 1.5 3
Initiation angle [rad]
I
n
i
t
i
a
l
d
.
c
.
c
o
m
p
o
n
e
n
t
o
f
s
h
o
r
t
c
i
r
c
u
i
t
c
u
r
r
e
n
t
[
p
u
]
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 13
To illustrate this difference, Figure 8 shows the total asymmetrical current and d.c.
component of current for the two particular fault initiation angles viz. = zero and =
DCmax
. Although the d.c. component is higher for the later condition this does not result
in a higher peak in total current.
Figure 8 Comparison of peak currents.
It is evident that the evaluation of fault current magnitude at
DCmax
is not of concern for
fault interruption assessment. However when the maximum rms current is required for
earthing assessments it would be necessary, if the worst case is to be considered, to
calculate the current at
DCmax
.
2.3.2 Short Circuit Near to Generator
In the case of near to generator short circuits, the alternating component of the short
circuit current also decays with time since it is under the influence of near-by
generators or motors. This effect is recognised in the fault current calculation standards
and hence a broad treatment of this phenomenon based on semi-empirical tables and
graphs is provided for the three-phase balanced fault.
The near to generator type of fault is defined as: A short circuit to which at least one
synchronous machine contributes a prospective initial symmetrical short circuit current
which is more than twice the generators rated current, or a short circuit to which
synchronous or asynchronous motors contribute more than 5% of the initial
-1.0E+03
1.0E+03
3.0E+03
5.0E+03
0 0.005 0.01 0.015 0.02
Time [s]
C
u
r
r
e
n
t
[
A
]
Total Current with maximum peak DC component with maximum peak
Total Current with maximum transient DC component with maximum transient
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 14
symmetrical short circuit current without motors. However in IEC 909 this effect is
completely neglected for the single line-to-earth type of fault.
Illustrative waveforms of current for this condition can be seen in Figure 9 where the
a.c. component of the current is under the influence of the near-by generator and it has
a decaying component in relation to the generator time constants.
Figure 9 Time dependent short circuit current with a.c. and d.c. components.
The d.c. component of the current may be analysed as in the previous section of this
chapter. Additionally, equation - 5 which is given in section 2.3.1 remains valid. The
symmetrical decrement of the short circuit current, which is mainly due to the
synchronous machines of the system [14, 25] will be analysed in the following section.
2.3.2.1 Short Circuit on Generator Terminal Without Load
The transient behaviour of the short circuit current of a synchronous machine which is
subject to a sudden short circuit is a well known phenomenon and is dealt with in detail
by Kimbark [34] and Concordia [35]. In order to characterise the transient behaviour of
single line-to-earth fault current, the three-phase balanced fault will be first
investigated. The short circuit currents of a synchronous machine which is subject to a
sudden three-phase short circuit are presented in Figure 10.
Time in s.
C
u
r
r
e
n
t
i
n
A
.
Symmetrical DC Total
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 15
Figure 10 Short circuit current of synchronous machine (reproduced from 34).
Each phase current in Figure 10 has a symmetrical and asymmetrical or d.c.
component. The envelope of the symmetrical component is large at the first instant and
decays eventually to a sustained (steady state) value. If the sustained component of
the symmetrical current is subtracted, the remaining current can be found to have two
exponential components namely; sub-transient and transient components. The rms
symmetrical short circuit current can be formulated with a close approximation to
- 10
where I
ac
is the symmetrical rms fault current, I
k
is the symmetrical transient current,
I
k
is the symmetrical sub-transient current, T
d
and T
d
are the transient and sub-
transient d axis short circuit time constants of the machine, respectively. The time
constants of the machine will be discussed later in section 2.3.2.2.
Since there is no load on the machine terminal, the effective voltage of each stage,
namely the transient, sub-transient and steady state voltage, is equal to the phase to
neutral voltage of the machine. Additionally, since the resistance of the machine is
assumed to be constant throughout each stage, the decaying characteristics of short
( ) ( ) I I I e I I e I
ac k k
t T
k k
t T
k
d d
= + +
" ' '
/ " / '
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 16
circuit current may be explained by an increase of machine reactance. The associated
reactance in each stage is known as:
Synchronous reactance
Transient reactance
Sub-transient reactance.
