What is Earthing
NOVEMBER 27, 2011 59 COMMENTS
(HTTP://ELECTRICALNOTES.WORDPRESS.COM/2011/11/27/WHAT-IS-EARTHING
/#COMMENTS)
Introduction:
The main reason for doing earthing in electrical network is for the safety. When all metallic
parts in electrical equipments are grounded then if the insulation inside the equipments
fails there are no dangerous voltages present in the equipment case. If the live wire touches
the grounded case then the circuit is effectively shorted and fuse will immediately blow.
When the fuse is blown then the dangerous voltages are away.
Purpose of Earthing:
(1) Safety for Human life/ Building/Equipments:
To save human life from danger of electrical shock or death by blowing a fuse i.e. To
provide an alternative path for the fault current to ow so that it will not endanger the
user
To protect buildings, machinery & appliances under fault conditions.
To ensure that all exposed conductive parts do not reach a dangerous potential.
To provide safe path to dissipate lightning and short circuit currents.
To provide stable platform for operation of sensitive electronic equipments i.e. To
maintain the voltage at any part of an electrical system at a known value so as to
prevent over current or excessive voltage on the appliances or equipment .
About these ads (http://en.wordpress.com/about-these-ads/)
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
1 of 22 01/08/14 2:05 AM
(2) Over voltage protection:
Lightning, line surges or unintentional contact with higher voltage lines can cause
dangerously high voltages to the electrical distribution system. Earthing provides an
alternative path around the electrical system to minimize damages in the System.
(3) Voltage stabilization:
There are many sources of electricity. Every transformer can be considered a separate
source. If there were not a common reference point for all these voltage sources it would
be extremely difcult to calculate their relationships to each other. The earth is the most
omnipresent conductive surface, and so it was adopted in the very beginnings of
electrical distribution systems as a nearly universal standard for all electric systems.
Conventional methods of earthing:
(1) Plate type Earthing:
Generally for plate type earthing normal Practice is to use
Cast iron plate of size 600 mm x600 mm x12 mm. OR
Galvanized iron plate of size 600 mm x600 mm x6 mm. OR
Copper plate of size 600 mm * 600 mm * 3.15 mm
Plate burred at the depth of 8 feet in the vertical position and GI strip of size 50 mmx6
mm bolted with the plate is brought up to the ground level.
These types of earth pit are generally lled with alternate layer of charcoal & salt up to 4
feet from the bottom of the pit.
(2) Pipe type Earthing:
For Pipe type earthing normal practice is to use
GI pipe [C-class] of 75 mm diameter, 10 feet long welded with 75 mm diameter GI ange
having 6 numbers of holes for the connection of earth wires and inserted in ground by
auger method.
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
2 of 22 01/08/14 2:05 AM
These types of earth pit are generally lled with alternate layer of charcoal & salt or earth
reactivation compound.
Method for Construction of Earthing Pit (Indian
Electricity Board):
Excavation on earth for a normal earth Pit size is 1.5M X 1.5M X 3.0 M.
Use 500 mm X 500 mm X 10 mm GI Plate or Bigger Size for more Contact of Earth and
reduce Earth Resistance.
Make a mixture of Wood Coal Powder Salt & Sand all in equal part
Wood Coal Powder use as good conductor of electricity, anti corrosive, rust proves for
GI Plate for long life.
The purpose of coal and salt is to keep wet the soil permanently.
The salt percolates and coal absorbs water keeping the soil wet.
Care should always be taken by watering the earth pits in summer so that the pit soil
will be wet.
Coal is made of carbon which is good conductor minimizing the earth resistant.
Salt use as electrolyte to form conductivity between GI Plate Coal and Earth with
humidity.
Sand has used to form porosity to cycle water & humidity around the mixture.
Put GI Plate (EARTH PLATE) of size 500 mm X 500 mm X 10 mm in the mid of mixture.
Use Double GI Strip size 30 mm X 10 mm to connect GI Plate to System Earthling.
It will be better to use GI Pipe of size 2.5! diameter with a Flange on the top of GI Pipe
to cover GI Strip from EARTH PLATE to Top Flange.
Cover Top of GI pipe with a T joint to avoid jamming of pipe with dust & mud and also
use water time to time through this pipe to bottom of earth plate.
Maintain less than one Ohm Resistance from EARTH PIT conductor to a distance of 15
Meters around the EARTH PIT with another conductor dip on the Earth at least 500 mm
deep.