Thus, the rms value of currents may be expressed in terms of machine reactances
I
k
= U
n
/X
d
I
k
= U
n
/X
d
I
k
= U
n
/X
d
- 11
where U
n
is the terminal voltage and equal to the internal voltage of the machine. X
d
,
X
d
and X
d
are the machine reactances of corresponding stages. Thus, the total
instantaneous short circuit current with symmetrical and asymmetrical components,
can be expressed by
- 12
Substituting equation - 11 into equation - 12 yields
- 13
The first term of the equation is the sub-transient component of the short circuit current,
the second term is the transient component, the third is the sustained component and
the last one is the d.c. component. Therefore, the waveform of the short circuit current
can be expressed completely only using the machine reactances. In equation - 13, the
initiation angle, is assumed to be zero.
2.3.2.2 Time Constants
It has been shown that the time constants of the machine are dependent on machine
impedances [36] and may be determined by plotting the short circuit current on
logarithmic graph [34].
( ) ( ) i I t I e
k ac k k
t
T
k
a
= +
|
.
| +
|
\
|
.
| +
( +
(
2
1 1 1 1 1 1
" ' '
sin
"
sin
" '
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 17
The typical value of the sub-transient short circuit time constant is approximately 0.04s.
On the other hand, the transient time constant is much longer than the sub-transient
one and its value is about 1.5s [14, 25]. Each constant can be calculated by
T
d
= T
d0
(X
d
/X
d
)
T
d
= T
d0
(X
d
/X
d
)
- 14
where T
d0
and T
d0
are sub-transient and transient open circuit time constants of the
synchronous machine. However, all the time constants are highly dependent upon
external impedances if the fault occurs remote from the machines terminal. The given
time constants are valid for the direct axis representation of the machine, while a
similar treatment may be used for the quadrature axis of the machine.
Concardia [35] calculates these time constants for the single line-to-earth type fault and
provides the following equations.
T
d
= T
d0
[(X
d
+X
2
+X
0
)/(X
d
+X
2
+X
0
)]
T
d
= T
d0
[(X
d
+X
2
+X
0
)/(X
d
+X
2
+X
0
)]
- 15
where X
2
and X
0
refer to negative and zero sequence reactances of the machine,
respectively.
2.3.2.3 Short Circuit with Load
While the generator is feeding a load at a given power factor with a constant terminal
voltage, the effective (internal) voltage of the generator differs from the voltage
available on the machine terminal due to the voltage drop across the machine
impedances. Therefore, the effective voltage of the generator needs to be related to
sub-transient, transient and steady state stage values of the machine reactances.
Internal voltages of the machine may be calculated for each stage by employing related
reactances behind the terminal voltage. The machine internal voltages corresponding
to each stage are called the sub-transient, transient and steady state voltages, and are
symbolised as E, E and E.
In Figure 11, the general vector diagram of the synchronous machine for the transient
stage is presented.
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 18
Figure 11 The general vector diagram of the synchronous machine for the transient
state.
Fortunately, since direct and quadradure axis reactances are equal to each other for
turbo (cylindrical rotor) generators, internal voltages can be derived easily by equating
E to E
i
, E to E
i
and lastly E to E
i
. Additionally, ignoring the machine resistance the
following equations can be formulated
E = U
n
+ jI
b
X
d
E = U
n
+ jI
b
X
d
E = U
n
+ jI
b
X
d
- 16
where I
b
is the load current and the related phasor diagram is given in Figure 12.
Figure 12 Approximate phasor diagram
Quatrature
axis
E
E
E
U
n
Quadrature axis
Direct axis
I
b
I
b
X
d
I
b
X
d
I
b
X
d
E
d
E
q
E
E
d
E
q
E
E
i
I
q
X
d
I
b
R
a
U
n
Direct axis I
q
X
q
I
d
X
d
I
q
X
q
(X
q
-X
d
)I
q
I
b
X
d
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 19
Nevertheless, it should be appreciated in the case of salient pole machines, much
more calculation effort is required for accurate calculation of the internal voltages, due
to the differing d and q axis reactances. However, it is claimed in some published
literature that the same procedure may be applied with sufficient accuracy for short
circuit calculation, especially in the initial period of fault [14, 25].
It is possible to determine the actual voltages for each stage by knowing the direct and
quadrature axis currents of the machine for the initial loading condition. The d and q
axis currents can be determined by using Parks [37] transformations. The same
phasor diagram can be used to represent the sub-transient state of the machine by
substituting transient reactance values by sub-transient reactances. Thus the internal
voltages of the machine can be determined by
E = U
n
+ I
b
R
a
+ I
b
X
d
+ jI
q
(X
q
X
d
)
E = U
n
+ I
b
R
a
+ I
b
X
d
+ jI
q
(X
q
X
d
)
- 17
where the last term of each equation becomes negligible for round rotor machines,
since the d and q axis reactances are equal each other in this case.
Therefore, the equivalent circuit of the machine can be arranged by considering
equation - 17 as shown in Figure 13;
Figure 13 Equivalent circuit of the transient state
The phasor diagram of the machine is also given in Figure 14 for the steady-state
condition.
U
n
+
E
-
R
a
X
d
- j(X
q
-X
d
)I
q
+
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 20
Figure 14 Steady-state phasor diagram of the machine
The internal voltage of the machine can be determined by;
E =E
q
= U
n
+ I
b
R
a
+ jI
b
X
q
+ jI
d
(X
d
X
q
)
- 18
Substituting the appropriate voltages into equation - 11 yields more accurate results
[21].
2.3.3 The Effect of the External Network Impedance
In general, there is always an impedance between the short circuit point and the
machine terminal. Since this impedance can be proportionally larger than the machine
impedances, it can not only have considerable influence upon the rms value of the
symmetrical short circuit current but also has a large effect on the time constants of the
short circuit. Therefore, equation - 11 may be modified as
- 19
where subscript s refers to system values, and R
a
represents the machine armature
resistance. The time constants of the short circuit current which are given in equations
- 5 and - 14 may be rewritten as
I
E
Z
E
R R j X X
I
E
Z
E
R R j X X
I
E
Z
E
R R j X X
k
k a s d s
k
k a s d s
k
k a s d s
"
"
"
"
( " )
'
'
'
'
( ' )
( )
= =
+ + +
= =
+ + +
= =
+ + +
E
I
q
X
q
E
i
U
n
Quadrature axis
Direct axis
I
b
I
b
R
a
I
b
X
q
I
d
X
d
(X
d
-X
q
)I
d
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 21
- 20
If the system impedance has a relatively high resistance, the time constants need to be
extended to consider the systems resistance. This effect is particularly important for
the transient time constant since it is significantly larger. Hence
- 21
The external resistance is the main element that determines whether there is significant
decrement or not.
2.4 Overview of Standards
The short circuit current calculation standards are intended to give simple but
conservative estimates of short circuit current magnitude. The standards employ a
quasi steady state calculation technique to enable particular short circuit values to be
determined related to short circuit duties. In general, the machine model adopted has
been kept very simple and referred to as the constant impedance behind the constant
voltage source. IEC 909 uses the sub-transient reactance of the machine in this
respect. IEC 909 and IEEE/ANSI approaches calculate similar values, however each
uses a particular terminology for each duty. The duties are presented in Table 2
Table 2 Comparison of short circuit current quantities and terminologies.
Initial Short circuit currents Breaking currents
Symmetrical
Peak
Asymmetrical Symmetrical
Steady-state short
circuit current
IEC 909
I
K
i
p
I
basym
I
bsym
I
k
First cycle duty Contact parting duty
Symmetrical Peak Asymmetrical Symmetrical
Short circuit current
for time delaying
relays
IEEE/ANSI
I
sc
i
p
I
asym
I
sym
I
k
The above duties coincide with the specific values of the short circuit current and can
be visualised on the wave shape of the short circuit current as presented in Figure 15.
T
X X
X X
T T
X X
X X
T T
L L
R R
d
d s
d s
d d
d s
d s
d a
s
G s
"
"
'
" '
'
' =
+
+
=
+
+
=
+
+
0 0
2
T
R X X X X
R X X
T
d
s d s d s
s d s
d
'
( ' )( )
( )
' =
+ + +
+ +
2
2 2 0
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 22
Figure 15 Short circuit current reproduced from [8].
The relevant details of each standard are described in the following sections.
2.4.1 IEC 909 Standard
IEC 909 classifies the short circuit with respect to its location as near-to-generator and
far from the generator or motor. The main objective of the standard is to establish a
general, practicable and concise procedure leading to conservative results with
sufficient accuracy. The short circuit current is treated as the sum of a decaying
unidirectional (d.c.) and a symmetrical component (a.c.). For near-to-generator types of
short circuit, the symmetrical component of the current is treated as a decaying current
while for far-from-generator faults it is considered constant. It should be noted that the
standard treats the single line-to-earth fault as a far-from-generator type without paying
any attention to the location of the fault. Therefore, no symmetrical decrement is
considered for this type of fault. IEC 909 in particular is interested in the following
current duties and describes calculation techniques for each of them.