Check Voltage between Earth Pit conductors to Neutral of Mains Supply 220V AC 50 Hz
it should be less than 2.0 Volts.
Factors affecting on Earth resistivity:
(1) Soil Resistivity:
It is the resistance of soil to the passage of electric current. The earth resistance value
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
3 of 22 01/08/14 2:05 AM
(ohmic value) of an earth pit depends on soil resistivity. It is the resistance of the soil to
the passage of electric current.
It varies from soil to soil. It depends on the physical composition of the soil, moisture,
dissolved salts, grain size and distribution, seasonal variation, current magnitude etc.
In depends on the composition of soil, Moisture content, Dissolved salts, grain size and
its distribution, seasonal variation, current magnitude.
(2) Soil Condition:
Different soil conditions give different soil resistivity. Most of the soils are very poor
conductors of electricity when they are completely dry. Soil resistivity is measured in
ohm-meters or ohm-cm.
Soil plays a signicant role in determining the performance of Electrode.
Soil with low resistivity is highly corrosive. If soil is dry then soil resistivity value will be
very high.
If soil resistivity is high, earth resistance of electrode will also be high.
(3) Moisture:
Moisture has a great inuence on resistivity value of soil. The resistivity of a soil can be
determined by the quantity of water held by the soil and resistivity of the water itself.
Conduction of electricity in soil is through water.
The resistance drops quickly to a more or less steady minimum value of about 15%
moisture. And further increase of moisture level in soil will have little effect on soil
resistivity. In many locations water table goes down in dry weather conditions.
Therefore, it is essential to pour water in and around the earth pit to maintain moisture
in dry weather conditions. Moisture signicantly inuences soil resistivity
(4) Dissolved salts:
Pure water is poor conductor of electricity.
Resistivity of soil depends on resistivity of water which in turn depends on the amount
and nature of salts dissolved in it.
Small quantity of salts in water reduces soil resistivity by 80%. common salt is most
effective in improving conductivity of soil. But it corrodes metal and hence discouraged.
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
4 of 22 01/08/14 2:05 AM
(5) Climate Condition:
Increase or decrease of moisture content determines the increase or decrease of soil
resistivity.
Thus in dry whether resistivity will be very high and in monsoon months the resistivity
will be low.
(6) Physical Composition:
Different soil composition gives different average resistivity. Based on the type of soil,
the resistivity of clay soil may be in the range of 4 150 ohm-meter, whereas for rocky or
gravel soils, the same may be well above 1000 ohm-meter.
(7) Location of Earth Pit :
The location also contributes to resistivity to a great extent. In a sloping landscape, or in
a land with made up of soil, or areas which are hilly, rocky or sandy, water runs off and
in dry weather conditions water table goes down very fast. In such situation Back ll
Compound will not be able to attract moisture, as the soil around the pit would be dry.
The earth pits located in such areas must be watered at frequent intervals, particularly
during dry weather conditions.
Though back ll compound retains moisture under normal conditions, it gives off
moisture during dry weather to the dry soil around the electrode, and in the process
loses moisture over a period of time. Therefore, choose a site that is naturally not well
drained.
(8) Effect of grain size and its distribution:
Grain size, its distribution and closeness of packing are also contributory factors, since
they control the manner in which the moisture is held in the soil.
Effect of seasonal variation on soil resistivity: Increase or decrease of moisture content in
soil determines decrease or increase of soil resistivity. Thus in dry weather resistivity
will be very high and during rainy season the resistivity will be low.
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
5 of 22 01/08/14 2:05 AM
(9) Effect of current magnitude:
Soil resistivity in the vicinity of ground electrode may be affected by current owing
from the electrode into the surrounding soil.
The thermal characteristics and the moisture content of the soil will determine if a
current of a given magnitude and duration will cause signicant drying and thus
increase the effect of soil resistivity
(10) Area Available:
Single electrode rod or strip or plate will not achieve the desired resistance alone.
If a number of electrodes could be installed and interconnected the desired resistance
could be achieved. The distance between the electrodes must be equal to the driven
depth to avoid overlapping of area of inuence. Each electrode, therefore, must be
outside the resistance area of the other.
(11) Obstructions:
The soil may look good on the surface but there may be obstructions below a few feet
like virgin rock. In that event resistivity will be affected. Obstructions like concrete
structure near about the pits will affect resistivity. If the earth pits are close by, the
resistance value will be high.