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 23
2.4.1.1 Initial Symmetrical Short Circuit Current
The standard employs an approximate superposition method to calculate this current
as explained in section 2.2.3. A series of correction factors are employed to improve
the accuracy of the results while erring on the safe side. These factors are employed to
calculate the effective impedance of the power system components. The magnitude of
the factors depend upon the network configuration and fault location and include the
voltage factor which is given in Table 1,
generator correction factor, (K
G
),
transformer correction factors (K
T
),
power station units correction factors, (K
PS
).
Once the short circuit network is established by ignoring all non-rotating loads and
system shunts, the initial symmetrical short circuit current can be calculated using
equation - 3. The short circuit impedance in equation - 3 is calculated by considering
the above given correction factors for the specific elements. For the other elements of
the network such as; overhead lines, cables, external network infeed, the standard also
provides appropriate formulae and techniques. If the fault is considered as far-from-
generator, rotating machine impedances are ignored.
For unbalanced faults, the standard provides an appropriate equation to calculate the
short circuit current by considering the connection of the sequence networks. The
single line-to-earth type of fault is calculated using equation - 3.
2.4.1.2 Peak Short Circuit Current
The peak short circuit current is shown in Figure 15 and defined by the standard as
The maximum possible instantaneous value of the prospective (available) short circuit
current. The standard also notes that The magnitude of the peak short circuit current
varies in accordance with the moment at which the short circuit occurs. Consequently
the standard calculates the greatest possible short circuit current by considering the
worst case scenario.
In the case of calculation of the peak short circuit current, it is necessary to distinguish
between the cases of a radial or meshed network to calculate this current. In the case
of a radial network, the total peak current is the sum of the contributions from the
converging path to the faulted bus. The summation of each converging branch is
advised to be done by algebraic sum. To employ an algebraic sum instead of a vector
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 24
one will result in a conservative result. However this greatly simplifies the calculation
process. Each branchs peak current is calculated using the equation.
i
pi
= K
i
2 I
ki
- 22
where coefficient K
i
depends on the X/R ratio of the related branch. It is also possible
to evaluate this value by empirical formulae. In the case of a meshed network the
standard describes three different methods (viz. Method A, B and C) to compute the
equivalent X/R ratio for the system. The same methods can be used for near-to
generator or far-from-generator types of faults. For unbalanced faults, the peak short
circuit current is calculated using the same techniques.
2.4.1.3 Symmetrical and Asymmetrical Breaking Current
The standard adopts different approaches for the treatment of near-to-generator and
far-from-generator short circuits to compute this current. In the case of the far-from-
generator fault, I
b
is assumed to be the initial symmetrical current without any
decrement. For the near-to-generator case, the standard distinguishes between the
types of network as meshed or radial in a similar way to the treatment of peak short
circuit current. In a radial network, the total symmetrical breaking current is expressed
as the sum of the contributing branches currents. Each branch current is calculated by
multiplying the initial symmetrical current of the branch by a multiplication factor,
namely . The factor , is given by a series of empirical formulae which depend on a
number of factors including
time delay,
the partial symmetrical rms short circuit current at the machine
terminal,
the highest symmetrical rms current of the machine with locked
rotor fed with rated voltage at rated frequency.
In the case of a meshed network, with a conservative approximation, the factor is
assumed equal to unity.
Asymmetrical breaking current is not separately considered in the main body of the
standard. However, in the appendix of the standard, this current is calculated with the
given formulae, which enables the asymmetrical current to be determined for a given
time interval.
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 25
- 23
In the case of a radial network i
dc
is computed by the summation of branch currents.
The X/R ratio of related branches is calculated by the methods used for the
determination of peak short circuit current. In a meshed network, the total X/R ratio is
computed by either method B or C.
2.4.1.4 Steady-State Short Circuit Current
For the computation of the steady-state short circuit current in the case of the near-to-
generator fault, the standard supplies several graphs for each type of machine. These
graphs provide a factor to calculate the current injected from generators. The
contribution from motors is accepted to fade away rapidly and hence neglected. The
factor depends on; the generator type (viz. turbo or salient pole machine), steady
state reactance of the generator and the ratio between the partial short circuit current
on the generator terminal and the highest symmetrical rms current of the generator with
locked rotor fed with rated voltage at rated frequency.
In the case of a meshed network, the standard re-structures the network diagram and
re-calculates the symmetrical short circuit current without considering motors. This new
calculated value is assumed equal to the steady-state current. For far-from-generator
type of faults, no decrement is considered and therefore this current is assumed equal
to the initial symmetrical one. Since no decrement is foreseen for the single line-to-
earth types of faults in the standard, no calculation technique is provided.
2.4.2 IEEE/ANSI Approach
The main scope of this standard is to allow the installation of suitable sizes of medium
and high voltage circuit breakers for systems at 1000kV and above [1]. The standard
specifies a simplified calculation of short circuit current based on the method described
in section 2.2.3. According to this method the standard reduces the network to an
equivalent voltage source and reactance. The voltage source is the typical operating
voltage of the system. The nominal voltage of the system could also be employed for
this purpose. In general, only a reactance network is considered to determine the first
cycle current. However, it is also recommended that two different reactance and
I I i
i I e
basym b dc
dc k
ftR X
= +
=
2 2
2
2
" ( / )
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 26
resistance networks should be used to evaluate the total short circuit impedance. The
networks are built by considering all rotating loads without taking into account whether
they are remote from or near to the fault location. However, depending upon duty types
a series of impedance multiplication factors are introduced. Particular guidelines are
provided for the determination of single line-to-earth fault current levels.
2.4.2.1 First Cycle Duty
To compute this duty, two separate first cycle networks, namely resistance and
reactance networks, are built. These networks consist of branch impedances and
corrected rotating machine sub-transient impedances. All passive loads are neglected.
Correction factors for rotating machines are provided in the standard. These factors
depend upon rated power, number of poles and type of the machine. All machines are
modelled in the first cycle network whether the fault is remote or not. The first cycle
duty can be then evaluated as E/X. This is the symmetrical rms value of the current in
the first cycle. The asymmetrical rms current can be calculated by multiplying this
current by the factor 1.6. In addition, peak current is given as 2.7 times the first cycle
symmetrical rms current. The factors 1.6 and 2.7 are not empirically determined values
as they may appear. The calculation procedure for arriving at these values has been
described in references [33, 38] in detail. The multiplication factors for the asymmetrical
first cycle current S
rms
and for the peak current S
peak
can be derived by using the given
formulae below
- 24
Where, f is the frequency of the system and t is the half cycle time. The above factors
of 1.6 and 2.7 correspond to a ratio of X/R 25. However, the standard pays particular
attention to calculating the contact parting currents by considering different X/R ratios.
These factors are also called capability factors and it has been recognised that they
predict a pessimistic total fault current value [38].
For the single line-to-earth fault, the standard provides multiplication factors to
calculate the asymmetrical and peak values from the symmetrical value.
S e
S e
rms
ft
R
X
peak
ft
R
X
= +
= +
1 2
2 1
4
2
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 27
2.4.2.2 Contact Parting Duty
To calculate this current value, the standard rebuilds the resistance and reactance
network by considering different machine reactances and related multiplication factors.
A table which lists machine reactances and multiplication factors according to
IEEE/ANSI C37 [1] is provided below.
Table 3 IEEE/ANSI machine reactance and multipliers
First cycle network Contact parting
Machine Type
Factor Reactance Factor Reactance
Turbo alternators 1.00 X
d
1.00 X
d
Hydro with dampers 1.00 X
d
1.00 X
d
Hydro no dampers 0.75 X
d
0.75 X
d
G
e
n
e
r
a
t
o
r
s
Condenser 1.00 X
d
1.00 X
d
Synchronous Motor 1.00 X
d
1.50 X
d
Larger than 1000 HP
1800 rpm or less
1.00 X
d
1.50 X
d
Above 250 HP at
3600 rpm
1.00 X
d
1.50 X
d
All others 50 HP and
above
1.20 X
d
3.00 X
d
M
o
t
o
r
s
I
n
d
u
c
t
i
o
n
m
o
t
o
r
s
Smaller than 50 HP 1.67 X
d
Neglect -
The standard also provides several curves to determine the multiplication factor for
each time interval, (viz. Two, three, five and eight cycles.) Using these factors the
asymmetrical breaking current can be calculated. For remote faults this current could
also be calculated using equation- 24. In the case of a local fault empirical look up
tables are provided in the appendix of the standard. However it is claimed that a curve
fit equation is also available for this purpose [39, 40]. Similar curves are also provided
for the single line-to-earth fault.