(12) Current Magnitude:
A current of signicant magnitude and duration will cause signicant drying condition
in soil and thus increase the soil resistivity.
Measurement of Earth Resistance by use of
Earth Tester:
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
6 of 22 01/08/14 2:05 AM
For measuring soil resistivity Earth Tester is used. It is also called the MEGGER.
It has a voltage source, a meter to measure Resistance in ohms, switches to change
instrument range, Wires to connect terminal to Earth Electrode and Spikes.
It is measured by using Four Terminal Earth Tester Instrument. The terminals are
connected by wires as in illustration.
P=Potential Spike and C=Current Spike. The distance between the spikes may be 1M,
2M, 5M, 10M, 35M, and 50M.
All spikes are equidistant and in straight line to maintain electrical continuity. Take
measurement in different directions.
Soil resistivity =2!LR.
R= Value of Earth resistance in ohm.
Distance between the spikes in cm.
" = 3.14
P = Earth resistivity ohm-cm.
Earth resistance value is directly proportional to Soil resistivity value
Measurement of Earth Resistance (Three point method):
In this method earth tester terminal C1 & P1 are shorted to each other and connected to
the earth electrode (pipe) under test.
Terminals P2 & C2 are connected to the two separate spikes driven in earth. These two
spikes are kept in same line at the distance of 25 meters and 50 meters due to which
there will not be mutual interference in the eld of individual spikes.
If we rotate generator handle with specic speed we get directly earth resistance on
scale.
Spike length in the earth should not be more than 1/20th distance between two spikes.
Resistance must be veried by increasing or decreasing the distance between the tester
electrode and the spikes by 5 meter. Normally, the length of wires should be 10 and 15
Meter or in proportion of 62% of D.
Suppose, the distance of Current Spike from Earth Electrode D = 60 ft, Then, distance of
Potential Spike would be 62 % of D = 0.62D i.e. 0.62 x 60 ft = 37 ft.
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
7 of 22 01/08/14 2:05 AM
Four Point Method:
In this method 4 spikes are driven in earth in same line at the equal distance. Outer two
spikes are connected to C1 & C2 terminals of earth tester. Similarly inner two spikes are
connected to P1 & P2 terminals. Now if we rotate generator handle with specic speed,
we get earth resistance value of that place.
In this method error due to polarization effect is eliminated and earth tester can be
operated directly on A.C.
GI Earthing Vs Copper Earthing:
As per IS 3043, the resistance of Plate electrode to earth (R) = (r/A) X under root(P/A).
Where r = Resistivity of Soil Ohm-meter.
A=Area of Earthing Plate m3.
The resistance of Pipe electrode to earth (R) = (100r/2!L) X loge (4L/d).
Where L= Length of Pipe/Rod in cm
d=Diameter of Pipe/Rod in cm.
The resistivity of the soil and the physical dimensions of the electrode play important
role of resistance of Rod with earth.
The material resistivity is not considered important role in earth resistivity.
Any material of given dimensions would offer the same resistance to earth. Except the
sizing and number of the earthing conductor or the protective conductor.
Pipe Earthing Vs Plate Earthing:
Suppose Copper Plate having of size 1.2m x 1.2m x 3.15mm thick. soil resistivity of 100
ohm-m,
The resistance of Plate electrode to earth (R)=( r/A)X under root("/A) =
(100/2.88)X(3.14/2.88)=36.27 ohm
Now, consider a GI Pipe Electrode of 50 mm Diameter and 3 m Long. soil resistivity of
100 Ohm-m,
The resistance of Pipe electrode to earth (R) = (100r/2"L) X loge (4L/d) =
(100X100/2X3.14X300) X loge (4X300/5) =29.09 Ohm.
From the above calculation the GI Pipe electrode offers a much lesser resistance than
even a copper plate electrode.
As per IS 3043 Pipe, rod or strip has a much lower resistance than a plate of equal
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
8 of 22 01/08/14 2:05 AM
surface area.
Length of Pipe Electrode and Earthing Pit:
The resistance to earth of a pipe or plate electrode reduces rapidly within the rst few
feet from ground (mostly 2 to 3 meter) but after that soil resistivity is mostly uniform.
After about 4 meter depth, there is no appreciable change in resistance to earth of the
electrode. Except a number of rods in parallel are to be preferred to a single long rod.
Amount of Salt and Charcoal (more than 8Kg) :
To reduce soil resistivity, it is necessary to dissolve in the moisture particle in the Soil.
Some substance like Salt/Charcoal is highly conductive in water solution but the
additive substance would reduce the resistivity of the soil, only when it is dissolved in
the moisture in the soil after that additional quantity does not serve the Purpose.
5% moisture in Salt reduces earth resistivity rapidly and further increase in salt content
will give a very little decrease in soil resistivity.
The salt content is expressed in percent by weight of the moisture content in the soil.
Considering 1M3 of Soil, the moisture content at 10 percent will be about 144 kg. (10
percent of 1440 kg). The salt content shall be 5% of this (i.e.) 5% of 144kg, that is, about
7.2kg.
Amount of Water Purring:
Moisture content is one of the controlling factors of earth resistivity.
Above 20 % of moisture content, the resistivity is very little affected. But below 20% the
resistivity increases rapidly with the decrease in moisture content.
If the moisture content is already above 20% there is no point in adding quantity of
water into the earth pit, except perhaps wasting an important and scarce national
resource like water.
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
9 of 22 01/08/14 2:05 AM
Length Vs Diameter of Earth Electrode:
Apart from considerations of mechanical strength, there is little advantage to be gained
from increasing the earth electrode diameter with the object in mind of increasing
surface area in contact with the soil.
The usual practice is to select a diameter of earth electrode, which will have enough
strength to enable it to be driven into the particular soil conditions without bending or
splitting. Large diameter electrode may be more difcult to drive than smaller diameter
electrode.
The depth to which an earth electrode is driven has much more inuence on its electrical
resistance characteristics than has its diameter.
Maximum allowable Earth resistance:
Major power station= 0.5 Ohm.
Major Sub-stations= 1.0 Ohm
Minor Sub-station = 2 Ohm
Neutral Bushing. =2 Ohm
Service connection = 4 Ohm
Medium Voltage Network =2 Ohm
L.T.Lightening Arrestor= 4 Ohm
L.T.Pole= 5 Ohm
H.T.Pole =10 Ohm
Tower =20-30 Ohm
Treatments to for minimizing Earth resistance:
Remove Oxidation on joints and joints should be tightened.
Poured sufcient water in earth electrode.
Used bigger size of Earth Electrode.
Electrodes should be connected in parallel.
Earth pit of more depth & width- breadth should be made.
FILED UNDER UNCATEGORIZED
About Jignesh.Parmar
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
10 of 22 01/08/14 2:05 AM
Jignesh Parmar has completed his B.E(Electrical) from Gujarat University. He has more than
11 years experience in Power Transmission-Power Distribution-Electrical energy theft
detection-Electrical Maintenance-Electrical Projects(Planning-Designing-coordination-
Execution). He is Presently associate with one of the leading business group as a Assistant
Manager at Ahmedabad,India. He is Freelancer Programmer of Advance Excel and design
useful Excel Sheets of Electrical Engineering as per IS,NEC,IEC,IEEE codes. He is technical
Author for "Electrical Mirror" and "Electrical India" Magazines. He is Technical Blogger and
Familiar with English, Hindi, Gujarati, French languages. He wants to Share his experience
& knowledge and help technical enthusiasts to nd suitable solutions and updating
themselves on various Engineering Topics.
59 Responses to What is Earthing
Saravanakumar T says:
November 28, 2011 at 6:07 am
Informative. Thanks.
Reply
Anil says:
November 28, 2011 at 8:09 am
what is the minimum frequency of earthpit maintenence as per indian standards in a LV
installation like for example in petrol pumps etc.
Our ofce has incomer feeder of 11 kv with sanctioned load of 600 kw in delhi. What
should be the value of grid resistance /Individual pit resistance and frequency of eart
pit maintenance that should be observed in such instllations, asper the relevent indian
IE rules.
Thanks,
anil
Reply
umashankar says:
December 10, 2011 at 3:40 am
Hi parmar,
Nice to see u r aticle, its great and useful to other electrical engineers for their reference,
i need to share and learn about the following points.
1. Electrical clearance and creepage distance for air and oil medium, wat would be the
minimum clearances required between two phase contacts and phase to earth clearance
and phase to phase clearance inside the oil medium (transformer oil) and also outdoor
with reference to study.