2.4.2.3 Short Circuit Current for Time Delaying Relays
In order to calculate the sustained value of short circuit current a different network
should be built by considering only generators and passive elements of the system. All
loads including rotating ones are neglected. The generators are modelled by their
transient reactance or by a larger reactance that takes into account a.c. decrement.
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 28
The d.c. component of the current is supposed to be zero. Symmetrical decrement on
the single line-to-earth fault is also treated in the standard.
2.4.3 Comparison of the Standards
It has been shown in many publications [11, 16, 17, 18, 19, 41] that IEC 909 provides
more conservative results than IEEE/ANSI. This is mainly due to the higher pre-fault
voltages recommended by IEC 909. In addition, smaller machine reactances (mainly
sub-transient) are employed in IEC 909 for all types of duties. IEC 909 is probably
more complicated to use than the IEEE/ANSI, particularly, in the treatment of meshed
networks. On the other hand the IEC standard treats the effects of machine excitation
systems for the sustained value of short circuit current while IEEE/ANSI does not.
However, in terms of data requirements, both standards are similar.
For comparison, both standards have been applied to an example network which is
detailed in the IEC 909 appendices. It should be noted that only balanced three phase
faults are considered. The circuit is a high voltage system fed by an infinite bus which
is modelled by a constant impedance behind a voltage source and hence no
decrement of a.c. component of the short circuit current is simulated. The network also
includes two induction machines. Resulting current values from each standard are
reproduced in Table 4.
Table 4 Comparison of standards for three-phase fault current magnitudes [8, 19].
IEC 909 current in
kA
IEEE/ANSI current in
kA
Percentile
difference in %
Initial symmetrical 18.82 16.74 11.10
Peak 47.18 42.50 9.92
Breaking
symmetrical
16.33 15.60 4.47
Breaking
asymmetrical
17.51 15.69 10.39
Steady-state 14.32 13.32 6.98
It is clear from the above figures, the IEC 909 calculation over-estimates all current
values. Differences in percentile rank suggest that differences between the two
standards reduce in the later period of the fault.
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 29
2.4.4 Engineering Recommendation G.74
The realisation of conservative modelling in IEC 909 has prompted the employment of
more precise calculation practices. For example, ER G.74 [30, 42] Procedure to Meet
the Requirements of IEC 909 for the Calculation of Short Circuit Currents in Three
Phase ac Systems sets out a Good Industry Practice for a computer-based method of
calculating short-circuit currents, which can be used as an alternative to the methods
presented in IEC 909.
This engineering recommendation does not provide or recommend any particular
software for short circuit calculation but describes a computer-based technique and
details the models of the power system components. The main principle of the
recommendation is the consideration of pre-fault network conditions and inclusion of all
loads including passive ones and rotating plants. ER G.74 pays particular attention to
induction machine contributions in the case of three phase faults. However, the scope
of the document is limited to circuit breaker sizing in three phase ac power systems
having a nominal voltage range 380V to 400kV.
2.5 Conclusions
The factors which give rise to and affect the transient nature of fault current have been
identified in terms of a.c. and d.c. components. A simple parametric study has shown
how a particular fault initiation angle results in the maximum d.c. component of fault
current but this does not coincide with the maximum peak total asymmetrical current. It
has been shown that the IEC and IEEE/ANSI standards characterise a.c. and d.c.
transients in an approximate way. Both standards and particularly IEC 909 appear to
over-estimate short circuit current magnitudes.
In view of this apparent overestimation through the use of simple models and
simplifying assumptions, and the fact that IEC 909 does not correctly deal with single
line-to-earth faults, a more detailed treatment of the fault condition is required which is
in line with the consensus of the reviewed literature. Accordingly, chapter 3 investigates
different a.c. machine models in an attempt to identify the appropriate level of
complexity required for short circuit current evaluation for earthing design applications.
2.6 References
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 30
1 IEEE/ANSI C37: IEEE standard Rating Structure for AC High-Voltage Circuit
Breakers Rated on a Symmetrical Current Basis, (The IEEE Inc. November, 1985)
1986 edn.