2. sizing of copper conductor, how to choose the copper conductor size for 600 A and
2000 amps, how to derive and references copper contact will be single piece. wat would
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
11 of 22 01/08/14 2:05 AM
be the max amps that can allow per sqmm conductor, temperature withstand.
thank you
Reply
Laxmi Narayan Sharma says:
February 2, 2012 at 11:29 am
good information
Reply
taruntripathy says:
February 4, 2012 at 9:45 am
Where does electricity go after it goes through our appliances?
Reply
m.janardhana reddy says:
January 15, 2013 at 11:29 am
It is utilised by them as by converting into another form of energy (or) when earthed
it will be nuetralised by earth potential (as earth is always at zero potential)
Reply
Yallappa says:
March 22, 2012 at 4:16 pm
please mail
Reply
Yallappa says:
March 22, 2012 at 4:18 pm
please post technical publications to my e-mail id
Reply
Jignesh.Parmar says:
March 22, 2012 at 5:49 pm
All Technical Notes are Free of Cost so Just Copy & past of each Notes from Blog Else
Purchase it in PDF version at very Nominal price from Blog.
Reply
muthuvel says:
May 29, 2012 at 11:56 am
can you answer?
Why the Copper(plate) earth pit needed for neutral Earthing and G.I(pipe) earth
pit needed for Body earthing?
Jignesh.Parmar says:
May 29, 2012 at 3:53 pm
Is there any IS code which mention that Neutral earthing should be Copper !!!
Vishwa Murthy says:
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
12 of 22 01/08/14 2:05 AM
April 14, 2012 at 4:00 am
Sir, I have a small doubt regarding earthing of power transformer neutral..sir whether
the earth pit connected to neutral of PTR is kept separately from the grid earth mat or
this has to be connected with the grid earth mat and whats the reason behind this.??
Reply
Upendra Badal says:
June 12, 2012 at 3:06 am
sir,
nice to read ur article its very useful.
however i have a question regarding the difference between Body earthing and Neutral
Earthing for Distribution Transformer and/or Diesel generating set is there any
differences? and can we bond both earth station together or there should be different
earthing?
Reply
Asman says:
August 11, 2012 at 8:57 am
Thanku very much Jignesh for of the share your experiance with us and we pray for you
regarding u will share your expiriance with us and u go always boss
Reply
Sridharan S says:
August 29, 2012 at 11:35 am
To:Jignesh.Parmar
Thank you very much for your article on Impact of Floating Neutral. I live in chennai
in an apt where there are 11 ats and a transformer (3 phase, 1 neutral grounded) inside
the premises supplied by the electricity board. We had 3 major booms from the
transformer in the past one month and the ats suffered major losses of equipment
(lights, fans, inverters, TV, lift etc). We called some specialists and they said the reason is
the oating neutral (not grounded properly) on the distribution transformer side. The
local EB staff came and have strengthened the earthing on the transformer side. They
have also connected the neutral in the DB box of the transformer to the earth pit.
On our side i.e. the Flat main distribution panel, they have recommended that we
strengthen our earthing by installing 2 new earth pits and connecting them to the
common neutral (coming from the transformer). Pls conrm whether the advise is ok;
specically can we also ground the neutral on our distribution panel.
Thank you
Reply
Jignesh.Parmar says:
August 30, 2012 at 4:24 pm
If Transformer is dedicated to your Apartment and This transformer neutral is
earthed at T/C and If Your main Panel is also in Your Premises near Transformer
(Not so Long Distance) than It might be not make worse effect on your system but I
have not yet done such type of Practice.
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
13 of 22 01/08/14 2:05 AM
Here please note that Neutral always drain to earth which have low impedance path
so some of current may drain to your panels Neutral earth or some at Your T/C
neutral earth.Both Neutral earth may be not at equal impedance so may be some
potential difference hence at some time you may get Neural Back at either at T/c or
Panel.
System is always work in healthy condition when amount of feeding current from
its feeding station (here T/C or Generator) is need to be back in same amount to its
source and drain to earth.
In your case If Distance between T/C neutral earth and Your Panel is huge, If Some
Other load which are not feed from your panel but still connected on T/C may be
get worse effect on system.
Please concern Local authority for such type of connection.
Reply
Sridharan S says:
August 31, 2012 at 1:43 am
Thank you for your reply
Sridharan S says:
September 3, 2012 at 5:35 am
Dear Sir,
Thank you for nice reply.
We have a dedicated 3-phase, 4-wire 100 KVA transformer. As I told you in my
earlier mail, we had major damages to our equipment-lift,lights, fans etc. in our
apartments in the past one month. We measured the current at the consumer
distribution panel and got the following values:
Distribution panel currents:
R-Phase 10.4 Amps
Y-Phase 7.4 Amps
B-Phase 8.4 Amps
Neutral 5.6 Amps
The earth resistance was also checked at the transformer side and we got the
following value:
Transformer Earth Pit: Earth Value: 4.2 Ohms.
We have only body earth at the distribution panel. Neutral is not grounded.
Kindly advise what needs to be done.
Thanks & Regards
Sridharan
Jignesh.Parmar says:
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
14 of 22 01/08/14 2:05 AM
September 3, 2012 at 2:09 pm
Neutral of Your Panel need not to connect Neutral Earth Pit.
Please measure Voltage between your neutral and Earth wire It should be less
than 2Volt if You nd more than 2Volts ,means You have still Problem of Neutral.
First measure Voltage between Neutral and Earth..
S Sridharan says:
September 5, 2012 at 5:46 am
Sir,
Thank you for your reply.
The current on the neutral wire at the Panel when checked with the clamp meter
was 5.6 Amps. The voltage between Neutral and Earth at the Panel is 0 volt.
We are planning to do the following:
On the Transformer Side:
1) Strengthen Existing Body earth on the transformer side
2) Prepare another earth pit on the transformer side and connect the transformer
neutral to this pit.
3) If required,make one more earth pit on the transformer side and connect this
also to the transformer neutral
Hope we are on the right track. pls advise
Thanks & Regards
Sridharan
K.Venkat Ramana says:
October 31, 2012 at 3:31 am
Dear Sir Can you please explain me, with clear example of Star and Delta connection for
a motor, why we use Star and Delta with a small ckt diagram.
Reply
anoop sukumaran says:
November 26, 2012 at 4:44 am
dear sir,
by profession am a mechanical engineer and presently working as a MEP engineer in a
landscaping company .so i need to do all the electrical landscape lighting also.i got a
drawing of electrical lighting. the xtures are connected from a LCP with distribution
boards. each LCP having 6 or more circuits. in drawing each circuit is grounded at the
last end point. also the lcp cabinet also grounded.does it required actually in the site???
then how we will select the earthing pit and electrode dimensions for purchase and
installation???
i will be really thankful , if you help me in this.
thanks and regards
Anoop Sukumaeran
UAE
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
15 of 22 01/08/14 2:05 AM
Reply
Venkatesh says:
January 17, 2013 at 5:00 pm
shall we use Earthing Backll Compound for conventional earth pits???
Sir please give a reply to my mail.
Reply
K.Sudhesh says:
February 11, 2013 at 2:04 am
For my house wiring what are all the standards to be adhered for earth pit
measurements, pipe standard and related things for safe earthing. if i get a sketch reg.
earthing it will be useful..
Reply
nmr says:
March 9, 2013 at 9:40 am
SIRS,
A. IF THE DISTANCE BETWEEN TWO EARTH ELECTRODES IS LESS THAN 6 MTS (
2 X 3=6 MTS) WHAT IS THE EFFECT ON THE ELECTRICAL SYSTEM.
B.IF THE DISTANCE BETWEEN TWO EARTH ELECTRODES IS MORE THAT 6 MTS
WHAT IS THE EFFECT ON THE ELECTRICAL SYSTEM.
C. WHAT IS BASIC CALCULATION FOR ARRIVING NUMBER OF ELECTRODES
ARE REQUIRED FOR A 3 PHASE 415 V WORK SHOP HAVING A CONNECTED
LOAD OF 500 KW
INFORMATION IS URGENTLY NEEDED PLEASE. PL SEND TO MY MAIL THANX
VERY MUCH SIRS
Reply
nmr says:
March 9, 2013 at 9:41 am
SIRS,
A. IF THE DISTANCE BETWEEN TWO EARTH ELECTRODES IS LESS THAN 6 MTS (
2 X 3=6 MTS) WHAT IS THE EFFECT ON THE ELECTRICAL SYSTEM.
B.IF THE DISTANCE BETWEEN TWO EARTH ELECTRODES IS MORE THAT 6 MTS
WHAT IS THE EFFECT ON THE ELECTRICAL SYSTEM.