2 AIEE COMMITTEE REPORT: Calculated symmetrical and asymmetrical short-circuit
current decrement rates on typical power systems, AIEE Trans. on PAS, June 1956,
part 3, vol. 75, pp. 274-285
3 AIEE COMMITTEE REPORT: Calculation of electric power system short-circuits
during the first few cycles, AIEE Trans. on PAS, April 1956, part 3, vol. 75, pp. 120-
127
4 LANTZ, M.: Power System Fault Current Analysis Including Study of Transient
Offset, AIEE Trans. on PAS, October 1954, vol. 73, part 3, pp. 1073-1078
5 IEEE Std. 242-1975: IEEE Recommended Practice for Protection and Co-ordination
of Industrial and Commercial Power Systems, Buff Book, (IEEE Press, New York,
1980)
6 IEEE Std. 399-1980: IEEE Recommended Practise for Power System Analysis,
Brown Book, (IEEE Press, New York 1980)
7 IEEE/ANSI, C37.12-1981: Guide to Specifications for AC High-Voltage Circuit
Breakers Rated on a Symmetrical Current Basis and a Total Current Basis,
Approved on August 1981, (The IEEE Inc. November, 1985)
8 IEC 909: Short Circuit Calculation in Three Phase ac Systems, IEC, International
Electrotechnical Commission publication, 1988, First edn.
9 DUNKI-JACOBS, J.R., LAM, B.P., STRATFORD, R.P.: A comparison of ANSI-based
and dynamically rigorous short-circuit current calculation procedures, IEEE Trans. on
Industry Applications, November/December 1988, Vol. 24, No. 6, pp. 1180-1194
10 ROENNSPIESS, O.E., EFTHYMIADIS, A.E.: A comparison of static and dynamic
short-circuit analysis procedures, IEEE Trans. on Industry Applications, May/June
1990, Vol. 26, No. 3, pp. 463-475
11 BERIZZI, A., MASSUCCO, S., SILVESTRI, A., ZANINELLI, D.: Short-circuit current
calculation: A comparison between methods of IEC and ANSI standards using
dynamic simulation as reference, IEEE Trans. on Industry applications, July/August
1994, Vol. 30, No. 4, pp. 1099-1106
12 PROFESSIONAL GROUP P9: IEE Colloquium on Fault level assessment-guessing
with greater precision?, The IEE, London, 30 January 1996, Digest No: 1996/016
13 ARRIILAGA, J., ARNOLD, C.P.: Computer Analysis of Power Systems (J. Willey
and Sons, London, 1990)
14 ANDERSON, P.M.: Analysis of Faulted Power Systems (Iowa State University
Press Ames, Iowa, 1973)
15 WESTINGHOUSE ELECTRIC CORPORATION: Electrical Transmission and
distribution Reference Book, (East Pittsburgh, PA., 1950) 4
th
edn.
16 CASTELLI-DEZZA, F., SILVESTRI, A., ZANINELLI, D.: The IEC 909 standard and
dynamic simulation of short-circuit currents, ETEP (European Transactions on
Electrical Power), May/June 1994, Vol. 4, No. 3, pp. 213-221
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 31
17 BRIDGER, B.: All amperes are not created equal: A comparison of current of high
voltage circuit breakers rated according to ANSI and IEC standards, IEEE Trans. on
Industry Applications, January/February 1993,Vol. 29, No. 1, pp. 195-201
18 KNIGHT, G., SIELING, H.: Comparison of ANSI and IEC 909 short-circuit current
calculation procedures, IEEE Trans. on Industry Applications, May/June 1993, Vol.
29, No. 3, pp. 625-630
19 BERIZZI, A., MASSUCCO, S., SILVESTRI, A., ZANINELLI, D.: ANSI/IEEE and IEC
standards for short-circuit current evaluation: methodologies, computed values and
results, 6
th
International symposium on short-circuit currents in power systems,
September 1994, Liege Belgium, pp. 1.1.1-1.1.8
20 MORCHED, A.S., TENCH, G.A., KUNDUR, P.: Accurate calculation of
asymmetrical fault currents in complex power systems, IEEE Trans. on PAS, August
1981, Vol. 100, No. 8, pp. 3875-3790
21 GIUSEPPE, P.: A new approach to calculate the decaying AC contributions to
short-circuit: The characteristics current method, IEEE Trans. on Industry
Applications, January/February 1995, Vol. 31, No. 1, pp. 214-221
22 HALPIN, S.M., GROSS, C.A., GRIGSBY, L.L.: An improved method of including
detailed synchronous machine representations in large power system models for
fault analysis, IEEE Trans. on Energy conversion, December 1993, Vol. 8, No. 4, pp.