C. WHAT IS BASIC CALCULATION FOR ARRIVING NUMBER OF ELECTRODES
ARE REQUIRED FOR A 3 PHASE 415 V WORK SHOP HAVING A CONNECTED
LOAD OF 500 KW
INFORMATION IS URGENTLY NEEDED PLEASE.
THANX sirs VERY MUCH SIRS urgent please.
Reply
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
16 of 22 01/08/14 2:05 AM
Rahul says:
March 11, 2013 at 7:16 am
Dear Sir,
My question is not related to the topic.
It is related to cable sizing
How will we choose the cable size in sqmm if only the ampere is given ,with out the
help of any charts
i mean like a thumb rule.
i didnt see any provision to ask questions in the website that is why i put my query
here.
I hope you will give me the answer.
Thanks
Rahul
Reply
Ashish says:
April 13, 2013 at 5:20 am
what are the chemicals like salt charcoal etc are used in chemical earth and purpose of
each. How to make a good chemical earth pit. When measureing the earth resistance by
fall of potential method using 3 pole eath testor (C1 & P1 shorted, P2 and C2) then at the
time of measuring whether earth electrode going to electronic device should be
disconnected or not. If not not disconnected then reading will be correct or not. Please
reply.
Reply
mvrahul says:
April 15, 2013 at 6:32 am
dear sir;
i have a doubt, we are using a plc block (cpu 224 ac/dc/rly) inside a panel. recently, the
plc block got burnt. they say it was due to not providing earthing. my question is,
whether not providing earthing will result in such a situation or is it due to their
incoming supply which is coming from a diesel generator set.? please help?
Reply
Aamir shahzad says:
June 9, 2013 at 9:11 am
its good information. thanks
Sir pls tell me the size of earth cablr for 1200kva transformer
Reply
Samuel says:
June 24, 2013 at 10:40 am
thanks for creating this forum where you can ask question and get response i was just
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
17 of 22 01/08/14 2:05 AM
thrilled reading through the various questions and answers provided. well thank and
thank you.
Sam.
Reply
Aman says:
June 30, 2013 at 8:27 am
Dear Sir,
What would be good Depth of Dig for home earthing. Someone asks 100 feet Someone
just 10 feet??
Reply
upendra says:
July 2, 2013 at 12:28 am
for Conventional plate earthing IS says: Plate burred at the depth of 8 feet in the vertical
position
Reply
DIRGHAYU GANDHI, VADODARA says:
July 4, 2013 at 5:46 am
how can i calculate copper wire gauge? for plate earthing
Reply
Aman says:
July 13, 2013 at 5:43 am
thx upendra, so 8-10 feet earthing pit would be good for home earthing.
Reply
Arslan says:
July 18, 2013 at 5:10 am
i want to ask you one thing that, should we go for separate pits for eld instruments
and control room. or we can use single pit for both.
Reply
pit2014 says:
July 19, 2013 at 4:10 pm
Thanks a bunch for sharing this with all of us you actually understand what you are
speaking approximately! Bookmarked.
Reply
feroz says:
July 30, 2013 at 5:09 am
Jigneshsir i have confusion the pipe earthing and plate earthing plz detail
Reply
Mohammad yaqoob says:
August 2, 2013 at 7:09 am
Does the eathing condutor use for neutral of distribution transformer grounding
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
18 of 22 01/08/14 2:05 AM
depends on the size of distribution transformer, if it does than could you please help me
to calculate the required size of earth conductor for transformers of different capacities
such as 250kva,500kva,1000kva,1500kva,2000kva.on what basis we can determine the
size of copper earth conductor.
I will apriciate your earl reply.
Thanks,
Engieer M.Yaqoob
Electron UAE
Reply
niklesh says:
October 8, 2013 at 6:07 am
why earthing is necessary?
Reply
Jignesh.Parmar says:
October 8, 2013 at 3:00 pm
The answer of your Question is inside the answer of the question Why Human or
Equipment safety is necessary?
Reply
Guru says:
November 23, 2013 at 7:26 am
but one question is un-answered why copper conductor is required for Nuetral
earthing? -Guru
Reply
Jignesh.Parmar says:
November 23, 2013 at 4:52 pm
Normally We use copper for T/C Neutral earthing but As per My knowledge there
is no any relevant IS or Other Code state that Copper is required for neutral earthing.
Reply
Guru says:
November 25, 2013 at 6:12 am
Thanks Mr. Jignesh. We are facing problem in one of ofce bldg everyone enter
in ofce experience shock if he touch another person or Laptop. We checked
earthing value which is 0.2 Ohm in grid. Considering Static electricity problem
checked HVAC humidity. No Problem found in the same. What to do?
Aviral Saigal says:
December 6, 2013 at 10:40 am
Dear sir,
Normally we follow the pipe earthing (treated or non treated type) depending upon the
nature of job to be executed with a depth of 3.5 m. But sir is there any possibility of
having a horizontal earthing for temporary basis with a depth of 0.5 m so that the
purpose of earhing is met and with the earth resistance is maintained. As i am facing
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
19 of 22 01/08/14 2:05 AM
this problem due to hard rock area and for pipe type earthing to follow we need to mae
a bore, but due to some or the other delay.
Sir please help.
Reply
mmpatel says:
January 17, 2014 at 9:23 am
SIR,
I wanted to know more about Chemical Earthing that is be installed in Hilly area (where
hard rocks are underneath).
Reply
dileep says:
January 19, 2014 at 1:50 pm
with reference to above calculation for plate earthing area in 0.004536m but ur showing
that 2.88 please calrify my doubt. and also i didnt get the ans which ur showing. coming
to pipe earthing calc length in cm u hav considered but resistivity ur taken ohm-meter.
pl clarify my doubt.
Reply
Jignesh.Parmar says:
January 22, 2014 at 7:04 pm
Not getting PointPlease clarify with Quote
Reply
dileep phani says:
January 23, 2014 at 5:37 pm
Dear Sir,
Pl explain the calculation of plate and pipe earthing .
1) How did u calculate the plate size?
2) *(R) = (100**r**/2!L) X loge (4L/d).* in formula you have given Cm. where as
come to calculation u took the meters for resistivity.
On Thu, Jan 23, 2014 at 12:34 AM, Electrical Notes & Articles wrote:
> Jignesh.Parmar commented: Not getting PointPlease clarify with >
Quote
Jignesh.Parmar says:
January 23, 2014 at 6:06 pm
(1) Equation for Plate size is indicating in task bar of excel sheet Just press
appropriate cell.
(2) As per IS 3043, Equation for Resistance of Pipe or Rod R=
(100#/2$L)*log%(4L/d)ohms where Length of Road is cm but normally we use
length of rod in meter so I converted meter to cm in equation
I think this is clear for your query..
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
20 of 22 01/08/14 2:05 AM
dileep says:
January 23, 2014 at 5:37 pm
Dear Sir,
Pl explain the calculation of plate and pipe earthing .
1) How did u calculate the plate size?
2) (R) = (100r/2"L) X loge (4L/d).
in formula you have given Cm. where as come to calculation u took the meters
for resistivity.
dileep says:
January 22, 2014 at 6:16 pm
i didnt get reply till date sir
Reply
dileep says:
January 23, 2014 at 6:19 pm
sir, u took the 100 ohm-meter. pl check in ur calculations. Plate size 1.2mX1.2 m = 1.44
sq-m. where as 2.88 how was it come.
Reply
Jignesh.Parmar says:
January 23, 2014 at 6:32 pm
Dear Dileep,
It show both surface of Plate earthing because both surface of plate are with touch of
soil so plate surface area would be double
I think this is enough clearness i may explain..
Reply
John says:
February 19, 2014 at 3:19 pm
what is the formular to be used in calculating the size of a copper conductor required for
earthing a 18MW substation.
Reply
Saurabh Mohta says:
April 12, 2014 at 6:05 am
sir, this is indeed a fantastic and a very organised article. Can I have some detail as
regards to the comparison of The Copper and GI with the cast iron plate or pipe
electrodes and their conductivity values, my architect has been telling me about cast
iron pipes a lot.
Reply
Pradip says:
May 17, 2014 at 3:37 pm
SIR,please tell me distribution transformer neutral earthing strip ho select size copper
& G.I. ?
What is Earthing | Electrical Notes & Articles http://electricalnotes.wordpress.com/2011/11/27/what-is-earth...
21 of 22 01/08/14 2:05 AM
Reply
Jignesh.Parmar says:
May 18, 2014 at 11:25 am
Already given in the blog with example..review post of this blog.
Reply
sivakumar says:
June 20, 2014 at 2:32 pm
Respected sir,
how we determine the size of conductor for respective voltage.