719-725
23 HALPIN, S.M., GRIGSBY, L.L., GROSS, C.A., NELMS, R. M.: An improved fault
analysis algorithm for unbalanced multi-phase power distribution systems, IEEE
Trans. on PWD., July 1994, Vol. 9, No. 3, pp. 1332-1338
24 CLARKE, E.: Circuit Analysis of A-C Power Systems, Volume I and II, (J. Willey
and Sons, London, 1950)
25 ROEPER, R.: Short-circuit Currents in Three-phase Systems, (J. Willey and Sons,
the Bath press. Avon, 1985) 2
nd
edn.
26 STAGG, W.G., EL-ABIAD, A.: Computer Methods in Power System Analysis,
(McGraw-Hill Book Company, 1968)
27 FORTESCUE, C. L.: Method of symmetrical co-ordinates applied to the solution of
polyphase networks, Trans. AIEE ,1918, Vol. 37, pp. 1027-1140
28 OEDING, D., SCHEIFELE, J.: Maximum short-circuit current at pessimal load flow,
18
th
Universities Power Engineering Conference, April 1983, University of Surrey
Guildford UK, pp. 545-550
29 IEC 909-1: Short Circuit Calculation in Three Phase ac Systems Part 1. Factors for
the calculation of short-circuit currents in three-phase a.c. systems according to IEC
909, International Electrotechnical Commission publication, 1991 First edn.
30 EA ER-G74, (Electricity Association, Engineering Recommendation G74) 1992:
Procedure to meet the requirements of IEC 909 for the calculation of short circuit
currents in three phase ac systems, Electricity Association Services Limited, London
1992
31 ROBERTSON, D. ed.: Power System Protection Manual, (Oriel Press Ltd.,
Northumberland UK, 1982) pp. 47-65
Shor t Ci r cui t Cur r ent Cal cul at i on Theor y and Techni ques
Power Syst em Tr ansi ent s and Ear t hi ng Syst ems 2- 32
32 KAI, T, TAKEUCHI, N., FUNABASHI, T., SASAKI, H.: A simplified Fault Current
Analysis Method Considering Transient of Synchronous Machine, IEEE Trans. on
Energy Conversion, Sep 1997, Vol. 12, No. 3, pp.225-231
33 HERMANN, W.R., JUAN, C.G.: Relationship of X/R, I
p
, and I
rms
to asymmetry in
resistance/reactance circuits, IEEE Trans. on Industry Applications, March/April
1985, Vol. IA-21, No.2, pp. 481-492
34 KIMBARK, W.E.: Power System Stability, Volume III Synchronous machines, (John
Willey & Sons, INC. New York, 1956)
35 CONCORDIA, C.: Synchronous Machines, Theory and Performance, (J. Willey and
Sons Inc. New York, Chapman & Hall Ltd. London, 1951)
36 ADKINS, B., HARLEY, R.G.: The General Theory of Alternating Current Machines:
Application to Practical Problems (Chapman and Hall, London, 1975)
37 PRENTICE, B.R.: Fundamental concepts of synchronous machine reactances,
AIEE. Trans. 1937, vol. 56 supplement, pp. 1-21
38 CRAIG, N.H.: Understanding Asymmetry, IEEE Trans. on Industry Applications,
July/August 1985, Vol. IA-21, No. 4, pp. 842-848
39 CONRAD, R. ST. PIERRE: Sample System for Three-Phase Short Circuit
Calculations, IEEE Trans. on Industry Applications, March/April 1990, Vol. 26, No. 2,
pp. 204-211
40 SIMPSON, R.H.: Multivoltage Short-Circuit Duty Calculation for Industrial Power
Systems, IEEE Trans. on Industry Applications, March/April 1986, Vol. IA-22, No. 2,
pp. 365-381
41 RODALAKIS, A.: A Comparison of North American (ANSI) and European (IEC)
Fault Calculation Guidelines, IEEE Trans. on Industry Applications, May/June 1993,
Vol. 29, No. 3, pp. 515-521
42 EA ETR-120, (Electricity Association, Engineering Technical Report No. 120) 1995:
Application Guide To Engineering Recommendation G74 for calculation of fault
currents in three phase ac power systems, Electricity Association Services Limited,
London 1995